This is a construction design document for an electric vehicle charging station installation project at the Microtel Inn by Wyndham Champaign located at 1615 Rion Drive, Champaign, Illinois. The project is under the jurisdiction of the Champaign County Regional Planning Commission (CCRPC) and requires compliance with the 2024 Illinois Building Code, 2024 International Fire Code, 2024 International Building Code, 2023 National Electrical Code, and other applicable standards. The scope of work includes installation of four Tesla V4 Superchargers (500 kW each, limited to 150 kW output) with NACS + CCS1 connectors via Tesla Magic Dock, conversion of four standard parking stalls into three standard EV parking stalls and one accessible EV parking stall, installation of one 750 kVA utility transformer, one 1200A main switchboard, one Tesla V4 Supercharger Power Cabinet (625 kVA), one CT/PT metering cabinet, four EV sign posts, a 54-square-foot parallel curb ramp sidewalk with curb, and five concrete foundations for various equipment. Civil work includes demolition of existing asphalt pavement (942 square feet) and landscaping (640 square feet), grading to comply with ADA requirements, construction of new asphalt pavement (968 square feet), installation of concrete curbs, bollards, striping, and site restoration. The document indicates this is a design-for-construction document dated August 21, 2026, prepared by Nordic Asia Solutions as the engineer with Universal EV LLC as the developer and Connect Electrical as the contractor.
The contractor shall obtain all necessary permits from federal, state, and local governing agencies and coordinate with the City of Champaign Building Codes Department and the Champaign County Engineer for required inspections. All work must comply with utility company requirements and applicable codes in effect at the time of building permit issuance. The contractor is responsible for verifying existing utility locations through 811 (J.U.L.I.E. Underground) and conducting a private utility locate before construction begins. The contractor must warrant all installed systems for proper operation for not less than one calendar year from project completion and shall submit as-built redlines, operation and maintenance manuals, catalogs, and shop drawings upon completion. Post-completion civil and electrical drawings must be updated to reflect as-built status and submitted to Illinois DOT. The project requires Illinois Electrical License and EVITP certification for qualified personnel. A build-back-better certification regarding equipment sourcing is required.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IMAGE REFERENCE
AERIAL IMAGERY PROVIDED BY:
SITE
VICINITY MAP DRAWING INDEX PROJECT DESCRIPTION
SITE INFORMATIONAPPLICABLE CODES C
O
VE
R
S H
EE
T
NOTE:
IN THE EVENT OF CONFLICT, THE MOST RESTRICTIVE CODE SHALL PREVAIL.
PERMITTING JURISDICTION:
CHAMPAIGN COUNTY REGIONAL PLANNING
COMMISSION (CCRPC), CHAMPAIGN COUNTY
LATITUDE :
40°09'33.7"N
LONGITUDE :
88°16'22.4"W
SITE COUNTY:
CHAMPAIGN COUNTY
SITE ADDRESS:
1615 RION DR,
CHAMPAIGN, IL 61822
CONTRACTOR SHALL COMPLETE INSTALL PER THE SIGNED AND THE SEALED SET OF DRAWINGS.
ANY NECESSARY DEVIATIONS FROM THE DRAWINGS MUST BE SUBMITTED THROUGH AN RFI
REQUEST PROCESS WITH ENGINEERING FOR AN APPROVAL PRIOR TO CONTRACTOR PROCEEDING
WITH A DEVIATION OF THE SIGNED AND SEALED SET OF DRAWINGS.
CONTRACTOR SHALL VERIFY ALL PLANS, EXISTING DIMENSIONS AND CONDITIONS ON THE JOB SITE
THEN IMMEDIATELY NOTIFY THE ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE WORK.
CONTRACTOR IS TO VERIFY PRESENCE
AND EXACT LOCATION OF ALL UTILITIES
PRIOR TO CONSTRUCTION.
CAUTION!!
INSTALLATION OF ELECTRIC VEHICLE CHARGING INFRASTRUCTURE
MICROTEL INN BY WYNDHAM CHAMPAIGN
SITE
EV LOCATION
ALL WORK SHALL COMPLY WITH THE FOLLOWING APPLICABLE CODES:
• 2024 ILLINOIS BUILDING CODE
• 2018 ILLINOIS ACCESSIBILITY CODE
• 2024 INTERNATIONAL FIRE CODE
• 2024 INTERNATIONAL BUILDING CODE
• 2024 INTERNATIONAL EXISTING BUILDING CODE
• 2023 NATIONAL ELECTRICAL CODE
SHEET NUMBER SHEET TITLE THIS PLAN IS DEVELOPED WITH THE INTENT TO PROVIDE PUBLIC ELECTRIC VEHICLE (EV) CHARGING STATIONS IN AN EXISTING PARKING LOT. THE EXTENT OF DESIGN WITHIN THIS CONSTRUCTION DOCUMENT INCLUDES THE EV
CHARGING STATIONS AND THEIR ACCOMPANYING CIVIL AND ELECTRICAL INFRASTRUCTURE.
• DEMOLITION OF EXISTING SURFACES FOR THE INSTALLATION OF EV CHARGERS.
• GRADING OF SURFACES ASSOCIATED WITH EV SERVICE EQUIPMENT TO COMPLY WITH ADA
REQUIREMENTS.
SCOPE OF WORK:
• CONVERTING (4) STANDARD PARKING STALLS TO (3) STANDARD EV PARKING STALLS AND (1) ACCESSIBLE
EV PARKING STALLS.
• INSTALL (1) UTILITY TRANSFORMER TO BE COORDINATED WITH UTILITY PROVIDER.
• INSTALL (1) MAIN SWITCHBOARD.
• INSTALL (1) TESLA V4 SUPERCHARGER POWER CABINET.
· INSTALL (4) TESLA V4 SUPERCHARGER.
· INSTALL (4) EV SIGN POSTS.
• CONSTRUCT 54 SQ.FT PARALLEL CURB RAMP SIDEWALK W/CURB.
• CONSTRUCT (4) CONCRETE EV CHARGER FOUNDATIONS.
• CONSTRUCT (1) CONCRETE CT CABINET FOUNDATION.
• CONSTRUCT (1) CONCRETE SWITCHBOARD FOUNDATION.
• CONSTRUCT (1) CONCRETE POWER CABINET FOUNDATIONS.
• CONSTRUCT (1) CONCRETE TRANSFORMER FOUNDATION.
NOT TO SCALE
NORTH
GENERAL PLAN DESIGNATION : GENERAL COMMERCIAL
1615 RION DR,
CHAMPAIGN, IL 61822
NOT TO SCALE
NORTH
CONTRACTOR NOTES
AERIAL MAP
CODE INSPECTIONS:
OWNER AND/OR CONTRACTOR SHALL COORDINATE CONSTRUCTION ACTIVITIES WITH CITY OF CHAMPAIGN BUILDING CODES DEPARTMENT AND THE CHAMPAIGN COUNTY ENGINEER AS NECESSARY TO COMPLY WITH ANY AND ALL INSPECTIONS REQUIRED BY FEDERAL, STATE, AND/OR LOCAL CODE AUTHORITIES. IT IS THE RESPONSIBILITY OF THE DEVELOPER TO OBTAIN ALL APPROPRIATE PERMITS FROM ALL THE GOVERNING AGENCIES THAT HAVE JURISDICTION
OVER THE AREA WHERE THE WORK IS PROPOSED TO BE DONE.
NOTE: NO CONSTRUCTION PERMITS SHALL
BE ISSUED UNLESS AND UNTIL A PLAN IS
APPROVED BY THE CHAMPAIGN COUNTY
REGIONAL PLANNING COMMISSION (CCRPC)
PERMITS:
IT IS THE RESPONSIBILITY OF THE DEVELOPER/CONTRACTOR TO OBTAIN ALL APPROPRIATE PERMITS FROM ALL THE GOVERNING AGENCIES THAT HAVE JURISDICTION OVER THE AREA WHERE WORK IS PROPOSED TO BE DONE.
OWNER:
MICROTEL INN BY WYNDHAM CHAMPAIGN
ENGINEER:
NORDIC ASIA SOLUTIONS
CONTRACTOR:
CONNECT ELECTRICAL
DEVELOPER:
UNIVERSAL EV LLC.
NOTES:
· THE PLANS PROVIDED ARE DESIGNED FOR CONSTRUCTION. POST COMPLETION OF CONSTRUCTION, DRAWINGS (CIVIL AND ELECTRICAL)
ARE TO BE UPDATED TO REFLECT AS BUILT STATUS AND SUBMITTED TO ILLINOIS DOT.
· CONTRACTOR MUST REFER THE O&M AND COMMISSIONING PLAN DOCUMENTS FROM UNIVERSAL EV FOR ADDITIONAL CONSTRUCTION
RELATED DETAIL THAT COULD NOT BE INCLUDED IN THESE PLANS.
CS0.0 COVER SHEET
G1.0 GENERAL NOTES
C0.0 PROPERTY LAYOUT - EXISTING CONDITION
C3.0
CIVIL DETAILS - 1
EV2.0
EV CHARGER PLAN
EV3.0
CHARGING STALL SIGNAGE AND BOLLARD LAYOUT
CIVIL DETAILS - 2
EV1.0
THREE LINE DIAGRAM
C1.0 EV INFRASTRUCTURE PLAN
EV4.0
SYSTEM LABELING DETAILS
EV6.0 DATASHEETS - 1
EV7.0 DATASHEETS - 2
C0.1 DEMOLITION PLAN
ELECTRICAL DETAILS
EV5.0
C2.0
EXPANDED VIEW OF GRADING PLANC1.1
EV8.0 DATASHEETS - 3
305 W SPRING CREEK PKWY,
SUITE 100 B PLANO, TX 75023
M
IC
R O
TE
L
IN
N
B Y
W
YN
D H
A M
C H
A M
PA
IG
N
R
IO
N
D R
C
H A
M
PA
IG
N
, I L
0 1 2 3 4 5 6 7 8 9N o.
BY
D
AT
E
IS
SU
E
BL
O C
K
DESIGNED BY:
CHECKED BY:
DRAWN BY:
AD
JP
VP
DOCUMENT DATE: AUG 21, 2026
NORDIC PROJECT ID/R: UNE-24-66/23
SHEET NUMBER
SH
EE
T
TI
TL
E:
3040 78 TH AVENUE SE,
UNIT 1619, MERCER ISLAND, WA 98040
Mob:720 492 2885 | www.nordicasia.net www.nordicasia.net
UNIVERSAL EV LLC
NORDIC ASIA
CS0.0
http://www.nordicasia.net
G
EN
ER
AL
N O
TE
S
GENERAL NOTES :
1. Installation shall comply with all applicable laws, codes, government regulations, utility company requirements, etc. of all authorities having jurisdiction in effect at the time of the building permit.
