This is a structural calculations document prepared by BHB Engineers for the Division of Facilities Construction and Management (DFCM) of the State of Utah, detailing the approved engineering calculations for the Scofield Shed Solar Power & Generators Project (DFCM Project No. 27302500) located at coordinates 39°22'22.0"N, 111°19'00.8"W. The project involves construction of a new enclosure building around a generator installation, with associated electrical upgrades including a new generator, exterior building structure, lighting systems, and upgrades to an existing photovoltaic system. The structural design includes roof and live load calculations based on a 20 psf snow load and 214 psf design snow load, wind load analysis per 2024 IBC standards with basic wind speed of 102 mph in Exposure Category C, and seismic design per ASCE 7-22 for Site Class D in Seismic Design Category A. The calculations, prepared on August 14, 2026 and reviewed for code compliance on August 19, 2026, specify various structural members including metal stud framing, joists, headers, and wall systems designed to support the anticipated loads.
The structural design specifications include gravity framing utilizing multiple joist configurations (Joist 1 through Joist 5) with materials such as cold-formed steel members (1200S200-97, 1200S200-118, 600S162-54, and 600S162-68 sections at 50 ksi yield strength), metal stud walls at 16-inch on-center spacing, and a boxed header configuration to accommodate a 6.33-foot-wide by 7-foot-tall opening. The construction cost estimate for the overall project is $76,000.00, with the invitation limited to five specific contractors: Gladwell Construction, Rod Lewis Construction, Slider Construction, Strong Solutions LLC, and Xcel General Contracting. All lateral load analysis indicates wall shear requirements manageable with standard 6-inch nailing for sheathing, and deflection limits are satisfied across all structural elements, confirming code compliance under 2021 IBC standards with AISI S100-16 specifications.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCOFIELD SHED
SOLAR POWER & GENERATORS
PROJECT ADDRESS
39°40'22.0"N 111°19'00.8"W
DFCM PROJECT NO. 27302500
STRUCTURAL CALCULATIONS
2766 South Main Street - SLC, Utah 84115 - Phone: 801.355.5656 - Fax: 801.355.5950 www.bhbengineers.com
8/14/2026
CHB
Scott P. Evans Architect & Associates
Structural Calculations
BHB Project # 260651
DNR Scofield Generator Pad
These calculations were prepared solely for the client and project listed on the cover sheet.
They shall not be copied or used for the benefit of any other party or project.
Rev 0
Prepared For:
Prepared By:
08/14/2026
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/19/2026
REVIEWED FOR CODE
COMPLIANCE
Roof Σ = 20 psf
Deck 3
Joists/Girders 3
Ceiling 3
Roofing 2
Mech 5
Collateral 4
Dead Loads
DNR Scofield Generator Pad 260651
8/14/26
2766 South Main Street - SLC, Utah 84115
Phone: 801.355.5656 - Fax: 801.355.5950
CHB
Project: Sheet:
Job#:
Date:
By:
Roof Live Σ = 20 psf
Roof Live 20
DNR Scofield Generator Pad 260651
8/14/26
2766 South Main Street - SLC, Utah 84115
Phone: 801.355.5656 - Fax: 801.355.5950
CHB
Live Loads
Project: Sheet:
Job#:
Flat Roof Snow Data psf Flat Roof Snow Load:
psf psf psf per Table 7.3-2 psf (Pg at 20-yr MRI)
Snow Drift Data
Hr ft D pcf Hb ft
W2 Hc ft
TRUE
TRUE
Term Definition
Pf Minimum Roof Snow Load (psf)
Pg Basic Ground Snow Load (psf)
Pm Maximum Intensity of Load at the Height Change (psf)
Ce Snow Exposure factor (Table 7-2)
Ct Thermal Factor (Table 7-3)
