The project involves the expansion of gravesites and facility condition assessment (FCA) improvements at the Tallahassee National Cemetery. The structural design is governed by the U.S. Department of Veterans Affairs construction procedures and standards. The structural system consists of reinforced concrete walls, steel beams, and a metal roof deck. Key structural elements include a slab-on-grade foundation, reinforced masonry walls, and detailed specifications for concrete, steel, and masonry construction. The document provides comprehensive structural general notes, schedules, and standard details to guide the construction of the building and site work.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRUCTURAL GENERAL NOTES
GOVERNING CODE: THE DESIGN AND CONSTRUCTION OF THIS PROJECT IS GOVERNED BY THE
DESIGN AND CONSTRUCTION PROCEDURES OF VA FACILITIES PRODUCED BY THE OFFICE OF
CONSTRUCTION & FACILITIES MANAGEMENT OF THE U.S. DEPARTMENT OF VETRANS AFFAIRS.
REFERENCE STANDARDS: REFER TO CHAPTER 35 OF THE 2021 IBC. WHERE OTHER STANDARDS ARE NOTED IN THE DRAWINGS, USE THE LATEST EDITION OF THE STANDARD UNLESS A SPECIFIC DATE IS INDICATED. REFERENCE TO A SPECIFIC SECTION IN A CODE DOES NOT RELIEVE THE CONTRACTOR
FROM COMPLIANCE WITH THE ENTIRE STANDARD.
NOTE PRIORITIES: PLAN AND DETAIL NOTES AND SPECIFIC LOADING DATA PROVIDED ON INDIVIDUAL PLANS AND DETAIL DRAWINGS SUPPLEMENTS INFORMATION IN THE STRUCTURAL GENERAL NOTES.
DISCREPANCIES: IN CASE OF DISCREPANCIES BETWEEN THE GENERAL NOTES, SPECIFICATIONS PLAN/DETAILS OR REFERENCE STANDARDS, THE CONTRACTING OFFICER'S REPRESENTATIVE "COR" SHALL DETERMINE WHICH SHALL GOVERN. DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE COR BEFORE PROCEEDING WITH THE WORK. SHOULD ANY DISCREPANCY BE FOUND IN THE CONTRACT DOCUMENTS, THE CONTRACTOR WILL BE DEEMED TO HAVE INCLUDED IN THE PRICE THE
MOST EXPENSIVE WAY OF COMPLETING THE WORK, UNLESS PRIOR TO THE SUBMISSION OF THE
PRICE, THE CONTRACTOR ASKS FOR A DECISION FROM THE COR AS TO WHICH SHALL GOVERN.
ACCORDINGLY, ANY CONFLICT IN OR BETWEEN THE CONTRACT DOCUMENTS SHALL NOT BE A BASIS
FOR ADJUSTMENT IN THE CONTRACT PRICE.
COORDINATION: THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING DETAILS AND ACCURACY
OF THE WORK; FOR CONFIRMING AND CORRELATING ALL QUANTITIES AND DIMENSIONS; FOR
SELECTING FABRICATION PROCESSES; FOR TECHNIQUES OF ASSEMBLY; AND FOR PERFORMING
WORK IN A SAFE AND SECURE MANNER.
MEANS, METHODS, AND SAFETY REQUIREMENTS: THE CONTRACTOR IS RESPONSIBLE FOR THE
MEANS AND METHODS OF CONSTRUCTION AND ALL JOB RELATED SAFETY STANDARDS SUCH AS
OSHA AND DOSH (DEPARTMENT OF OCCUPATIONAL SAFETY AND HEALTH). CONTRACTOR IS
RESPONSIBLE TO ADHERE TO OSHA REGULATIONS REGARDING STEEL ERECTION ITEMS
SPECIFICALLY ADDRESSED IN THE LATEST OSHA REGULATIONS.
TEMPORARY SHORING, BRACING: THE CONTRACTOR IS RESPONSIBLE FOR THE STRENGTH AND
STABILITY OF THE STRUCTURE DURING CONSTRUCTION AND SHALL PROVIDE TEMPORARY SHORING, BRACING AND OTHER ELEMENTS REQUIRED TO MAINTAIN STABILITY UNTIL THE STRUCTURE IS
COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO BE FAMILIAR WITH THE WORK REQUIRED IN
THE CONSTRUCTION DOCUMENTS AND THE REQUIREMENTS FOR EXECUTING IT PROPERLY.
SITE VERIFICATION: THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE. CONFLICTS BETWEEN THE DRAWINGS AND ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO
THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE WORK.
ADJACENT UTILITIES: THE CONTRACTOR SHALL DETERMINE THE LOCATION OF ALL ADJACENT
UNDERGROUND UTILITIES PRIOR TO EARTHWORK, FOUNDATIONS, SHORING, AND EXCAVATION. ANY
UTILITY INFORMATION SHOWN ON THE DRAWINGS AND DETAILS IS APPROXIMATE AND NOT
NECESSARILY COMPLETE.
ALTERNATES: ALTERNATE PRODUCTS OF SIMILAR STRENGTH, NATURE, AND FORM FOR SPECIFIED ITEMS MAY BE SUBMITTED WITH ADEQUATE TECHNICAL DOCUMENTATION TO THE COR FOR REVIEW.
ALT MATERIALS THAT ARE SUBMITTED WITHOUT ADEQUATE DOCUMENTATION OR THAT
SIGNIFICANTLY DEVIATE FROM THE DESIGN INTENT OF MATERIALS SPECIFIED MAY BE REJECTED.
ALTS. THAT REQUIRE SUBSTANTIAL EFFORT TO REVIEW WILL NOT BE REVIEWED UNLESS
AUTHORIZED BY THE COR.
GENERAL REQUIREMENTS
CONTRACTING OFFICER'S REPRESENTATIVE (COR)
STRUCTURAL ENGINEER OF RECORD (SER): THE STRUCTURAL ENGINEER WHO IS LICENSED TO
STAMP & SIGN THE STRUCTURAL DOCUMENTS FOR THE PROJECT. THE SER IS RESPONSIBLE FOR
THE DESIGN OF THE PRIMARY STRUCTURAL SYSTEM.
GENERAL CONTRACTOR (CONTRACTOR): THE CONSTRUCTION MANAGER RESPONSIBLE FOR THE
OVERALL COORDINATION OF THE PROJECT CONSTRUCTION.
CONTRACT DOCUMENTS (CDs): THE CONTRACT BETWEEN GOVERNMENT AND CONTRACTOR AND
ANY DOCUMENTS EXPRESSLY INCORPORATED THEREIN INCLUDING THE BID SUBMITTED BY THE
CONTRACTOR, THE DRAWINGS AND THE SPECIFICATIONS, AND ALL MODIFICATIONS, INCLUDING
ADDENDA AND SUBSEQUENT CHANGE ORDERS.
SPECIFICATIONS: REFER TO THE PROJECT SPECIFICATIONS ISSUED AS PART OF THE CONTRACT
DOCUMENTS FOR INFORMATION SUPPLEMENTAL TO THESE DRAWINGS.
OTHER DRAWINGS: REFER TO THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, CIVIL AND
PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION INCLUDING BUT NOT LIMITED TO:
DIMENSIONS, ELEVATIONS, SLOPES, DOOR AND WINDOW OPENINGS, CANOPIES, NON-BEARING
WALLS, FINISHES, DRAINS, WATERPROOFING, RAILINGS, CURTAIN WALLS, CURBS, DEPRESSIONS, MECHANICAL UNIT LOCATIONS, AND OTHER NONSTRUCTURAL ITEMS.
DEFINITIONS
DESIGN CRITERIA
RISK CATEGORY IIWIND DESIGN
DATA ULTIMATE DESIGN WIND SPEED (3 SECOND
GUST), VULT
139 MPH
EXPOSURE CATEGORY C
MAIN WIND FORCE RESISTING SYSTEM
RISK CATEGORY II
INTERNAL PRESSURE COEFFICIENT, CPI +/- 0.55
TOPOGRAPHIC FACTOR, KZT 1.0
ANALYSIS PROCEDURE DIRECTIONAL PROCEDURE
EARTHQUAKE
DESIGN DATA
SEISMIC DESIGN CATEGORY, SDC D
SEISMIC FORCE RESISTING SYSTEM REINFORCED MASONRY & CONCRETE
SHEARWALL
SITE CLASSIFICATION, SITE CLASS D
IMPORTANCE FACTOR, IE 1.0
MAPPED SPECTRAL
RESPONSE
ACCELERATION
0.658 g
0.208 g
SHORT PERIOD,
SS
1-SECOND
PERIOD, S1
DESIGN SPECTRAL
RESPONSE
COEFFICIENT
0.559 g
0.303 g
SEISMIC RESPONSE COEFFICIENT,
CS = SDS/R
0.2795
DESIGN BASE SHEAR 3 KIPS
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
LIVE LOADS ROOF 20 PSF
FLOOR: (NA) NA
ROOF SNOW
LOAD (IN
ACCORDANCE
WITH CHAPTER
7 OF ASCE7-16)
FLAT ROOF SNOW LOAD, PF 4.0 PSF
IMPORTANCE FACTOR, IS 1.0
GROUND SNOW LOAD, PG 7 PSF
EXPOSURE FACTOR, CE 0.9
THERMAL FACTOR, CT 1.2
DEFLECTION
LIMITS
ROOF: DEAD + (LIVE OR SNOW OR WIND),
TOTAL LOAD
L/240
ROOF: ( LIVE OR SNOW OR WIND) L/360
FLOOR: TOTAL LOAD UNO L/240
FLOOR: LIVE LOAD UNO L/360
FLOOR: CORRIDORS &
STAIRS
NA
RESPONSE MODIFICATION COEFFICIENT, R 2
NA
NA
UNIFORMLY DIST
CONCENTRATED
IMPACT
UNIFORMLY DIST
SPECIAL LOADS AND SPECIFIED SECTION
OF CODE
NASPECIAL
LOADS
DRIFT SURCHARGE LOADS, PD NA
WIDTH OF SNOW DRIFT NA
PHOTOVOLTAIC DEAD LOAD NA
UNIFORMLY DIST
PROJECT ELEVATION 19.81 FT (SEE CIVIL)
REINFORCED MASONRY & CONCRETE
SHEARWALL
SHORT PERIOD,
SS
1-SECOND
PERIOD, S1
NACONCENTRATED
NAIMPACT
COMPONENTS AND CLADDING PRESSURES (PSF)
ROOF ZONES WALL ZONESEFFECTIVE AREA
(SQ FEET)
INTERIOR ZONES (ROOFS: ZONE 1, WALLS: ZONE 4)
END ZONES (ROOFS: ZONE 2, WALLS: ZONE 5)
CORNER ZONES (ROOFS: ZONE 3)
NOTES:
1. H = MEAN ROOF HEIGHT = 15 FT.
2. A = END/CORNER WIDTH = 3 FT.
3. WALL ZONE DESIGN PRESSURES SHALL BE CONSIDERED
TO ACT AS BOTH POSITIVE AND NEGATIVE PRESSURES.