2. Where conflicts exist between codes, standards or this specification, the higher requirement shall apply.
3. The contractor is solely responsible for the safety of his workers,all construction means, methods,techniques, sequences and procedures for coordinating the work under this contract.
4. Continuously maintain the construction premises in a neat and orderly condition.
damage to finishes shall be properly restored.
5. EVSE enclosure shall be NEMA rated.
6. EVSE cord length shall not exceed 25'.
7. EVSE charging stations has 4 doors i.e. front, rear, left and right. clear 24” distance on the four sides of a charger to be maintained for air circulation for cooling and opening panel for maintenance.
8. Mechanical and electrical support components, including strut and hardware, shall be hot dipped galvanized or equivalent electroplated finish.
9. All grounded conductors are white and equipment grounding conductors are green or bare per (NEC 200-6 (A), EX 5).
10. Liquid tight flexible metal conduit is generally suitable for installation in wet and dry locations. should it be employed, supports will be no more 12 inches from boxes (junction box, cabinets, or conduit fitting) and no more than 54 inches apart per
NEC.
11. All conductors below 100A shall be copper, unless otherwise noted.
12. In order to provide accessible operation of EVSE, a 3’ by 3’ (minimum) handicapped accessible operating area must be kept clear of vehicles and snow between the nose of the vehicle and the EVSE.
13. Reliable protective grounding must be provided. it is recommended to have separate dedicated ground exclusively for the charger considering the safety aspects. the ground resistance should be less than or equal to 4Ωcopper cable of in accordance with NEC shall be used to connect charge housing to external ground.
14. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter).
the raceway shall originate at the main service or sub-panel and shall terminate into a listed cabinet, box or enclosure in close proximity to the proposed location of the EV space.
15. Location of installation is not located where excessive water run-offs, pooling or flooding may occur.
16. Exterior signs and zoning concerns per site requirements.
FOOTINGS:
Footings shall bear on firm undisturbed material or on engineered fill material. Any unsuitable material shall be removed from the footings excavations and spot reinforced.
Foundation concrete shall be poured the same day excavations are opened, or steps shall be taken to adequately protect the open excavation.
FROST PROTECTION:
The underside of all footings and grade beams subjected to outside weather conditions shall have a minimum cover of 24" from top of finished grade to bottom of footing at any point above the footing, unless otherwise noted. This meets the frost depth of 24 inches as set forth by the Illinois Building Code, 2024 edition with latest errata.
SITE PREPARATION:
Prior to construction of any permanent structure, all topsoil and organic material, or frozen, wet, soft, loose, or undesirable soil shall be stripped from the site.
TYPICAL DETAILS:
Typical details shown herein are provided to illustrate design intent and minimum requirements. The contractor shall be responsible for accommodating specific field conditions while providing for the intent of the typical details.
REBAR CONTINUOUS THRU CORNERS:
All reinforcing steel shall be continuous through corners.
WELDING OF REINFORCEMENT STEEL:
Welding, including tack welding, of reinforcing steel is prohibited, unless weldable rebar is used with approval of engineer.
LAP SPLICES:
All lap splices shall be Class ‘B’ laps of minimum 24-inches in accordance with the requirements of ACI 318 – current edition, unless otherwise noted.
PLACEMENT OF STEEL:
All reinforcement, including dowels, shall be tied in place before placing concrete.
Inserting dowels into the plastic concrete shall not be permitted. Contractor shall furnish additional reinforcing bars as necessary, whether shown in plans or not, to tie all reinforcements in place and to form cages to withstand forces due to placing and consolidation of concrete.
CONCRETE PLACEMENT:
The placement of concrete shall conform to ACI-304R, "Guide for Measuring, Mixing, Transporting and Placing Concrete", unless otherwise noted herein. The sides of all footings and foundation systems shall be formed to the exact dimensions as shown herein. Pouring concrete in trenches using sides of earth as forms is not permitted, except for spread footings.
ADVERSE WEATHER:
Placement of concrete in cold weather shall be in accordance with ACI-306R-88, "Cold Weather Concreting". Placement of concrete in hot weather shall be in accordance with ACI-305R-99, "Hot Weather Concreting".
CHEMICAL ADMIXTURES:
No chemical or mineral admixtures other than those noted herein shall be used in concrete without expressed and written consent by the engineer.
SECURING STEEL REINFORCEMENT:
All steel reinforcement shall be secured in-place prior to placement of concrete.
ELEVATION OF FOOTINGS:
All footings shall bear on solid undisturbed soil of consistent bearing to generally support an allowable bearing pressure of 2000 PSF. Any soft or unsuitable areas of bearing shall be undercut and properly replaced.
DESIGN CONSIDERATIONS:
CONCRETE: f'c = 3500PSI (Curb & Sidewalk) f'c = 4000PSI (Footings/Foundations) (Min. Comp. Strength at 28 days) Air Content = 6% Slump 3 – 5 inches REINF.STEEL: fy = 60KSI (ASTM A615 Grade 60) DESIGN CODE: ILLINOIS Building Code, 2024
CONCRETE COVER:
Concrete cover shall be provided for reinforcing steel as outlined below unless noted otherwise:
FOOTINGS: Top: 2" Cover Bottom & Sides: 3" Clear (Unformed)
FORMED WALLS & PIERS: Stirrups: 1-1/2" Clear Reinf. Bars: 1-1/4" Clear
CONTROL JOINTS:
Sidewalks to have construction or control joints not to exceed 5ft apart.
Control joints shall be a min. depth of 25% of slab thickness unless noted otherwise and shall be sawn within 4 to 6 hours of placement of concrete.
SUBGRADE PREPARATION, EXCAVATION AND BACK FILLING:
Where fill is required under slabs, sidewalks, trenches, pavements, etc., fill material shall be compacted Dense Graded Aggregate (DGA).
All subgrade material to be compacted to 95% of its maximum density as measured by the Modified Proctor Method. Use mechanical compactor.
Slab sub base material under concrete shall be 57's crushed stone.
CODE INSPECTIONS:
Owner and/or contractor shall coordinate construction activities with code officials as needed to comply with any and all inspections as deemed necessary by code officials.
305 W SPRING CREEK PKWY,
SUITE 100 B PLANO, TX 75023
M
IC
R O
TE
L
IN
N
B Y
W
YN
D H
A M
C H
A M
PA
IG
N
R
IO
N
D R
C
H A
M
PA
IG
N
, I L
0 1 2 3 4 5 6 7 8 9N o.
BY
D
AT
E
IS
SU
E
BL
O C
K
DESIGNED BY:
CHECKED BY:
DRAWN BY:
AD
JP
VP
DOCUMENT DATE: AUG 21, 2026
NORDIC PROJECT ID/R: UNE-24-66/23
SHEET NUMBER
SH
EE
T
TI
TL
E:
3040 78 TH AVENUE SE,
UNIT 1619, MERCER ISLAND, WA 98040
Mob:720 492 2885 | www.nordicasia.net www.nordicasia.net
UNIVERSAL EV LLC
NORDIC ASIA
G1.0
NOTES:
• All jobsite activities will be conducted in a safe and orderly manner in compliance with OSHA requirements.
• The jobsite area shall be clearly marked and barricaded with orange barrels, safety cones, and/or caution fence as appropriate.
• All potential erosion shall be controlled in such a manner so as to prevent any displacement of silt to the area adjacent to the project.
• Erosion control shall be properly inspected and maintained during the entirety of the project.
• Contractor shall remove erosion control measures upon completion of project and only after potential for erosion has been eliminated.
• All equipment must comply with Build America Buy America Act (BABA).
WARRANTY AND DELIVERABLES UPON PROJECT COMPLETION:
A. WARRANTY: The contractor shall warranty all of the systems for proper operation installed by the contractor for not less than one calendar year from date of project completion. this completion date shall be set by the architect, engineer deliverables.
B. DELIVERABLES: The contractor shall submit a complete set of as-built redlines, all brochures, operating and maintenance manuals, catalogs, shop drawings, and other documents upon completion of the project.
SAFETY:
A. The general contractor shall be responsible for the safety of work area, adjacent areas and building occupants that are likely to be affected by the work under this contract. work shall conform to all osha requirements and the local jurisdiction.
B. The contractor shall provide portable fire extinguishers with a rating of not less than 2-a:10-b:c and shall be within 25 feet of travel distance to all portions of where the work is being completed during construction.
C. All existing active sewer, water, gas, electric, and other utilities shall be protected at all times, and where required for the proper execution of the work, shall be relocated as directed by the engineer. extreme caution should be used by the contractor when excavating or drilling piers around or near utilities. the contractor shall provide safety training for the working crew. this shall include but not be limited to a) fall protection, b) confined space, c) electrical safety, and d) trenching and excavation.
D. The general contractor shall be responsible for security of the site for the duration of construction until job completion.
SUPERCHARGER NOTES:
1. All conduit furnished and installed by contractor. All wiring furnished by contractor (except tesla signal wire) and installed by contractor.
2. All bushings and wiring internal of proposed service equipment provided by manufacturer. Any modifications shall require engineering approval prior to any changes being made.
3. All aluminum (Al) conductors to receive anti-oxidation coating during installation. All other conductors are copper unless otherwise noted.
4. The following charging cabinets and the charging posts used on this project comply with the following Standards:
· IEC 61851-23: 2014 / EN 61851-23: 2014
· UL 2202: 2009(R2012)
· CAN CSA C22.2 NO. 107.1-01(R2011)
6. The aforementioned standards identify the requirements met by the equipment, including but not limited to:
· Protection against electric shock
· Overload and short circuit protection
· Fault protection
· Degrees of protection against access to hazardous live parts
· The internal components of the system are proprietary. Any questions concerning actual internal protective devices must be coordinated directly with tesla.
7. Tesla supercharger signal wiring rated 1000V and used for power limited class 1 circuits shall be permitted to run in conduits, cable trays, wire ways or raceways along with associated DC conductors as allowed per NEC 725.48(B)(1), 300.3(C)(1) and 620.36.
8. Supercharger cabinet ac conductors sized under engineering supervision using thermal modeling software. Specifications about the trenching requirements are shown in the electrical details.
9. For DC runs in excess of 330 feet, contact tesla.
10. Underground conduits shall be schedule 40 PVC or UL listed HDPE. The aboveground portion of an underground / above ground transition shall be schedule 80 PVC or UL listed HDPE.
