4-2-CR27012-27302500 Approved Plans.pdf
PDF 6 MB Posted
- Solicitation number
- CR27012
- Issued by
- Utah
About this file
Summary of Approved Plans for Scofield Shed Solar Power & Generators Project
This document set comprises architectural and electrical approved permit plans for the Division of Facilities Construction and Management (DFCM) in Utah, specifically for Project #27302500 located at Scofield. The project scope involves construction of a new generator enclosure building, electrical system upgrades including a hybrid solar power system with battery storage, and associated infrastructure. The architectural plans include a new 13'4" by 11'4" steel-framed generator shed with concrete foundations, metal wall and roof panels, a concrete housekeeping pad for the generator, site grading, utility connections, and protective measures for existing structures and utilities. The electrical scope encompasses installation of a new generator with ventilation system, photovoltaic array with disconnect switches, battery energy storage system, hybrid inverter, conduit routing, grounding systems, underground utilities, gas piping from the propane tank, lighting fixtures, and all associated power distribution equipment. Deferred submittals include the generator ventilation system design, generator concrete pad design with structural engineer certification, and the overcurrent protective device coordination and arc-flash studies. The project requires coordination with the selected generator manufacturer to finalize louver sizing, air flow requirements, and exhaust system specifications. A mandatory bidder's meeting is required, with participation limited to five invited contractors: Gladwell Construction, Rod Lewis Construction, Slider Construction, Strong Solutions LLC, and Xcel General Contracting.
The construction cost estimate is $76,000.00. The project is governed by the 2024 International Building Code, 2024 International Mechanical Code, 2024 International Plumbing Code, 2024 International Fire Code, 2023 National Electrical Code, and ICC A117.1-2009 accessibility guidelines. All work must comply with DFCM standards and state requirements for hot works permits, site safety, underground utility blue-staking, and final inspections. The contractor is responsible for dust walls, temporary chain-link fencing for the staging area, OSHA compliance, all costs associated with safety measures and site requirements, and protection of existing utilities and building elements. Prior to final certificate of occupancy, the contractor must provide code inspection reports, structural engineer final observation reports, fire clearance certificates, and fabricator compliance certificates as applicable. The project plans were issued on August 14, 2026, as a permit set reviewed and approved for code compliance by DFCM on August 19, 2026.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500
26-31
GTE
ELM
ELM
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
L a s t P lo tt e d
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
/1
/2
:3 :5
P
M
S C
O F
IE
L
D S
H E
D S
O L
A R
P O
W E
R
G E
N E
R A
T O
R S
°4
'2
.0
"N
°1
'0
.8
"W
TITLE SHEET
GI-001
SCOFIELD SHED
SOLAR POWER & GENERATORS
PROJECT ADDRESS
39°40'22.0"N 111°19'00.8"W
AUGUST 14, 2026
PERMIT SET
STATE OF UTAH
DEPARTMENT OF ADMINISTRATIVE SERVICES
DIVISION OF FACILITIES CONSTRUCTION AND MANAGEMENT
4315 South 2700 West, Floor 3 | Taylorsville, UT 84129 / www.dfcm.utah.gov
DFCM PROJECT NO. 27302500
LYNK ENGINEERS
ELECTRICAL ENGINEER
244 WEST 300 NORTH #100 / SALT LAKE CITY, UTAH
84103 801.534.1130 / https://www.lynkengineers.com/
BHB CONSULTING ENGINEERS
2766 SOUTH MAIN STREET / SALT LAKE CITY, UTAH
84115 801.355.5656 / www.bhbengineers.com
STRUCTURAL ENGINEER
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
REVIEWED FOR CODE
COMPLIANCE
AE-101
A1
SIM
Room name
150 SF
DETAIL CALLOUT
BUILDING SECTION
WALL SECTION
DETAIL SECTION
ROOM NAME
ROOM NUMBER
ROOM SQ. FT.
(WHERE OCCURS)
DRAWING REVISION
REVISION NUMBER
NORTH ARROW
A GRID REFERENCE
CENTER LINE
CEILING HEIGHT
LEVEL
ELEVATION
VERTICAL ELEVATION
SPOT ELEVATION
DOOR NUMBER
WALL TYPE
WINDOW TYPE
KEYED NOTE
KEYED NOTE
GLASS TYPE
GRAPHIC SYMBOLS
N
A1
AE-101
SIM
A1
AE-101
SIM
A1
AE-101
SIM
CMU MASONRY
EARTH
CONCRETE
GRAVEL
STEEL
ALUMINUM
RIGID INSULATION
BATT INSULATION
STRUCTURAL FILL
BRICK MASONRY
PLYWOOD
PARTICLEBOARD
GYPSUM BOARD
ASPHALT PAVING
MATERIALS
WOOD (STUDS / NAILERS)
WOOD (BLOCKING)
WOOD
For the purpose of this section, deferred submittals are defined as per section 107.3.4.1 of the IBC. Submittal documents for deferred submittal items shall be submitted to the engineer/architect for their review for general conformance with the design of the building. After submittals are reviewed for general conformance by the architect and engineer of record, deferred submittals must be submitted to the building official for approval and that deferred items are not to be installed until approved by the building official (see IBC 107.3.4.1). Deferred submittals for this project are:
ITEM #1 GENERATOR AND RELATED ITEMS NEEDING COORDINATION SPECIFIC TO THE GENERATOR (HOUSEKEEPING PAD, VENTILATION LOUVERS, ETC.) PROVIDE ENGINEERED, STAMPED WORKING PLANS AS APPROVED BY THE AUTHORITIES HAVING JURISDICTION. CONTRACTOR SHALL PROVIDE WITHIN 3 WEEKS AFTER BID HAS BEEN AWARDED. THIS SUBMITTAL SHALL PROVIDE CONFIRMATION THAT THE SYSTEM
MEETS ALL APPLICABLE CURRENT CODES
1. THE CONTRACTOR IS TO THOROUGHLY FAMILIARIZE HIMSELF WITH THE
EXTENT OF WORK AND COORDINATE ALL TRADES.
2. ALL DIMENSIONS ARE TO BE FIELD VERIFIED - ANY VARIATIONS IN
DIMENSIONS ARE TO BE REVIEWED WITH THE ARCHITECT.
3. WHERE EXISTING WALLS ARE REMOVED PATCH REMAINING WALLS AS
REQUIRED FOR FLUSH FINISHED APPEARANCE.
4. THIS CONTRACTOR IS RESPONSIBLE FOR PATCHING/ REPAIRING ALL
IMPERFECTIONS IN ALL NEW AND EXISTING WALLS AFFECTED BY THIS
CONTRACT, INCLUDING HOLES, DENTS, BUMPS WAVES ETC. IT IS THE
CONTRACTORS RESPONSIBILITY TO VISIT THE JOB SITE PRIOR TO BIDDING
AND THOROUGHLY FAMILIARIZE HIMSELF WITH ALL SUCH WORK, THAT WILL
BE REQUIRED.
5. CORRIDORS SHALL NOT BE USED FOR STORAGE OF MATERIALS OR
STAGING OF THE WORK.
6. PATCH AND REPAIR WALLS AT OUTLETS AND AT OTHER OPENINGS
REQUIRED BY THIS REMODELING.
7. GRID LINES ARE ORIGINAL BUILDING GRID LINES.
8. PROTECT EXTG. FINISHES FROM DAMAGE.
9. DO NOT SCALE DRAWINGS. STATED & WRITTEN DIMENSIONS GOVERN. THE
GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD AND
SHALL BE RESPONSIBLE FOR THEIR ACCURACY. NO EXTRA CHARGE OR
COMPENSATION SHALL BE ALLOWED BECAUSE OF DIFFERENCE BETWEEN
ACTUAL DIMENSIONS AND THOSE INDICATED ON THE DRAWINGS, UNLESS
THEY CONTRIBUTE TO A CHANGE IN THE SCOPE OF THE WORK. ANY
DIFFERENCE WHICH MAY BE FOUND SHALL BE SUBMITTED TO THE
ARCHITECT FOR DECISION PRIOR TO ORDERING, MANUFACTURING, OR
PROCEEDING WITH THE WORK. HORIZONTAL DIMENSIONS INDICATED ARE
TO/FROM FACE OF FINISH, UNLESS NOTED OTHERWISE. VERTICAL
DIMENSIONS ARE FROM TOP OF FLOOR SLAB EXCEPT WHERE NOTED TO BE
ABOVE FINISHED FLOOR (AFF). DIMENSIONS ARE NOT ADJUSTABLE
WITHOUT A APPROVAL OF ARCHITECT UNLESS NOTED +/-.
10. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL WORK REGARDLESS
OF THE LOCATION OF THE INFORMATION IN THE DOCUMENTS. THE
GENERAL CONTRACTOR SHALL UTILIZE THE CONSTRUCTION DRAWINGS
AND WRITTEN SPECIFICATIONS FOR ALL REQUIRED INFORMATION TO
PROVIDE COMPLETE CONSTRUCTION OF THIS PROJECT. ITEMS LISTED IN
DRAWINGS MAY NOT BE INCLUDED IN SPECIFICATIONS. ITEMS LISTED IN
SPECIFICATIONS MAY NOT BE INCLUDED IN DRAWINGS.
11. DISCREPANCIES BETWEEN PORTIONS OF THE CONTRACT DOCUMENTS ARE
NOT INTENDED. THE GENERAL CONTRACTOR IS TO CLARIFY WITH THE
ARCHITECT ANY SUCH DISCREPANCIES PRIOR TO COMMENCING WORK.
12. THE CONTRACTOR IS TO PROVIDE DUST WALL AS REQUIRED TO PERFORM
NEW WORK - COORDINATE LOCATION OF DUST WALLS WITH OWNER.
