This document is a Questions and Answers file for a U.S. Coast Guard solicitation for a standby generator package at Tillamook Bay Station. The Q&A clarifies technical details about the generator installation, including confirmation that delivery is only required (not installation), and specifying the automatic transfer switch (ATS) will be indoor with a neutral switch. Additional technical clarifications include potential transition types (open or delayed) and current utility side configurations.

The related solicitation seeks a 150KW diesel-powered generator with a 600-amp automatic bus transfer switch and a 48-hour fuel tank, to be delivered to USCG Station Tillamook Bay in Garibaldi, Oregon. Quotes are due by 05/29/25 at 12pm PST, with all submissions required to be on SF1449 and include a cost breakdown. The government intends to award to the lowest-priced, technically acceptable quote, with vendors required to be registered in the System Award Management (SAM) prior to award.

View the file

Other files

File Type Posted
Questions and Answers.docx DOCX document
Questions and Answers.docx DOCX document
Questions and Answers.docx DOCX document
Questions and Answers.docx DOCX document
Smart Matrix Acquisition.GOV.pdf PDF
SF1449_STA Tillamook Generator.pdf PDF
Statement of Requirement_STA Tillamook_Generator.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers

Q.- Is this delivery only or is installation needed.

A. - Delivery only

Q. – Do you know the transition type: Open, delayed, or closed A. – Open transition (primary) or delayed (back up) will be suitable Q. – Will there be a breaker on the utility side of the ATS A. – Currently there is no breaker on utility side, will be looked into later.

Q. – Will the ATS be indoor or outdoor A. – ATS will be indoor as utility conduit is in mechanical room.

Q. – Solid, neutral, or switched A. – Neutral switch should work