11. Above ground conduits exposed to vehicular or equivalent physical damage shall be RMC. Above ground conduits not exposed to vehicular or equivalent damage shall be permitted to be EMT.
12. Wire splices are not permitted to extend wire run length. Contractor is responsible for rerunning full length of wire if run length is miscalculated.
13. Special inspection is required for all post-installed concrete anchors.
14. Plant guarantee: contractor shall guarantee all plants for a period of one (1) year from date of project acceptance by the owner.
Contractor is responsible for plant maintenance for the first growing season.
15. If existing grass is damaged/removed during construction, contractor shall apply seed per hydroseed method. Rating of seed shall be per distributor based on species type.
16. Contractor shall match existing landscape; use grass, river rock, mulch etc. to match existing landscape around equipment, unless otherwise noted.
17. Contractor to install weed barrier in front of supercharger cabinets and switchboard. Barrier to extend full width and depth of
NEC required working clearances.
18. For (N) accessible EV charging area(S), contractor to field verify slopes are compliant per accessible stall detail (ref.
architectural or structural sheets). Regrade and add asphalt overlay, new full depth asphalt, and/or asphalt milling if required.
Existing spot elevations are approximate per survey data and are to be field verified by contractor.
19. Pad extents and footing to be confirmed by contractor prior to construction.
20. All precast foundations should have 1" separation filled with asphaltic material, between all precast pads and maintenance pads.
21. Switchboard dimensions and anchor locations are liable to change. Contractor to verify against vendor final shop drawings.
EXISTINGBITUMINOUSPARKING LOT
EXISTINGBITUMINOUSPARKING LOT
EX
IS
TI
NG
BI
TU
M
IN
O
US
DR
IV
EW
AY
RION DR
RION DR
RION DR
(APPROX.)
(A
PP
R O
X.
(APPROX.)
(APPROX.)
(APPROX.)
W
ID
E
W
AY
D R
IV
E
AI
SL
E
(A
PP
RO
X.
EX
IS
TI
N
G
BI
TU
M
IN
O
U S
PA
R
KI
N
G L
O T
EXISTINGBITUMINOUSPARKING LOT
T
CONCRETE CURB
CONCRETE CURB
EXISTING LIGHT POLE (TYP)
EXISTING LIGHT POLE (TYP)
EXISTING ELECTRIC
TRANSFORMER
STORM INLET
FIRE HYDRANT
EXISTING BUILDING
EXISTING LIGHT POLE (TYP)
EXISTING LIGHT POLE (TYP)
5' EXISTING CONCRETE
SIDEWALK (TYP)
EXISTING BILLBOARD
EXISTING LIGHT POLE (TYP)
EXISTING ADVERTISING
BILLBOARD
PR
O
PE
R
TY
L
IN
E
PROPERTY LINE
PROPERTY LINE
PR
O
PE
R
TY
L
IN
E
PR
O
PE
R
TY
L
IN
E
STORM INLET
5' EXISTING CONCRETE
SIDEWALK (TYP)
EXISTING LIGHT POLE (TYP)
EXISTINGLIGHT POLE (TYP)
PR
O
PE
RT
Y
LI
NE
STORM SEWER MANHOLE
EXISTING TRANSFORMER
EXISTING LANDSCAPING (TYP)
EXISTING STRIPING (TYP)
BENCHMARK
WATER VALVE
FIBER OPTIC
PEDESTAL
UNDERGROUND
ELECTRIC
FIBER OPTIC LINE
STORM SEWER
MANHOLE
N
E
S
W270
350 0 10
4O
170180190
Scale : N.T.S
PR
O
PE
R
TY
L
AY
O
U T
EX
IS
TI
N G
C O
N D
IT
IO
N
REQUIRED PARKING SPACES FOR DEVELOPMENT : 87*
EXISTING AVAILABLE PARKING SPACES : 87
PARKING SPACES ELIMINATED BY EV STALLS : 4
PARKING SPACES POST-CONSTRUCTION : 83
(*) NOTE: REQUIRED PARKING BASED ON REPORT OF
40 HOTEL SUITES AND MAX ON-SITE STAFF
OF 10 PERSONS.
PARKING SUMMARY
LEGEND:
- EXISTING BUILDING
- EXISTING LANDSCAPE
- EXISTING SIDEWALK
Note:
Property lines shown are approximate.
305 W SPRING CREEK PKWY,
SUITE 100 B PLANO, TX 75023
M
IC
R O
TE
L
IN
N
B Y
W
YN
D H
A M
C H
A M
PA
IG
N
R
IO
N
D R
C
H A
M
PA
IG
N
, I L
0 1 2 3 4 5 6 7 8 9N o.
BY
D
AT
E
IS
SU
E
BL
O C
K
DESIGNED BY:
CHECKED BY:
DRAWN BY:
AD
JP
VP
DOCUMENT DATE: AUG 21, 2026
NORDIC PROJECT ID/R: UNE-24-66/23
SHEET NUMBER
SH
EE
T
TI
TL
E:
3040 78 TH AVENUE SE,
UNIT 1619, MERCER ISLAND, WA 98040
Mob:720 492 2885 | www.nordicasia.net www.nordicasia.net
UNIVERSAL EV LLC
NORDIC ASIA
C0.0
EX
IS
TI
N
G
BI
TU
M
IN
O
U S
PA
R
KI
N
G L
O T
5'
23'
LOD
LOD
LOD
LOD
LO
D
LOD
LOD
LOD
LOD
LO
D
EX
IS
TI
NG
BU
IL
DI
NG
18.5'
18.5'
66.5'
8'
.7
18'
5'
5'
.7
(0 .3
5%
(0 .2
4%
(1.55%)
(2 .0
0%
(0 .2
4%
(1.56%)
(0 .9
4%
(0 .1
2%
(2.37%)
(2.86%)
(1 .7
6%
(0 .7
1%
(1 .4
1%
(0 .3
5%
(3.35%)
(3.83%)
(0 .8
2%
(1 .8
8%
(1 .1
8%
(1 .8
8%
(2.33%)
(0.83%)
(0.42%)
(4.61%)
(9 .4
(0 .1
1%
18.5'
(3 .4
3%
(1.36%)
(6.03%)
(4.40%)
(0.56%
(0 .5
6%
(6.19%)
(0 .5
0%
(0.11%)
(0.15%
(0.19%)
(1 .8
1%
(3.31%)
13.6'24.6'
(76 2.9
2)
(76 2.3
5)
(76 2.2
7) (76
2.8 2)
(76 2.5
2)
(76 1.9
4)
(76 2.3
4) (76
1.7 8)
(76 1.9
0)
(76 1.9
2)
(76 2.2
6)
(76 2.3
5)
(76 2.1
7)
(76 2.0
9) (76
2.3 2)
(76 2.0
3)
(76 1.9
9) (76
2.2 7)
(76 2.2
1)
(76 1.9
6)
(76 1.9
0) (76
2.1 2)
(76 2.6
(76 2.6
(76 2.6
4)
(76 2.1
7)
(76 2.0
1)
(76 1.5
9)
(76 1.6
3)
(76 1.9
1)
(762.2)
(76 2.6
(76 1.9
4)
(76 1.6
5)
(76 1.6
7)
(76 2.1
1)
(76 2.1
9)
(76 1.6
6)
(76 1.7
2)
(76 2.3
4)
(76 2.4
6)
(76 1.7
5)
(76 1.9
1)
(76 2.5
3)
(76 2.6
1)
(76 2.0
4)
(76 2.1
3)
(76 2.6
3)
(76 3.5
(76 2.8
(76 2.4
(76 2.0
7)
2.5
(76 2.3
2)(76 1.8
7)
(76 1.6
4)
(76 2.2
7)
(76 2.1
1)
(76 1.6
3)
(76 1.6
5)
(76 1.9
0)
(76 2.0
3)
(76 2.1
9)
(76 2.5
5)
(76 2.6
9)
(76 2.7
6) (76
2.8 5)
(76 1.7
0)(76 1.6
7)
(76 2.4
3)
(76 2.7
4)
(76 3.1
7) (76
3.2 9)
(76 2.5
9)
(76 2.3
6)
(76 2.3
4)
(76 2.5
1)
(76 2.3
4)
(76 2.2
3) (76
2.9 3)
(76 3.0
6)
(76 3.8
2) (76
2.8 7)
(76 2.0
8)
(76 2.6
3)
(76 2.2
3)(76 2.5
7)
(76 2.1
8)
(762.36)
(762.72)
(76 2.3
4) (76
2.7 6)
(76 3.7
5)
(76 3.4
5)
(76 3.7
2)
(76 3.7
6)
3.8
(76
3.8 3)
3.7
(76 3.6
18.5'
.3
20'
15'
(761.47)
71.5'
.1
5'
(76 2.4
6) (76
2.9 8)
LO
D
LO
D
LO
D
LOD
LOD
LOD LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
19'
5'
5' EXISTING CONCRETE
SIDEWALK (TYP)
UTILITY SERVICE
JUNCTION BOX
EXISTING LIGHT
POLE (TYP)
EXISTING LIGHT
POLE (TYP)
PR
O
PE
RT
Y
LI
NE
STORM MANHOLE
SAND BAG FILTER
AROUND STORM
DRAIN INLET
EXISTING LIGHT
POLE (TYP)
AREA OF APPARENT PAST
SETTLEMENT OF FILL MATERIAL
AND FAILURE OF PAVEMENT
REMOVED THE EXISTING
ASPHALT PAVEMENT
STRIPING (TYP)
EXISTING LANDSCAPE
AREA REMOVAL (640 SF)
FULL-DEPTH ASPHALT PAVEMENT
REMOVAL (942 SQ FT)
FULL DEPTH CONCRETE
SIDEWALK REMOVAL (90 SF)
9'
9'
9'
9'
9'
9'
D
EM
O
LI
TI
O
N P
LA
N
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ANY
AND ALL PERMITS AND SHALL PAY ALL FEES NECESSARY FOR
ENCROACHMENT, GRADING, DEMOLITION, AND DISPOSAL OF SAID
MATERIALS AS REQUIRED BY PRIVATE, LOCAL AND STATE
JURISDICTIONS.
2. ALL DEMOLITION SHALL COMPLY WITH CHAPTER 24 OF THE
INTERNATIONAL FIRE CODE.
3. CONTINUOUS ACCESS SHALL BE MAINTAINED FOR SURROUNDING
PROPERTIES AT ALL TIMES DURING DEMOLITION OF EXISTING
FACILITIES.