13. CONTRACTOR'S STAGING AREA IS TO BE PROVIDED WITH A SECURE,
LOCKED, 6'-0" (PER IBC 3306) TALL TEMPORARY CHAIN LINK FENCE. STAGING
AREA SHALL NOT BLOCK DOORS, DOCKS, SIDEWALKS ETC. ALL GAPS IN
FENCE TO BE MAINTAINED LESS THAN 4". REMOVE AND SECURE ALL
LADDERS AT THE END OF EACH DAY. DUMPSTER MUST BE KEPT IN LOCKED
FENCED AREA. COORDINATE LOCATION OF STAGING WITH OWNER.
SAFETY COMPLIANCE AND REQUIREMENTS:
THE CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE COMPLIANCE WITH THE INTERNATIONAL BUILDING CODE (IBC) 2021, CHAPTER 33, "SAFEGUARDS DURING CONSTRUCTION," AS WELL AS TO OTHER APPLICABLE REGULATIONS, SUCH AS OSHA STANDARDS. THIS INCLUDES BUT IS NOT LIMITED TO, IMPLEMENTING VARIOUS SAFETY MEASURES, SUCH AS TEMPORARY BARRIERS, FALL PROTECTION SYSTEMS, AND DESIGNATED SAFE ACCESS AND EGRESS ROUTES. ADDITIONALLY, PROPER HANDLING PROCEDURES FOR HAZARDOUS MATERIALS, A COMPREHENSIVE SAFETY PLAN, ADEQUATE LIGHTING AND VENTILATION, REGULAR INSPECTIONS, THOROUGH TRAINING, AND STRICT ADHERENCE TO ALL RELEVANT SAFETY REGULATIONS MUST ALSO BE DONE AS REQUIRED BY THE SCOPE OF THIS PROJECT. THE CONTRACTOR MUST DEMONSTRATE A PROACTIVE APPROACH TO SAFETY, ENSURING THAT ALL NECESSARY MEASURES ARE IN PLACE TO PROTECT WORKERS, VISITORS, AND THE GENERAL PUBLIC THROUGHOUT THE CONSTRUCTION PROCESS. THE CONTRACTOR IS RESPONSIBLE FOR FULLY UNDERSTANDING AND COORDINATING ALL APPLICABLE REQUIREMENTS AS WELL AS ALL SAFETY MEANS & METHODS AS THEY PERTAIN TO THIS PROJECT. FAILURE TO COMPLY WITH THESE REQUIREMENTS MAY RESULT IN INJURIES OR DAMAGES, FOR WHICH THE CONTRACTOR WILL BE HELD LIABLE. ALL COSTS AND TIME ASSOCIATED WITH THESE REQUIREMENTS MUST BE REFLECTED IN THE CONTRACTOR'S BID AND SHALL NOT
INCUR ADDITIONAL COST TO THE OWNER.
SITE WORK DIGGING REQUIREMENTS:
WHEN CONDUCTING EXTERIOR OR SITE WORK, AS TO MINIMIZE POTENTIAL DAMAGE TO EXISTING UNDERGROUND UTILITIES AND BURIED INFRASTRUCTURE, THE CONTRACTOR HOLDS THE RESPONSIBILITY OF ENSURING THE SITE IS BLUE STAKED BEFORE ENGAGING IN ANY DIGGING, TRENCHING, OR EXCAVATING ACTIVITIES, IRRESPECTIVE OF WHETHER THESE ACTIONS ARE EXPLICITLY SPECIFIED IN THE PROJECT PLANS. ADDITIONALLY, THE CONTRACTOR IS ACCOUNTABLE FOR EXERCISING DUE DILIGENCE BY INVESTIGATING AREAS THAT REQUIRE DIGGING BUT WERE NOT MARKED DURING THE BLUE STAKES PROCESS. THIS CAN BE ACHIEVED THROUGH METHODS LIKE POTHOLING
AND/OR HYDROVAC EXCAVATION OR SIMILAR METHODS.
North: ______ South: ______ East: ______ West: ______
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
Official for Complex Buildings. Including, but not limited to:
g) Fire Stopping, Including Tested Design Number.
f) Exterior and Interior Accessibility Route.
e) Fire Assembly Locator Sheet.
a) High Rise Requirements.
b) Atriums.
c) Performance Based Criteria.
d) Means or Egress Analysis.
2) Additional Code Information shall be provided at the discretion of the Building
Code Accessibility Chapters, the more restrictive requirement shall govern.
through - ADA Guidelines and specific reference to the International Building
1) In case of conflict with the U.S. Department of Justice Federal Registers Parts
FOOTNOTES:
d) Drinking Fountains: ______ Service Sinks: ______
c) Bath Tubs or Showers: ______
b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______
a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
M. Minimum Number of Required Plumbing Facilities:
Exit Width Required: ______ Exit Width Provided: ______
Element Hours Assembly
ListingListing Element
Assembly Hours
Smoke Partitions
Fire Partitions
Exterior Bearing Walls
Interior Bearing Walls
Exterior Non-Bearing Walls
Structural Frame
Partitions - Permanent
Fire Barriers
Floors - Ceiling Floors
Roofs - Ceiling Roofs
Exterior Doors and Windows
Shaft Enclosures
Fire Walls
BAHTBABABA
Design Wind Speed: ______ mphB. Seismic Design Category: ______
L. Design Occupant Load: ______
K. Fire Resistance Rating Requirements for Building Elements (hours).
Area Modifications:J:
____________________________________________Tabular Area:I:
per Floor (square feet): ___________________Actual AreaH:
Number of Stories: ______ Building Height: ____________G:
Required: ______ Provided: ______ Type of Sprinkler System: ____________
Sprinklers:F:
Mixed Occupancies: ______ Nonseparated Uses: ______E.
separation distance (in hours):
Requirements for the Exterior Walls based on the fireFire Resistance RatingD.
C. Type of Construction (circle one):
Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______
Guidelines
ADA Accessibility
Building Conservation
Uniform Code for
National Electrical Code
Conservation Code
International Energy
International Fire Code
International Plumbing Code
International Mechanical Code
International Building Code
YearYear
APPLICABLE CODES
A. Occupancy and Group: ________ ________ ________ ________ ________
CODE ANALYSIS
U
X X
2024 IBC
2024 IMC
2024 IPC
2024 IFC
2023 NEC
N.A.
2024 IECC ICC A117.1-2009
NO NO
1 12'
151 S.F.
N.A.
N.A.
N.A.
N.A.
NO NO
N.A.
D 102
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500
26-31
GTE
ELM
ELM
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
L a s t P lo tt e d
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
/1
/2
:3 :5
P
M
S C
O F
IE
L
D S
H E
D S
O L
A R
P O
W E
R
G E
N E
R A
T O
R S
°4
'2
.0
"N
°1
'0
.8
"W
GENERAL
INFORMATION
GI-002
@ at
ABV above
ACOUS acoustical
ACT acoustical ceiling tile
AD area drain
ADJ adjustable
AFF above finished floor
ALT alternate
ALUM aluminum
APPROX approximate
ARCH architect
B.O. bottom of
BALC balcony
BD board
BET between
BLDG building
BLKG blocking
BLW below
BM beam
BOT bottom
BRKT bracket
BULKHD bulkhead
BUR built up roof
C.G. corner guard
C.J. control joint
CAB cabinet
CALK caulking
CEM cement
CER ceramic
CLG ceiling
CLOS closet
CLR clear
CO cased opening
COL column
CONC concrete
CONT continuous
CPT carpet
CT ceramic tile
CTR center
DBL double
DET detail
DIA diameter
DIM dimension
DN down
DR door
DS down spout
DW dishwasher
DWG drawing
Ø diameter
(E) existing
E east
ABBREVIATIONS DRAWING INDEX
DRAWING TITLESHT. #
GENERAL:
GI-001 TITLE SHEET
GI-002 GENERAL INFORMATION
GI-003 DFCM FORMS
ARCHITECTURAL:
AS-101 SITE PLAN
AE-101 PLANS
AE-201 ELEVATIONS
AE-301 SECTIONS
AE-501 DETAILS
AE-502 DETAILS
AE-601 SCHEDULES
ELECTRICAL:
EE001 ELECTRICAL COVER SHEET
EE002 SYMBOLS LEGEND
EE501 ELECTRICAL DETAILS
EE601 GROUNDING RISER DIAGRAM
EE702 TYPICAL LABELING DETAILS
ES100 ELECTRICAL SITE PLAN DEMO
ES101 ELECTRICAL SITE PLAN
ES502 CONDUIT RISER DIAGRAM
EP101 LEVEL 1 POWER PLAN
EP400 ENLARGED POWER PLANS
EP401 ELECTRICAL ELEVATIONS
EP601 ONE-LINE DIAGRAM
EP615 PANEL SCHEDULES
EL101 LEVEL 1 LIGHTING PLAN
EL601 INTERIOR LIGHTING FIXTURE SCHEDULE
PROJECT LOCATION
DEFERRED SUBMITTALS
GENERAL NOTES
E.J. expansion joint
EA each
EIFS exterior insulation & finish system
ELEC electrical
ELEV elevation
EMER emergency
ENCL enclosure
EOS edge of slab
EQ equal
EQUIP equipment
ETR existing to remain
EW each way
EWC electric water cooler
EXTG. existing
F.O. face of
FA fire alarm
FAP fire annunciator panel
FD floor drain
FE fire extinguisher
FEC fire extinguisher cabinet
FG finish group
FH fire hydrant
FHC fire hose cabinet
FIN finish
FLR floor
FRT fire retardant treated
FT foot or feet
FUR furring
FV field verify
GAL gallon
GALV galvanized
GB grab bar
GC general contractor
GL glass
GND ground
GWB gypsum board
GYP gypsum
H.W.H. hot water heater
HC handicapped
HDWD hardwood
HDWR hardware
HM hollow metal
HORIZ horizontal
HR hour
HT height
ID inner diameter
INCAN incandescent
INSUL insulation
INT interior
JAN janitor
JST joist
JT joint
LAM laminate
LAV lavatory
LB(S) pounds
LDG landing
LT light
MAX maximum
MECH mechanical
MEMB membrane
MFR manufacturer
MIN minimum
MISC miscellaneous
MO masonry opening
MTD mounted
MTL metal
(N) new
N north
NIC not in contract
NO number
NOM nominal
NTS not to scale
O.P. overflow pipe
OA overall
OC on center
OD outside diameter
OFF office
OH opposite hand
OPG opening
OPP opposite
PART partition
PERM perimeter
PG paint grade
PLAM plastic laminate
PLAS plaster
PLYWD plywood
PR pair
PT paint
PTD painted
R riser
RAD radius
RCP reflected ceiling plan
RD roof drain
RE refer
REF refrigerator
REINF reinforced
REQD required
RESIL resilient
RM room
RO rough opening
RTU roof top unit (mechanical)
S south
SAFB sound attenuation fiber batt
SC scupper
SCHED schedule
SEAL sealant
SECT section
SF square foot
SHT sheet
SIM similar
SPEC specification
SQ square
SS stainless steel
STD standard
STL steel
STOR storage
STRUCT structural
SUSP suspended
SYM symmetrical
T tread
T&G tongue & groove
TEL telephone
TER terrazzo
THK thick
THR threshold
TO top of
TOM top of masonry
TYP typical
UC undercut
UNFIN unfinished
UNO unless noted otherwise
UON unless otherwise noted
UTIL utility
VCT vinyl composition tile
VERT vertical
VIF verify in field
VTR vent termination pipe
VWC vinyl wall covering
W west
W/ with
W/O without
WC water closet
WIN window
WP waterproof
WS wet stack
WSCT wainscot
WT weight
CODE ANALYSIS INFORMATION IS IN REFERENCE TO THE
NEW GENERATOR ENCLOSURE ONLY - NO CHANGES TO
EXISTING BUILDINGS OTHER THAN NEW ELECTRICAL /
SOLAR EQUIPMENT - OVERALL PROJECT CONSISTS
PRIMARILY OF SITE RELATED ELECTRICAL WORK
PROJECT
LOCATION
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
N .A
T h e f o ll o w in g d o c u m e n ts a re r e q u ir e d b e fo re a c e rt if ic a te o f o c c u p a n c y i s i s s u e d
A c o d e i n s p e c ti o n r e p o rt r e c o m m e n d in g t h a t a c e rt if ic a te o f o c c u p a n c y b e i s s u e d
F in a l re p o rt f ro m t h e s p e c ia l in s p e c ti o n a g e n c y
C e rt if ic a te o f fi re c le a ra n c e f ro m t h e S ta te
F ir e M a rs h a ll.