D Density of Snow (pcf)
Hb Height of Balanced Snow Load on Lower Roof
Hd Maximum Height of Drift Surcharge (feet)
Hc Height Difference Between Upper Roof and Top of Balanced Snow Load on Lower Roof
Hr Height Difference Between Roof Elevations
Lu Length of Roof Upward of Drift Normal to the Line of Change in Roof Level (feet)
But Not Less than 25 feet
For Windward Drifts, Program Takes 75% of "Hd" for Claculating Snow Drift
W Width of Drift (feet)
Drift 1 - Typical ParapetDescription
Snow Loads (ASCE7-22)
Leeward Drift
Windward Drift
Pm,max 30.0
7.1
Pm 30.0
-3.6
DNR Scofield Generator Pad
Parapet
-3.6
-3.6
Ct 1.20
3.5 30
Pg, Service
260651
8/14/26
2766 South Main Street - SLC, Utah 84115
Phone: 801.355.5656 - Fax: 801.355.5950
CHB
Pg 255.0
Ce 1.0 214 Pf
Thermal Condition Unheated/Open-Air
Rroof ≤ 50
Pd [psf]W [ft] Pm [psf]Hd [ft]Lu m *K/W
14.1
0.35
Leeward Drift Windward Drift
Project: Sheet:
Job#:
Design Data ft ft ft ft deg mph
Importance Factor, Iw
Main Wind Force Resisting System
Surface
Windward Walls at
1 1 L1, z= 10 ft or
0 ft
0 ft
0 ft
0 ft
Leeward Walls or
Side Walls or
Roof Parallel and or
Normal, θ < 10 or or or
Roof (Normal, θ > 10, WW) or
Roof (Normal, θ > 10, LW) or
Windward Parapet
Leeward Parapet
-10.8
14.0
-0.90
-0.50 16.5 -5.9 0.18 2.5 -3.4 -8.5
-1 -14.0
-21.0
Elevation Factor, Ke
-2.7
2.5 -1.0
-13.2
2.5 -8.2 -13.2
-8.5
-6.1
2.5 -3.4
-10.8
0.18
GCpi
7.0
1.00
23.5
260651
8/14/26
2766 South Main Street - SLC, Utah 84115
Phone: 801.355.5656 - Fax: 801.355.5950
CHB
Full q Kd GCpi
0.85
Enclosure
Gust Factor, G
Topographic Factor, Kzt
Directionality Factor, Kd
Velocity Pressure Factor, Kh
Velocity Pressure, qh
Internal Pressure, GCPi
0.73
Combined [psf]
C
Mean Roof Height, h
Building Length, L
Building Width, B
Parapet Height, hp
Roof Angle
IBC
Basic Wind Speed, V
Exposure Category
DNR Scofield Generator Pad
0.85
0.85
0.18
16.5
0.85
Wind Loads
G Cp q q Kd G Cp
0.85 0.80 16.5 9.5 0.18 2.5 12.0
2.5 -8.2
16.5 -8.3 0.18 2.5
2.5 2.3
2.5 -5.8
16.5 -0.2 0.18
-0.30 16.5 -3.6
0.85 -0.70
0 - h/2 h/2 - h h - 2h
> 2h
0.85 -0.02
0.85
-5.8
-0.90 16.5 -10.7 0.18
1.5 21.0
16.5 -5.9 0.18-0.50
16.5 -10.7 0.18
0.85
0.85
0.85
0.85 -0.70 16.5 -8.3 0.18
Project: Sheet:
Job#:
Components and Cladding Roof Type
Effective Trib Area ft^2 'a' dimension ft
Mean Roof Height, h ft Velocity Pressure, qh psf
Surace
Walls Pos Zone 4 & 5 or
Neg Zone 4 or
Neg Zone 5 or
Roof Pos Zone 1 or
Pos Zone 2 or
Pos Zone 3 or
Neg Zone 1 or
Neg Zone 2 or
Neg Zone 3 or
Parapet WW Zone 4 (+Zone 4) - (-Zone 2) or
WW Zone 5 (+Zone 5) - (-Zone 3) or
LW Zone 4 (-Zone 4) - (+Zone 2) or
LW Zone 5 (-Zone 5) - (+Zone 3) or
16.0
16.0
Roof
Zone 3: Within 3 feet of building corners 34.7 32.5 29.5 27.3 22.1
Zone 2: Within 3 feet of building edges 34.7 32.5 29.5 27.3 22.1 Zone 1: All other areas 26.3 24.6 22.3 20.5 16.5
Location
Tributary Area (square feet) 10 20 50 100 500
Zone
-18.8-18.8-13.82.50.1816.5-16.3-1.16
-16.0-15.7
9.414.42.50.18
16.01.36.32.50.1816.53.80.27
-10.72.50.1816.5-13.2-0.94
14.42.50.1816.511.90.85
2.50.1816.511.90.85 16.09.414.4
Maximum
-29.9-2.14
-32.5-32.5-27.42.50.1816.5-29.9-2.14
2.50.1816.5
2.50.1816.5-22.0-1.58
16.09.4
41.941.941.9
-32.5-32.5-27.4
-24.6-24.6-19.5
-28.2-28.2-28.2
-25.1-25.1-25.1
41.941.941.9
16.511.90.85 q Kd GCpiGCpiqiq Kd GCpGCp Combined [psf]
Flat/Gable
10 16.5
20 3.00
CHB 2766 South Main Street - SLC, Utah 84115
Phone: 801.355.5656 - Fax: 801.355.5950
8/14/26
260651DNR Scofield Generator Pad
Wind Loads
Walls Zone 5: Within 3 feet of building corners 20.1 18.8 17.0 16.0 16.0
Zone 4: All other areas 16.4 16.0 16.0 16.0
