Questions and Answers.docx

DOCX document 17 KB Posted

Attached to
Standby generator package for USCG Station Tillamook Bay
Solicitation number
37400PR250000066
Issued by

About this file

The document is a Questions and Answers file for a U.S. Coast Guard solicitation for a standby generator package at Tillamook Bay Station. Key technical details include requirements for a 150KW diesel-powered generator with a 600-amp automatic transfer switch and a 48-hour fuel tank, with specific clarifications about equipment specifications. Notable Q&A points reveal the generator is for backup power expected to run indefinitely during storm outages, requires UL2200 certification, will use a double-wall UL-142 fuel tank, and will be installed indoors with an indoor automatic transfer switch. The generator has a 22-week lead time, which is not considered problematic by the contracting team, and does not require remote monitoring capabilities. The solicitation seeks a lowest-priced, technically acceptable quote, with submission due by 05/29/25 at 12pm PST to the Contract Officer Patrick Stewart, with quotes to be submitted via email with a complete cost breakdown on SF1449 form.

View the file

Other files

File Type Posted
Questions and Answers.docx DOCX document
Questions and Answers.docx DOCX document
Questions and Answers.docx DOCX document
Questions and Answers.docx DOCX document
Smart Matrix Acquisition.GOV.pdf PDF
SF1449_STA Tillamook Generator.pdf PDF
Statement of Requirement_STA Tillamook_Generator.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers

Q.- Is this delivery only or is installation needed.

A. - Delivery only

Q. – Do you know the transition type: Open, delayed, or closed A. – Open transition (primary) or delayed (back up) will be suitable Q. – Will there be a breaker on the utility side of the ATS A. – Currently there is no breaker on utility side, will be looked into later.

Q. – Will the ATS be indoor or outdoor A. – ATS will be indoor as utility conduit is in mechanical room.

Q. – Solid, neutral, or switched A. – Neutral switch should work

Q. - Should this be a service rated ATS?

A. - This is a service rated ATS Q. - Lead time on the Generator is 22 weeks, ATS is 12 weeks. Is this an issue?

A. - No rush for timelines

Q. - What is the generator being used for (Prime Power / Backup Power)?

A. - This is a backup generator but is expected to run indefinitely until utility is restored after storms. Extra fuel is located on site in another tank if refuel is needed.

Q. - Are there any certifications (i.e.: UL2200) required for the generator?

A. - The generator shall be UL2200 Q. - Does the generator need remote monitoring capability?

A. - No need for remote monitoring.

Q. - Does the fuel tank need to be UL-142 certified?

A. - UL 142 tank shall be used Q. - Does the fuel tank need to be single wall or double wall?

A. - Double wall tank, void between wall needs to have access to remove liquids if any become present, fuel/water build up. and accessory port for leak detection.

Q. - Also does it require a spill bucket and fluid containment pan?

A. - Double wall tank counts as containment. No need for the spill bucket/pad.

Q. - Would a 24,000 BTU 3-zone system (7k + 7k + 12k) be a suitable replacement for the current 6k + 6k + 12k configuration?

A. - As long as it is a 24, 3 head unit yes that would be fine