4. THE CONTRACTOR SHALL VERIFY AND LOCATE ALL EXISTING ABOVE
AND UNDERGROUND UTILITIES. THE LOCATIONS OF EXISTING
INFRASTRUCTURE DEPICTED IN THIS PLAN ARE APPROXIMATE AND
ARE SHOWN FOR REFERENCE ONLY.
5. THE CONTRACTOR SHALL PERFORM A PRE-CONSTRUCTION SITE
VISUAL INSPECTION TO FAMILIARIZE THEMSELVES WITH EXISTING
CONDITIONS AND THE EXTENT OF DEMOLITION WORK AS SHOWN
ON THE PLANS.
6. EROSION CONTROL MEASURES SHALL BE IMPLEMENTED TO
PREVENT DEBRIS AND UNSUITABLE MATERIALS FROM ENTERING
STORM DRAINS, SANITARY SEWERS AND STREETS.
7. DUST CONTROL MEASURES SHALL BE IMPLEMENTED DURING
DEMOLITION.
8. REMOVAL OF LANDSCAPING SHALL INCLUDE ROOTS AND ORGANIC
MATERIAL.
9. CONTRACTOR TO INSTALL CHAIN LINK FENCE WITH MESH SCREEN
TO PROTECT PUBLIC FROM ENTERING CONSTRUCTION AREA.
10. THE CONTRACTOR SHALL CLEAR THE PROJECT SITE AREA WITHIN
THE CONFINES OF THE SAWCUT LINE. THE CONTRACTOR SHALL
DEMOLISH AND REMOVE FROM THE SITE ANY NOTED EXISTING
UTILITY STRUCTURES, PLANTERS, TREES, AND OTHER SITE
FEATURES, NOTED TO BE REMOVED ON THE DEMOLITION PLAN.
11. REFER TO THE PROPERTY LAYOUT (EXISTING CONDITION) ON
SHEET C0.0 FOR ADDITIONAL DETAILS OF EXISTING STRUCTURES,
ETC., LOCATED WITHIN THE PROJECT AREA. UNLESS OTHERWISE
NOTED, ALL EXISTING STRUCTURES, SLABS, CONCRETE, ASPHALT,
DEBRIS PILES, SIGNS, AND ALL APPURTENANCES SHALL BE
REMOVED FROM THE SITE BY THE CONTRACTOR SHALL BE
PROPERLY DISPOSED OF AS PART OF THIS PLAN. SOME ITEMS TO
BE REMOVED MAY NOT BE DEPICTED ON THE PROPERTY SURVEY. IF
ANY ITEMS ARE IN QUESTION, THE CONTRACTOR SHALL CONTACT
THE OWNER PRIOR TO REMOVAL OF SAID ITEMS.
12. CONTRACTOR TO USE CARE IN HANDLING DEBRIS FROM SITE TO
ENSURE THE SAFETY OF THE PUBLIC. HAUL ROUTE TO BE CLOSELY
MONITORED FOR DEBRIS OR MATERIALS TRACKED ONTO
ADJOINING ROADWAYS, SIDEWALKS, ETC. ROADWAYS AND
WALKWAYS TO BE CLEARED DAILY OR AS NECESSARY TO MAINTAIN
PUBLIC SAFETY.
13. ALL MATERIAL REMOVED FROM THIS SITE BY THE CONTRACTOR
SHALL BE DISPOSED OF BY THE CONTRACTOR IN A LEGAL MANNER.
14. THE CONTRACTOR SHALL RETURN SIDEWALKS, LANDSCAPING,
PLANTERS, IRRIGATION SYSTEMS, AND ANY OTHER FACILITIES
DISTURBED OR OTHERWISE DAMAGED DURING CONSTRUCTION TO
THE SAME OR BETTER CONDITION THAN EXISTED PRIOR TO THE
COMMENCEMENT OF THE WORK.
15. ALL QUANTITIES LISTED ON THIS PLAN ARE FOR THE CONVENIENCE
OF THE CLIENT / CONTRACTOR AND SHALL BE CONSIDERED
APPROXIMATIONS. ACTUAL QUANTITIES FOR BIDDING AND
CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR.
16. UNLESS OTHERWISE NOTED, THE CONTRACTOR SHALL PROTECT
IN-PLACE ALL EXISTING SITE ELEMENTS AND INFRASTRUCTURE
WITHIN THE AREA OF IMPROVEMENTS.
17. ALL DIMENSIONS ARE TO THE FACE OF CURB UNLESS NOTED
OTHERWISE.
18. ALL EXISTING STRIPING AND PAVEMENT MARKINGS OR TEXT WITHIN
THE LIMITS OF THE WORK AREA SHALL BE REMOVED VIA SODIUM
BICARBONATE (SODA) BLASTING. ANY DIRECTIONAL ARROWS, STOP
BARS/TEXT OR CROSSWALKS THAT ARE NOT CORRECTLY LOCATED
OR INCONSISTENT WITH THE DETAILS PROVIDED SHOULD BE
REMOVED. APPLY SEAL COAT TO THE EXTENT THAT THE STRIPING
OR TEXT HAS BEEN REMOVED IN A SINGLE COMPLETE RECTANGLE
TO COVER ALL REMOVED STRIPING. DO NOT APPLY SEAL COAT
OVER EXISTING STRIPING OR CONCRETE. INSTALL NEW STRIPING
AND SIGNAGE AS SHOWN ON THE SITE CONSTRUCTION PLAN.
DEMOLITION NOTES:
THE LOCATIONS OF ALL EXISTING ELEVATIONS SHOWN ON THIS PLAN
HAVE BEEN DETERMINED FROM THE PRECISION ENGINEERING GROUP,
INC. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THEIR ACCURACY.
PRIOR TO THE START OF ANY DEMOLITION ACTIVITY, THE SITE
CONTRACTOR SHALL NOTIFY THE UTILITY COMPANIES FOR ONSITE
LOCATIONS OF EXISTING UTILITIES AND PERFORM A PRIVATE UTILITY
LOCATE.
CONTRACTOR SHALL VERIFY ALL PLANS, EXISTING DIMENSIONS &
CONDITIONS ON THE JOB SITE & SHALL IMMEDIATELY NOTIFY THE
ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING
WITH THE WORK.
EXISTING CONDITIONS NOTES:
FOR THE PURPOSE OF THIS PLAN, THE LIMITS OF DISTURBANCE (LOD) IS
THE BOUNDARY WITHIN WHICH ALL CONSTRUCTION, CLEARING,
EXCAVATION, GRADING, AND RELATED ACTIVITIES SHALL OCCUR.
EXISTING IRRIGATION NOTE:
SPOT ELEVATION KEY:
(XXX.XX) - EXISTING ELEVATION
N
E
S
W270
350 0 10
4O
170180190
BENCHMARK DATA
BM#1 - TOP CAP BOLT ON FIRE HYDRANT NEAREST "O" IN
OPEN. HYDRANT LOCATED ON SOUTH SIDE OF RION
DRIVE, ±650' EAST OF BLARNEY DRIVE.
ELEVATION = 764.02'
SURVEY NOTE:
J.U.L.I.E. UNDERGROUND (1-800-892-0123/ 811) (CALL BEFORE YOU DIG)
UNDERGROUND UTILITIES/STRUCTURES WERE NOT LOCATED FOR
PREPARATION OF THIS PLAN. BURIED UTILITIES/STRUCTURES MAY
BE ENCOUNTERED. IDENTIFICATION AND LOCATION OF UTILITIES
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE
CONTRACTOR IS ADVISED THAT HE/SHE MAY CALL 811 (JULIE
UNDERGROUND - FORMERLY B.U.D.) A MINIMUM OF TWO (2) DAYS AND
NO MORE THAN 10 DAYS PRIOR TO EXCAVATION FOR LOCATION OF
UNDERGROUND UTILITIES. THE CONTRACTOR IS FURTHER ADVISED
THAT HE/SHE IS RESPONSIBLE FOR LOCATION OF ANY AND ALL
UNDERGROUND UTILITIES, INCLUDING THOSE
THAT DO NOT SUBSCRIBE AND/OR PARTICIPATE IN THE 811 SYSTEM.
- LIMITS OF DISTURBANCE (2040 SF)
DEMOLITION PLAN LEGEND:-
- SAWCUT LINE
LOD
- REFERENCE POINT FOR MEASUREMENT
- FULL DEPTH CONCRETE SIDEWALK REMOVAL (90 SF)
- EXISTING LANDSCAPE AREA REMOVAL (640 SF)
- EXISTING LANDSCAPE REMOVAL
- FULL DEPTH ASPHALT PAVEMENT REMOVAL (942 SF)
00 5' 10'
305 W SPRING CREEK PKWY,
SUITE 100 B PLANO, TX 75023
M
IC
R O
TE
L
IN
N
B Y
W
YN
D H
A M
C H
A M
PA
IG
N
R
IO
N
D R
C
H A
M
PA
IG
N
, I L
0 1 2 3 4 5 6 7 8 9N o.
BY
D
AT
E
IS
SU
E
BL
O C
K
DESIGNED BY:
CHECKED BY:
DRAWN BY:
AD
JP
VP
DOCUMENT DATE: AUG 21, 2026
NORDIC PROJECT ID/R: UNE-24-66/23
SHEET NUMBER
SH
EE
T
TI
TL
E:
3040 78 TH AVENUE SE,
UNIT 1619, MERCER ISLAND, WA 98040
Mob:720 492 2885 | www.nordicasia.net www.nordicasia.net
UNIVERSAL EV LLC
NORDIC ASIA
C0.1Sheet size : 24" X 36" Scale 1" = 5'
(76 2.2
7) (76
2.8 2)
(76 2.5
2)
(76 1.9
4)
(76 2.3
4) (76
1.7 8)
(76 1.9
0)
(76 1.9
2)
(76 2.0
9)
(76 2.2
9)
(76 2.0
3)
(76 1.9
9)
(76 2.2
7)
(76 2.2
1)
(76 1.9
6)
(76 1.9
0)
(76 2.1
2)
(76 2.0
1)
(76 1.5
9)
(76 1.6
3)
(76 1.9
1)
(76 2.2
(76 2.6
(76 1.9
4)
(76 1.6
5)
(76 1.6
7)
(76 2.1
1)
(76 2.1
9)
(76 1.6
6)
(76 1.7
2)
(76 2.3
4)
(76 2.4
6)
(76 1.7
5)
(76 1.9
1)
(76 2.5
3)
(76 2.6
1)
(76 2.0
4)
(76 2.6
3)
(76 2.8
(76 2.4
(76 2.3
2)
(76 1.8
7)
(76 1.6
4)
(76 2.2
7)
(76 2.1
1)
(76 1.6
3)
(76 1.6
5)
(76 1.9
0)
(76 2.0
3)
(76 2.5
5)
(76 2.6
9)
(76 2.7
6)
(76 1.7
0)
(76 1.6
7)
(76 2.5
9)
(76 2.3
4)
(76 2.5
1)
(76 2.3
4)
(76 2.2
3)
(76 2.9
3)
(76 3.0
6)
(76 3.8
2)
(76 2.8
7)
(76 2.6
3)
(76 2.2
3)(76 2.5
7)
(76 2.1
8)
(76 2.4
6)
(76 3.0
6)
(76 3.7
5)
(76 3.4
5)
(76 3.7
2)
(76 3.7
6)
(76 3.6
(761.47)
23'
13'
18.5'
8' 20'
5'
9'
9'
9'
18'
NO
PA
RK
IN
G
13'
5'
5'
(1.53%)
(2
(1.60%)
C2.0
(1 .5
5%
(1 .6
6%
(1.66%)
(1 .2
2%
(1 .6
6%
(1.61%)
(1 .2
2%
(1 .1
1%
(1.38%)
(1.40%)
(1.40%)
(0 .6
(0 .6
(1 .5
4%
(1.40%)
(1 .5
4%
11.7'
11.7'
C2.0
(3.