Project: Sheet:
Job#:
Design Data deg Building Period, T = Ta s deg ft s
Max Period Coefficient s s s s
Seismic Force Resisting System
Response Modifiction Coefficient, R
System Overstrength Factor, Ωo
Deflection Amplification Factor, Cd
0.41 (Eq.12.8-2)
Response Spectrum Data
Spectral Response Paramaters TRUE
SS g Cs = Sa/(R/Ie) (Eq.12.8-2)
S1 g Cs (Lower Bound) (Eq.12.8-6)
MCE Spectral Acceleration Paramaters Design Spectral Acceleration Paramaters
SMS g SDS g
SM1 g SD1 g
MCE Spectral Acceleration Design Spectral Acceleration
Sa = Sa_max g Sa = Sa_max g
0.160 0.021
0.080
Long Period Transition, TL
260651
8/14/26
D
0.02
0.75
0.112
0.160
2766 South Main Street - SLC, Utah 84115
Phone: 801.355.5656 - Fax: 801.355.5950
CHB
Seismic Loads
Default
0.112
II
DNR Scofield Generator Pad
Seismic Design Category
2024 Period Parameter, Ct
Building Height, hn
1.00
FALSESite Specific Ground Motion
1.426667
Calculated Period, Ta
Max Allowed Period, Tmax
Lattitude
Longitude
IBC
Risk Category
Site Class
Importance Factor, Ie
-111.317
39.673
Period Parameter, x
0.115
0.577
T0 = 0.2 * SD1 / SDS
TS = SD1 / SDS
0.520
Seismic Response Coefficient - Method 1
Cs[Method 1] = Sa/(R/Ie) > Lower Bound
0.080
0.790
8.00
0.410
0.473
0.273
0.710
6.5
0.520 ρ 1.3
Light-Frame (Cold-Formed Steel) Walls Sheathed with Wood Structural Panels Rated for Shear Resistance or Steel Sheets
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.0 1.0 2.0 3.0 4.0 5.0
A cc e le ra ti o n
[g
Period, [s]
Maximum Considered Earthquake Response Spectrum
0.1
0.2
0.3
0.4
0.5
0.6
0 1 2 3 4 5
A cc e le ra ti o n
[g
Period, [s]
Design Earthquake Response Spectrum
Project: Sheet:
Job#:
GRAVITY FRAMING KEY PLAN
JOIST 1
JO
IS
T
JO
IS
T
JO
IS
T
JO
IS
T
JOIST 3
JOIST 3
JO
IS
T
JO
IS
T
Metal Stud Wall
2766 South Main Street • Salt Lake City • Utah 84115
Project: Sheet:
Job#:
Date:
By:
Phone: 801.355.5656 • Fax: 801.355.5950
DNR Scofield
CHB
08.12.2026
260651
Joist 3 Loading:
Dead Load = 20 psf Snow Load = 214 psf Cantilever Ends:
w_TL = (20 psf + 0.7 * 214 psf) * 2 ft = 339.6 plf Mid-Span:
w_TL = (20 psf + 0.7 * 214 psf) * 8 ft = 1358.4 plf *Point Load Reactions from Joist 5* Use (2)1200S200-97
Joist 4 Loading:
Dead Load = 20 psf Snow Load = 214 psf All Spans:
w_TL = (20 psf + 0.7 * 214 psf) * 2.75 ft = 467 plf *Point Load Reactions from Joist 3* Use (2) 1200S200-118
Joist 5 Loading:
Dead Load = 20 psf Snow Load = 214 psf All Spans:
w_TL = (20 psf + 0.7 * 214 psf) * 2.0 ft = 339.6 plf Use 1200S200-97
Metal Stud Wall:
Dead Load = 20 psf Snow Load = 214 psf w_TL = (20 psf + 0.7 * 214 psf) * (5.5 ft + 3.33 ft) = 1500 plf * (16"/12) = 2000 lbf Use 600S162-54 @ 16" O.C.
Footing Check:
TL/Bearing = 1500 plf / 1500 psf = 1 ft required -> 2'-0" Continuous Footing is acceptable.
Mid-Pt
Section : 1200S162-68 (50 ksi) @ 24" o.c. Single C Stud (punched)
Maxo = 6599.5(ft-lb) 2770.7Va = I = 18.390
Flexural Bracing None
0 lb-in/inDistortional Buckling, K-phi
NoneDistortional Buckling Bracing, Lm
Axial Bracing NA
Bracing, Interconnection and Distortional Buckling Parameters
Span Overhang
None
0 lb-in/in
None
Span (psf)
Load Cases Overhang
(psf)
Dead Load 20 20
Live Load 20 20
Snow Load 150 150
Inward Wind Load 5 5
Outward Wind Load -19 -19
Dead
Load Combinations
LiveLC Number Snow Inward Wind
Outward Wind
1 1 1 0 0 0
2 1 0 1 0 0
3 1 0 0 1 0
4 1 0.75 0 0.75 0
5 1 0 0.75 0.75 0
6 0.6 0 0 0 1 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Joist 1
IBC 2021(AISI S100-16 w/S2-20)Code:
Date: 08/14/2026
Simpson Strong-Tie® CFS Designer™ 6.2.0.0
Reactions
Vertical Horizontal
Max Rxn (lb)
Load Comb.