F in a l a p p ro v a l fr o m t h e S ta te
E le v a to r in s p e c to r, i f a p p lic a b le
F in a l a p p ro v a l fr o m t h e S ta te b o ile r in s p e c to r, i f a p p lic a b le
R e p o rt o f th e d is in fe c ti o n o f th e p o ta b le w a te r s y s te m I P
C
A
C e rt if ic a te o f C o m p lia n c e f ro m t h e a p p ro v e d f a b ri c a to r, i f a p p lic a b le
IB
C
.2
.2
A s ta m p e d a n d s ig n e d f in a l re p o rt f ro m t h e s tr u c tu ra l e n g in e e r w h e n s tr u c tu ra l o b s e rv a ti o n i s r e q u ir e d b y I B
C
A n N
F R
C C e rt if ic a te f o r fe n e s tr a ti o n w it h o u t th e N
F R
C l a b e l.
F in a l re p o rt f ro m t h e s p e c ia l in s p e c to r a n d t h e m e c h a n ic a l e n g in e e r w h e n s m o k e c o n tr o l is r e q u ir e d
T h e r e p o rt s m u s t c o m p ly w it h I B
C
.1
.8
.3
N .A
N .A
N .A
N
.A
N .A
N
.A
G E
N E
R A
L D
F C
M N
O T
E S
C
O N
S T
R U
C T
IO
N
O F
N E
W S
T A
T E
B U
IL
D
IN
G
S A
N D
R E
M O
D E
L
IN
G O
F E
X
IS
T
IN
G B
U
IL
D
IN
G S
H A
L L C
O M
P L Y
W
IT
H A
L L T
H E
R E
Q U
IR
E
M E
N T
S O
F T
H E
D F
C M
S T
A N
D A
R D
S T
H E
D F
C M
T A
N D
A R
D S
C A
N B
E F
O U
N D
A T
T H
E F
O L L O
W
IN
G W
E B
S
IT
E w w w
.d fc m .u ta h .g o v
A
R C
H
IT
E C
T E
N G
IN
E
E R
S H
A S
D E
S
IG
N E
D T
H
IS
P R
O J E
C T
T O
M E
E T
A L L D
F C
M S
T A
N D
A R
D S
P
R
IO
R T
O F
IN
A
L A
P P
R O
V A
L O
F T
H E
P R
O J E
C T
A F
IN
A
L I N
S P
E C
T
IO
N N
E E
D S
T O
B E
U B
M
IT
T E
D T
O T
H E
B U
IL
D
IN
G
O F
F
IC
IA
L I N
D
IC
A T
IN
G
T H
A T
T H
E P
R O
J E
C T
I S
C O
M P
L E
T E
I N
A
C
O R
D A
N C
E W
IT
H
T H
E A
P P
R O
V E
D D
R A
W
IN
G S
A N
D D
O C
U M
E N
T S
T
H E
F O
L L O
W
IN
G D
O C
U M
E N
T S
A R
E R
E Q
U
IR
E D
B E
F O
R E
A C
E R
T
IF
IC
A
T E
O F
O C
C U
P A
N C
Y I
IS
U
E D
A
C O
D E
I N
S P
E C
T
IO
N R
E P
O R
T R
E C
O M
M E
N D
IN
G
T H
A T
A C
E R
T
IF
IC
A
T E
O F
O
C
U P
A N
C Y
B E
I S
S U
E D
F
IN
A L R
E P
O R
T F
R O
M T
H E
S P
E C
IA
L I N
S P
E C
T
IO
N A
G E
N C
Y
C
E R
T
IF
IC
A
T E
O F
F
IR
E C
L E
A R
A N
C E
F R
O M
T H
E S
T A
T E
F
IR
E M
A R
S H
A L L
R
E P
O R
T O
F T
H E
D
IS
IN
F
E C
T
IO
N O
F T
H E
P O
T A
B L E
W A
T E
R S
Y S
T E
M I P
C
A
C E
R T
IF
IC
A T
E O
F C
O M
P L
IA
N C
E F
R O
M T
H E
A P
P R
O V
E D
F A
B R
IC
A
T O
R
IF
P P
L
IC
A B
L E
IB
C
.2
.2
A
S
IG
N E
D F
IN
A
L O
B S
E R
V A
T
IO
N R
E P
O R
T F
R O
M T
H E
S T
R U
C T
U R
A L E
N G
IN
E
R
W
E
N S
T R
U C
T U
R A
L O
B S
E R
V A
T
IO
N I S
R E
Q U
IR
E
D B
Y I B
C
H O
T W
O R
K
Q
U
IR
E M
E N
T S
N O
T E
T H
A T
T H
E S
T A
T E
O F
U T
A H
D
F C
M R
E Q
U
IR
A
IN
IN
G T
E S
T
IN
G A
N D
P E
R M
IT
S
F O
R E
V E
R Y
O N
E T
H
W
IL
L P
E R
F O
R M
H O
T W
O R
K S
O N
S T
A T
E P
R O
J E
C T
S
V
IS
IT
E U
R L I N
D
IC
A T
E D
B E
L O
W F
O R
M O
R E
I N
F O
R M
A T
IO
N h tt p s /d fc m
.u ta h .g o v /c o n s tr u c ti o n -m a n a g e m e n t/ b u ild in g -o ff ic ia l/ h o t-w o rk s
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500
26-31
GTE
ELM
ELM
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
L a s t P lo tt e d
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
/1
/2
:3 :5
P
M
S C
O F
IE
L
D S
H E
D S
O L
A R
P O
W E
R
G E
N E
R A
T O
R S
°4
'2
.0
"N
°1
'0
.8
"W
DFCM FORMS
GI-003
X
X
X
X
X
X
X X
X
X
X
X
X
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
AE-101
A1
PROJECT
AREA
EXISTING UN-IMPROVED DRIVE
EXISTING HIGHWAY UT-31
EXISTING BUILDINGS IN THIS
AREA TO REMAIN - NO NEW
WORK
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500
26-31
GTE
ELM
ELM
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
L a s t P lo tt e d
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
/1
/2
:3 :5
P
M
S C
O F
IE
L
D S
H E
D S
O L
A R
P O
W E
R
G E
N E
R A
T O
R S
°4
'2
.0
"N
°1
'0
.8
"W
SITE PLAN
AS-1011" = 30'-0"A1 SITE PLAN
PROJECT
NORTH
ACTUAL
NORTH
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
AE-201
C1
AE-201A3
AE-201
AE-201
A1
C3
SNOW CAT SHED
A1
AE-301
A3
AE-301
B
A
13' - 4"
EQ EQ
GENERATOR
6' - 4"
E
E E
E
AE-502
A1
7"
3' - 2" 7' - 0" 3' - 2"
7"
10 11
1414 1' - 0"
1' - 0"
G E
N E
R A
T O
R M
F R
V E
R
IF
Y W
C .J
C
.J
C.J.