4. ROOF ZONE DESIGN PRESSURES ARE NEGATIVE (UPLIFT).
5. COMPONENT AND CLADDING PRESSURES SHOWN ARE
UNFACTORED.
52.9
MONOSLOPED
ROOF
a a a a
1 2 3
50.7
47.9
45.7
63.6
59.3
53.6
49.3
110.1
100.4
87.6
77.9
45.7
43.8
41.3
39.4
56.5
52.7
47.6
43.8
4a
4a
2a
BIDDER-DESIGNED ELEMENTS: SUBMIT "BIDDER-DESIGNED" DEFERRED SUBMITTALS TO THE
CONTRACTING OFFICER'S REPRESENTATIVE FOR REVIEW PRIOR TO SUBMISSION TO THE CITY FOR
APPROVAL.
DESIGN OF PREFABRICATED, "BIDDER DESIGNED", MANUFACTURED, PRE-ENGINEERED, OR OTHER
FABRICATED PRODUCTS SHALL BE COMPLIANT WITH THE FOLLOWING REQUIREMENTS:
· DESIGN CONSIDERS TRIBUTARY DEAD, LIVE, WIND, AND EARTHQUAKE LOADS IN
COMBINATIONS REQUIRED BY CODE.
· DESIGN WITHIN THE DEFLECTION LIMITS NOTED HEREIN AND AS SPECIFIED OR REFERENCED
IN 2018 IBC.
· DESIGN SHALL CONFORM TO THE SPECIFICATIONS AND REFERENCE STANDARDS OF THE
GOVERNING CODE.
· SUBMITTAL SHALL INCLUDE:
A. CALCULATIONS PREPARED, STAMPED AND SIGNED BY THE SSE DEMONSTRATING CODE
CONFORMANCE.
B. ENGINEERED COMPONENT DESIGN DRAWINGS ARE PREPARED, STAMPED AND SIGNED BY
THE SSE.
C. PRODUCT DATA, TECHNICAL INFORMATION AND MANUFACTURER'S WRITTEN
REQUIREMENTS AND AGENCY APPROVALS AS APPLICABLE.
D. SSE MAY SUBMIT TO THE ARCHITECT/ENGINEER, A REQUEST TO UTILIZE RELEVANT
ALTERNATE DESIGN CRITERIA OF SIMILAR NATURE AND GENERALLY EQUIVALENCY WHICH
IS RECOGNIZED BY THE CODE AND ACCEPTABLE TO THE AUTHORITY HAVING
JURISDICTION. SUBMIT ADEQUATE DOCUMENTATION OF DESIGN.
GENERAL CONTRACTOR'S PRIOR REVIEW: ONCE THE CONTRACTOR HAS COMPLETED HIS REVIEW
OF THE SSE COMPONENT DRAWINGS, THE COR WILL REVIEW THE SUBMITTAL FOR GENERAL
CONFORMANCE WITH THE DESIGN OF THE BUILDING AND WILL STAMP THE SUBMITTAL
ACCORDINGLY. REVIEW OF THE SPECIALTY STRUCTURAL ENGINEER'S (SSE) SHOP DRAWINGS
(COMPONENT DESIGN DRAWINGS) IS FOR COMPLIANCE WITH DESIGN CRITERIA AND COMPATIBILITY
WITH THE DESIGN OF THE PRIMARY STRUCTURE AND DOES NOT RELIEVE THE SSE OF
RESPONSIBILITY FOR THAT DESIGN. ALL NECESSARY BRACING, TIES, ANCHORAGE, PROPRIETARY
PRODUCTS SHALL BE FURNISHED AND INSTALLED PER MANUFACTURER'S INSTRUCTIONS OR THE
SSE'S DESIGN DRAWINGS AND CALCULATIONS. THESE ELEMENTS INCLUDE BUT ARE NOT LIMITED
TO:
• STEEL DECK EDGE FORMS
• EXTERIOR CLADDING SYSTEMS: CURTAIN WALL/STOREFRONT SYSTEMS, PRE-ENGINEERED
PANELS
DEFERRED SUBMITTALS
SOILS AND FOUNDATIONS
GEOTECHNICAL
REPORT ECS SOUTHWEST, LLP 23:3490
PREPARED BY: REPORT NO. REPORT DATE
MARCH 1, 2023
1. FOUNDATIONS FOR ALL STRUCTURES SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE
WITH THE GEOTECHNICAL REPORT PREPARED FOR THIS SITE.
2. THE CONTRACTOR MUST FULLY REVIEW THIS REPORT PRIOR TO CONSTRUCTION.
3. INFORMATION IN THE GEOTECHNICAL REPORT SUPERSEDES ANY CONFLICTING INFORMATION
CONTAINED IN THE CDS.
DESIGN
CRITERIA
NET ALLOWABLE SOIL BEARING PRESSURE 2000 PSF
MINIMUM EMBEDMENT (BELOW EXT GRADE
OR SLAB SUBGRADE)
12 INCHES
MINIMUM CONTINUOUS FOOTING WIDTH 18 INCHES
MINIMUM ISOLATED FOOTING WIDTH 30 INCHES
ESTIMATED TOTAL SETTLEMENT LESS THAN 1 INCH
ESTIMATED DIFFERENTIAL SETTLEMENT LESS THAN 1/2 INCH OVER 30 FT.
SOIL PREPARATION AT BUILDING: PER PLAN AND GEOTECHNICAL REPORT
CAST-IN-PLACE CONCRETE
CONCRETE MIX DESIGN REQUIREMENTS
S T
R E
N G
T H
F 'C
P
S I)
ALL CONCRETE
M A
X
IM
U M
W
/C M
R A
T
IO
A G
G R
E G
A T
E , M
A X
IN
A
IR
C O
N T
E N
T
1.
5%
R E
C O
M M
E N
D
S
LU
M P
IN
T E
S T
A G
E
28 1
E X
P O
S U
R E
C
LA
S S
0.5 3
REFERENCE STANDARDS:
1. ACI 301-16 "SPECIFICATIONS FOR STRUCTURAL CONCRETE"
2. ACI 305R-10 "GUIDE TO HOT WEATHER CONCRETING"
3. ACI 305.1-10 "SPECIFICATIONS FOR HOT WEATHER CONCRETING"
4. ACI 306R-10 "GUIDE TO COLD WEATHER CONCRETING"
5. ACI 306.1-10 "SPECIFICATION FOR COLD WEATHER CONCRETING"
6. ACI 318-19 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"
7. ACI 117-10 "SPECIFICATION FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND
MATERIALS"
SUBMITTALS
PROVIDE ALL SUBMITTALS REQUIRED BY ACI 301 SECTION 4.1.2. SUBMIT MIX DESIGNS FOR EACH MIX
IN THE TABLE BELOW. SUBSTANTIATING STRENGTH RESULTS FROM PAST TESTS SHALL NOT BE
OLDER THAN 24 MONTHS PER ACI 318 SECTION 26.4.3.1(b).
MIX DESIGN REQUIREMENTS NOTES:
1. FLY ASH: THE USE OF FLY ASH, OTHER POZZOLANS, SILICA FUME OR SLAG SHALL CONFORM
TO ACI 318 TABLE 26.4.2.2(b) AND SECTION 26.4.2.2 MAXIMUM AMOUNT OF FLY ASH SHALL BE
25% OF TOTAL CEMENTITIOUS CONTENT UNLESS REVIEWED AND APPROVED OTHERWISE BY
SER.
2. AGGREGATES SHALL CONFORM TO ASTM C33.
3. NON-CHLORIDE ACCELERATOR: NON-CHLORIDE ACCELERATING ADMIXTURE MAY BE USED IN
CONCRETE PLACED AT AMBIENT TEMPERATURES BELOW 50°F AT THE CONTRACTOR'S
OPTION.
4. RECOMMENDED SLUMP APPLY WHEN VIBRATION IS USED TO CONSOLIDATE THE CONCRETE
AND MAY BE INCREASED BY 1" FOR OTHER CONSOLIDATION METHODS. SLUMP MAY BE
INCREASED WHEN CHEMICAL ADMIXTURES ARE USED, PROVIDED THAT THE TREATED
CONCRETE HAS THE SAME OR LOWER WATER/CEMENT RATIO AND DOES NOT SHOW
SEGREGATION POTENTIAL OR EXCESSIVE BLEEDING. MEASURED SLUMP TOLERANCE SHALL
BE +/-1.5" MAXIMUM.