(0 .1
2%
(0 .3
4%
(1.44%
(0 .9
(0 .1
7%
(1.
16.7'
(1.25%)
(1.96%)
(1.70%)
(76 2.9
8)
(6.38%)
1.5'
(1 .8
(1.40%)
2'
(76 2.6
(76 2.6
(0 .7
5%
(0 .6
6%
(76 2.1
7)
STORM INLET
SAND BAG FILTER
AROUND STORM
DRAIN INLET
PROPOSED ONE-WAY
DIRECTIONAL RAMP
5' EXISTING CONCRETE
SIDEWALK (TYP)
PROPOSEDADA PATH
FG:762.00 CONSTRUCT 90 SQ FT OF
SIDEWALK CONCRETE (SEE
DETAIL 4 / SH C2.0)
FS: 762.16
FS: 762.10
FS: 761.93
FS: 761.90
(FS: 762.36)
FS: 761.80
FS: 762.05
(FS: 761.72)
(FS: 761.73)
FS: 761.94JOINT EXISTING
FS: 761.95JOINT EXISTING
FS:762.03
(TC:762.77)(FS:762.27)
(FS: 761.62)
(FS: 761.74)
(FS: 761.63)
(FS: 761.65)
FS: 761.65
FS: 761.94
FS: 761.50
FS: 761.80
(FS:762.86)
CONSTRUCT 25 SQ FT OF
FULL-DEPTH PROPOSED ASPHALT
PAVEMENT (SEE DETAIL 12 / SH C3.0
FS: 762.42
EXISTING LIGHT
POLE (TYP)
FS: 762.16
CONSTRUCT 6" CONCRETE
CURB (SEE DETAIL / SH C2.0)
PROPOSED ASPHALT
PAVEMENT
FS: 762.38
TF: 762.70FG:762.20
FS: 762.21
TF: 762.72FG:762.22FS: 762.18
TF: 762.71FG:762.21
DEMO'ED TRENCH TO BE RESTORED
TO MATCH EXISTING CONDITIONS
IN ALL LOCATIONS (TYP.)
3.9'
3.
5'
3.8'
4'
2.6'
4'
4.
8'
5' 5.8'
(76 2.6
4)
3'
7'
6'
NEW POLEW/ CAMERA
ENCLOSURE
NVR & POE
AC DISCONNECT
NEW 1kVA TRANSFORMER WITH
NEMA 3R WEATHERPROOFING
ENCLOSURE
4.
6'
3'
4'
EV
IN
FR
AS
TR
U
C
TU
R E
PL
AN
LEGEND & ABBREVIATION:
1. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES OR
STRUCTURES SHOWN ON THEIR PLANS ARE OBTAINED BY A SEARCH OF THE AVAILABLE
RECORDS. TO THE BEST OF MY KNOWLEDGE, THERE ARE NO EXISTING UTILITIES
EXCEPT AS SHOWN ON THESE PLANS. THE CONTRACTOR IS REQUIRED TO TAKE DUE
PRECAUTION. ANY MEASURES TO PROTECT THE UTILITIES AND STRUCTURES SHOWN
AND ANY OTHER LINES OR STRUCTURES NOT OF RECORD OR NOT SHOWN ON THESE
PLANS, AND IS RESPONSIBLE FOR THE PROTECTION OF, AND ANY DAMAGE TO, THESE
LINES OR STRUCTURES.
2. CONTRACTOR TO VERIFY CLEARANCE AT ALL UTILITY CROSSINGS. IF INTERFERENCE
OCCURS, OTHER THAN NOTED ON PLAN, CONTRACTOR TO CONTACT DESIGN ENGINEER
FOR POSSIBLE REDESIGN. IF REDESIGN IS UNFEASIBLE, CONTRACTOR TO RELOCATE
UTILITY AT NO EXPENSE TO ENGINEER.
3. THE CONTRACTOR AGREES THAT HE WILL ASSUME SOLE AND COMPLETE
RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION
OF THIS PROJECT, INCLUDING SAFETY OF PERSONS AND PROPERTY; THAT THIS
REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL
WORKING HOURS; AND THAT THE CONTRACTOR SHALL DEFEND, INDEMNIFY, AND HOLD
THE OWNER AND ENGINEER HARMLESS FROM ANY AND ALL LIABILITY REAL OR ALLEGED
IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING FOR
LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF THE OWNER OR THE ENGINEER, OR
ANY PUBLIC AGENCY.
CIVIL ENGINEER’S NOTICE TO CONTRACTOR:
NEW EV CHARGING STATION SITE PLAN
1. CONTRACTOR TO BORE AND/OR HAND-TRENCH CONDUIT AS REQUIRED PER NEC.
2. ALL EQUIPMENT SHALL BE INSTALLED PER CLIENT DESIGN STANDARDS.
3. CONTRACTOR TO RETURN ALL AREAS OF DISTURBANCE BACK TO EXISTING GRADE
AND UP TO OR BETTER THAN EXISTING CONDITIONS.
4. ALL DIMENSIONS ARE TO THE FACE OF CURB UNLESS NOTED OTHERWISE.
CONSTRUCTION NOTES:
1. CONTRACTOR SHALL TAKE FIELD MEASUREMENTS OR OTHERWISE ESTABLISH A
SURVEY OF THE EXISTING STRIPING IN ALL WORK AREAS IN ORDER TO ESTABLISH ALL
EXISTING PAVEMENT MARKINGS WITH FULL COORDINATION OF NEW MARKINGS.
2. UNLESS OTHERWISE INDICATED ON THIS PLAN, THE CONTRACTOR SHALL ESTABLISH
PAVEMENT MARKINGS FOR ALL FIRE LANES, DIRECTIONAL ARROWS, STOP BARS, CURBS,
SIDEWALK, LIGHT POLE BASES, SIGN BASES AND PARKING STALLS TO MATCH THE
EXISTING SITE WITHIN REPAIR LIMITS.
3. CONTRACTOR TO USE APPROPRIATE PAINT COLORS TO MATCH THE EXISTING
FEATURES. ADA BARRIER-FREE AREAS TO COMPLY WITH ALL LOCAL AND FEDERAL ADA
STANDARDS. PAVEMENT MARKINGS SHALL BE A HIGH QUALITY PAINT RECOMMENDED BY
THE PAINT MANUFACTURER. PAINT COLORS SHALL CLOSELY MATCH THE FEDERAL
STANDARD 595B COLOR NUMBERS AS FOLLOWS: BLUE—COLOR 15080, WHITE—COLOR
37925, AND YELLOW—COLOR 33538.
4. IN AREAS NOT BEING RESURFACED BUT REQUIRING RESTRIPING, CONTRACTOR SHALL
REMOVE EXISTING STRIPING BY EITHER SAND BLASTING, WATER BLASTING, OR BY
ANOTHER APPROVED METHOD OF STRIPING REMOVAL. WHERE THE STRIPING REMOVAL
CHANGES THE SURFACE TEXTURE OF THE EXISTING ASPHALT, CONTRACTOR SHALL
SEAL THAT AREA PRIOR TO RESTRIPING. CONTRACTOR TO SUBMIT STRIPING REMOVAL
METHOD TO PROPERTY MANAGER AND ENGINEER FOR APPROVAL PRIOR TO
CONSTRUCTION.
PAVEMENT MARKING NOTES:
1615 RION DR, CHAMPAIGN, IL 61822
CONSTRUCTION NOTES:-
- TREE
- PROPOSED ELEVATION
(XXX.XX) - EXISTING ELEVATION
XXX.XX
- FINISHED SURFACEFS
- TOP OF CONCRETETC
- EXISTING LANDSCAPE
NOTES:
· ALL TREES, SIDEWALKS, CURB & FLOW LINES SHALL BE PROTECTED IN PLACE.
· CONTRACTOR SHOULD VERIFY THE EXISTING SPOT ELEVATION AND SLOPES,
TO HAVE POSITIVE DRAINAGE AWAY FROM BUILDING AND EV DEVICES.
· CONTRACTOR TO FIRST INSTALL V4 CABINET AND THEN INSTALL BOLLARDS
FOR PROTECTION ON THE SIDE, AS THE MINIMUM REQUIRED CLEARANCE FOR
CONSTRUCTION OF V4 CABINET IS 36" AND THE MINIMUM REQUIRED
CLEARANCE FOR SERVICING IS 18"
- TOP OF FOUNDATIONTF
N
E
S
W270
350 0 10
4O
170180190
- FINISHED GRADEFG
DEMOLITION PLAN LEGEND:-
- EXISTING LANDSCAPE AREA FILL
- PROPOSED ASPHALT PAVEMENT BOUNDARY
- PROPOSED ASPHALT PAVEMENT FILL (968 SQFT)
- PROPOSED CONCRETE SIDEWALK (90 SQFT)
CONSTRUCT EV CHARGING PER STRUCTURAL/ELECTRICAL PLAN
CONSTRUCT CONCRETE PAD FOR POWER CABINET PER STRUCTURAL/ELECTRICAL PLAN
CONSTRUCT CONCRETE PAD FOR MAIN SWITCHBOARD PER STRUCTURAL/ELECTRICAL PLAN
CONSTRUCT CONCRETE PAD FOR TRANSFORMER PER STRUCTURAL/ELECTRICAL PLAN
CONSTRUCT CONCRETE PAD FOR CT CABINET PER STRUCTURAL/ELECTRICAL PLAN
INSTALL EV SIGNBOARD CENTERED IN EACH PARKING SPACE, ALIGNED WITH THE
CONCRETE PAD OF EV CHARGERS, PER DETAIL G ON SHEET EV2.0
INSTALL EV "USE LAST" SIGNBOARD ON BOLLARD PER DETAIL H ON SHEET EV2.0
PAINT STRIPING ACCESSIBLE PARKING SPOTS PER DETAIL 8 ON SHEET C2.0
INSTALL TRUNCATED DOMES PER CITY OF CHAMPAIGN STANDARD, PER DETAIL 4 ON SHEET C2.0
ONE-WAY DIRECTIONAL RAMP PER COUNTY OF CHAMPAIGN STANDARD,
PER DETAIL 4 ON SHEET C2.0.