Min Rxn (lb)
Load Comb.
Max Rxn (lb)
Load Comb.
Min Rxn (lb)
Load Comb.
R1 1430.32 2 -47.07 6 23.33 3 -88.67 6
R2 3337.41 2 -144.30 6 0.00 1 0.00 1
Mmax (ft-lb)
Load Comb.
Mmax/ Ma
Load Comb.
Load Comb.
Span Defl
Overhang Defl
Rafter Flexural and Deflection
Ma (ft-lb)
3004 0.59 2 L/1350 2 L/1350 25126
Support Load (lb)
Bearing (in)
Pa (lb)
Pn (lb)
Max Intr.
Load Comb.
Stiffeners Req'd
Rafter Bending and Web Crippling
Load Comb.
R1 1410.9 1.00 828.0 1449.1 0.89 2 YES2
R2 3292.0 3.50 2485.4 4100.9 0.98 2 YES2
Support Vmax (lb)
Load Comb.
Va Factor V/Va M/Ma
V + M Intr.
Rafter Bending and Shear
Load Comb.
R1 1411 2 0.51 0.00 0.511.000 2
R2 1948 2 0.70 0.41 0.821.000 2 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Joist 1
IBC 2021(AISI S100-16 w/S2-20)Code:
Mid-Pt
Section : 1200S162-54 (50 ksi) @ 24" o.c. Single C Stud (punched)
Maxo = 4776.1(ft-lb) 1377.4Va = I = 14.298
Flexural Bracing None
0 lb-in/inDistortional Buckling, K-phi
NoneDistortional Buckling Bracing, Lm
Axial Bracing NA
Bracing, Interconnection and Distortional Buckling Parameters
Span Overhang
None
0 lb-in/in
None
Span (psf)
Load Cases Overhang
(psf)
Dead Load 20 20
Live Load 20 20
Snow Load 150 150
Inward Wind Load 5 5
Outward Wind Load -19 -19
Dead
Load Combinations
LiveLC Number Snow Inward Wind
Outward Wind
1 1 1 0 0 0
2 1 0 1 0 0
3 1 0 0 1 0
4 1 0.75 0 0.75 0
5 1 0 0.75 0.75 0
6 0.6 0 0 0 1 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Joist 2
IBC 2021(AISI S100-16 w/S2-20)Code:
Reactions
Vertical Horizontal
Max Rxn (lb)
Load Comb.
Min Rxn (lb)
Load Comb.
Max Rxn (lb)
Load Comb.
Min Rxn (lb)
Load Comb.
R1 547.32 2 -18.91 6 7.50 3 -28.50 6
R2 985.17 2 -42.60 6 0.00 1 0.00 1
Mmax (ft-lb)
Load Comb.
Mmax/ Ma
Load Comb.
Load Comb.
Span Defl
Overhang Defl
Rafter Flexural and Deflection
Ma (ft-lb)
440 0.12 2 L/18875 2 L/15738 23766
Support Load (lb)
Bearing (in)
Pa (lb)
Pn (lb)
Max Intr.
Load Comb.
Stiffeners Req'd
Rafter Bending and Web Crippling
Load Comb.
R1 539.9 1.00 N/A N/A 2 YES2
R2 971.8 3.50 N/A N/A 2 YES2
Support Vmax (lb)
Load Comb.
Va Factor V/Va M/Ma
V + M Intr.
Rafter Bending and Shear
Load Comb.
R1 540 2 0.39 0.00 0.391.000 2
R2 636 2 0.46 0.04 0.461.000 2 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Joist 2
IBC 2021(AISI S100-16 w/S2-20)Code:
Section: (2) 1200S200-97 (50 ksi) Back-To-Back C Stud (punched)
Maxo = 23252.2 ft-lb 16294.0 lbVa = I = 60.35 in^4
Loads have not been modified for strength checks Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors - Design Method =AISI S100
Span KyLy, KtLt Flexual, Distortional Connector
Stress Ratio
Axial
Left Cant. NA None, 42.0" N/A -
Span NA 60.0", 96.0" N/A -
Right Cant. NA None, 42.0" N/A -
Web Crippling
Support Load (lb) (in) Max Int. Stiffener?
Bearing Pa M
(lb) (ft-lbs)
R1 9169.20 1.00 NO10994.5 0.6612765.2
R2 9169.20 1.00 NO10994.5 0.6612765.2
P1 2547.00 1.50 NO0.0 0.138797.7
P2 2547.00 1.50 NO0.0 0.138797.7
"*" after support means punched near support
P1Point Loads P2
Load(lb) 2547.002547.00
0.00 15.00X-Dist.(ft)
Code Check Required Interaction NotesAllowed
Max. Axial, lbs 0.0(t) 0% KΦ=0.00 lb-in/in Max KL/r = N/A-Left Cant.
