3PH 277 480 CT PT cabinet 201 to 1201amp.pdf
PDF 201 KB Posted
- Solicitation number
- rfp-champaign-il-002
- Issued by
- Champaign County, Illinois
About this file
This is an Instrument Transformer installation service manual document from Ameren Illinois providing technical specifications for CT/PT rated meter installation at 600 volts, 480Y/277 volts, three-phase, four-wire service for electric systems rated between 201 and 1200 amperes. The document outlines construction requirements and installation guidelines for current transformer (CT) and potential transformer (PT) equipment positioning, including mandatory placement heights of 36 inches minimum to 66 inches maximum above final grade. The specifications require bar-type CTs, galvanized steel or aluminum rigid metal conduit (RMC), EMT, or Schedule 40 piping, with neutral conductor termination along the enclosure side and ground-level conduit runs of minimum 24 inches if duct-run or 30 inches if direct-buried cable. A warning label indicating that meter removal does not de-energize service must be affixed to the CT enclosure lid, and 480-volt stickers are required. Indoor CT installations require prior approval from both the Field Metering Supervisor and Field Supervising Engineer.
This technical document directly supports the EV Charging Station Installation project at the Microtel Inn by Wyndham in Champaign, Illinois, which requires substantial electrical infrastructure including a 750kVA utility transformer, 1200A main switchboard, and CT/PT metering cabinet to support four Tesla V4 Superchargers with 625kVA power cabinet specifications operating at 480V AC input. The project requires coordination with Ameren Illinois utility services, Illinois electrical licensure, and EVITP certification for installation personnel, with completion of civil work, signage, permits, inspections, and all regulatory approvals.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Section 1001 Instrument Transformer – CT / PT Rated Meter Installation Service
600 Volt
480Y/277 VOLTS, 3-PHASE, 4-WIRE 201 – 1200 AMPERES
ELECTRIC SERVICE
MANUAL
Figure 1001-6
36” Min 66” Max
CONSTRUCTION NOTE(s): (FIGURE 1001-6)
1. Refer to ASM Section 1001.04 for detailed meter socket requirements.
2. Refer to ASM Section 200.02 for indoor metering criteria. Indoor CT installations require prior approval by the Field Metering Supervisor and Field Supervising Engineer.
3. Instrument Transformers shall be located 36 in. minimum to 66 in. Maximum above final grade.
4. Neutral conductors will terminate along the side of the enclosure.
5. For service riser conduits, refer to ASM Section 700.03 (A) (2).
6. Requires bar-type CTs.
Ameren to install a 480 volt sticker on the lid (door) of CT enclosure
X H
WARNING
Removing Meter does not
De-Energize Service
X H
XH 4” Min
54” Min 66” Max
1-1/2” Galv. Steel RMC, Alum. RMC, EMT, or Sch 40 (or greater)
Ground Level
24” min if duct run or 30” min if direct buried cable
S E
E S
E C
T
IO
N
G R
O U
N D
IN
G
E
LE
C
T R
O D
E
File details come from the government source that posted it. Updated .