PROVIDE 48" X 30" GROUND CLEAR SPACE IN FRONT OF ADA EV CHARGER
INSTALL EMERGENCY DISCONNECT SWITCH IN NEARBY THE ADA ACCESS,
PER DETAIL F ON SHEET EV2.0
CONSTRUCT NEW ASPHALT PAVEMENT, AGGREGATE BASE, AND SUBGRADE TO THE REQUIRED
ELEVATIONS TO ACHIEVE THE PROPOSED SLOPES AND SURFACE ELEVATIONS SHOWN ON THE
PLANS. PLACE COMPACTED BASE MATERIAL TO THE REQUIRED ELEVATION AND INSTALL ASPHALT, PER DETAIL 12 ON SHEET C2.0
CONSTRUCT 6" CONCRETE CURB PER DETAIL 1 ON SHEET C2.0
INSTALL PROTECTION BOLLARD, PER DETAIL 13 ON SHEET C2.0
305 W SPRING CREEK PKWY,
SUITE 100 B PLANO, TX 75023
M
IC
R O
TE
L
IN
N
B Y
W
YN
D H
A M
C H
A M
PA
IG
N
R
IO
N
D R
C
H A
M
PA
IG
N
, I L
0 1 2 3 4 5 6 7 8 9N o.
BY
D
AT
E
IS
SU
E
BL
O C
K
DESIGNED BY:
CHECKED BY:
DRAWN BY:
AD
JP
VP
DOCUMENT DATE: AUG 21, 2026
NORDIC PROJECT ID/R: UNE-24-66/23
SHEET NUMBER
SH
EE
T
TI
TL
E:
3040 78 TH AVENUE SE,
UNIT 1619, MERCER ISLAND, WA 98040
Mob:720 492 2885 | www.nordicasia.net www.nordicasia.net
UNIVERSAL EV LLC
NORDIC ASIA
C1.0
00 5' 10'
Sheet size : 24" X 36" Scale 1" = 5'
CONCRETE FOOTING SCHEDULE
ITEM QUANTITY DIMENSION REINFORCEMENT
(EACH WAY BOTTOM, UNO)WIDTH LENGTH DEPTH
TRANSFORMER 1 7'-0" 6'-0" 5" 10 X #6 REBAR
MAIN SWITCHBOARD 1 4'-10" 4'-0" 2'-6" 11 X #6 REBAR
CT CABINET 1 4'-0" 2'-7" 2'-6" 9 X #6 REBAR
POWER CABINET 1 5'-7" 4'-11" 10" 13 X #5 REBAR
EV CHARGER 4 2'-0" 4'-8" 1'-6" 10 X #4 REBAR
4 X #5 REBAR
ONE-WAY DIRECTIONAL RAMP 1 9'-0" 9'-0" 4" -
STRIPING SCHEDULE
ITEM QUANTIT
Y
DIMENSION PROPERTIES
WIDTH LENGTH ON CENTER TYPE COLOR
PAVEMENT STRIPING 3 4" 18'-0" 9'-0" SOLID WHITE— 37925
ADA AISLE 3 4" 20'-0" 11'-0" & 5'-0" SOLID WHITE— 37925
ADA AISLE STRIPING 6 4" 5'-10" 3'-0" SOLID WHITE— 37925
PATH OF TRAVEL
1 8" 23'-2" - SOLID WHITE— 37925
1 8" 27'-7" - SOLID WHITE— 37925
PATH OF TRAVEL STRIPING 12 6" 4'-0" 2'-0" SOLID WHITE— 37925
Note: The quantities and dimensions are above mentioned items are nominal and not intended for bidding purposes.
(762.35)
(761.75)
(762.93)(763.06)
(27.62')
13'
EXISTING BUILDING
.5
8'
5'
20'
11' 5' 9' 9' 9'
18'
NO
PARKING
5' 5'
(1.53%
(2%)
(1.60%
(1.55%)
(1.66%)
(1.66%
(1.22%)
(1.66%)
(1.61%
(1.22%)
(1.33%)
(1.38%
(1.40%
(1.30%
(0.6%)
(0.6%)
(1.54%)
(1.40%
(1.54%)
.7
.7
(3.13%)
(0.12%) (0.34%)
(1.
(0.63%) (0.17%)
(1.73%)
.7
(1.25%
(1.96%
(1.70%
1.
5'
(1.40%
C2.0
EXISTING PROPERTY LINE
(1.60%
(6.38%
(1.8%)
(1.44%
(0.66%)
(0.75%) 4.6'
STORM
INLET
PROPOSED
ADA PATH
FG:762.00
FS: 762.16
FS: 762.10
FS: 761.93
FS: 762.21
FS: 761.90 FS: 761.80
FS: 762.05
FS: 761.72FS: 761.73
FS: 761.94
JOINT EXISTING
FS: 761.95
JOINT EXISTING
FS:762.03
TC:762.77
FS:762.27
(FS: 761.62)(FS: 761.74)
(FS: 761.63) (FS: 761.65)
FS: 761.65
FS: 761.94
FS: 761.50
FS: 761.80
FS:762.86
PROPOSED ONE-WAY
DIRECTIONAL RAMP
CONSTRUCT 90 SQ FT OF SIDEWALK
CONCRETE (SEE DETAIL 4 / SH C2.0)
PROPOSED ASPHALT
PAVEMENT
SAND BAG FILTER
AROUND STORM
DRAIN INLET
FS: 762.42
FS: 762.10
CONSTRUCT 6" CONCRETE CURB
(SEE DETAIL 1 / SH C2.0)
TF: 762.65
FG:762.15
TF: 762.63
FG:762.13
TF: 762.67
FG:762.17
FS: 762.18
PROPOSED UNDERGROUND
CONDUITS
3.5'
3.8'
4'
2.
6'
4'
4.8'
5.8'
3.
9'
5'
3'
7'
6'
FS: 762.36
FS: 762.38
4.7'
NEW POLE W/ CAMERA
NEW 1kVA TRANSFORMER WITH
NEMA 3R WEATHERPROOFING
ENCLOSURE
ENCLOSURE
NVR & POE
AC DISCONNECT
4.6'3' 4'
EX
PA
N D
ED
V
IE
W
O F
G R
AD
IN
G P
LA
N
GRADING PLAN LEGEND:
- PROPOSED ASPHALT PAVEMENT BOUNDARY
- PROPOSED ASPHALT PAVEMENT FILL
- PROPOSED CONCRETE SIDEWALK
SPOT ELEVATION KEY:
TF - TOP OF FOUNDATION
FS - FINISHED SURFACE
TC - TOP OF CONCRETE
FG - FINISHED GRADE
- EXISTING ELEVATIONS
- PROPOSED FLOW ARROW (DIRECTION AND SLOPE)(## %)
- EXISTING FLOW ARROW (DIRECTION AND SLOPE)(## %)
N
E
S
W
300 310 320 330
4O
8090100
305 W SPRING CREEK PKWY,
SUITE 100 B PLANO, TX 75023
M
IC
R O
TE
L
IN
N
B Y
W
YN
D H
A M
C H
A M
PA
IG
N
R
IO
N
D R
C
H A
M
PA
IG
N
, I L
0 1 2 3 4 5 6 7 8 9N o.
BY
D
AT
E
IS
SU
E
BL
O C
K
DESIGNED BY:
CHECKED BY:
DRAWN BY:
AD
JP
VP
DOCUMENT DATE: AUG 21, 2026
NORDIC PROJECT ID/R: UNE-24-66/23
SHEET NUMBER
SH
EE
T
TI
TL
E:
3040 78 TH AVENUE SE,
UNIT 1619, MERCER ISLAND, WA 98040
Mob:720 492 2885 | www.nordicasia.net www.nordicasia.net
UNIVERSAL EV LLC
NORDIC ASIA
C1.1
00 4' 8'
Sheet size : 24" X 36" Scale 1" = 4'
6.38%
1.8%
1.60%
5'-0"
13'
5'-0"
SIDEWALK WIDTH
5'
EXISTING PARKING LOT
EXISTING PARKING LOT
A
A
EXISTING SIDEWALK 13'
Depressed corner Ramp Upper landing Sidewalk
1:50 max. 1:12 max. 1:50 max.2
.5'
0.5"
SECTION A-A
SIDE CURB DETAIL
DETAIL A
1. Upper landing(s) not required for ramp slopes flatter than 1:20.
2. The running slope of the curb ramp shall not require the ramp length to exceed 15' (4.5 m).Ramp
Flush with top of roadway curb and top of sidewalk
Variable
Ramp thickness
2" R
Expansion joint
(20' M
IN
SEE SITE PLA
N
FO
R D
IM
PER PLAN
(5' MIN.)
60°
36"O.C.
M
AX.
NO PARKING
4" WHITE PAINT,
60 DEGREES
2'-4" ON CENTER
THE WORDS "NO PARKING"
SHALL BE PAINTED ON THE
GROUND WITHIN THE
ACCESS AISLE. THIS NOTICE
SHALL BE PAINTED IN WHITE
LETTERS NO LESS THAN 12
INCHES HIGH
ELEVATION
PLAN
0.90" MIN
0.92" MAX
0.
M
IN
0.
M A
X
2.30" MIN O.C.
2.40" MAX O.C.
2.
M
IN
O
.C
2.
M
A X
O .C
0.45" MIN
0.47" MAX
3.00%
1.5'
0.3'
1'
0.77'
.1 2'
.4 5'
EXISTING LANDSCAPE
BOLLARD
ASPHALT
PAVEMENT
EXISTING LANDSCAPE
(TO BE REMOVED)
EV CHARGER
ON CONCRETE PEDESTAL
BT
M e nc b ox
FRONT VIEWSIDE VIEW
MAX 10"
1.
3'
4' 4'
6.
4'
1.