Max. Shear, lbs 3735.6 25% Shear (Punched)14822.2
Max. Moment (MaFy, Ma-dist), ft-lbs 10994.5 54% Ma-dist (control),KΦ=0.00 lb-in/in20450.6
Moment Stability, ft-lbs 8450.6 36%23252.2
Shear/Moment 0.54 54% Shear 3735.6, Moment 10994.51.00
Axial/Moment 0.54 54% Axial 0.0(c), Moment 10994.51.00
Deflection Cant. L/2392 - 2 x (Cant. + span inflection),Δ=0.0647″-
L/6 interconnection spacing (S100 l1.1), in 7 See S100 l1.1 for add'nl Req'mts
Max. Axial, lbs 0.0(t) 0% KΦ=0.00 lb-in/in Max KL/r = N/A-Span
Max. Shear, lbs 5433.6 37% Shear (Punched)14822.2
Max. Moment (MaFy, Ma-dist), ft-lbs 10994.5 54% Ma-dist (control),KΦ=0.00 lb-in/in20450.6
Moment Stability, ft-lbs 4013.5 18%21774.4
Shear/Moment 0.60 60% Shear 5433.6, Moment 10994.51.00
Axial/Moment 0.54 54% Axial 0.0(c), Moment 10994.51.00
Deflection Span L/9111 - Δ= 0.0105″-
L/6 interconnection spacing (S100 l1.1), in 16 See S100 l1.1 for add'nl Req'mts
Max. Axial, lbs 0.0(t) 0% KΦ=0.00 lb-in/in Max KL/r = N/A-Right Cant.
Max. Shear, lbs 3735.6 25% Shear (Punched)14822.2
Max. Moment (MaFy, Ma-dist), ft-lbs 10994.5 54% Ma-dist (control),KΦ=0.00 lb-in/in20450.6
Moment Stability, ft-lbs 8450.6 36%23252.2 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Joist 3
IBC 2021(AISI S100-16 w/S2-20)Code:
Shear/Moment 0.54 54% Shear 3735.6, Moment 10994.51.00
Axial/Moment 0.54 54% Axial 0.0(c), Moment 10994.51.00
Deflection Cant. L/2392 - 2 x (Cant. + span inflection),Δ=0.0647″-
L/6 interconnection spacing (S100 l1.1), in 7 See S100 l1.1 for add'nl Req'mts
Support Rx(lb) Ry(lb) Simpson Strong-Tie Connector Connector Interaction
Anchor Interaction
NAR1 0.0 9169.2 NABy Others & Anchorage Designed by Engineer
NAR2 0.0 9169.2 NABy Others & Anchorage Designed by Engineer
* Reference catalog for connector and anchor requirement notes as well as screw placement requirements www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Joist 3
IBC 2021(AISI S100-16 w/S2-20)Code:
Section: (2) 1200S200-118 (50 ksi) Back-To-Back C Stud (punched)
Maxo = 29265.6 ft-lb 29971.1 lbVa = I = 72.69 in^4
Loads have not been modified for strength checks Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors - Design Method =AISI S100
Span KyLy, KtLt Flexual, Distortional Connector
Stress Ratio
Axial
Left Cant. NA None, 42.0" N/A -
Span NA 60.0", 96.0" N/A -
Right Cant. NA None, 42.0" N/A -
Web Crippling
Support Load (lb) (in) Max Int. Stiffener?
Bearing Pa M
(lb) (ft-lbs)
R1 10124.50 1.00 NO26037.4 0.8218593.9
R2 10124.50 1.00 NO26037.4 0.8218593.9
P1 6622.00 1.50 NO0.0 0.2412487.9
P2 6622.00 1.50 NO0.0 0.2412487.9
"*" after support means punched near support
P1Point Loads P2
Load(lb) 6622.006622.00
0.00 15.00X-Dist.(ft)
Code Check Required Interaction NotesAllowed
Max. Axial, lbs 0.0(t) 0% KΦ=0.00 lb-in/in Max KL/r = N/A-Left Cant.
Max. Shear, lbs 8256.5 37% Shear (Punched)22073.4
Max. Moment (MaFy, Ma-dist), ft-lbs 26037.4 97% Ma-dist (control),KΦ=0.00 lb-in/in26858.8
Moment Stability, ft-lbs 20344.5 70%29265.6
Shear/Moment 0.97 97% Shear 8256.5, Moment 26037.41.00
Axial/Moment 0.97 97% Axial 0.0(c), Moment 26037.41.00
Deflection Cant. L/518 - 2 x (Cant. + span inflection),Δ=0.2443″-
L/6 interconnection spacing (S100 l1.1), in 7 See S100 l1.1 for add'nl Req'mts
Max. Axial, lbs 0.0(t) 0% KΦ=0.00 lb-in/in Max KL/r = N/A-Span
Max. Shear, lbs 1868.0 8% Shear (Punched)22073.4
Max. Moment (MaFy, Ma-dist), ft-lbs 26037.4 97% Ma-dist (control),KΦ=0.00 lb-in/in26858.8
Moment Stability, ft-lbs 23637.4 87%27271.7
Shear/Moment 0.89 89% Shear 1868.0, Moment 26037.41.00
Axial/Moment 0.97 97% Axial 0.0(c), Moment 26037.41.00
Deflection Span L/928 - Δ= 0.1034″-
L/6 interconnection spacing (S100 l1.1), in 16 See S100 l1.1 for add'nl Req'mts
Max. Axial, lbs 0.0(t) 0% KΦ=0.00 lb-in/in Max KL/r = N/A-Right Cant.