CONCRETE CURING: PROVIDE CURING COMPOUNDS FOR CONCRETE AS FOLLOWS:
1. USE MEMBRANE CURING COMPOUNDS THAT ARE COMPATIBLE WITH AND WILL NOT AFFECT
SURFACES TO BE COVERED WITH FINISH MATERIALS APPLIED DIRECTLY TO CONCRETE.
2. APPLY CURING COMPOUNDS AT A RATE EQUIVALENT TO THE RATE OF APPLICATION AT
WHICH CURING COMPOUND WAS ORIGINALLY TESTED FOR IN CONFORMANCE TO THE
REQUIREMENTS OF ASTM C 309-18 AND THE MANUFACTURER'S RECOMMENDATIONS.
TESTING: OBTAIN SAMPLES AND CONDUCT TESTS IN ACCORDANCE WITH ACI 301 SECTION 1.6.3.2
ADDITIONAL SAMPLES MAY BE REQUIRED TO OBTAIN CONCRETE STRENGTHS AT ALTERNATE
INTERVALS THAN SHOWN BELOW. CURE 4 CYLINDERS FOR 28-DAY TEST. TEST 1 CYLINDER AT 7 DAYS, TEST 2 CYLINDERS AT 28 DAYS, AND HOLD 1 CYLINDER IN RESERVE FOR USE AS THE SER DIRECTS. AFTER 56 DAYS, UNLESS NOTIFIED BY THE ENGINEER TO THE CONTRARY, THE RESERVE
CYLINDER MAY BE DISCARDED WITHOUT BEING TESTED FOR SPECIMENS MEETING 28 DAY
STRENGTH REQUIREMENTS.
ACCEPTANCE: STRENGTH IS SATISFACTORY WHEN:
1. THE AVERAGES OF ALL SETS OF 3 CONSECUTIVE TESTS EQUAL OR EXCEED THE SPECIFIED
STRENGTH.
2. NO INDIVIDUAL TEST FALLS BELOW THE SPECIFIED STRENGTH BY MORE THAN 500 PSI.
3. A "TEST" FOR ACCEPTANCE IS THE AVERAGE STRENGTH OF TWO 6 BY 12 IN CYLINDERS OR
THREE 4 BY 8 IN CYLINDERS TESTED AT THE SPECIFIED TEST AGE.
F2/S0/ W0/C1
6.0
CONCRETE REINFORCEMENT
REFERENCE STANDARDS:
1. ACI 301-16 "STANDARD SPECIFICATIONS FOR STRUCTURAL CONCRETE", SECTION 3
"REINFORCEMENT AND REINFORCEMENT SUPPORTS.
2. ACI SP-66-04 "ACI DETAILING MANUAL" INCLUDING ACI 315-99 "DETAILS AND DETAILING OF
CONCRETE REINFORCEMENT.
3. CRSI MSP-18, 29TH EDITION, "MANUAL OF STANDARD PRACTICE".
4. ANSI/AWS D1.4-18 "STRUCTURAL WELDING CODE-REINFORCING STEEL.
5. IBC CHAPTER 19-CONCRETE.
6. ACI318-19.
7. ACI117-10.
SUBMITTALS: SUBMIT PLACING DRAWINGS SHOWING FABRICATION DIMENSIONS AND LOCATIONS
FOR PLACEMENT OF REINFORCEMENT AND REINFORCEMENT SUPPORTS.
MATERIALS REINFORCING BARS ASTM A615 GRADE 60 DEFORMED BARS
WELDABLE REINFORCING BARS ASTM A706 GRADE 60 DEFORMED BARS
SMOOTH WELDED WIRE FABRIC ASTM A185
DEFORMED WELDED WIRE FABRIC ASTM A497
BAR SUPPORTS CRS I MSP-09, CHAPTER 3 "BAR
SUPPORTS"
TIE WIRE 16 GAGE OR HEAVIER, BLACK ANNEALED
STUD RAILS ASTM A1044 DECON OR APPROVED
EQUIVALENT
HEADED DEFORMED BARS ASTM A970
PLACING: CONFORM TO ACI 301 SECTION 3.3.2 "PLACEMENT." PLACING TOLERANCES SHALL
CONFORM TO ACI 117.
CONCRETE
COVER:
CONFORM TO
THE FOLLOWING
COVER
REQUIREMENTS
UNLESS NOTED
OTHERWISE IN
THE DRAWINGS:
CONCRETE CAST AGAINST EARTH 3"
CONCRETE EXPOSED TO EARTH OR
WEATHER
2"
TIES IN COLUMNS AND BEAMS 1-1/2"
BARS IN SLABS 3/4"
BARS IN WALLS 3/4"
EXTERIOR BARS IN TILT-UP PANELS 1"
SPLICES: CONFORM TO ACI 301 SECTION 3.3.2.7, "SPLICES". REFER TO "TYPICAL LAP SPLICE AND
DEVELOPMENT LENGTH SCHEDULE" FOR TYPICAL REINFORCEMENT SPLICES.
BAR PLACEMENT: ALL REINFORCEMENT SHALL BE ACCURATELY PLACED AND SUPPORTED (TIED)
BEFORE CONCRETE IS POURED. WET STABBING REBAR IS NOT ALLOWED WITHOUT CONSENT OF
THE STRUCTURAL ENGINEER OF RECORD.
EPOXY-COATED REINFORCEMENT: ALL REINFORCEMENT IN SLABS OR FOOTINGS SHALL BE
EPOXY-COATED AND PROTECTED AND HANDLED ACCORDINGLY.
POST-INSTALLED ANCHORS (INTO CONCRETE AND MASONRY)
REFERENCE STANDARDS:
1. ACI 318-19 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE", CHAPTER 17 -
"ANCHORING TO CONCRETE"
POST-INSTALLED ANCHORS: INSTALL ONLY WHERE SPECIFICALLY SHOWN IN THE DETAILS OR
ALLOWED BY COR. ALL POST-INSTALLED ANCHORS TYPES AND LOCATIONS SHALL BE APPROVED BY
THE SER AND SHALL HAVE A CURRENT ICC-EVALUATION SERVICE REPORT THAT PROVIDES
RELEVANT DESIGN VALUES NECESSARY TO VALIDATE THE AVAILABLE STRENGTH EXCEEDS THE
REQUIRED STRENGTH. SUBMIT CURRENT MANUFACTURER'S DATA AND ICC ESR REPORT TO SER
FOR APPROVAL REGARDLESS OF WHETHER OR NOT IT IS A PRE-APPROVED ANCHOR.
ANCHORS INSTALLED IN STRICT ACCORDANCE TO ICC-ESR AND MANUFACTURERS INSTRUCTIONS.
NO REINFORCING BARS SHALL BE DAMAGED DURING INSTALLATION OF POST INSTALLED ANCHORS.
SPECIAL INSPECTION SHALL BE PER THE TESTS AND INSPECTIONS SECTION. ANCHOR TYPE
DIAMETER AND EMBEDMENT SHALL BE AS INDICATED ON DRAWINGS.
1. ADHESIVE ANCHORS: THE FOLLOWING ADHESIVE-TYPE ANCHORING SYSTEMS HAVE BEEN
USED IN THE DESIGN AND SHALL BE USED FOR ANCHORAGE TO CONCRETE AND MASONRY
AS APPLICABLE AND IN ACCORDANCE WITH CORRESPONDING CURRENT ICC ESR REPORT.
DRILLED-IN ANCHOR EMBEDMENT LENGTHS SHALL BE AS SHOWN ON DRAWINGS OR NOT
LESS THAN 7 TIMES THE ANCHOR NOMINAL DIAMETER (7D).
A. SIMPSON "SET-3G"- ICC ESR 4057 FOR ANCHORAGE TO CONCRETE
B. HILTI "HIT RE 500 SD" - ICC ESR 2322 FOR ANCHORAGE TO CONCRETE
C. POWERS "PE1000" - ICC ESR-2583 FOR ANCHORAGE TO CONCRETE
2. SCREW ANCHORS: THE FOLLOWING SCREW TYPE ANCHOR IS PRE-APPROVED FOR
ANCHORAGE TO CONCRETE OR MASONRY IN ACCORDANCE WITH CORRESPONDING
CURRENT ICC ESR REPORT:
A. SIMPSON "TITEN HD" - ICC ESR-2713 FOR CONCRETE ONLY AND ICC ESR-1056 FOR
MASONRY ONLY
B. POWERS "WEDGE-BOLT" - ICC ESR-2526 FOR CONCRETE ONLY AND ICC ESR-1678 FOR
MASONRY ONLY
C. POWERS "SNAKE" - ICC ESR-2272 FOR ANCHORAGE TO CONCRETE ONLY
MIN REQS FOR ANCHOR BOLTS IN CONCRETE
NOTES:
1. ALL MATERIAL SHALL BE A307 OR BETTER.
2. ANCHORS AND DEPTHS APPLY TO CONCRETE INSTALLATION ONLY AND MAY NOT BE USED IN
CMU APPLICATIONS.
3. CONTRACTOR SHALL NOTIFY COR OF MISSED OR MISLOCATED ANCHORS FOR APPROPRIATE
REPAIR REQUIREMENTS. SEE SGN FOR ADDITIONAL INFORMATION REGARDING POST-INSTALLED
ANCHORS.
