Questions and Answers.docx
DOCX document 17 KB Posted
- Solicitation number
- 37400PR250000066
About this file
This document is a Questions and Answers file for a U.S. Coast Guard solicitation (RFQ 37400PR250000066) for a standby power system at Tillamook Bay Station. The Q&A clarifies technical specifications for a 150KW diesel-powered standbyGenerator, including requirements that the unit be UL2200 certified, have a double-wall UL-142 fuel tank, and function as a backup power source capable of running indefinitely during utility outages. Key technical details include an indoor automatic transfer switch (ATS), neutral switch configuration, and no requirement for remote monitoring.
The solicitation seeks a complete standby power package delivered to USCG Station Tillamook Bay, comprising a 150KW 208V 3-phase outdoor dieselGenerator, 600-amp automatic bus transfer switch, and a 48-hour fuel tank with level indicator. Quotes are due by 09/29/25 at 12pm PST, with the government intending to award to the lowest-priced, technically acceptable quote. Vendors must submit quotes on SF1449 with a detailed cost breakdown and be registered in the System Award Management (SAM) to be considered for the contract.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions and Answers.docx | DOCX document | |
| Questions and Answers.docx | DOCX document | |
| Questions and Answers.docx | DOCX document | |
| Questions and Answers.docx | DOCX document | |
| Smart Matrix Acquisition.GOV.pdf | ||
| SF1449_STA Tillamook Generator.pdf | ||
| Statement of Requirement_STA Tillamook_Generator.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions and Answers
Q.- Is this delivery only or is installation needed.
A. - Delivery only
Q. – Do you know the transition type: Open, delayed, or closed A. – Open transition (primary) or delayed (back up) will be suitable Q. – Will there be a breaker on the utility side of the ATS A. – Currently there is no breaker on utility side, will be looked into later.
Q. – Will the ATS be indoor or outdoor A. – ATS will be indoor as utility conduit is in mechanical room.
Q. – Solid, neutral, or switched A. – Neutral switch should work
Q. - Should this be a service rated ATS?
A. - This is a service rated ATS Q. - Lead time on the Generator is 22 weeks, ATS is 12 weeks. Is this an issue?
A. - No rush for timelines
Q. - What is the generator being used for (Prime Power / Backup Power)?
A. - This is a backup generator but is expected to run indefinitely until utility is restored after storms. Extra fuel is located on site in another tank if refuel is needed.
Q. - Are there any certifications (i.e.: UL2200) required for the generator?
A. - The generator shall be UL2200 Q. - Does the generator need remote monitoring capability?
A. - No need for remote monitoring.
Q. - Does the fuel tank need to be UL-142 certified?
A. - UL 142 tank shall be used Q. - Does the fuel tank need to be single wall or double wall?
A. - Double wall tank, void between wall needs to have access to remove liquids if any become present, fuel/water build up. and accessory port for leak detection.
Q. - Also does it require a spill bucket and fluid containment pan?
A. - Double wall tank counts as containment. No need for the spill bucket/pad.