Max. Shear, lbs 8256.5 37% Shear (Punched)22073.4
Max. Moment (MaFy, Ma-dist), ft-lbs 26037.4 97% Ma-dist (control),KΦ=0.00 lb-in/in26858.8
Moment Stability, ft-lbs 20344.5 70%29265.6 www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Joist 4
IBC 2021(AISI S100-16 w/S2-20)Code:
Shear/Moment 0.97 97% Shear 8256.5, Moment 26037.41.00
Axial/Moment 0.97 97% Axial 0.0(c), Moment 26037.41.00
Deflection Cant. L/518 - 2 x (Cant. + span inflection),Δ=0.2443″-
L/6 interconnection spacing (S100 l1.1), in 7 See S100 l1.1 for add'nl Req'mts
Support Rx(lb) Ry(lb) Simpson Strong-Tie Connector Connector Interaction
Anchor Interaction
NAR1 0.0 10124.5 NABy Others & Anchorage Designed by Engineer
NAR2 0.0 10124.5 NABy Others & Anchorage Designed by Engineer
* Reference catalog for connector and anchor requirement notes as well as screw placement requirements www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Joist 4
IBC 2021(AISI S100-16 w/S2-20)Code:
Section: 1200S200-68 (50 ksi) Single C Stud (punched)
Maxo = 7392.7 ft-lb 2770.7 lbVa = I = 20.86 in^4
Loads have not been modified for strength checks Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors - Design Method =AISI S100
Span KyLy, KtLt Flexual, Distortional Connector
Stress Ratio
Axial
Left Cant. NA None, 42.0" N/A -
Span NA 60.0", 96.0" - -
Right Cant. NA None, 42.0" N/A -
Web Crippling
Support Load (lb) (in) Max Int. Stiffener?
Bearing Pa M
(lb) (ft-lbs)
R1* 2547.00 1.00 YES2080.0 0.991709.7
R2* 2547.00 1.00 YES2080.0 0.991709.7
"*" after support means punched near support
Code Check Required Interaction NotesAllowed
Max. Axial, lbs 0.0(t) 0% KΦ=0.00 lb-in/in Max KL/r = N/A-Left Cant.
Max. Shear, lbs 1188.6 43% Shear (Punched)2770.7
Max. Moment (MaFy, Ma-dist), ft-lbs 2080.0 34% Ma-dist (control),KΦ=0.00 lb-in/in6192.4
Moment Stability, ft-lbs 1327.9 18%7392.7
Shear/Moment 0.51 51% Shear 1188.6, Moment 2080.01.00
Axial/Moment 0.34 34% Axial 0.0(c), Moment 2080.01.00
Deflection Cant. L/4846 - 2 x (Cant. + span inflection),Δ=0.0199″-
Max. Axial, lbs 0.0(t) 0% KΦ=0.00 lb-in/in Max KL/r = N/A-Span
Max. Shear, lbs 1358.4 49% Shear (Punched)2770.7
Max. Moment (MaFy, Ma-dist), ft-lbs 2080.0 34% Ma-dist (control),KΦ=0.00 lb-in/in6192.4
Moment Stability, ft-lbs 636.8 9%6904.5
Shear/Moment 0.57 57% Shear 1358.4, Moment 2080.01.00
Axial/Moment 0.34 34% Axial 0.0(c), Moment 2080.01.00
Deflection Span L/33194 - Δ= 0.0029″-
Max. Axial, lbs 0.0(t) 0% KΦ=0.00 lb-in/in Max KL/r = N/A-Right Cant.