E M
B E
D 3"
BOLT
DIAMETER
EMBED
1/2" 6"
5/8" 6"
3/4" 7"
7/8" 8"
1" 9"
1 1/4" 11"
E M
B E
D 3"
1/2"
3 1/2"
5/8"
4 1/2"
3/4"
6"
6 3/4"
"J" BOLT HEX
HEAD
SIMPSON
TITEN HDE
M B
E D
3/8"
FOLLOW ALL THE MANUFACTURER'S
RECOMMENDATIONS FOR INSTALL
BOLT
DIAMETER
EMBEDBOLT
DIAMETER
EMBED
1/2" 6"
5/8" 6"
3/4" 7"
7/8" 8"
1" 9"
1 1/4" 11"
2021 IBC, REF ACI 318-19, SECTION 25.4.2 AND 25.5
TENSION LAP SPLICE LENGTHS (GRADE 60 BARS)
NOTES:
1. ALL DIMENSIONS SHOWN ARE IN INCHES
2. TOP BARS ARE DEFINED AS HORIZONTAL BARS PLACED WITH MORE THAN 12" OF FRESH
CONCRETE BELOW THEM. ALL OTHER BARS ARE NON-TOP BARS.
3. LAP LENGTHS IN TABLES ABOVE ARE BASED ON CLEAR COVER BEING GREATER THAN 1.0db
(BAR DIAMETERS) AND MIN CLEAR SPACING BETWEEEN BARS BEING GREATER THAN 2.0db.
4. IF BAR IS EPOXY COATED, AND CLEAR COVER IS LESS THAN 3db OR CLEAR SPACING IS LESS
THAN 6db, MULTIPLY LAP LENGTH BY 1.5.
5. FOR ALL OTHER EPOXY COATED BAR CONDITIONS, MULTIPLY LAP LENGTH BY 1.2.
6. IF CONCRETE IS LIGHTWEIGHT, MULTIPLY LAP LENGTH BY 0.75.
f'c = 3,000 PSI
CLASS A CLASS BBAR DIA
NON-TOP BARS
f'c = 4,000 PSI f'c = 5,000 PSI
CLASS A CLASS B CLASS A CLASS B
17 22#3 0.375" 15 19 13 17
22 29#4 0.500" 19 25 17 23
28 36#5 0.625" 24 31 22 28
33 43#6 0.750" 29 37 26 34
48 63#7 0.875" 42 54 38 49
55 72#8 1.000" 48 62 43 56
62 81#9 1.128" 54 70 48 62
69 89#10 1.270" 60 78 53 69
74 98#11 1.410" 63 85 59 76
96 125#14 1.693" 83 108 75 97
TOP BARS
f'c = 3,000 PSI
CLASS A CLASS BBAR DIA
f'c = 4,000 PSI f'c = 5,000 PSI
CLASS A CLASS B CLASS A CLASS B
22 28#3 0.375" 19 24 17 22
29 37#4 0.500" 25 33 23 29
36 47#5 0.625" 31 41 28 36
43 56#6 0.750" 37 49 34 43
63 81#7 0.875" 54 71 49 63
72 93#8 1.000" 62 81 56 72
81 105#9 1.128" 70 91 62 81
89 116#10 1.270" 78 101 69 90
98 128#11 1.410" 85 111 76 99
125 162#14 1.693" 108 141 97 126
MINIMUM LAP SPLICE LENGTH (IN INCHES) FOR:LONGITUDINAL
BAR SIZE COMPRESSION DEVELOPMENT LENGTHS PER f'c COMPRESSION LAP
SPLICE LENGTHf'c = 3,000 PSI
NO. 3 (M #10) 9 8 8 12
2021 IBC, REF ACI 318-19, SECTION 25.4.9
REINFORCEMENT IN CENTER OF WALL
f'c = 4,000 PSI f'c = 5,000 PSI
COMPRESSION LAP SPLICE LENGTHS
NOTES:
1. ALL DIMENSIONS SHOWN ARE IN INCHES.
2. IF BAR IS CONFINED BY TIES PER TABLE 25.4.9.3 OF ACI318-14, MULTIPLY LAP LENGTH BY 0.75.
3. IF CONCRETE IS LIGHTWEIGHT, MULTIPLY LAP LENGTH BY 0.75.
NO. 4 (M #13) 12 10 9 15
NO. 5 (M #16) 14 12 12 19
NO. 6 (M #19) 17 15 14 23
NO. 7 (M #22) 20 17 16 27
NO. 8 (M #25) 22 19 18 30
NO. 9 (M #29) 25 22 21 34
NO. 10 (M #32) 28 24 23 38
NO. 11 (M #36) 31 27 26 43
NO. 14 (M #43) 39 34 31 NA
NO. 18 (M #57) 50 43 41 NA
TYPICAL HOOKS AND BENDS SCHEDULE
BAR
#3
#4
#5
#6
#7
#8
#9
DIAMETER
0.375"
0.500"
0.625"
0.750"
0.875"
1.000"
1.128"
STANDARD REINFORCING STIRRUPS AND TIE HOOKS
#10 1.270"
#11 1.410"
#14 1.693"
#18 2.257"
4.5"
6"
7.5"
9"
10.5"
12"
11.25"
15.25"
17"
20.5"
27"
2.25"
3"
3.75"
4.5"
5.25"
6"
5.625"
7.625"
8.5"
10.25"
13.5"
1.5"
2"
2.5"
3"
3.5"
4"
4.5"
5"
5.75"
6.75"
9"
2.25"
3"
3.75"
9"
1.5"
2"
2.5"
4.5"
STANDARD EXTENSION
90° BEND
FINISHED BEND
DIAMETER "FBD"
180° BEND
FINISHED BEND
DIAMETER "FBD"
H O
O K
E X
T E
N S
IO
N
S T
A N
D A
R
D STIRRUP EXTENSION
90° BEND
STIRRUP BEND
DIAMETER
135° BEND
STIRRUP BEND
DIAMETER
3" M
IN
6 x BAR DIA
NOTES:
1. ALL DIMENSIONS PER CRSI MANUAL OF STANDARD PRACTICE AND ACI 318.
2. ALL BARS TO BE BENT COLD.
3. DO NOT BEND OR STRAIGHTEN BARS IN A MANNER THAT WILL DAMAGE THE BARS.
4. DO NOT FIELD BEND BARS PARTIALLY EMBEDDED IN CONCRETE OR MASONRY.
STD
EXTENSION
FBD STD HOOK
EXT
STIRRUP
EXT
STIRRUP
BEND
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
WFS U
N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
N
C
A
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Bid Documents
CEMETERY EXPANSION
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
PRIME CONSULTANT
EMETERY
ATIONAL
DMINISTRATION
BEAUFORT NATIONAL CEMETERY
CONSULTANTS
STRUCTURAL GENERAL
NOTES
831CM3016
CABER
S-001
March 8, 2024
Dwg. 187 Of 194
03/07/2024
STRUCTURAL GENERAL NOTES
INSPECTIONS: SPECIAL INSPECTIONS AND TESTING SHALL BE IN ACCORDANCE WITH THE
STATEMENT OF SPECIAL INSPECTIONS PER IBC SECTIONS 1704, 1705, AS APPLICABLE.
SPECIAL INSPECTORS: SPECIAL INSPECTORS SHALL BE EMPLOYED BY CONTRACTOR TO PROVIDE SPECIAL INSPECTIONS FOR THE PROJECT. SPECIAL INSPECTORS SHALL BE QUALIFIED PERSONS
WHO ARE REGISTERED WITH AN APPROVED AGENCY.
INSPECTION SUBMITTALS: PROVIDE SPECIAL INSPECTION REPORTS ON A WEEKLY BASIS. FINAL SPECIAL INSPECTION REPORTS WILL BE REQUIRED BY EACH SPECIAL INSPECTION FIRM PER IBC
1704.2.4. SUBMIT COPIES OF ALL INSPECTION AND TESTING REPORTS TO THE ARCHITECT/ENGINEER
AND THE AUTHORITY HAVING JURISDICTION FOR REVIEW AS SOON AS THEY ARE AVAILABLE.
STRUCTURAL OBSERVATION: THIS PROJECT IS SEISMIC DESIGN CATEGORY D, THEREFORE
STRUCTURAL SEISMIC OBSERVATIONS AREN'T REQUIRED. NOTIFY THE COR IN A TIMELY MANNER TO
ALLOW SCHEDULED OBSERVATIONS TO OCCUR.
STATEMENT OF SPECIAL INSPECTIONS: PROVIDE SPECIAL INSPECTIONS AND TESTING IN
ACCORDANCE WITH IBC SECTIONS 1704 AND 1705 AND PER THE FOLLOWING SCHEDULE OF SPECIAL
INSPECTIONS.