E.J.
# KEYED NOTES
1. NEW GENERATOR SHED - NOTE THAT FINISH FLOOR
ELEVATION IS TO BE FIELD VERIFIED AND COORDINATED AS
TO BE 2" ABOVE SURROUNDING GRADE - REGRADE AS
REQUIRED TO ACHIEVE - SEE SECTIONS AND ELEVATIONS
INDICATED
2. DASHED LINE INDICATES EDGE OF ROOF / OVERHANG ABOVE
3. NEW GENERATOR ON CONCRETE HOUSEKEEPING PAD
(DEFERRED SUBMITTAL) - SEE ELECTRICAL DRAWINGS.
4. PREFINISHED WALL LOUVER WITH INSECT SCREEN - NOTE
THAT THE LOUVER IS TO BE A DEFERRED SUBMITTAL AND
MUST BE COORDINATED WITH THE REQUIREMENTS OF THE
SELECTED GENERATOR MANUFACTURER - FINAL SIZE, AIR
FLOW REQUIREMENTS, LOCATION ETC. SHALL BE
DETERMINED AS PART OF THE DEFERRED SUBMITTAL
DESIGN.
5. REMOVE EXISTING AND PROVIDE NEW ELECTRICAL
EQUIPMENT AT THIS LOCATION - COORDINATE WITH
ELECTRICAL DRAWINGS.
6. EXISTING SNOW CAT STORAGE BUILDING TO REMAIN AND BE
PROTECTED FROM DAMAGE - NO NEW WORK WITH THE
EXCEPTION OF THAT INDICATED IN THE ELECTRICAL
DRAWINGS - COORDINATE AS REQUIRED.
7. EXISTING SOLAR PANEL SUPPORT POST AND CONCRETE
BASE TO REMAIN AND BE PROTECTED FROM DAMAGE - SEE
ELECTRICAL DRAWINGS FOR NEW SOLAR PANEL WORK.
8. NEW 48" x 84" CONCRETE LANDING AT DOORWAY -
CONCRETE TO BE 4" THICK OVER 4" GRAVEL BASE - SLOPE
AWAY FROM THE BUILDING 1/2" / 12"
9. EXISTING PROPANE TANK TO REMAIN AND BE PROTECTED
FROM DAMAGE - SEE ELECTRICAL DRAWINGS FOR NEW
CONNECTIONS TO NEW GENERATOR
10. EXISTING CONCRETE PAD TO REMAIN AND BE PROTECTED
FROM DAMAGE
11. EXISTING STEEL BOLLARD TO REMAIN AND BE PROTECTED
FROM DAMAGE
12. EXISTING MANHOLES AND RELATED ELEMENTS TO REMAIN
AND BE PROTECTED FROM DAMAGE - FIELD VERIFY EXACT
LOCATION AND ANY UNDERGROUND PIPING AS REQUIRED TO
ENSURE THAT THERE WILL BE NO CONFLICTS WITH THE NEW
SHED.
13. EXISTING UN-IMPROVED LANDSCAPING - MODIFY / REGRADE /
REPAIR AS REQUIRED TO PERFORM NEW WORK - WHERE
NEW DIGGING / EARTHWORK IS REQUIRED, FIELD VERIFY ANY
UNDERGROUND PIPING, CONDUIT AND OTHER EXISTING
ELEMENTS THAT MAY BE IMPACTED BY NEW WORK -
COORDINATE AS REQUIRED TO PROTECT EXISTING
UNDERGROUND ELEMENTS AS REQUIRED
14. NEW PIPE BOLLARD - PAINT - SEE DETAIL A3/AE-502
15. PREFINISHED, EXPOSED FASTENER, CORRUGATED, METAL
ROOF PANEL SYSTEM OVER SELF ADHERED HIGH TEMP
UNDERLAYMENT (OVER ENTIRE ROOF) OVER STRUCTURAL
SHEATHING OVER LIGHT GAUGE METAL JOISTS - PROVIDE
COLOR MATCHING, NEOPRENE GASKETED SCREWS FOR ALL
EXPOSED FASTENERS - ALL DETAILING AND MISC. TRIM /
COMPONENTS SHALL BE PROVIDED AND INSTALLED AS
REQUIRED TO ACHIEVE THE PANEL SYSTEM
MANUFACTURERS SPECIFIED WARRANTY - SEE SPEC.
A1
AE-301
A3
AE-301
B
A
CLICK URL BELOW (ORIGINAL .PDF FILE ONLY), OR SCAN
QR CODE OR ENTER URL BELOW INTO AN INTERNET
BROWSER FOR 3D SCAN OF EXISTING CONDITIONS
https://bit.ly/26-31-3d (note that url is case sensitive)
EXTG. CONDITIONS
3D SCAN LINK
B
A
(2
S
0-
PROVIDE SIMPSON
'S/HJCT' HANGER, TYP.
@ CORNERS
7" 13' - 4" 7"
(2
S
0-
1200S200-68
AT 2'-0" O
.C.
(2) 1200S200-97 FASCIA
(2) 1200S200-97 FASCIA
S
0-
F A
S C
IA
S
0-
F A
S C
IA
S
2-
'-0
O .C
S
2-
'-0
O .C
AT DBL JOISTS, PROVIDE SIMPSON
'S/HJCT' EA SIDE OF JOIST
CONNECTING INTO FASCIA. TYP AT
EACH SIDE.
B
A
Bearing Footing -
24" x 12"
Bearing Footing -
24" x 12"
Bearing Footing -
24" x 12"
Bearing Footing -
24" x 12"
8" CONCRETE WALL (TYP.) -
SEE ARCHITECTURAL
SECTIONS / DETAILS
DROP IN FOUNDATION AT
OPENING - SEE ARCHITECTURAL
SECTIONS / DETAILS
13' - 4"
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500
26-31
GTE
ELM
ELM
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
L a s t P lo tt e d
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
/1
/2
:3 :5
P
M
S C
O F
IE
L
D S
H E
D S
O L
A R
P O
W E
R
G E
N E
R A
T O
R S
°4
'2
.0
"N
°1
'0
.8
"W
PLANS
AE-101
PROJECT
NORTH
1/4" = 1'-0"A1 LEVEL 1 ACTUAL
NORTH
1/4" = 1'-0"A4 ROOF PLAN
PROJECT
NORTH
ACTUAL
NORTH
1/4" = 1'-0"C4 ROOF FRAMING PLAN
1/4" = 1'-0"D4 FOOTING & FDN PLAN
PROJECT
NORTH
ACTUAL
NORTH
PROJECT
NORTH
ACTUAL
NORTH
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
LEVEL 1
0"
A1
AE-301
T Y
P
5 5
LEVEL 1
0"
A3
AE-301B A
T Y
P
LEVEL 1
0"
A1
AE-301
1 2
T Y
P
LEVEL 1
0"
A3
AE-301
BA
T Y
P
# KEYED NOTES
1. PREFINISHED, EXPOSED FASTENER, CORRUGATED, METAL
WALL PANEL SYSTEM - ALL DETAILING AND MISC. TRIM /
COMPONENTS SHALL BE PROVIDED AND INSTALLED AS
REQUIRED TO ACHIEVE THE PANEL SYSTEM
MANUFACTURERS SPECIFIED WARRANTY - SEE SPEC.
2. PREFINISHED, EXPOSED FASTENER, CORRUGATED, METAL
ROOF PANEL SYSTEM - ALL DETAILING AND MISC. TRIM /
COMPONENTS SHALL BE PROVIDED AND INSTALLED AS
REQUIRED TO ACHIEVE THE PANEL SYSTEM
MANUFACTURERS SPECIFIED WARRANTY - SEE SPEC.
3. DOOR - SEE DOOR SCHEDULE.
4. PREFINISHED FASCIA METAL - SEE SECTIONS AND RELATED
DETAILS
5. PREFINISHED METAL SOFFIT - SEE SECTIONS AND RELATED
DETAILS
6. EXPOSED CONCRETE FOUNDATION / STEM WALL - PROVIDE
RUBBED FINISH ON EXPOSED SURFACES
7. PREFINISHED WALL LOUVER WITH INSECT SCREEN - NOTE
THAT THE LOUVER IS TO BE A DEFERRED SUBMITTAL AND
MUST BE COORDINATED WITH THE REQUIREMENTS OF THE
SELECTED GENERATOR MANUFACTURER - FINAL SIZE, AIR
FLOW REQUIREMENTS, LOCATION ETC. SHALL BE
DETERMINED AS PART OF THE DEFERRED SUBMITTAL
DESIGN.
8. MODIFY EXISTING GRADE AS REQUIRED TO PROVIDE A 2"
DIFFERENCE IN ELEVATION BETWEEN THE FINISHED FLOOR
AND THE GRADE AT THE PERIMETER OF THE BUILDING -
GRADE AS TO PROVIDE POSITIVE SLOPE AWAY FROM THE
BUILDING FOR A MINIMUM OF 10'
9. NEW PIPE BOLLARD - PAINT - SEE DETAIL A3/AE-502
10. WALL PACK LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500
26-31
GTE
ELM
ELM
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
L a s t P lo tt e d
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
/1
/2
:3 :5
P
M
S C
O F
IE
L
D S
H E
D S
O L
A R
P O
W E
R
G E
N E
R A
T O
R S
°4
'2
.0
"N
°1
'0
.8
"W
ELEVATIONS
AE-2013/8" = 1'-0"A1 NORTH ELEVATION
3/8" = 1'-0"A3 EAST ELEVATION
3/8" = 1'-0"C1 SOUTH ELEVATION
3/8" = 1'-0"C3 WEST ELEVATION
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
A3
AE-301
B A
2" / 12"
AE-501
A1
AE-501
C1
AE-501
A2
AE-501
C2
7" 11' - 4" 3' - 3"
1/2" / 12"
C L
E A
R
LEVEL 1
0"
A1
AE-301
1 2
AE-501
C4
AE-501
C4
Sim
" 2
7" 13' - 4" 7"
AE-501
A4
AE-501
A4
Sim
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500
26-31
GTE
ELM
ELM
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
L a s t P lo tt e d
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
/1
/2
:3 :5
P
M
S C
O F
IE
L
D S
H E
D S
O L
A R
P O
W E
R
G E
N E
R A
T O
R S
°4
'2
.0
"N
°1
'0
.8
"W
SECTIONS
AE-301
1/2" = 1'-0"A1 SECTION 01
1/2" = 1'-0"A3 SECTION 02
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
B
4" CONCRETE SLAB OVER 4"
GRAVEL BASE
SILL GASKET - SET ON (2) CONT.