Max. Shear, lbs 1188.6 43% Shear (Punched)2770.7
Max. Moment (MaFy, Ma-dist), ft-lbs 2080.0 34% Ma-dist (control),KΦ=0.00 lb-in/in6192.4
Moment Stability, ft-lbs 1327.9 18%7392.7
Shear/Moment 0.51 51% Shear 1188.6, Moment 2080.01.00
Axial/Moment 0.34 34% Axial 0.0(c), Moment 2080.01.00
Deflection Cant. L/4846 - 2 x (Cant. + span inflection),Δ=0.0199″-
Support Rx(lb) Ry(lb) Simpson Strong-Tie Connector Connector Interaction
Anchor Interaction
NAR1 0.0 2547.0 NABy Others & Anchorage Designed by Engineer
NAR2 0.0 2547.0 NABy Others & Anchorage Designed by Engineer www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Joist 5
IBC 2021(AISI S100-16 w/S2-20)Code:
* Reference catalog for connector and anchor requirement notes as well as screw placement requirements www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Joist 5
IBC 2021(AISI S100-16 w/S2-20)Code:
Job#:
Date:
By:
Phone: 801.355.5656 • Fax: 801.355.5950
DNR Scofield
CHB
08.12.2026
260651
Header Calc:
Opening Width - 6.33 ft Opening Height - 7.0 ft Dead Load = 20 psf Snow Load = 214 psf Uniform Load on Header - w_TL = (20 psf + 0.7 * 214 psf) * 8 ft = 1358.4 plf = 1019 lbf per stud Use a 600S162-54 Boxed Header w/ 600T125-54 T&B. Works for both MH-1 & MH-2.
Design Loads
Wall Lateral Pressure :
RO Lateral Pressure :
Parapet Lateral Pressure :
12 psf
4-Ways
20 psf
Lateral element force multiplier
Strength :
Deflection : 0.7
1.0
Gravity Load at Header: 9 psf
Box (lateral top, bottom)Header:
Cant. Deflection:
Lateral Deflection Limit:
Gravity Deflection Limit:
No Limit
No Limit
2 x Cantilever
Additional Pt. Load ea. Stud :
1019 lbs
Back-to-Back Member L/6 Interconnection Spacing per AISI S100 l1.1
Member Span Cantilever
Jamb Studs 20.0 in 4.0 in
See AISI S100 l1.1 for Add'nl Requirements
Component(s) Members(s) Flexural Bracing Axial KyLy Axial KtLt
Distortional K-Phi(lb-in/in)
Distortional Lm
Brace Settings
Interconnection Spacing
Wall Studs 600S162-54(50), Single@16 in o/c 60 in 60 in 0 None60 in N/A
Jamb Studs 600S162-54(50), Back-To-Back 60 in 60 in 0 None60 in 12 in
Vertical Header 800S162-54(50), Boxed Full N/A 0 NoneN/A N/A
Lat. Top Head 600T125-54(50), Single Full N/A 0 NoneN/A N/A
Lat. Bottom Head 600T125-54(50), Single Full N/A 0 NoneN/A N/A
Max KL/rComponent(s) Members(s)
Axial Load (lb)
Max. Moment (ft-lb)
Max.
Shear (lb)
Bottom Reaction (lb)
Top or End Reaction (lb)
Analysis Results
Wall Studs 600S162-54(50), Single@16 in o/c 1019.0 85.3 74.7 138.7174.2105
Jamb Studs 600S162-54(50), Back-To-Back 2561.3 154.5 214.6 172.7438.788
Vertical Header 800S162-54(50), Boxed N/A 2561.3 N/A 2561.34053.2N/A
Lat. Top Head 600T125-54(50), Single N/A 14.8 N/A 14.823.4N/A
Lat. Bottom Head 600T125-54(50), Single N/A 60.1 N/A 60.1126.8N/A
Component(s) Members(s)
Deflection
A + M V + M Web Stiffners Design OK
Design Results
Span Parapet
Interaction
Defl.
Wall Studs 600S162-54(50), Single@16 in o/c L/4780 0.04 No Yes0.33L/3622 -
Jamb Studs 600S162-54(50), Back-To-Back L/3706 0.09 No Yes0.35L/2445 -
Vertical Header 800S162-54(50), Boxed L/858 0.66 R1, R2 Yes0.66NA -
Lat. Top Head 600T125-54(50), Single L/42552 0.02 No Yes0.02NA -
Lat. Bottom Head 600T125-54(50), Single L/8169 0.02 No Yes0.09NA -
Simpson Strong-Tie® Connectors @ Studs www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Header Calc
IBC 2021(AISI S100-16 w/S2-20)Code:
Support Rx(lb) Ry(lb) Simpson Strong-Tie® Connector
Connector
Interaction
Anchor
Interaction
12.44 %R2 138.67 0.00 19.67 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel
33.91 %R1 74.67 1163.00 10.85 %600T125-33 (33) & (1) .157" SST PDPA/PDPAT-62KP to steel (3/16" to 1/2" thickness)
* Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Support Rx(lb) Ry(lb) Simpson Strong-Tie® Connector
Connector
Interaction
Anchor
Interaction
Simpson Strong-Tie® Connectors @ Jambs
15.49 %R2 172.72 0.00 24.50 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel
48.72 %R1 214.57 2675.28 41.58 %600T125-33 (33) & (2) .157" SST PDPA/PDPAT-62KP to steel (3/16" to 1/2" thickness)
* Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Span/Parapet
Bracing Length(in.)
Design Number of Braces Pn(lb.)