SPECIAL INSPECTIONS AND TESTING
DESCRIPTION OF SPECIAL INSPECTION PERIODIC CONTINUOUS
SCHEDULE OF SPECIAL INSPECTIONS
STRUCTURAL
STEEL
PRIOR TO THE
START OF
FABRICATION
FOR:
VERIFICATION OF STOP
COMPLIANCE WITH IBC SECTION
1704.2.1 FOR COMPLETENESS
AND ADEQUACY OF FABRICATION
AND QUALITY CONTROL
PROCEDURES
VERIFICATION OF SHOP
COMPLIANCE WITH AWS D1.1-2004
STRUCTURAL WELDING CODE
VERIFICATION OF SHOP
COMPLIANCE WITH AISC 360-05
CHAPTER M & CODE OF
STANDARD PRACTICE
DURING WELDING OF SINGLE PASS FILLET WELDS
NOT EXCEEDING 5/16" SIZE AS NOTED IN IBC TABLE
1704.3
DURING FIELD WELDING OF ALL STEEL FLOOR AND
METAL ROOF DECK PER AWS D1.3 AS NOTED IN
IBC TABLE 1704.3
DURING THE WELDING OPERATIONS -
VERIFICATION OF WELDER QUALIFICATIONS
DURING THE WELDING OPERATIONS -
VERIFICATION OF VALID WELD PROCEDURE
SPECIFICATIONS PER AWS 01.1
PRIOR TO PAINTING, SHIPPING TO SITE AND
ERECTION - VERIFICATION OF ALL WELDED JOINTS
PER AWS 01.1 TABLE 6.1
PRIOR TO THE START OF ERECTION -
VERIFICATION OF FRAMING REQUIREMENTS AND
BOLTING PROCEDURES PER AISC
DURING HIGH STRENGTH BOLTING PER IBC
SECTION 1704.3.2 AND 1704.3.3
WELDING OF COMPLETE OR PARTIAL JOINT
PENETRATION (CJP OR PJP) GROOVE WELDS PER
IBC TABLE 1704.3 & 1707
WELDING OF MULTI-PASS FILLET WELDS AND
FILLET WELDS EXCEEDING 5/16" SIZE PER IBC
TABLE 1704.3 & 1707
X
X
X
X
X
X
X
X
X
X
X
X
FOOTING SOIL BEARING SURFACES ARE ADEQUATE
TO ACHIEVE DESIGN BEARING CAPACITY X
PERFORM CLASSIFICATION AND TESTING OF
COMPACTED FILL MATERIALS
EXCAVATION DEPTH AND BEARING LAYER X
SOILS
TABLE 1705.06
BACKFILLING OPERATIONS IN ACCORDANCE WITH
GEOTECHNICAL REPORT RECOMMENDATIONS
INCLUDING LIFT THICKNESS, DENSITY TESTING,
MOISTURE CONTENT, MATERIAL PROPERTIES
PRIOR TO PLACEMENT OF COMPACTED FILL,
INSPECT SUBGRADE AND VERIFY THAT SITE HAS
BEEN PREPARED PROPERLY
X
X
X
CONCRETE
CONSTRUCTION
TABLE 1703.3
INSPECT REINFORCEMENT, INCLUDING
PRESTRESSING TENDONS, AND VERIFY PLACEMENT
VERIFY WELDABILITY OF
REINFORCING BARS OTHER
THAN ASTM A706
VERIFY USE OF REQUIRED DESIGN MIX (1904.1,
1904.2)
REINFORCING
BAR WELDING
INSPECT SINGLE - PASS FILLET
WELDS, MAXIMUM 5/16"
INSPECT ALL OTHER WELDS
INSPECT ANCHOR CAST IN CONCRETE
INSPECT
ANCHOR POST
INSTALLED IN
HARDENED
CONCRETE
MEMBERS
ADHESIVE ANCHORS INSTALLED
IN HORIZONTALLY OR UPWARDLY
INCLINED ORIENTATIONS TO
RESIST TENSION LOADS
MECHANICAL ANCHORS AND
ADHESIVE ANCHORS NOT
DEFINED ABOVE
PRIOR TO CONCRETE PLACEMENT, FABRICATE
SPECIMENS FOR STRENGTH TESTS, PERFORM
SLUMP AND AIR CONTENT TESTS, AND DETERMINE
THE TEMPERATURE OF THE CONCRETE.
INSPECT CONCRETE AND SHOTCRETE PLACEMENT
FOR PROPER APPLICATION TECHNIQUES
APPLICATION OF PRESTRESSING
FORCES
INSPECT
PRESTRESSED
CONCRETE FOR
GROUTING OF BONDED
PRESTRESSING TENDONS
INSPECTION OF PRECAST CONCRETE MEMBERS
FOR PRECAST CONCRETE
DIAPHRAGM CONNECTIONS
OR REINFORCEMENT AT
JOINT CLASSIFIED AS
MODERATE OR HIGH
DEFORMABILITY ELEMENTS
IN STRUCTURES ASSIGNED
TO SEISMIC DESIGN
CATEGORY C, D, E, OR F,
INSPECT SUCH
CONNECTIONS AND
REINFORCEMENT IN THE
FIELD FOR:
INSTALLATION OF
EMBEDDED PARTS
COMPLETION OF
THE CONTINUITY OF
REINFORCEMENT
ACROSS JOINTS
COMPLETION OF
CONNECTIONS IN
THE FIELD
INSPECT INSTALLATION TOLERANCES OF PRECAST
CONCRETE DIAPHRAGM CONNECTIONS FOR
COMPLIANCE WITH ACI 550.5
VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO
STRESSING TENDONS IN PT CONCRETE AND PRIOR
TO REMOVAL OF SHORES AND FORMS FROM
BEAMS AND STRUCTURAL SLABS
INSPECT FORMWORK FOR SHAPE, LOCATION AND
DIMENSIONS OF THE CONCRETE MEMBER BEING
FORMED
X
X
X
X
X
X
X
X
X
X
VERIFY MAINTENANCE OF SPECIFIED CURING
TEMPERATURE AND TECHNIQUES X
X
X
X
X
X
X
X
X
X
BRICK VENEER
REFERENCE STANDARDS:
1. ACI 530-13/ASCE 5-13/TMS 402-16 ''BUILDING CODE REQUIREMENTS FOR MASONRY
STRUCTURES". HEREIN REFERENCED AS MSJC.
2. ACI 530.1-13/ASCE 6-13/TMS 602-16 "SPECIFICATION FOR MASONRY STRUCTURES". HEREIN
REFERENCED AS MSJC.1.
3. BRICK INDUSTRY ASSOCIATION (BIA) "TECHNICAL NOTES"
SUBMITTALS:
1. MATERIAL CERTIFICATES FOR ALL ANCHORS, TIES AND METAL ACCESSORIES CERTIFYING
COMPLIANCE WITH REQUIRED STRENGTH GRADE AND ASTM STANDARDS.
2. CERTIFICATION LETTERS FOR BRICK VENEER AND MORTAR CERTIFYING COMPLIANCE WITH
REQUIRED STRENGTH AND RESPECTIVE ASTM STANDARDS.
3. LOCATION OF EXPANSION AND CONTROL JOINTS.
4. PRODUCT INFORMATION, ICC ESR REPORTS, AND MATERIAL CERTIFICATIONS CERTIFYING
COMPLIANCE FOR ALL NON-PRE-APPROVED POST-INSTALLED ANCHORS.
5. HOT AND/OR COLD WEATHER CONSTRUCTION PROCEDURES.
STRENGTH: THE ASSUMED COMPRESSIVE STRENGTH OF THE MASONRY ASSEMBLAGE, F'M, IS 2000
PSI.
MATERIALS
1. BRICK VENEER: CONFORM TO ASTM C 216, GRADE SW
2. MORTAR: CONFORM TO ASTM C270, TYPE S OR N, AND IBC SECTION 2103.2 "MORTAR".
3. JOINT REINFORCEMENT: CONFORM TO ASTM A951 AND IBC SECTION 2103.4.
4. ANCHORS TIES AND ACCESSORIES: CONFORM TO MSJC SECTION 6.2.2.5.
QUALITY ASSURANCE: CONFORM TO IBC SECTION 2105 "QUALITY ASSURANCE''.
1. MASONRY UNITS: A LETTER OF CERTIFICATION FROM THE MANUFACTURER OF THE UNITS
SHALL BE PROVIDED TO THE SER AT THE TIME OF, OR PRIOR TO THE DELIVERY OF THE UNITS
TO THE JOBSITE TO ENSURE THE UNITS HAVE BEEN TESTED ACCORDING TO ASTM C 140 AND
COMPLY WITH THE COMPRESSIVE STRENGTH SPECIFIED ABOVE AND ASTM C 90.
2. MORTAR: NO MORTAR TESTING IS REQUIRED.
3. GROUT: A LETTER OF CERTIFICATION FROM THE SUPPLIER OF THE GROUT SHALL BE
PROVIDED TO THE SER AT THE TIME OF, OR PRIOR TO, DELIVERY OF THE GROUT TO THE
JOBSITE TO ENSURE THAT THE GROUT COMPLIES WITH ASTM C 476.
ANCHORS, TIES, AND CONNECTORS:
• BRICK VENEER ANCHORS, TIES, AND CONNECTORS SHALL BE AS SPECIFIED ON STRUCTURAL
DRAWINGS. CONSULT ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR VENEER ANCHORS
AND TIES NOT INCLUDED ON THE STRUCTURAL DRAWINGS.
• BRICK VENEER TALLER THAN 30'-0" IN HEIGHT WITH A SPACING OF 1" TO 3" BETWEEN THE INSIDE FACE OF VENEER AND OUTSIDE FACE OF SOLID SHEATHING; ATTACH ENTIRE HEIGHT WITH TWO
PIECE ADJUSTABLE VENEER ANCHOR WITH MINIMUM 3/16"∅ TRIANGULAR WIRE TIES. GENERAL
CONTRACTOR SHALL PROVIDE SUBMITTAL FOR APPROVAL PRIOR TO CONSTRUCTION. PROVIDE
AT LEAST ONE ANCHOR FOR EACH 2.67 SQ FT. OF WALL AREA. SPACE ANCHORS AT A MAXIMUM OF 16" HORIZONTALLY AND 24" VERTICALLY. ATTACH ANCHORS INTO STRUCTURAL BACKING PER
MANUFACTUER'S RECOMMENDATION.
• ALL COMPONENTS, INCLUDING FASTENERS, SHALL BE STAINLESS STEEL CONFORMING TO ASTM A 580-AISI TYPE 304. EMBED ALL ANCHORS IN THE MORTAR JOINT 2" MIN WITH AT LEAST 5/8" COVER
TO THE OUTSIDE FACE. PROVIDE ADDITIONAL ANCHORS AROUND ALL OPENINGS GREATER THAN
16" IN EITHER DIMENSION. SPACE ANCHORS AROUND PERIMETER OF OPENINGS AT A MAXIMUM
OF 3'-0" ON CENTER. PLACE ANCHORS WITHIN 12" OF OPENING. BRICK VENEER SHALL BE
DESIGNED AND DETAILED BY THE ARCHITECT/CONTRACTOR TO ALLOW FOR DIFFERENTIAL
MOVEMENT, RESULTING FROM WOOD SHRINKAGE, AT ALL OBJECTS ATTACHED TO THE WOOD
FRAMING AND EXTEND INTO THE VENEER INCLUDING DOORS, WINDOWS, BEAMS, TRIM, ETC.