BEADS OF SEALANT
CONCRETE FOOTING AND
FOUNDATION WALL
MODIFY EXISTING GRADE AS
REQUIRED TO PROVIDE A 2"
DIFFERENCE IN ELEVATION
BETWEEN THE FINISHED FLOOR
AND THE GRADE AT THE
PERIMETER OF THE BUILDING -
GRADE AS TO PROVIDE POSITIVE
SLOPE AWAY FROM THE BUILDING
FOR A MINIMUM OF 10'
WALL PANEL MFR'S STANDARD,
COLOR MATCHED, PREFINISHED
METAL TRIM / DRIP EDGE
600S162-54 STUDS AT 16" O.C.
PREFINISHED, EXPOSED FASTENER,
CORRUGATED, METAL WALL PANEL
SYSTEM OVER AWB - SEE SPEC.
#4 x 1'-6" @ 48" O.C.
(3) #4 x CONT. BARS
7/16" THICK WALL SHEATHING FASTENED
WITH #8 SCREWS AT 6" O.C. AT EDGES AND
12" O.C. IN FIELD
8" THICK CONCRETE WALL
REINFORCED WITH #4 AT 16" O.C.
VERTICAL AND #4 AT 12" O.C.
HORIZONTAL - PROVIDE RUBBED
FINISH ON EXPOSED SURFACES
600S125-54 CONT BOTTOM TRACK
FASTENED TO CONCRETE WALL WITH
5/8" DIA x 4" BOLTS AT 32" O.C.
2' - 0"
B
E L
O W
G R
A D
E
B
PREFINISHED, EXPOSED
FASTENER, CORRUGATED, METAL
WALL PANEL SYSTEM OVER AWB -
SEE SPEC.
600S162-54 STUDS AT 16" O.C.
7/16" THICK WALL SHEATHING
FASTENED WITH #8 SCREWS AT 6"
O.C. AT EDGES AND 12" O.C. IN
FIELD
7"
ROOF JOIST - SEE ROOF FRAMING
PLAN
STRUCTURAL FASCIA (SEE PLAN)
WITH (2) #10 STS TO EACH JOIST
600S125-54 CONT TOP TRACK
EDGE FASTENING
EDGE FASTENING
METAL STUD BLOCK TO MATCH
METAL JOISTS WITH #10 STS AT 8"
O.C. INTO TOP TRACK
23/32" ROOF SHEATHING WITH #10
FASTENERS AT 6" O.C. AT EDGES
AND 12" O.C. IN FIELD
FULL-HEIGHT STIFFENER
(362S200-54) AT OUTRIGGERS.
ATTACH TO OUTRIGGERS WITH (4)
#10 STS
PREFINISHED, EXPOSED FASTENER,
CORRUGATED, METAL ROOF PANEL SYSTEM
OVER SELF ADHERED UNDERLAYMENT - LAP
UNDERLAYMENT OVER ROOF EDGE (BEHIND
FASCIA METAL) - SEE SPEC.
1"
LEVEL 1
0"
A
ALUMINUM THRESHOLD WITH
GASKET - SET IN (2) CONT. BEADS OF
SEALANT - SEAL ALL JOINTS - SEE
SPECS
4" CONCRETE SLAB OVER 4"
GRAVEL BASE 4" CONCRETE PAD OVER 4" GRAVEL
BASE - SLOPE AWAY FROM BUILDING
1/2" EXPANSION JOINT
DOOR / FRAME - SEE PLAN
AND DOOR SCHEDULE
(24" NTS)
(1 8"
CONCRETE FOOTING
#4 x 1'-6" @ 48" O.C.
(3) #4 x CONT. BARS
8" THICK CONCRETE WALL
REINFORCED WITH #4 AT 16" O.C.
VERTICAL AND #4 AT 12" O.C.
HORIZONTAL - PROVIDE RUBBED
FINISH ON EXPOSED SURFACES
#4 DOWEL x 3'-6" AT 16" O.C.
2' - 0"
B
E L
O W
G R
A D
E
A
WALL PANEL MFR'S
STANDARD, COLOR
MATCHED, PREFINISHED
METAL TRIM / DRIP EDGE
DOOR / FRAME - SEE PLAN
AND DOOR SCHEDULE
WALL PACK LIGHT FIXTURE - SEE
ELECTRICAL - DETAIL / TRIM
METAL WALL PANEL SYSTEM PER
PANEL MFR'S STANDARD
DETAILS
PREFINISHED, EXPOSED
FASTENER, CORRUGATED, METAL
WALL PANEL SYSTEM OVER AWB -
SEE SPEC.
600S162-54 STUDS AT 16" O.C.
7/16" THICK WALL SHEATHING
FASTENED WITH #8 SCREWS AT 6"
O.C. AT EDGES AND 12" O.C. IN
FIELD
ROOF JOIST - SEE ROOF FRAMING
PLAN
600S125-54 CONT TOP TRACK EDGE FASTENING
EDGE FASTENING
METAL STUD BLOCK TO MATCH
METAL JOISTS WITH #10 STS AT 8"
O.C. INTO TOP TRACK
23/32" ROOF SHEATHING WITH #10
FASTENERS AT 6" O.C. AT EDGES
AND 12" O.C. IN FIELD
FULL-HEIGHT STIFFENER
(362S200-54) AT OUTRIGGERS.
ATTACH TO OUTRIGGERS WITH (4)
#10 STS
PREFINISHED, EXPOSED FASTENER,
CORRUGATED, METAL ROOF PANEL SYSTEM OVER
SELF ADHERED UNDERLAYMENT - LAP
UNDERLAYMENT OVER ROOF EDGE (BEHIND
FASCIA METAL) - SEE SPEC.
STRUCTURAL FASCIA (SEE PLAN)
WITH (2) #10 STS TO EACH JOIST
BOX HEADER - SEE
SCHEMATIC "A"
SCHEMATIC "A"
600T150-54
(3) 800S162-54
600T150-54
CONT. METAL
TRACK TO MATCH
WALL TOP TRACK
WALL PANEL MFR'S
STANDARD, COLOR
MATCHED, PREFINISHED
METAL TRIM / DRIP EDGE PREFINISHED WALL LOUVER WITH INSECT
SCREEN - NOTE THAT THE LOUVER IS TO BE A
DEFERRED SUBMITTAL AND MUST BE
COORDINATED WITH THE REQUIREMENTS OF
THE SELECTED GENERATOR MANUFACTURER -
FINAL SIZE, AIR FLOW REQUIREMENTS,
LOCATION ETC. SHALL BE DETERMINED AS PART
OF THE DEFERRED SUBMITTAL DESIGN.
7"
PREFINISHED, EXPOSED
FASTENER, CORRUGATED, METAL
WALL PANEL SYSTEM OVER AWB -
SEE SPEC.
600S162-54 STUDS AT 16" O.C.
7/16" THICK WALL SHEATHING
FASTENED WITH #8 SCREWS AT 6"
O.C. AT EDGES AND 12" O.C. IN
FIELD
ROOF JOIST - SEE ROOF
FRAMING PLAN
600S125-54 CONT TOP TRACK
EDGE FASTENING
EDGE FASTENING
METAL STUD BLOCK TO MATCH
METAL JOISTS WITH #10 STS AT 8"
O.C. INTO TOP TRACK
23/32" ROOF SHEATHING WITH #10
FASTENERS AT 6" O.C. AT EDGES
AND 12" O.C. IN FIELD
FULL-HEIGHT STIFFENER (362S200-54)
AT OUTRIGGERS. ATTACH TO
OUTRIGGERS WITH (4) #10 STS
PREFINISHED, EXPOSED FASTENER,
CORRUGATED, METAL ROOF PANEL SYSTEM
OVER SELF ADHERED UNDERLAYMENT - LAP
UNDERLAYMENT OVER ROOF EDGE (BEHIND
FASCIA METAL) - SEE SPEC.
FULL HEIGHT- 43 MIN (18 GA)
OUTRIGGERS AT 24" O.C.
STRUCTURAL FASCIA (SEE
PLAN) WITH (2) #10 STS TO
EACH JOIST
METAL PANEL MFR'S. STANDARD
SOFFIT / FASCIA METAL AND
ASSOCIATED TRIM - DETAIL PER
MFR'S. WRITTEN REQUIREMENTS -
COORD. AS REQ'D.
METAL PANEL MFR'S.