SUBH
(Min)¹
SUBH
(Max)¹
MSUBH
(Min)¹
Simpson Strong-Tie® Wall Stud Bridging Connectors @ Studs
MSUBH
(Max)¹
LSUBH
(Min)¹
LSUBH
(Max)¹
Top Parapet Span N/A N/A N/A N/AN/A N/AN/A N/A
Span 60 8062.1 OK (0.26) OK (0.17) OK (0.17)2 OK (0.11)OK (0.38) OK (0.25)
Span/Parapet
Bracing Length(in.)
Design Number of Braces Pn(lb.)
SUBH
(Min)¹
SUBH
(Max)¹
MSUBH
(Min)¹
Simpson Strong-Tie® Wall Stud Bridging Connectors @ Jambs
MSUBH
(Max)¹
LSUBH
(Min)¹
LSUBH
(Max)¹
Top Parapet Span N/A N/A N/A N/AN/A N/AN/A N/A
Span 60 N/A N/A N/A N/AN/A N/AN/A N/A
1) Values in parentheses are stress ratios.
2) “Min.” designates a solution with the minimum number of fasteners (1) #10 screw.
9) Reference
Notes:
4) Bridging connector solutions display only if the flexural and axial bracing settings are the same.
5) If the bracing length is larger than the span length, bridging connectors are not designed.
for latest load data, important information, and general notes. www.strongtie.com
3) “Max.” designates a solution requiring the maximum number of fasteners (2) #10 screws.
6) “N/A” will also appear if the brace length is greater than the span length, i.e., if a cantilever is 24” long and the brace length is 60”.
7) “No Good” will display when the required brace strength exceeds the corresponding connector capacity.
8) “No Soln” will display if the stud thickness is outside the range of the bridging connector applicability.
For example, an 18 ga stud is outside the acceptable thickness range for MSUBH, which is 16 ga to 12 ga.
www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Header Calc
IBC 2021(AISI S100-16 w/S2-20)Code:
Section : 600S162-54 (50 ksi) @ 16" o.c. Single C Stud (punched)
Maxo = 2313.4 ft-lb 2822.9 lbVa = I = 2.86 in^4
Loads have not been modified for strength checks Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors - Design Method =AISI S100
Span KyLy, KtLt Flexual, Distortional Connector
Stress Ratio
Axial
Span 60.0", 60.0" 60.0", 120.0" LSUBH3.25 (Min) 0.45
Web Crippling
Support Load (lb) (in) Max Int. Stiffener?
Bearing Pa M
(lb) (ft-lbs)
R2 80.00 --Shear Connection w/ clip-- NO
R1 80.00 --Stud/Track Design, Ref Connectors-- NO
Gravity Load
Type Load (lb)
Uniform 12.00plf
P1y 2000.00lb @ 10.00ft
Code Check Required Interaction NotesAllowed
Max. Axial, lbs 2120.0(c) 47% KΦ=0.00 lb-in/in Max KL/r = 1054478.9(c)Span
Max. Shear, lbs 80.0 4% Shear (Punched)1947.4
Max. Moment (MaFy, Ma-dist), ft-lbs 200.0 10% Ma-dist (control),KΦ=0.00 lb-in/in1930.2
Moment Stability, ft-lbs 200.0 11%1813.9
Shear/Moment 0.09 9% Shear 0.0, Moment 200.01.00
Axial/Moment 0.58 58% Axial 2063.5(c), Moment 199.31.00
Deflection Span L/4018 - Δ= 0.0299″-
Support Rx(lb) Ry(lb) Simpson Strong-Tie Connector Connector Interaction
Anchor Interaction
7.17 %R2 80.0 0.0 11.35 %SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel
36.33 %R1 80.0 2120.0 11.63 %600T125-33 (33) & (1) .157" SST PDPA/PDPAT-62KP to steel (3/16" to 1/2" thickness)
* Reference catalog for connector and anchor requirement notes as well as screw placement requirements www.strongtie.comSIMPSON STRONG-TIE COMPANY INC.
Project Name: Metal Stud Designs
Model: Typical Wall Stud
IBC 2021(AISI S100-16 w/S2-20)Code:
LATERAL KEY PLAN
WALL LINE A
WALL LINE B
W A
LL
L
IN
E
C
W A
LL
L
IN
E
C
Job#:
Date:
By:
Phone: 801.355.5656 • Fax: 801.355.5950
DNR Scofield
CHB
08.12.2026
260651
Lateral Loading:
Dead Load = 20 psf Snow Load = 214 psf
Area = 16 ft * 16 ft = 256 ft^2 Weight = (20 psf + 0.15 * 214 psf) * Area = 13337.6 lbf = 13.4 kips V = Cs * W = 0.080 * 13.4 kips = 1.072 kips Shear per Line = 1.072 kips / 4 = 0.268 kips
Wall Line C:
Shear per Ft of Wall = 0.268 kips / 6.25 ft = 0.043 klf; Therefore, all panels are acceptable with 6" nailing for the sheathing.