BRICK SUPPORT LINTELS: STEEL LINTELS SHALL BE ASTM A36 AND SHALL HAVE A CORROSION-
RESISTANT GALVANIZED COATING, APPROVED COAT OF PAINT, ENAMEL OR OTHER APPROVED
PROTECTION PRIOR TO INSTALLATION. STEEL LINTELS MAY ALSO BE FABRICATED OF APPROVED CORROSION-RESISTANT STEEL (STAINLESS STEEL OR ASTM A242) REFER TO THE MASONRY VENEER
LINTEL SCHEDULE FOR ADDITIONAL REQUIREMENTS.
CONTROL AND EXPANSION JOINTS: REFERENCE ARCH DRAWINGS FOR TYPICAL DETAILS OF BRICK
CONTROL AND EXPANSION JOINTS.
1. LOCATION OF CONTROL AND EXPANSION JOINTS SHALL BE APPROVED BY ARCHITECT.
UNLESS OTHERWISE INDICATED ON DRAWINGS, INSTALL VERTICAL CONTROL AND
EXPANSION JOINTS PER THE FOLLOWING:
A. BRICK WALLS W/O OPENINGS: 25 FEET ON CENTER MAXIMUM.
B. BRICK WALLS W/ OPENINGS: 20 FEET ON CENTER MAXIMUM.
C. BRICK WALLS WITH PARAPETS: WHEN SPACING IS PARAPETS IS MORE THAN 15 FEET,
MAKE EXPANSION JOINTS WIDER OR PLACE ADDITIONAL EXPANSION JOINTS HALFWAY
BETWEEN FULL-HEIGHT EXPANSION JOINTS.
D. CORNERS AND INTERSECTING WALLS: FIRST VERTICAL JOINT SHOULD BE WITHIN 10'
FROM THE CORNER IN ONE OF THE TWO INTERSECTING WALLS. AT WALL JOG LOCATIONS
PLACE EXPANSION JOINTS AT THE OFFEST ON THE INSIDE CORNER.
E. AT ABRUPT CHANGES IN WALL HEIGHT.
F. WHILE INSTALLING CONTROL JOINTS AT WALL OPENINGS IS CONSIDERED GOOD
PRACTICE, FIRST CONSULT THE SER TO DETERMINE WHETHER DOING SO DOES NOT
HAVE AN EFFECT ON THE LINTEL DESIGN.
STRUCTURAL STEEL
REFERENCE STANDARDS:
1. ANSI/AISC 303-16 - CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS & BRIDGES
HEREAFTER REFERENCED AS AISC 303.
2. ANSI/AISC 360-16 - SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS HEREAFTER
REFERENCED AS AISC 360.
3. RCSC - SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS, 2014.
4. AWS D1.1-15 - STRUCTURAL WELDING CODE - STEEL HEREAFTER REFERENCED AS AWS D1.1.
SUBMITTALS:
1. SHOP DRAWINGS SHALL BE PREPARED IN ACCORDANCE WITH AISC 360 SECTION M.1 AND AISC
303 SECTION 4.
2. SUBMIT WELDERS CERTIFICATES VERIFYING QUALIFICATION WITHIN PAST 12 MONTHS.
3. AFFIDAVIT STATING THE STEEL PROVIDED MEETS THE REQUIREMENTS OF THE GRADE(S)
SPECIFIED.
MATERIALS WIDE FLANGE (W), TEE (WT) SHAPES ASTM A992 FY = 50 KSI
STANDARD (S), MISCELLANEOUS (M)
SHAPES
ASTM A572 GRADE 50 FY = 50 KSI
CHANNEL (C), MISC. CHANNEL (MC), ANGLE
(L) SHAPES
ASTM A36 FY = 36 KSI
STRUCTURAL BARS & PLATES (PL) ASTM A36 FY = 36 KSI
HOLLOW STRUCTURAL SECTION-
SQUARE/RECT (HSS)
ASTM A500 GRADE C FY = 50 KSI
ASTM A53 GRADE B FY = 35 KSI
HOLLOW STRUCTURAL SECTION-ROUND
(HSS)
ASTM A500 GRADE C FY = 46 KSI
ASTM A325/F1852 TYPE 1, PLAIN
NUTS ASTM A563
WASHERS (FLAT OR BEVELED) ASTM F436-REQ'D @ SLOTTED &
OVERSIZE HOLES
WELDING ELECTRODES E70XX, E71TXX UNLESS NOTED
OTHERWISE WITH A MINIMUM
TOUGHNESS OF 20FT-LBS AT 40° F
THREADED RODS (ANCHOR BOLTS) ASTM A307 FY = 35 KSI
WELDED HEADED STUDS (WHS) 3/4" OR
7/8"
ASTM A108- NELSON/TRW S3L OR
EQUAL
WELDED HEADED STUDS (WHS)
1/2" OR 5/8"
ASTM A108- NELSON/TRW H4L OR
EQUAL
DOWEL BAR ANCHORS ASTM A496- NELSON/TRW D2L OR
EQUAL
ANCHOR RODS (ANCHOR BOLTS) ASTM F1554 GR. 55 (WELDABLE) PER
SUPPLEMENT NO. 1
STRUCTURAL PIPE (PIPE) 12" DIA AND LESS
HIGH-STRENGTH BOLTS
MILD THREADED RODS ASTM A36 FY = 36 KSI
WELDING:
1. WELDING SHALL CONFORM TO AWS D1.1 AND VISUALLY CONFORM TO AWS SECTION 6 AND
TABLE 6.1. FABRICATION/ERECTION INSPECTIONS BY THE CONTRACTOR PER AWS D1.1
SECTION 6 SHALL BE BY ASSOCIATE/CERTIFIED INSPECTORS (AWI/CWI) PER AWS QC1 OR AWS B5.1. SPECIAL INSPECTIONS (VERIFICATION INSPECTIONS) SHALL BE BY A CERTIFIED WELDING
INSPECTOR (CWI) OR SENIOR WELDING INSPECTOR (SWI) PER AWS B5.1.
2. WELDERS SHALL BE QUALIFIED FOR THE SPECIFIC PREQUALIFIED JOINTS REQUIRED BY THE
DESIGN AND CERTIFIED IN ACCORDANCE WITH AWS REQUIREMENTS.
3. WELDING SHALL BE IN ACCORDANCE WITH APPROPRIATE WELD PROCEDURE SPECIFICATIONS
(WPS'S) WELDERS SHALL BE FAMILIAR WITH THE APPLICABLE WPS'S.
4. WELDER QUALIFICATIONS AND WPS'S SHALL BE MAINTAINED AT THE SITE OF THE WORK AND
SHALL BE READILY AVAILABLE FOR INSPECTION UPON REQUEST BOTH IN THE SHOP AND IN
THE FIELD.
5. USE E70 OR E71T, 70 KSI STRENGTH ELECTRODES APPROPRIATE FOR THE PROCESS
SELECTED.
6. PRIOR TO THE START OF WORK, SPECIAL INSPECTOR OR, IF "AISC CERTIFIED" OR OTHERWISE
"APPROVED" SHOP, A SHOP CERTIFIED WELD INSPECTOR (CWI) CERTIFIED IN ACCORDANCE
WITH PROVISIONS OF AWS QC1 SHALL INSPECT AND DOCUMENT COMPLIANCE WITH THE
FOLLOWING:
A. CONFIRM WELDER QUALIFICATIONS PRIOR TO THE START OF WORK.
B. REVIEW ALL WPS PRIOR TO THE START OF WORK.
C. CONFIRM MATERIALS IN FABRICATIONS CONFORM TO THE SPECIFICATIONS.
D. PERIODICALLY OBSERVE JOINT PREPARATION, FIT-UP AND WELDER TECHNIQUES.
E. IDENTIFY ON PLANS ALL MULTI-PASS FILLET WELDS, SINGLE PASS FILLET WELDS GREATER
THAN 5/16", AND COMPLETE-AND PARTIAL-JOINT PENETRATION (CJP OR PJP) GROOVE
WELDED BUTT JOINTS THAT REQUIRES CONTINUOUS (SPECIAL) INSPECTION.
F. VISUALLY INSPECT ALL WELDS PER SPECIAL INSPECTION REQUIREMENTS FOR STEEL AND
AWS SECTION 6.5 AND TABLE 6.1.
7. WELDING OF HIGH STRENGTH ANCHOR RODS (F1554-105) IS PROHIBITED UNLESS APPROVED
BY ENGINEER.
8. WELDING OF SHEAR STUDS ON STEEL BEAMS: HEADED SHEAR STUDS WELDED TO TOPS OF
WIDE FLANGE BEAM SHALL BE WELDED IN ACCORDANCE WITH AWS D1.1 CHAPTER 7 "STUD
WELDING".
9. WELDING OF HEADED STUDS ON EMBEDDED STEEL PLATES FOR ANCHORAGE TO CONCRETE:
HEADED STUDS WELDED TO STEEL EMBEDMENT PLATES CAST MONOLITHIC WITH CONCRETE
AND SHALL BE WELDED IN ACCORDANCE WITH AWS D11 CHAPTER 7 "STUD WELDING" UNLESS
NOTED OTHERWISE ON PLANS.