STANDARD ROOF EDGE
CLOSURE TRIM
1.1/2" x 1.1/2" x 0'-6" LONG 33MIL (20 GA)
CLIP WITH (2) #10 STS INTO OUTRIGER
AND (2) #10 STS INTO JOIST
BOX HEADER - SEE
SCHEMATIC "A"
LEVEL 1
0"
4" CONCRETE SLAB OVER 4"
GRAVEL BASE
MODIFY EXISTING GRADE AS
REQUIRED TO PROVIDE A 2"
DIFFERENCE IN ELEVATION
BETWEEN THE FINISHED FLOOR
AND THE GRADE AT THE
PERIMETER OF THE BUILDING -
GRADE AS TO PROVIDE POSITIVE
SLOPE AWAY FROM THE BUILDING
FOR A MINIMUM OF 10'
WALL PANEL MFR'S
STANDARD, COLOR
MATCHED, PREFINISHED
METAL TRIM / DRIP EDGE
PREFINISHED WALL LOUVER WITH INSECT
SCREEN - NOTE THAT THE LOUVER IS TO BE A
DEFERRED SUBMITTAL AND MUST BE
COORDINATED WITH THE REQUIREMENTS OF
THE SELECTED GENERATOR MANUFACTURER -
FINAL SIZE, AIR FLOW REQUIREMENTS,
LOCATION ETC. SHALL BE DETERMINED AS PART
OF THE DEFERRED SUBMITTAL DESIGN.
CONCRETE FOOTING AND
FOUNDATION WALL
#4 x 1'-6" @ 48" O.C.
(3) #4 x CONT. BARS
8" THICK CONCRETE WALL
REINFORCED WITH #4 AT 16" O.C.
VERTICAL AND #4 AT 12" O.C.
HORIZONTAL - PROVIDE RUBBED
FINISH ON EXPOSED SURFACES
SEAL PERIMETER (TYP.)
2' - 0"
B
E L
O W
G R
A D
E
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500
26-31
GTE
ELM
ELM
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
L a s t P lo tt e d
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
/1
/2
:3 :5
P
M
S C
O F
IE
L
D S
H E
D S
O L
A R
P O
W E
R
G E
N E
R A
T O
R S
°4
'2
.0
"N
°1
'0
.8
"W
DETAILS
AE-5011 1/2" = 1'-0"A1 BASE OF WALL
1 1/2" = 1'-0"C1 HEAD OF WALL - LOW
1 1/2" = 1'-0"A2 DOOR SILL
1 1/2" = 1'-0"C2 HEAD OF WALL - HIGH
1 1/2" = 1'-0"C4 HEAD OF WALL - RAKE
1 1/2" = 1'-0"A4 BASE OF WALL @ LOUVER
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
SEAL (BOTH SIDES TYP.)
16 GA. H.M. DOOR FRAME WITH (3)
ANCHORS PER JAMB - PAINT
DOOR - SEE DOOR
SCHEDULE
WALL PANEL MFR'S STANDARD,
COLOR MATCHED, PREFINISHED
METAL TRIM / CLOSURE WALL PANEL MFR'S
STANDARD, COLOR
MATCHED, PREFINISHED
METAL TRIM / CLOSURE
TOP EDGE OF FOUNDATION WALL
BELOW
PREFINISHED, EXPOSED
FASTENER, CORRUGATED, METAL
WALL PANEL SYSTEM OVER AWB -
SEE SPEC.
600S162-54 STUDS AT 16" O.C.
7/16" THICK WALL SHEATHING
FASTENED WITH #8 SCREWS AT 6"
O.C. AT EDGES AND 12" O.C. IN
FIELD
CONSTRUCTION JOINT
BACKER ROD AND
GRAY SELF LEVELING
POLYURETHANE JOINT
SEALER
CONTROL JOINT (C.J.)
EXPANSION JOINT (E.J.)
30' O.C. MAX.
V A
R
IE
S
/8
5/8" DIA. x 24" SMOOTH
DOWEL @ 18" O.C. - GREASE
AND USE PAPER SLEEVE
OVER ONE END
1/2" PREMOLDED EXPANSION
FILLER STRIP
/4
S L
A B
D E
P T
H
EDGE EACH SIDE OF
JOINT W/ 1/8" RADIUS
5/8" DIA. x 24" SMOOTH
DOWEL @ 18" O.C. - GREASE
AND USE PAPER SLEEVE
OVER ONE END
SAW-CUT CONTROL JOINT WITH AN
EARLY ENTRY SAW AS SOON AS
FINAL SET IS ACHIEVED. FINAL SET
IS TYPICALLY ACHIEVED WITHIN
FIRST 4 TO 6 HOURS OF SLAB POUR
6" DIA. EXTRA STRONG STEEL
PIPE BUMPER POST FILLED WITH
CONC.
24" CONCRETE PIER
REINF. WITH (4) #4 VERT.
BARS AND (4) #3 TIES
SLOPE TOP OF FOOTING
EXISTING GRADE
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500
26-31
GTE
ELM
ELM
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
L a s t P lo tt e d
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
/1
/2
:3 :5
P
M
S C
O F
IE
L
D S
H E
D S
O L
A R
P O
W E
R
G E
N E
R A
T O
R S
°4
'2
.0
"N
°1
'0
.8
"W
DETAILS
AE-502
1 1/2" = 1'-0"A1 TYP. CORNER DETAIL
1" = 1'-0"A4 CONCRETE JOINT DETAILS
3/4" = 1'-0"A3 PIPE BOLLARD DETAIL
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
"A"
PAIR OF HOLLOW METAL
DOORS - PAINTED
PAINTED
HOLLOW
METAL FRAME
"01"
A S
S C
H E
D U
L E
D
2" TYP.
REMOVABLE
CENTER
MULLION
AS SCHEDULED
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500
26-31
GTE
ELM
ELM
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
L a s t P lo tt e d
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
/1
/2
:3 :5
P
M
S C
O F
IE
L
D S
H E
D S
O L
A R
P O
W E
R
G E
N E
R A
T O
R S
°4
'2
.0
"N
°1
'0
.8
"W
SCHEDULES
AE-601
DOOR SCHEDULE
D O
O R
DOOR
D O
O R
T Y
P E
DOOR
F
IR
E R
A T
IN
G
H A
R D
W A
R E
FRAME
F R
A M
E
L
J A
M B
D E
T A
IL
F R
A M
E
R
J A
M B
D E
T A
IL
F R
A M
E H
E A
D D
E T
A
IL
T H
R E
S H
O L D
D E
T A
IL
S
IG
N A
G E
T Y
P E
S
IG
N A
G E
T E
X T
COMMENTSW
ID
T H
H E
IG
H
T
T H
IC
K
N E
S S
M A
T E
R
IA
L
F
IN
IS
H
T Y
P E
M A
T E
R
IA
L
F
IN
IS
H
101 6' - 0" 7' - 0" A 1 3/4" HOLLOW METAL PAINT NONE SET 01 01 HOLLOW METAL PAINT A1/AE-502 A1/AE-502 C2/AE-501 A2/AE-501 NONE PAIR OF 3'-0" BY 7'-0" DOORS WITH REMOVABLE MULLION
ROOM FINISH SCHEDULE
ROOM
# ROOM NAME FLOOR FINISH BASE
BASE
FINISH
NORTH WALL
MATERIAL
NORTH
WALL
FINISH
EAST WALL
MATERIAL
EAST
WALL
FINISH
SOUTH WALL
MATERIAL
SOUTH WALL
FINISH
WEST WALL
MATERIAL
WEST WALL
FINISH CEILING MATERIAL
CEILING
FINISH
CEILING
HEIGHT COMMENTS
101 SNOW CAT SHED NO NEW FINISH WORK UNLESS EXISTING FINISHES ARE AFFECTED BY NEW WORK - MODIFY / PATCH / REPAIR / REFINISH
ANY EXISTING ELEMENTS ADVERSLY AFFECTED BY THE NEW WORK
102 GENERATOR CONCRETE NONE NONE EXPOSED MTL. STUDS NONE EXPOSED MTL. STUDS NONE EXPOSED MTL. STUDS NONE EXPOSED MTL. STUDS NONE EXPOSED MTL. JOISTS NONE
3/8" = 1'-0"
DOOR TYPES
3/8" = 1'-0"
DOOR FRAME TYPES
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
No. 7610045 Michael C.
Fackrell
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 www.lynkengineers.com
COPYRIGHT:
© 2026 SPE ARCHITECTS
DESIGNED BY:
CHECKED BY:
SPE PROJECT #:
OWNER PROJECT #:
SPE ARCHITECTS
P.O. Box 517
Kaysville, Utah 84037
t. 801.298.1368 info@spe-architect.com www.spe-architect.com
1 2 3 4 5
1 2 3 4 5
A
B
C
D
DRAWN BY:A
B
C
D
27302500 26-31
JDF
MCF
JDF
SHEET NUMBER:
SHEET TITLE:
ISSUED:
NO. DATE DESCRIPTION
PROFESSIONAL STAMP:
ARCHITECT'S INFORMATION:
PROJECT NAME:
REVISIONS:
NO. DATE DESCRIPTION
La st
P lo tte d:
CODE OFFICIAL STAMP:
01 8/14/26 PERMIT SET
08/14/2026
8/
/2
3:
:5
PM
SC
O
FI
EL
D S
H
ED
SO
LA
R P
O W
ER
G
EN
ER
AT
O R
S
°4
0'
.0 "N
°1 9'
.8
"W
ELECTRICAL
COVER SHEET
EE001
ELECTRICAL SHEET INDEX
EE001 ELECTRICAL COVER SHEET
EE002 SYMBOLS LEGEND
EE501 ELECTRICAL DETAILS
EE601 GROUNDING RISER DIAGRAM
EE702 TYPICAL LABELING DETAILS
ES100 ELECTRICAL SITE PLAN DEMO
ES101 ELECTRICAL SITE PLAN
ES502 CONDUIT RISER DIAGRAM
EP101 LEVEL 1 POWER PLAN
EP400 ENLARGED POWER PLANS
EP401 ELECTRICAL ELEVATIONS
EP601 ONE-LINE DIAGRAM
EP615 PANEL SCHEDULES
EL101 LEVEL 1 LIGHTING PLAN
EL601 INTERIOR LIGHTING FIXTURE SCHEDULE
DEFINITIONS
NOTE: ALL DEFINITIONS MAY NOT BE USED.
