Correct Life Safety Deficiencies Construction Iowa City
Solicitation number
36E77618R0052
Issued by

About this file

36E77618R0052 00005 Addendum 00005 - 04-19-2018.pdf

View the file

Other files

File Type Posted
36E77618R0052-00008000.docx DOCX document
36E77618R0052-00008001.pdf PDF
36E77618R0052-00008002.pdf PDF
36E77618R0052-00007000.docx DOCX document
36E77618R0052-00006000.docx DOCX document
36E77618R0052-00006002.pdf PDF
36E77618R0052-00006001.pdf PDF
36E77618R0052-00005006.pdf PDF
36E77618R0052-00005007.pdf PDF
36E77618R0052-00005000.docx DOCX document
36E77618R0052-00005005.pdf PDF
36E77618R0052-00005004.pdf PDF
36E77618R0052-00005001.pdf PDF
36E77618R0052-00005003.pdf PDF
36E77618R0052-00005008.pdf PDF
36E77618R0052-00004000.docx DOCX document
36E77618R0052-00004001.pdf PDF
36E77618R0052-00004002.docx DOCX document
36E77618R0052-00003000.docx DOCX document
36E77618R0052-00003001.pdf PDF
36E77618R0052-00002007.pdf PDF
36E77618R0052-00002001.pdf PDF
36E77618R0052-00002008.pdf PDF
36E77618R0052-00002003.pdf PDF
36E77618R0052-00002006.pdf PDF
36E77618R0052-00002009.pdf PDF
36E77618R0052-00002005.pdf PDF
36E77618R0052-00002004.pdf PDF
36E77618R0052-00002002.pdf PDF
36E77618R0052-00002000.docx DOCX document
36E77618R0052-00001003.zip ZIP file
36E77618R0052-00001006.zip ZIP file
36E77618R0052-00001000.docx DOCX document
36E77618R0052-00001001.pdf PDF
36E77618R0052-00001005.zip ZIP file
36E77618R0052-00001004.zip ZIP file
36E77618R0052-00001002.pdf PDF
36E77618R0052-018.docx DOCX document
36E77618R0052-010.pdf PDF
36E77618R0052-006.pdf PDF
36E77618R0052-016.pdf PDF
36E77618R0052-007.pdf PDF
36E77618R0052-021.doc DOC document
36E77618R0052-011.pdf PDF
36E77618R0052-014.pdf PDF
36E77618R0052-002.pdf PDF
36E77618R0052-019.docx DOCX document
36E77618R0052-008.pdf PDF
36E77618R0052-009.pdf PDF
36E77618R0052-017.zip ZIP file
Show 40 more

Latest 50 of 59 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Y:\171\171-005 Iowa City VA Additions\DOCUMENTS\ADM'S\ADM-00005_OPEN\171-005_VAIC Addendum No. 00005.doc 1

ADDENDUM NO. 00005 KENNETH HAHN ARCHITECTS

Architecture/Planning/ to the Interior Design/Engineering Specifications and Drawings 1343 South 75th Street Omaha, Nebraska 68124

19 APRIL 2018

KHA Project No. 171-005

IOWA CITY VA HEALTH CARE SYSTEM

CORRECT LIFE SAFETY DEFICIENCIES

Iowa City, Iowa

VA Project: 636A8-16-006

NOTICE TO BIDDERS: The Specification and Drawings for the above-referenced project are hereby amended as follows:

SPECIFICATIONS – VOLUME 1

ITEM NO. S-01, SECTION 08 71 00, DOOR HARDWARE

A. Paragraph 3.5, Hardware Sets:

a. Page 22, Set HW-4Y: Delete the words “X ADJUSTA-SCREWS” from the Hinges.

b. Page 22, Set HW-4Z: Delete the words “X ADJUSTA-SCREWS” from the Hinges.

c. Page 26, Set HW-SH-3F: Delete the words “X ADJUSTA-SCREWS” from the Continuous

Transfer Hinge.

d. Page 27, Set HW-SH-4A: Delete the words “X ADJUSTA-SCREW” from the Continuous

Hinge.

e. Page 30, Set HW-MH5: Delete the words “X ADJUSTA-SCREWS” from the Continuous Hinge.

f. Page 31, Set HW-MH5A: Delete the words “X ADJUSTA-SCREWS” from the Continuous

Hinge.

g. Page 32, Set HW-X2: Delete the words “X ADJUSTA-SCREWS” from the Continuous Hinge.

B. Paragraph 3.5, Hardware Sets, Page 19, Set 1K:

a. Revise Self-Adhesive Seals from 2 sets to 1 set.