HIGH-STRENGTH BOLTING: HIGH STRENGTH BOLTS SHALL BE OF THE ASTM GRADE AND TYPE
SPECIFIED IN THE MATERIALS SECTION. UNLESS NOTED OTHERWISE, INSTALL BOLTS IN JOINTS IN ACCORDANCE WITH THE RCSC SPECIFICATION AS JOINT TYPE ST, "SNUG TIGHT'', - PER RCSC SPECIFICATION TABLE 4.1 AND SECTION 8.1. INSPECTION IS PER RCSC SECTION 9.1. BOLTS HAVE
BEEN DESIGNED AS ASTM A325-N BOLTS - "THREADS INCLUDED IN THE SHEAR PLANE".
ASTM A36 FY = 36 KSI
WIDE FLANGE BEARING PILES (HP) SHAPES
STEEL FLOOR AND ROOF DECK
REFERENCE STANDARDS:
1. ANSI/SDI-RD-2017 "STANDARD FOR STEEL ROOF DECK" AND ANSI/SDI-C-2017 "STANDARD FOR
COMPOSITE STEEL FLOOR DECK - SLABS"
2. ANSI "SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS"
3. AWS D1.3-18 "STRUCTURAL WELDING CODE - SHEET STEEL"
SUBMITTALS: SUBMIT SHOP DRAWINGS (ERECTION LAYOUTS) TO THE ARCHITECT/ENGINEER FOR
REVIEW. SHOP DRAWINGS SHALL INCLUDE MATERIAL TYPE, SPAN LAYOUT BY SSE, DECK
ATTACHMENTS, STEEL DECK EDGE FORM DESIGN (AS REQUIRED) AND SHORING REQUIREMENTS.
ALTERNATE DECK TYPES AND GAGES SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR
REVIEW PRIOR TO FABRICATION AND SHALL INCLUDE A VALID ICC EVALUATION REPORT AND SHOP
DRAWINGS (COMPONENT DESIGN
MATERIAL: ASTM A653-SS DESIGNATION, GRADE 33. ZINC COATED PER A653, G60. MINIMUM YIELD
STRENGTH SHALL BE 38 KSI.
DRAWINGS).
OPENINGS: OPENINGS SHOWN ON THE CONTRACT DOCUMENTS SHALL BE REFLECTED IN THE SHOP DRAWINGS. DECK OPENINGS LESS THAN 6" DO NOT REQUIRE REINFORCEMENT. FOR SUPPORT TO
LARGER OPENINGS REFER TO TYPICAL DETAILS.
DECK SPECIFICATION: REFER TO FRAMING PLANS.
DECK FASTENING: REFER TO FRAMING PLANS.
DESCRIPTION OF SPECIAL INSPECTION PERIODIC CONTINUOUS
SCHEDULE OF SPECIAL INSPECTIONS CONTINUED
PROPORTIONS OF SITE-PREPARED MORTAR X
PRESTRESSING TECHNIQUE X
PROPERTIES OF THIN-BED MORTAR AAC MASONRY
2. PRIOR TO GROUTING, VERIFY THAT THE
FOLLOWING ARE IN COMPLIANCE:
GROUT SPACE
PLACEMENT OF PRESTRESSING TENDONS AND
ANCHORAGES
PLACEMENT OF REINFORCEMENT, CONNECTORS,
AND ANCHOR BOLTS
GRADE AND SIZE OF PRESTRESSING TENDONS
AND ANCHORAGES
X
GRADE, TYPE AND SIZE REINFORCEMENT,
CONNECTORS, ANCHOR BOLTS AND PRESTRESSING
TENDONS AND ANCHORAGES
X
X(1) X(2)
1. AS MASONRY CONSTRUCTION BEGINS, VERIFY THAT THE FOLLOWING ARE IN
COMPLIANCE:
X
X
PROPORTIONS OF SITE-PREPARED GROUT AND
PRESTRESSING GROUT FOR BONDED TENDONS
3. VERIFY COMPLIANCE OF THE FOLLOWING
DURING CONSTRUCTION:
MATERIALS AND PROCEDURES WITH APPROVED
SUBMITTALS
X
PLACEMENT OF MASONRY UNITS AND MORTAR JOINT
CONSTRUCTION
SIZE AND LOCATION OF STRUCTURAL MEMBERS
TYPE, SIZE, AND LOCATION OF ANCHORS, INCLUDING
OTHER DETAILS OF ANCHORAGE OF MASONRY TO
STRUCTURAL MEMBERS, FRAMES, OR OTHER
CONSTRUCTION
X
WELDING OF REINFORCEMENT
PREPARATION, CONSTRUCTION, AND PROTECTION
OF MASONRY DURING COLD WEATHER
(TEMPERATURE BELOW 40°F (4.4°C)) OR HOT
WEATHER (TEMPERATURE ABOVE 90°F (32.2°C))
X
APPLICATION AND MEASUREMENT OF
PRESTRESSING FORCE
PLACEMENT OF GROUT AND PRESTRESSING GROUT
FOR BONDED TENDONS IS IN COMPLIANCE
PLACEMENT OF AAC MASONRY UNITS AND
CONSTRUCTION OF THIN-BED MORTAR JOINTS
4. OBSERVE PREPARATION OF GROUT SPECIMENS,
MORTAR SPECIMENS, AND/OR PRISMS
X(1) X(2)
SAMPLE PANEL CONSTRUCTION
MASONRY
CONSTRUCTION
(LEVEL 2) -
ENGINEERED
MASONRY ON
NONESSENTIAL
STRUCTURES
TMS 602-16
TABLE 4
(1) REQUIRED
FOR THE FIRST
5,000 SQUARE
FEET (465
SQUARE
METERS) OF
AAC MASONRY.
(2) REQUIRED
AFTER THE
FIRST 5,000
SQUARE FEET
(465 SQUARE
METERS) OF
AAC MASONRY.
X
X
X
X
X
X
X
X
REINFORCED UNIT MASONRY
8" WALL
THICKNESS
VERTICAL REINFORCING PER PLANS AND DETAILS
HORIZONTAL REINFORCING (BOND BEAMS) PER PLANS AND DETAILS
COLD AND HOT WEATHER CONSTRUCTION: COLD AND HOT WEATHER CONSTRUCTION SHALL BE IN
ACCORDANCE WITH TMS602.
GROUT POUR HEIGHT: GROUT POUR HEIGHT SHALL NOT EXCEED HEIGHT SPECIFIED IN TMS602
SECTION 3.5C.
GROUT LIFTS: UNLESS OTHERWISE NOTED, GROUT LIFTS AND POUR HEIGHT SHALL NOT EXCEED 5
FT. GROUT LIFTS EXCEEDING 5 FT SHALL BE APPROVED BY SER.
REINFORCING
COVER AND
CLEARANCE
REQUIREMENTS
: UNLESS
OTHERWISE
NOTED:
CLEAR DIST BETWEEN PARALLEL BARS
(AND BETWEEN ADJACENT PAIRS OF LAP
SPLICED BARS) SHALL BE EQUAL TO THE
BAR ADJACENT BAR DIAMETER (FOR BARS
GREATER THAN #8) AND NOT LESS THAN:
1" AT 8" AND SMALLER BLOCK
2" AT 10" BLOCK
3" AT 12" BLOCK
CLEARANCE (CLEAR SPACE) BETWEEN THE
BLOCK AND THE REINFORCING SHALL BE:
1/4" AT FINE GROUT
1/2" AT COURSE GROUT
MASONRY COVER (INCLUDING GROUT AND
BLOCK WALL) AT MASONRY FACE EXPOSED
TO EARTH OR WEATHER SHALL BE:
1 1/2" MINIMUM
2" FOR BARS #6 AND LARGER
CONTROL AND EXPANSION JOINTS: REFERENCE DRAWINGS FOR TYPICAL DETAILS OF MASONRY
CONTROL AND EXPANSION JOINTS.
1. LOCATION OF CONTROL AND EXPANSION JOINTS SHALL BE APPROVED BY COR. UNLESS
OTHERWISE INDICATED ON DRAWINGS, INSTALL CONTROL AND EXPANSION JOINTS AT THE
FOLLOWING:
A. CONTINUOUS WALLS: VERTICAL JOINTS AT THE LESSER OF 2.5 TIMES THE WALL HEIGHT
OR 25 FEET ON CENTER MAXIMUM.
B. CORNERS AND INTERSECTING WALLS: FIRST VERTICAL JOINT FROM THE CORNER AT
LESSER OF 1.25 TIMES THE WALL HEIGHT OR 16 FEET.
C. ABRUPT CHANGES IN WALL HEIGHT AND WALL THICKNESS, SUCH AS ADJACENT TO
COLUMNS OR PILASTERS.
VERTICAL REINFORCING PER PLANS AND DETAILS
REFERENCE STANDARDS:
1. TMS 402-16 ''BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES". HEREIN
REFERENCED AS TMS402.
2. TMS 602-16 "SPECIFICATION FOR MASONRY STRUCTURES". HEREIN REFERENCED AS TMS602.
3. ACI SP-66 "ACI DETAILING MANUAL" INCLUDING ACI 315 "DETAILS AND DETAILING OF CONCRETE
REINFORCEMENT".
4. ANSI/AWS D1.4-18. "STRUCTURAL WELDING CODE-REINFORCING STEEL".
SUBMITTALS:
1. MASONRY REINFORCEMENT, SIZE, LAYOUT, AND GRADE IN ACCORDANCE WITH PLANS.
2. MATERIAL CERTIFICATES FOR ALL STEEL REINFORCING ANCHORS, TIES AND METAL
ACCESSORIES CERTIFYING COMPLIANCE WITH REQUIRED STRENGTH GRADE AND ASTM
STANDARDS.
3. CERTIFICATION LETTERS FOR MASONRY BLOCK AND GROUT MIX DESIGN CERTIFYING
COMPLIANCE WITH REQUIRED STRENGTH AND RESPECTIVE ASTM STANDARDS.