INDICATED: THE TERM "INDICATED" REFERS TO GRAPHIC REPRESENTATIONS, NOTES, OR
SCHEDULES ON THE DRAWINGS, OTHER PARAGRAPHS OR SCHEDULES IN THE SPECIFICATIONS,
AND SIMILAR REQUIREMENTS IN THE CONTRACT DOCUMENTS. WHERE TERMS SUCH AS "SHOWN",
"NOTED", "SCHEDULED", AND "SPECIFIED" ARE USED, IT IS TO HELP THE READER LOCATE THE
REFERENCE, NO LIMITATION ON LOCATION IS INTENDED.
DIRECTED: TERMS SUCH AS "DIRECTED", "REQUESTED", AUTHORIZED", "SELECTED", "APPROVED", "REQUIRED", AND "PERMITTED" MEAN "DIRECTED BY THE ENGINEER", "REQUESTED BY THE
ENGINEER", AND SIMILAR PHRASES.
APPROVED: THE TERM "APPROVED", WHERE USED IN CONJUNCTION WITH THE ENGINEER'S
ACTION ON THE CONTRACTOR'S SUBMITTALS, APPLICATIONS, AND REQUESTS, IS LIMITED TO THE
ENGINEER'S DUTIES AND RESPONSIBILITIES AS STATED IN GENERAL AND SUPPLEMENTARY
CONDITIONS.
FURNISH: THE TERM "FURNISH" IS USED TO MEAN "SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION, AND SIMILAR OPERATIONS."
INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT SITE INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, AND SIMILAR
OPERATIONS."
PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE AND READY FOR
THE INTENDED USE."
INSTALLER: AN "INSTALLER" IS THE CONTRACTOR OR AN ENTITY ENGAGED BY THE CONTRACTOR, EITHER AS AN EMPLOYEE, SUBCONTRACTOR, OR SUB-SUBCONTRACTOR, FOR PERFORMANCE OF
A PARTICULAR CONSTRUCTION ACTIVITY, INCLUDING INSTALLATION, ERECTION, APPLICATION, AND SIMILAR OPERATIONS. INSTALLERS ARE REQUIRED TO BE EXPERIENCED IN THE OPERATIONS THEY
ARE ENGAGED TO PERFORM.
TECHNOLOGY SYSTEMS: THE TERM "TECHNOLOGY SYSTEMS" IS USED TO DESCRIBE ALL LOW
VOLTAGE SYSTEMS GENERALLY REFERRED TO AS "SPECIAL SYSTEMS". THESE SYSTEMS INCLUDE BUT ARE NOT NECESSARILY LIMITED TO ALL SYSTEMS WHICH UTILIZE VOLTAGES OF LESS THAN 71 VOLTS SUCH AS SOUND SYSTEMS, VIDEO SYSTEMS, TV SYSTEMS, SECURITY SYSTEMS, VOICE AND
DATA CABLING SYSTEMS, ETC...
ABBREVIATIONS
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
1P SINGLE POLE
1PH SINGLE-PHASE
1WAY ONE-WAY
2/C TWO-CONDUCTOR
2WAY TWO-WAY
3/C THREE-CONDUCTOR
3WAY THREE-WAY
4OUT QUADRUPLE RECEPTACLE OUTLET
4PDT FOUR-POLE DOUBLE THROW
4PST FOUR-POLE SINGLE THROW
4W FOUR-WIRE
4WAY FOUR-WAY
A ABOVE COUNTER
AC ARMORED CABLE
ACS ACCESS CONTROL SYSTEM
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
ALUM ALUMINUM
AMP AMPERE
ANN ANNUNCIATOR
AP ACCESS POINT (WIRELESS DATA)
AR AS REQUIRED
ASC AMPS SHORT CIRCUIT
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO VISUAL
AWG AMERICAN WIRE GAGE
BB XFMR BUCK-BOOST TRANSFORMER
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
C CEILING MOUNTED
CAT CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCBA CUSTOM COLOR AS SELECTED BY
ARCHITECT
CCTV CLOSED CIRCUIT TELEVISION
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/ OWNER
INSTALLED
CFBA CUSTOM FINISH AS SELECTED BY
ARCHITECT
CI CONTACT INDICATOR
CKT CIRCUIT
CM CONSTRUCTION MANAGER
CND CONDUIT
CO CONVENIENCE OUTLET
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CP CONTROL PANEL
CR CARD READER
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
dBA UNIT OF SOUND LEVEL
DPDT DOUBLE POLE, DOUBLE THROW
DS DISCONNECT SWITCH
E ENHANCED
EA EACH
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENT ELECTRIC NONMETALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ER EQUIPMENT ROOM
EX EXISTING
F FURNITURE MOUNTED
FA FIRE ALARM
FCP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
FMC FLEXIBLE METAL CONDUIT
FOB FREIGHT ON BOARD
FPP FIBER PATCH PANEL
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
GEN GENERATOR
GFCI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
GIG GIGA HERTZ
GND GROUND
HD HEAVY DUTY
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSE POWER
HPF HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
HV HIGH VOLTAGE
HWM HORIZONTAL WIRE MANAGEMENT
HZ HERTZ
I/O INPUT/ OUTPUT
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IN/IS INSULATED/ ISOLATED
IR INFRARED
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR
LED LIGHT EMITTING DIODE
LFMC LIQUID TIGHT FLEXIBLE METAL
CONDUIT
LFNC LIQUID TIGHT FLEXIBLE
NONMETALLIC CONDUIT
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTG LIGHTING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION
SYSTEM
MAX MAXIMUM
MC METAL CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTION
MDP MAIN DISTRIBUTION PANEL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT
PROTECTION
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OCP OVER CURRENT PROTECTION
OE OWNER ELECTRONICS
OF/CI OWNER FURNISHED/ CONTRACTOR
INSTALLED
OF/OI OWNER FURNISHED/ OWNER
INSTALLED
OFP OBTAIN FROM PLANS
OH DR OVERHEAD (COILING) DOOR
OL OVERLOAD
PB PUSHBUTTON
PF POWER FACTOR
PH PHASE
PNL PANEL
PNM PLENUM
PR PAIR
PS POWER SUPPLY
PT POTENTIAL TRANSFORMER
PTZ PAN/TILT/ZOOM
PV PHOTO VOLTAIC
QTY QUANTITY
R REMOVE
RCP REFLECTED CEILING PLAN
RMC RIGID METAL CONDUIT
RNC RIGID NONMETAL CONDUIT
RO REMOTE DOOR OPEN
RPM REVOLUTIONS PER MINUTE
RPP RISER PATCH PANEL
RR REMOVE AND RELOCATE
S/S START/STOP
SCA SHORT CIRCUIT AMPS
SCBA STANDARD COLOR AS SELECTED BY
ARCHITECT
SEC SECURITY
SF SQUARE FOOT (FEET)
SFBA STANDARD FINISH AS SELECTED BY
ARCHITECT
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE, DOUBLE THROW
SPEC SPECIFICATION
SPP STATION PATCH PANEL
SPST SINGLE POLE, SINGLE THROW
ST SINGLE THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TL TWIST LOCK
TP TELEPHONE POLE
TP TWISTED PAIR
TR TELECOMMMUNICATIONS ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSER
TYP TYPICAL
UF UNDERFLOOR
UGND UNDERGROUND
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT AMPERE
VFC/VFD VARIABLE FREQUENCY MOTOR
CONTROLLER
VIC VIDEO INTERCOM SYSTEM
VSS VIDEO SURVEILLANCE SYSTEM
VWM VERTICAL WIRE MANAGEMENT
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WPP WIRELESS PATCH PANEL
XFMR TRANSFORMER
SYMBOL DESCRIPTION
SYMBOLS LEGEND
REFERENCE AND LINE SYMBOLS
DETAIL INDICATOR: A5 INDICATES DETAIL NUMBER, E-501
INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN.
A5 E-501
ELEVATION OR SECTION INDICATOR, EXTERIOR: A5 INDICATES
ELEVATION OR SECTION NUMBER, E-201 INDICATES DRAWING
SHEET WHERE ELEVATION OR SECTION IS SHOWN.
A5 E-201
ELEVATION OR SECTION INDICATOR, INTERIOR: A5 INDICATES
ELEVATION OR SECTION NUMBER, E-201 INDICATES DRAWING
SHEET WHERE ELEVATION OR SECTION IS SHOWN.
A5 E-201
ROOM IDENTIFIER WITH ROOM NAME AND NUMBER.
ROOM NAME
KEYNOTE INDICATOR.1
REVISION INDICATOR.1
CU-1 EQUIPMENT INDICATOR.
NEW LINE: MEDIUM LINE.
HIDDEN FEATURES LINE: HIDDEN, THIN LINE
EXISTING TO REMAIN LINE: THIN LINE.
DEMOLITION LINE: DASHED, MEDIUM LINE
ELECTRICAL EQUIPMENT INDICATOR. "XXX" INDICATES TYPE OF EQUIPMENT OR
EQUIPMENT ID. "EF-X" IDENTIFIES MECHANICAL EQUIPMENT BEING SERVED.
REFER TO EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION.EF-X
XXX
EQUIPMENT INDICATOR. "X-X" INDICATES EQUIPMENT MARK SHOWN ON
EQUIPMENT SCHEDULE. "1LA-3" IDENTIFIES PANEL EQUIPMENT IS CIRCUITED TO.
REFER TO EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION.1LA-3
X-X
MECHANICAL EQUIPMENT INDICATOR. "X-X" INDICATES EQUIPMENT MARK
SHOWN ON EQUIPMENT SCHEDULE. "XMDP" IDENTIFIES PANEL EQUIPMENT IS
CIRCUITED TO. REFER TO EQUIPMENT SCHEDULE FOR ADDITIONAL
INFORMATION.