C. Paragraph 3.5, Hardware Sets, Page 21, Set 4P:

a. Revise Self-Adhesive Seals from 2 sets to 1 set.

D. Paragraph 3.5, Hardware Sets, Page 24, Set HW-12H:

a. Delete the entire set and replace with the following:

Hinges QUANTITY & TYPE AS REQUIRED

2 Exit Device TYPE 2 F08 LEVER

2 Key Cylinder TYPE AS REQUIRED

2 Kick Plate J102

2 Floor Stop L02121 x 3 FASTENERS

2 Set Self-Adhesive Seals R0Y154

AUTO DOOR OPERATORS (BOTH LEAFS) AND CONTROLS BY SECTION 08 71 13.

Y:\171\171-005 Iowa City VA Additions\DOCUMENTS\ADM'S\ADM-00005_OPEN\171-005_VAIC Addendum No. 00005.doc 2

ITEM NO. S-02, SECTION 08 88 00, GLAZING

A. Replace this section in its entirety with Attachment No. 1.

DRAWINGS – VOLUME 1

ITEM NO. D-01, SHEET A2-01W – FIRST FLOOR PLAN

A. Detail 1, First Floor Plan:

a. Revise the location of the automatic door operator controls at door 1CP01B as shown on the attached revised sheet A2-01W.

ITEM NO. D-02, SHEET AH1 – ROOM FINISH SCHEDULE

A. Schedule for Finishes:

a. At “08 80 00 GLAZING”, delete the line ‘SOLARCOOL BRONZE BY PPG, MATCH EXISTING” and replace with the following “SOLARCOOL SOLARBRONZE BY PPG

(VITRO), MATCH EXISTING COLOR”.

ITEM NO. D-03, SHEET AT20 – MISCELLANEOUS DETAILS

A. Detail 4, TV Cover At Group Room 9W42:

a. Replace the note “SG#1” with the note “SG#2”.

ITEM NO. D-04, SHEET AH2 – DOOR SCHEDULE

A. Door and Frame Schedule:

a. At door 1W70, delete Door Glass note “BR” and replace with note “SG#2”.

B. Door Schedule Legend:

a. Add the following line: “IL INSULATED LAMINATED GLAZING” C. Detail 3, Hollow Metal Frame Types:

a. At the frame type “F02” to the far left of the detail, rename frame type to read “F04”.

b. At frame type “F03”, delete the note “LG#_” and replace with the following note “LG#1”.

c. At frame type “F04”, delete the note “LG#_” and replace with the following note “LG#1”.

D. Detail 5, Service and Teller Window Unit

a. Delete the note “UL RATED LEVEL 1 BULLET RESISTANT ACRYLIC INCLUDING WALL

SECTIONS, WINDOWS” and replace with the following note “UL752 LEVEL 3 GLAZING

WITH SECURE AIR PASSAGE AS REQUIRED FOR VOICE TRANSMISSION.”.

DRAWINGS – VOLUME 2

ITEM NO. D-05, SHEET M3 – MECHANICAL SCHEDULES

A. Fan Coil Unit Schedule:

a. Revise remark 5 as shown on the attached revised sheet M3.

B. Variable Frequency Drive Schedule:

a. Revise the schedule as shown on the attached revised sheet M3.

ITEM NO. D-06, SHEET M4 – MECHANICAL SCHEDULES

A. Built-up Air Handling Unit Schedule:

a. Revise the schedule as shown on the attached revised sheet M4.

ITEM NO. D-07, SHEET EP2-01W – POWER FIRST FLOOR PLAN

A. Electrical Keynotes:

a. Revise keynote 18 as shown on the attached revised sheet EP2-01W.

ITEM NO. D-08, SHEET EY2-01W – SPECIAL SYSTEMS FIRST FLOOR PLAN

A. Detail 1, Special Systems First Floor Plan:

a. Revise the location of the special systems associated with door 1CP01B as shown on the attached revised sheet EY2-01W.

Y:\171\171-005 Iowa City VA Additions\DOCUMENTS\ADM'S\ADM-00005_OPEN\171-005_VAIC Addendum No. 00005.doc 3

ITEM NO. D-09, SHEET E4 – ELECTRICAL SCHEDULES

A. Luminaire Schedule – Luminaire Schedule Remarks:

a. Note 7: Delete the note in its entirety and replace with the following: “Not used.”.

ADDENDUM NO. 00005 KENNETH HAHN ARCHITECTS
Architecture/Planning/