2'
2.2'
1.
3'
4'
1'-1"
4'
2.5'
2.3'
REBOUNDING
BOLLARD
48" X 30"
GROUND SPACE
HANDLE TERMINUS
CABLE TERMINUS
CABLE TERMINUS
HANDLE
0.8' M ax 4'
EMERGENCY
DISCONNECT BUTTON
(MOUNTED ON POLE)
1.
6'
0.9'
0.5'
0.
5'PROPOSED 5' ONE-WAY
DIRECTIONAL RAMP
1" R1/2" R
SUBGRADE
COMPACTION PER
PLAN
EXISTING
PARKING LOT
TOP VIEW
1.
3'Ø
.4'Ø
2.
7'
3'
1.3'
GROUND
LEVEL
3'
CONCRETE
FOUNDATION
BOLLARD
CONCRETE
FOUNDATION
IMPACT RECOVERY
SIGN POST
SEE DETAILS ON SHEET EV8.0
VARIES
REFER TO SITE PLAN
4" THICK CONCRETE SIDEWALK
WITH 6x6-W1.2xAW1.2 WELDED
WIRE MESH REINFORCEMENT.
2,500 PSI AT 28 DAYS.
PREPARED EARTH SUBGRADE
(COMPACTED TO AT LEAST 95
PERCENT MODIFIED PROCTOR)
0.5'
0.75'
1'
1/2" R 1" R
SIDEWALK
WHERE SHOWN
1" ASPHALT SURFACE
3"ASPHALT BASE
6" COMP. DGA BASE
PROPOSED PAVEMENTEXISTING PAVEMENT
2” HMA SURFACE COURSE IL-9.5, MIX D, N50
2-1/4” HMA BINDER COURSE, IL-19, N50
6" COMP. DGA BASE
SAW CUT
0.40 LBS/SY ASPHALT MATERIAL FOR TACK COAT
MATCH EXISTING ASPHALT SURFACE COURSE
REMOVE EXISTING ASPHALT PAVEMENT,
AGGREGATE BASE, AND SUBGRADE MATERIAL
TO REQUIRED ELEVATION TO ACHIEVE
PROPOSED SLOPES AND SURFACE ELEVATIONS
SHOWN ON PLANS. PLACE COMPACTED BASE
MATERIAL TO REQUIRED ELEVATION AND
PLACE ASPHALT PER CROSS SECTION BELOW.
EXISTING DENSE GRADED AGGREGATE BASE
COURSE MEETING MATERIAL & COMPACTION
RATE OF 95% - TO REMAIN. ADD OR REMOVE
MATERIAL AS NECESSARY TO ACHIEVE FINAL
PROPOSED GRADES.
MATCH EXISTING ASPHALT SURFACE COURSE
EXISTING COMP. SOIL SUBGRADE - TO REMAIN
GROUND
LEVEL
TOP VIEW
SECTION VIEW
CONCRETE
FOUNDATION
DUCTILE IRON
STEEL PIPE
BOLLARD,FILLED
WITH CONCRETE
CAP
CONCRETE
FOUNDATION
BOLLARD
1/2"X9" STEEL
ROD THRU
BOLLARD
3' 2.
7'
3'.3
1.3'
1.
3'Ø
.4'Ø
305 W SPRING CREEK PKWY,
SUITE 100 B PLANO, TX 75023
M
IC
R O
TE
L
IN
N
B Y
W
YN
D H
A M
C H
A M
PA
IG
N
R
IO
N
D R
C
H A
M
PA
IG
N
, I L
0 1 2 3 4 5 6 7 8 9N o.
BY
D
AT
E
IS
SU
E
BL
O C
K
DESIGNED BY:
CHECKED BY:
DRAWN BY:
AD
JP
VP
DOCUMENT DATE: AUG 21, 2026
NORDIC PROJECT ID/R: UNE-24-66/23
SHEET NUMBER
SH
EE
T
TI
TL
E:
3040 78 TH AVENUE SE,
UNIT 1619, MERCER ISLAND, WA 98040
Mob:720 492 2885 | www.nordicasia.net www.nordicasia.net
UNIVERSAL EV LLC
NORDIC ASIA
C2.0
N.T.S.
SCALE 1 SECTION THRU CHARGING STALL AND EV CHARGING EQUIPMENT
N.T.S.
SCALE 4DEPRESSED CORNER RAMP (TYPICAL)
N.T.S.
SCALE 8
ACCESSIBILITY EV DETAILS N.T.S.
SCALE 5 OPERABLE PARTS HEIGHT N.T.S.
SCALE 6 ADA ACCESSIBILITY STANDARDS N.T.S.
SCALE 7
PAVEMENT STRIPING DETAIL
6" CONCRETE CURB
N.T.S.
SCALE 12
SCALE 3
C
IV
IL
D
ET
AI
LS
N.T.S.
SCALE 2FOUNDATION DETAILS - BOLLARD
CONCRETE:
f'c = 3500 PSI Air Content = 6% Slump 3-5 inches
CONCRETE:
f'c = 3500 PSI
0" CONCRETE CURB
00 10 20
CONCRETE SIDEWALK N.T.S.
SCALE 9 N.T.S.
SCALE 11 N.T.S.
SCALE 13SAWCUT & FULL DEPTH ASPHALT PAVEMENT DETAIL BOLLARD FOUNDATION DETAILS
3'
.5
7.
5'
3'
1.
6'
FOUNDATION DETAIL - TOP VIEW
CT CABINET - TOP VIEW
.5
FINISH GRADE
FINISH GRADE
2.
5'
4'
2' .5
FRONT VIEW
SIDE VIEW
2.6'
CT CABINET
4'
2.
6'
.3'
4 X 4" PVC
CONDUIT FROM TRANSFORMER
FINISH GRADE
4 X 4" PVC
CONDUIT TO MAIN SWITCHBOARD
CT CABINET
CT CABINET
CONCRETE
4000 PSI
CONCRETE
4000 PSI
(5) #6 REBARS @ 10" OC
(4) #6 REBARS @ 8" OC
(5) #6 REBARS @ 10" OC
(4) #6 REBARS @ 8" OC
(5) #6 REBARS @ 10" OC
(4) #6 REBARS @ 8" OC
3" CLEAR TYP.
EACH SIDE
1/2" DIAMETER SS THREADED ROD, W/
SIMPSON SET-3G ADHESIVE ANCHOR
SYSTEM WITH 4" MIN. EMBEDMENT INTO
(N) EQUIPMENT SLAB IN ACCORDANCE
WITH ESR-4057 OR APPROVED EQUAL.
DRILL AND SET OF EPOXY ANCHORS SHALL
NOT OCCUR LESS THAN 7 DAYS FROM
POURING CONCRETE.
6" CONCRETE
PAD (TYP)
5.
4'
3.8'
3.8'
3'
.5
FOUNDATION DETAIL - MAIN
SWITCHBOARD
MAIN SWITCHBOARD -
TOP VIEW
2.
5'
4.8'
2' .5
FRONT VIEW
SIDE VIEW
MAIN
SWITCHBOARD
4'
4'
4.8'
.3'
3 X 4" PVC
CONDUIT TO POWER CABINET
FINISH GRADE
FINISH GRADE
FINISH GRADE
4 X 4" PVC
CONDUIT FROM MAIN
SWITCHBOARD
1 X 1" PVC
CONDUIT TO POWER CABINET
MAIN SWITCHBOARD
MAIN SWITCHBOARD
CONCRETE
4000 PSI
CONCRETE
4000 PSI
(6) #6 REBARS @ 10" OC
(5) #6 REBARS @ 10" OC
(6) #6 REBARS @ 10" OC
(5) #6 REBARS @ 10" OC
3" CLEAR TYP.
EACH SIDE
(6) #6 REBARS @ 10" OC
(5) #6 REBARS @ 10" OC
1/2" DIAMETER SS THREADED ROD, W/
SIMPSON SET-3G ADHESIVE ANCHOR
SYSTEM WITH 4" MIN. EMBEDMENT INTO
(N) EQUIPMENT SLAB IN ACCORDANCE
WITH ESR-4057 OR APPROVED EQUAL.
DRILL AND SET OF EPOXY ANCHORS SHALL
NOT OCCUR LESS THAN 7 DAYS FROM
POURING CONCRETE.
7.
6'
3 X 4" PVC
CONDUIT FROM MAIN
SWITCHBOARD
4.6'
3.
9'
5.1'
4.
4'
GROUND LEVEL
GROUND LEVEL
4.9'
5.6'
.8
SIDE VIEW
FRONT VIEW
FOUNDATION DETAIL - TOP VIEW
POWER
CABINET
3.3'
2.8'
.5 '3"
POWER CABINET TOP VIEW
FRONT
VIEW
4.7'
.9'
.3
.3
1 X 1" PVC
CONDUIT FROM MAIN
SWITCHBOARD
4 X 4" PVC
CONDUIT TO
EV CHARGER
.8
PROVIDE 6" MIN. FROM
ANCHORS TO
CONDUIT WINDOW
AND PAD EDGE
(6) #5 REBARS
@ 10.5" OC
(7) #5 REBARS @ 10" OC
(6) #5 REBARS
@ 10.5" OC
(7) #5 REBARS
@ 10" OC
CONCRETE 4500 PSI
(6) #5 REBARS @ 10.5" OC
(7) #5 REBARS @ 10" OC
POWER CABINET
ETHERNET CONDUIT
(ETHER-LOOP)
DC POST CONDUIT
(CABINET TO POST)
CABINET ANCHORAGE
LOCATIONS, (TYP. 4)
1/2" DIAMETER SS THREADED ROD, W/
SIMPSON SET-3G ADHESIVE ANCHOR
SYSTEM WITH 4" MIN. EMBEDMENT INTO
(N) EQUIPMENT SLAB IN ACCORDANCE
WITH ESR-4057 OR APPROVED EQUAL.
DRILL AND SET OF EPOXY ANCHORS SHALL
NOT OCCUR LESS THAN 7 DAYS FROM
POURING CONCRETE.
AC CONDUIT
(SWITCHBOARD
TO CABINET)
.6' .6'
5.6'
4.
9'
.1
7'
6'
7' .4
6' .4
(7) #6 REBARS @ 11" OC
(7) #6 REBARS @ 13" OC
(7) #6 REBARS @ 13" OC
TRANSFORMER
(DETAILS PROVIDE
BY UTILITY)
TRANSFORMER
(DETAILS PROVIDE
BY UTILITY)
.4
.2
.1
.3
1.6' 1'1'
TRANSFORMER
(DETAILS PROVIDE
BY UTILITY)
TRANSFORMER
TRANSFORMER -
TOP VIEW
1'
FINISH GRADE
CONCRETE
4000 PSI
FINISH GRADE
CONCRETE
4000 PSI
3" CLEAR TYP.