XMDP
X-X
IN-GRADE PULLBOX INDICATOR. "XXXET" INDICATES LABEL SHOWN ON
SCHEDULE. "#" IDENTIFIES SEQUENCE NUMBER SHOWN ON SITE AND RISER
DIAGRAM. REFER TO PLANS AND EXTERIOR PULLBOX SCHEDULE FOR
ADDITIONAL INFORMATION.
XXXET
CONDUIT TYPES
GENERAL ELECTRICAL NOTES
1.
2.
A.
B.
C.
3.
4.
5.
6.
CLARIFICATION METHODS: AT THE TIME OF BIDDING, BIDDERS SHALL FAMILIARIZE THEMSELVES WITH THE DRAWINGS AND SPECIFICATIONS. ANY QUESTIONS, MISUNDERSTANDINGS, CONFLICTS, DELETIONS, DISCONTINUED PRODUCTS, CATALOG NUMBER DISCREPANCIES, DISCREPANCIES BETWEEN THE
EQUIPMENT SUPPLIED AND THE INTENT OR FUNCTION OF THE EQUIPMENT, ETC, SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER IN WRITING FOR CLARIFICATION PRIOR TO ISSUANCE OF THE FINAL ADDENDUM AND BIDDING OF THE PROJECT. WHERE DISCREPANCIES OR MULTIPLE INTERPRETATIONS OCCUR, THE MOST STRINGENT (WHICH IS GENERALLY RECOGNIZED AS THE MOST COSTLY) THAT MEETS THE INTENT OF
THE DOCUMENTS SHALL BE ENFORCED.
OWNER FURNISHED ITEMS: THE OWNER WILL FURNISH MATERIAL AND EQUIPMENT AS INDICATED IN THE CONTRACT DOCUMENTS TO BE INCORPORATED INTO THE WORK. THESE ITEMS ARE ASSIGNED TO THE INSTALLER AND COSTS FOR RECEIVING, HANDLING, STORAGE, IF REQUIRED, AND INSTALLATION ARE
INCLUDED IN THE CONTRACT SUM.
THE INSTALLER'S RESPONSIBILITIES ARE THE SAME AS IF THE INSTALLER FURNISHED THE MATERIALS
OR EQUIPMENT.
THE OWNER WILL ARRANGE AND PAY FOR DELIVERY OF OWNER FURNISHED ITEMS FREIGHT ON BOARD JOB SITE AND THE INSTALLER WILL INSPECT DELIVERIES FOR DAMAGE. IF OWNER FURNISHED ITEMS ARE DAMAGED, DEFECTIVE OR MISSING, DOCUMENT DAMAGED ITEMS WITH THE TRANSPORT COMPANY
AND THE OWNER WILL ARRANGE FOR REPLACEMENT. THE OWNER WILL ALSO ARRANGE FOR
MANUFACTURER'S FIELD SERVICES, AND THE DELIVERY OF MANUFACTURER'S WARRANTIES AND
BONDS TO THE INSTALLER.
THE INSTALLER IS RESPONSIBLE FOR DESIGNATING THE DELIVERY DATES OF OWNER FURNISHED ITEMS AND FOR RECEIVING, UNLOADING AND HANDLING OWNER FURNISHED ITEMS AT THE SITE.THE INSTALLER IS RESPONSIBLE FOR PROTECTING OWNER FURNISHED ITEMS FROM DAMAGE, INCLUDING DAMAGE FROM EXPOSURE TO THE ELEMENTS, AND TO REPAIR OR REPLACE ITEMS DAMAGED AS A
RESULT OF HIS OPERATIONS.
EXPOSED STRUCTURE AREAS (EXCLUDING MECHANICAL, ELECTRICAL, AND COMMUNICATION SPACES):
INSTALL RACEWAYS BETWEEN DECK AND STRUCTURE WHEREVER POSSIBLE IN EXPOSED STRUCTURE CEILING AREAS. ROUTE RACEWAYS IN CONCEALED AREAS WHEREVER POSSIBLE. REFER ALL CONDITIONS WHERE RACEWAYS MUST BE INSTALLED WHICH CANNOT COMPLY WITH THESE REQUIREMENTS TO THE
ARCHITECT.
SUBMITTALS: PROVIDE ORIGINAL ELECTRONIC PDF FORMAT, BOUND, BOOKMARKED (EACH SECTION AND PRODUCT), AND HIGHLIGHTED. JOB NAME AND SUBCONTRACTOR SHALL BE ON THE FRONT COVER.
PREPARE INDEX OF EQUIPMENT SUBMITTED IN EACH TAB.
REFLECTED CEILING PLANS: COORDINATE THE LOCATION OF LIGHT FIXTURES WITH THE ARCHITECTURAL
REFLECTED CEILING PLANS. REFER ALL DISCREPANCIES TO THE ARCHITECT AND ENGINEER.
ALL WORK SHALL BE DONE ACCORDING TO THE CURRENT NATIONAL ELECTRICAL CODE (NEC), IBC, NFPA, AND IFC. COMPLIANCE AND FINAL APPROVAL IS SUBJECT TO THE ON SITE FIELD INSPECTION OF THE AHJ.
CONDUIT, COMMUNICATIONS
CONDUIT, POWER
SYMBOL DESCRIPTION
SYMBOLS LEGEND
SWITCH, DIMMER.D
SWITCH, SINGLE POLE ("x" INDICATES FIXTURES CONTROLLED).
X
SWITCH, DOUBLE POLE ("x" INDICATES FIXTURES CONTROLLED).
X
SWITCH, DOOR.DS
SWITCH, WEATHERPROOF.WP
WIRING DEVICES
RECEPTACLE, DUPLEX: NEMA 5-20R.
RECEPTACLE, DUPLEX, CEILING: NEMA 5-20R.
C
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER,
WET LABEL, "WEATHERPROOF IN USE": NEMA 5-20R.W
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER: NEMA 5-20R.
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER, WEATHERPROOF: NEMA 5-20R.WP
RECEPTACLE, QUADRAPLEX: NEMA 5-20R.
DROP CORD, CEILING/ BEAM MOUNTED. REFER TO DROP CORD AND CORD REEL
SCHEDULE FOR ELECTRICAL SPECIFICATIONS FOR CONFIGURATIONS AND
DEVICES.D#XX
L = WITH SLACK LOOP
G = WITH GFCI MODULE
RECEPTACLE, DUPLEX PROTECTED AT THE CIRCUIT BREAKER (GFCI, AFCI, ETC.).
REFER TO "BKR" COLUMN IN INDICATED PANEL SCHEDULE FOR PROTECTION
REQUIREMENTS. NEMA 5-20R.
RECEPTACLE, DUPLEX PROTECTED AT THE CIRCUIT BREAKER (GFCI, AFCI, ETC.).
REFER TO "BKR" COLUMN IN INDICATED PANEL SCHEDULE FOR PROTECTION
REQUIREMENTS. CONNECTED TO UPS. NEMA 5-20R.
SYMBOL DESCRIPTION
SYMBOLS LEGEND
WIRING METHODS
WIRING.
WIRING TURNED UP OR TOWARDS OBSERVER.
WIRING TURNED DOWN OR AWAY FROM OBSERVER.
LOW VOLTAGE WIRING: DIVIDE, MEDIUM LINE.
CONDUIT STUB. DIMENSION RECORD DRAWINGS AND MARK.
CONDUCTOR & CONDUIT ("CC") SCHEDULE INDICATOR. REFER
TO ONE-LINE DIAGRAM.1
JUNCTION BOX.J
PULL BOX.PB
JUNCTION BOX, CEILING.CJ
MECHANICAL EQUIPMENT CONNECTION. REFER TO EQUIPMENT SCHEDULE FOR
REQUIREMENTS.
GROUND BUSBAR. REFER TO GROUNDING RISER DIAGRAM FOR ADDITIONAL
INFORMATION.
SINGLE BRANCH CIRCUIT HOME RUN TO PANELBOARD WITH DEDICATED NEUTRAL
CONDUCTOR. LETTER AND NUMBER NOTATION IDENTIFY PANEL AND CIRCUIT
NUMBER.A-1
DEFFERRED SUBMITTALS
DELEGATED DEFERRED DESIGN SUBMITTAL TO BE PROVIDED BY CONTRACTOR
GENERATOR VENTILATION SYSTEM
PROVIDE COMPLETE MECHANICAL COOL AIR INTAKE, RADIATOR EXHAUST, AND ENGINE
EXHAUST SYSTEM DESIGN FOR THE GENERATOR ENCLOSURE AS A DEFERRED SUBMITTAL
FOLLOWING SELECTION OF THE GENERATOR. COORDINATE THE EXHAUST SYSTEM DESIGN
AND EQUIPMENT REQUIREMENTS WITH THE SELECTED GENERATOR MANUFACTURER.
SUBMIT COMPLETE DESIGN DOCUMENTATION FOR REVIEW AND APPROVAL PRIOR TO
INSTALLATION. ENSURE THE FINAL DESIGN COMPLIES WITH ALL APPLICABLE CODES,
STANDARDS, AND MANUFACTURER REQUIREMENTS.
OVERCURRENT PROTECTIVE DEVICE STUDY AND ARC-FLASH STUDY REPORT & LABELING.
PROVIDE THE FOLLOWING ITEMS LISTED BELOW AND COMPLY WITH ADDITIONAL
REQUIREMENTS AS PROVIDED. SEE SPECIFICATIONS.
1. COORDINATION-STUDY INPUT DATA,…
This is the start of the file's text. The full file is on GovTribe.