EACH SIDE
3" CLEAR TYP.
EACH SIDE
FRONT VIEW
SIDE VIEW
7'
6'
(7) #6 REBARS @ 13" OC
(7) #6 REBARS @ 11" OC
FOUNDATION DETAIL - TOP VIEW
.3'
NO
PARKING
REBOUNDING
BOLLARD
ACCESSIBLE VAN EV CHARGE STALL - IBC & ADA
TOP VIEW
IF ACCESSIBLE ROUTE PASSES
BEHIND THE HEAD OF THE
ACCESSIBLE STALL, ENSURE
MINIMUM 4' CLEAR SPACE AT
BACK OF CHARGE POST, AND
1:48 MAX SLOPE ALL DIRECTIONS
FOR ACCESSIBLE ROUTE AT
HEAD OF STALL
HANDLE TERMINUS
BOLLARD SIGN
30" X 48"
CLEAR FLOOR
SPACE
4" WHITE BORDER
AND CROSS
STRIPING, TYP.
5' WIDE
ACCESS
AISLE
12" HIGH WHITE
TEXT
1:48 MAX SLOPE ALL DIRECTIONS AT ACCESSIBLE EV
VEHICLE STALL AND ACCESS AISLE
FOUNDATION DETAIL - TOP VIEW
2.3'
2'
.5 '4" M
IN
M
IN
11' MIN 5' MIN
HANDLE TERMINUS
CABLE
TERMINUS
5'-6"
CABLE
TERMINUS
4.7'
(N) V4 TESLA
SUPERCHARGER POST
(N) CIP PAD FLUSH
WITH (E) PAVEMENT
NATIVE SOIL
6" MIN. COMPACTED CLASS
2 AGGREGATE BASE
#4 REBAR (TOP&BOTTOM)
18" O.C. @ HORIZONTAL
12" O.C. @ VERTICAL
EXISTING LANDSCAPE
FRONT VIEW
SIDE VIEW
2'
.5
1.
5'
6.
4'
1'-1"
.3 '.3'
(10) #4 REBAR @ 10"
O.C.
(TOP&BOTTOM)
(4) #5 REBAR
(TOP&BOTTOM)
18" O.C. @ HORIZONTAL
12" O.C. @ VERTICAL
.2
2'
4.7'
V4 TESLA
SUPERCHARGER POST
WEIGHT: 198 LBS
TESLA SUPERCHARGER HANDLE
(MAX. 48" HEIGHT FOR
ACCESSIBLE CHARGE POSTS)
(4) 1/2" DIA SS HILTI KWIK-BOLT
TZ2 WITH 3.75" MIN. EMBEDMENT
PER ESR-4266, OR (4) 1/2" DIA SS
THREADED ROD WITH HILTI HIT-HY
200 V3 ADHESIVE ANCHOR SYSTEM
WITH 4" EMBEDMENT PER ESR-4868,
OR APPROVED EQUAL.
(10) #4 REBAR @ 10" O.C.
(TOP&BOTTOM)
(E) GRADE @ ACCESSIBLE
EV CHARGE POSTS
REBOUNDING
BOLLARD
(4) #5 REBAR @
TOP & BOTTOM
NATIVE SOIL 6" MIN. COMPACTED CLASS
2 AGGREGATE BASE
CABLE TERMINUS
2.2'
1.
5'
6' MIN
4'
.3
.3'
305 W SPRING CREEK PKWY,
SUITE 100 B PLANO, TX 75023
M
IC
R O
TE
L
IN
N
B Y
W
YN
D H
A M
C H
A M
PA
IG
N
R
IO
N
D R
C
H A
M
PA
IG
N
, I L
0 1 2 3 4 5 6 7 8 9N o.
BY
D
AT
E
IS
SU
E
BL
O C
K
DESIGNED BY:
CHECKED BY:
DRAWN BY:
AD
JP
VP
DOCUMENT DATE: AUG 21, 2026
NORDIC PROJECT ID/R: UNE-24-66/23
SHEET NUMBER
SH
EE
T
TI
TL
E:
3040 78 TH AVENUE SE,
UNIT 1619, MERCER ISLAND, WA 98040
Mob:720 492 2885 | www.nordicasia.net www.nordicasia.net
UNIVERSAL EV LLC
NORDIC ASIA
C3.0CT CABINET DETAILN.T.S.
SCALE A MAIN SWITCHBOARD DETAILN.T.S.
SCALE B POWER CABINET DETAILN.T.S.
SCALE CTRANSFORMER DETAIL N.T.S.
SCALE D EV CHARGER DETAIL N.T.S.
SCALE E
C
IV
IL
D
ET
AI
LS
-2
NOTE:
1. Charger slab foundation shall be of concrete slab with the dimensions of 4.7' length x 2' width, to accommodate the weight and dimensions of the EV charger base.
2. Each charger should include a QR code for payment and chargers should also include a credit card reader with RFID support for contactless payment.
3. Expansion joint material to be pre-formed with top tear-off for application of SL-2 Elastomeric sealant or approved equal.
3.9'
5'
20'
5'
9'
9'
9'
18'
5'13.1'
26.5'
23.4'
NO
PA
RK
IN
G
5'
C3.0
EV2.0
H
C3.0 E
EV2.0
F
EV2.0
G
C3.0 E
23'WIDE 2 WAY
DRIVE AISLE
US
E
LA
ST
C3.0
AC3.0
C
C3.0 B
3.
5'
3.8'
5' EXISTING CONCRETE
SIDEWALK (TYP)
EXISTING FIRE
HYDRANT
EXISTING LIGHT
POLE (TYP)
EXISTING LIGHT POLE (TYP)
STORM INLET
PROPOSEDADA PATH
PROPOSED ONE-WAY
DIRECTIONAL RAMP
VAN ACCESSIBLE
VAN ACCESSIBLE EV PARKING
SIGN WITH BOLLARDS
ELECTRIC VEHICLE
PARKING
EXISTING LIGHT POLE
TESLA V4 500 kW
SUPERCHARGER - 1A
FIRE LANE
NEW TRANSFORMER
NEW MAIN SWITCH BOARD
NEW CT CABINET
EXISTING UTILITTY CONDUIT LINE
EXISTING TRANSFORMER
FIBER OPTIC PEDESTAL
3'
4' -6
EMERGENCY
DISCONNECT SWITCH
(MOUNTED ON POLE)
8'
4'
2.6'
4'
4.
8'
TESLA V4 500 kW
SUPERCHARGER - 1B
STANDARD EV PARKING
SIGN WITH BOLLARDS
DOOR SWING
5' -6
5' 5.8'
PROTECTION BOLLARD
C3.0 D
C3.0 E
TESLA V4 500 kW
SUPERCHARGER - 1C&1D
(2
(1.40%)
(1.40%)
(0 .6
(0 .6
(1 .5
4%
(1.40%)
(1 .5
4%
(1.70%)
48"X30" GROUND SPACE
7'
6'
POWER CABINET
4.
7'
NEW POLE W/ CAMERA
ENCLOSURE
NVR & POE
NEW 1kVA TRANSFORMER WITH
NEMA 3R WEATHERPROOFING
ENCLOSURE
AC DISCONNECT
4'
4.
6'
3'
305 W SPRING CREEK PKWY,
SUITE 100 B PLANO, TX 75023
M
IC
R O
TE
L
IN
N
B Y
W
YN
D H
A M
C H
A M
PA
IG
N
R
IO
N
D R
C
H A
M
PA
IG
N
, I L
0 1 2 3 4 5 6 7 8 9N o.
BY
D
AT
E
IS
SU
E
BL
O C
K
DESIGNED BY:
CHECKED BY:
DRAWN BY:
AD
JP
VP
DOCUMENT DATE: AUG 21, 2026
NORDIC PROJECT ID/R: UNE-24-66/23
SHEET NUMBER
SH
EE
T
TI
TL
E:
3040 78 TH AVENUE SE,
UNIT 1619, MERCER ISLAND, WA 98040
Mob:720 492 2885 | www.nordicasia.net www.nordicasia.net
UNIVERSAL EV LLC
NORDIC ASIA
N
E
S
W270
350 0 10
4O
170180190
EV1.0
EV
C
H
AR
G
ER
P
LA
N
Charger Model : Tesla V4 Supercharger
Charger Quantity : 4 (1 port per EV Charger)
Capacity of EV DCFC : 500kW (Limited Output: 150 kW)
Power Cabinet Unit : Tesla V4 Power Cabinet (625kVA)
Power Cabinet Unit Quantity : 1 (One unit for four EV DCFC chargers)
Connector Types : CS-615-A2 (NACS + CCS1), CS-615-E2 (CCS2) (Up to 0V - 1000V DC)
Total Parking Slot : 4 (43 Feet with a 5 feet ADA access)
ADA Access : 5 Feet (Only for one parking slot)
CHARGING STATION SPECIFICATIONS:
1. Do not let the flammable, explosive or flammable materials, chemicals, flammable vapors, and other dangerous goods close to charging station.
2. No underground utilities are present in the trenching area.
3. Contractor must proceed with caution during EV conduit trenching and follow standard safety and verification procedures
CHARGING STATION SPECIFICATIONS:
The contractor shall verify that existing and/or new lighting levels at all EV charging stalls and associated accessible routes meet IESNA RP-20 recommendations for parking lots.
CONTRACTOR NOTE:
- ADA Charging Station Signage
SIGNAGE AND MARKING LABELS :
DESIGNED FOR ACCESSIBILITY
USE LAST
- Truncated Dome
- EV parking
- EV Charging Station and Signage
00 5' 10'
Sheet size : 24" X 36" Scale 1" = 5'
CONDUIT ESTIMATE SCHEDULE
ITEM CONDUIT QUANTITY LENGTH
TRANSFORMER TO CT CABINET 4" PVC 4 5'-0"
CT CABINET TO MAIN SWITCHBOARD 4" PVC 4 3'-5"
MAIN SWITCHBOARD TO POWER CABINET 4" PVC 3 14'-5"
POWER CABINET TO EV CHARGER -1A 4" PVC 1 79'-6"
POWER CABINET TO EV CHARGER -1B 4" PVC 1 61'-8"
POWER CABINET TO EV CHARGER -1C 4" PVC 1 51'-4"
POWER CABINET TO EV CHARGER -1D 4" PVC 1 41'-8"
Note: The quantities and dimensions are above…