4. MIX DESIGNS FOR EACH GROUT MIX INDICATING TYPE AND PROPORTIONS OF INGREDIENTS IN
COMPLIANCE OF PROPORTION SPECIFICATION.
5. LOCATION OF EXPANSION AND CONTROL JOINTS.
6. PRODUCT INFORMATION, ICC ESR REPORTS, AND MATERIAL CERTIFICATIONS CERTIFYING
COMPLIANCE FOR ALL NON-PRE-APPROVED POST-INSTALLED ANCHORS.
7. HOT AND/OR COLD WEATHER CONSTRUCTION PROCEDURES.
STRENGTH: THE ASSUMED COMPRESSIVE STRENGTH OF THE MASONRY ASSEMBLAGE, F'M = 2500 PSI.
MATERIALS
1. CONCRETE MASONRY UNITS: CONFORM TO ASTM C 90, TYPE-1 (MOISTURE CONTROLLED),
MEDIUM WEIGHT (APPROX. 115 PCF) UNITS. PROVIDE 3250 PSI COMPRESSIVE STRENGTH TO
ACHIEVE MASONRY ASSEMBLY STRENGTH INDICATED ABOVE UNDER STRENGTH.
2. MORTAR: CONFORM TO ASTM C270, TYPE S, AND IBC SECTION 2103.2 "MORTAR".
3. GROUT: CONFORM TO ASTM C476 AND IBC SECTION 2103.3 PROPORTION SPECIFICATIONS. USE
FINE GROUT EXCEPT COARSE GROUT MAY BE USED WHERE PERMITTED BY TMS402 TABLE
3.2.1. FINE GROUT REQUIRED FOR 4" AND 6" CMU.
4. REINFORCING BARS: CONFORM TO ASTM A615, GRADE 60 DEFORMED BARS AND IBC SECTION
2103.4 UNLESS NOTED OTHERWISE. LAP SPLICES SHALL BE AS NOTED ON PLANS.
FABRICATION SHALL BE IN ACCORDANCE WITH TMS602 SECTION 2.7.
5. JOINT REINFORCEMENT: CONFORM TO ASTM A951 AND IBC SECTION 2103.4.
6. ANCHORS TIES AND ACCESSORIES: CONFORM TO IBC SECTION 2103.4 AND TMS 602 ARTICLE
2.4D.
QUALITY ASSURANCE: CONFORM TO IBC SECTION 2105 "QUALITY ASSURANCE''.
1. MASONRY UNITS: A LETTER OF CERTIFICATION FROM THE MANUFACTURER OF THE UNITS
SHALL BE PROVIDED TO THE SER AT THE TIME OF, OR PRIOR TO THE DELIVERY OF THE UNITS
TO THE JOBSITE TO ENSURE THE UNITS HAVE BEEN TESTED ACCORDING TO ASTM C 140 AND
COMPLY WITH THE COMPRESSIVE STRENGTH SPECIFIED ABOVE AND ASTM C 90.
2. MORTAR: NO MORTAR TESTING IS REQUIRED.
3. GROUT: A LETTER OF CERTIFICATION FROM THE SUPPLIER OF THE GROUT SHALL BE
PROVIDED TO THE SER AT THE TIME OF, OR PRIOR TO, DELIVERY OF THE GROUT TO THE
JOBSITE TO ENSURE THAT THE GROUT COMPLIES WITH ASTM C 476.
ANCHORS, TIES, AND CONNECTORS: MASONRY ANCHORS, TIES, AND CONNECTORS SHALL BE AS
SPECIFIED ON STRUCTURAL DRAWINGS. CONSULT ARCHITECTURAL DRAWINGS FOR MASONRY
ANCHOR TIES NOT INCLUDED ON THE STRUCTURAL DRAWINGS.
MASONRY REINFORCING STEEL: MASONRY REINFORCING SHALL BE AS NOTED ON PLANS AND SHALL BE SECURELY PLACED IN ACCORDANCE WITH IBC SECTIONS 2104.1, 2106, AND TMS402 SECTION 6.1.
UNLESS OTHERWISE NOTED ON THE PLANS, THE MINIMUM WALL REINFORCEMENT SHALL BE AS
FOLLOWS:
2021 IBC, f'm = 1,500 PSI, REINF IN CENTER OF WALL
CMU REINF LAP SPLICE LENGTHS
LONGITUDINAL
BAR SIZE
6" CMU
UNCONFINED
8" CMU
UNCONFINED
10" CMU
UNCONFINED
12" CMU
UNCONFINED
NO. 3 (M #10) 12 12
NO. 4 (M #13)
15 12
NO. 5 (M #16)
23 18 15
NO. 6 (M #19)
43 34 28
NO. 7 (M #22) 60 46 38
NO. 8 (M #25) 72 71
NO. 9 (M #29)
82 74
NP
NP
NP NP
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
WFS U
N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
N
C
A
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Bid Documents
CEMETERY EXPANSION
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
PRIME CONSULTANT
EMETERY
ATIONAL
DMINISTRATION
BEAUFORT NATIONAL CEMETERY
CONSULTANTS
STRUCTURAL GENERAL
NOTES CONTINUED AND
SCHEDULES 831CM3016
CABER
S-002
March 8, 2024
Dwg. 188 Of 194
B B
A A
55'-0"
14'-0" 13'-6" 13'-6" 14'-0"
'-6
S-201
W F
[9
9' -4
W F
[9
9' -4
W F
[9
9' -4
W F
2.
[9 9'
-4
W F
2.
[9 9'
-4
WF2.5 [99'-4"]
8" SLAB-ON-GRADE WITH #5
EPOXY-COATED @ 18" OC MAX,
EA WAY (ISOLATE FROM WALLS
WITH 1/2" FILLER)
2' -0
'-8
1' -0
4" 1'-0" 12'-6" 1'-0" 12'-6" 1'-0" 12'-6" 1'-0" 12'-6" 1'-0" 4"
S-201
S-401
S-401
S-401
S-401
S-201
S
LO
P E
P E
R C
IV
IL
S
LO
P E
P E
R C
IV
IL
S
LO
P E
P E
R C
IV
IL
S
LO
P E
P E
R C
IV
IL
FOOTING MARK
TOP OF FOUNDATION
ELEVATION
ISOLATED FOUNDATION
STEEL COLUMN
F6 [98'-6"]
FOOTING
WALL
MARK
TOP OF FOOTING
ELEVATION
WF [97'-0"]
ISOLATED FOOTING CONTINUOUS FOOTING
C1
COLUMN MARK
BP1
BASE PLATE MARK
FOOTING MARK TYPES
WF WALL FOOTING
TD TURNDOWN
TS THICKENED SLAB
F ISOLATED FOUNDATION
FOUNDATION LEGEND
1. SEE S001 AND S002 FOR STRUCTURAL GENERAL NOTES AND DESIGN
CRITERIA. SEE G001 FOR ABBREVIATIONS. SEE S003 FOR ADDITIONAL
LEGENDS AND SCHEDULES.
2. TOP OF SLAB ELEVATION 19.81' (WITH APPLICABLE SLOPE). SEE CIVIL
DRAWINGS FOR RELATED ELEVATIONS AND SLOPES. VERIFY ALL
ELEVATIONS WITH ARCHITECTURAL AND CIVIL DRAWINGS.
3. TYPICAL SLAB ON GRADE SHALL BE 8" THICK, REINFORCED WITH EPOXY-
COATED #5 BAR @ 18" OC. SEE SOIL PREPARATION AND SLAB BASE FOR
SUBGRADE INFORMATION.
4. VERIFY DIMENSIONS WITH ALL OTHER DISCIPLINES. COORDINATE ANY
DISCREPANCIES WITH THE COR PRIOR TO CONSTRUCTION.
5. SUBMIT PLAN SHOWING LAYOUT OF SLAB CONSTRUCTION AND CONTROL
JOINTS TO EOR FOR REVIEW PRIOR TO POURING SLAB ON GRADE.
6. TOP OF TYPICAL INTERIOR FOOTINGS TO BE 99'-4" UNO.
7. TYPICAL TOP OF EXTERIOR AND PERIMETER FOOTINGS TO BE 99'-4"
UNLESS NOTED OTHERWISE ON PLAN. VERIFY THESE FOOTINGS BEAR 12"
BELOW ADJACENT FINISHED GRADE OR FLATWORK TO PROTECT AGAINST
FROST HEAVE.
8. SEE CIVIL DRAWINGS FOR GRADING DETAILS OUTSIDE THE BUILDING
ENVELOPE.
9. SEE TYPICAL FOUNDATION DETAILS ON SHEET S401.
10. LOCATE AND VERIFY THE FOLLOWING WITH OTHER DISCIPLINES PRIOR TO
POURING CONCRETE:
A. DOOR OPENINGS
B. DRAINS AND SLOPES
C. BLOCKOUTS AND CHASES
D. CONCRETE CURBS
E. OWNER SUPPLIED ITEMS
11. SEE ARCHITECTURAL AND CIVIL PLANS FOR SLAB DEPRESSIONS, STEPS,
SLOPES, DRAINS, EXTERIOR SLABS, ETC.
12. ESTABLISH AND VERIFY SIZE AND LOCATION OF OPENINGS AND INSERTS IN
SLAB AND FOOTINGS WITH OTHER DRAWINGS, TRADES AND
SUBCONTRACTOR'S PRIOR TO CONSTRUCTION.
SOILS PREPARATION AND SLAB BASE
SOILS WITHIN
BUILDING
ENVELOPE
SEE GEOTECH REPORT FOR SUBGRADE
SOIL PREPARATION INFORMATION.
SLAB BASE UNDERLAY SLAB ON GRADE WITH A 10 MIL VAPOR
BARRIER ON PREPARED SUBGRADE. REFER TO ACI
302 FOR PROCEDURES AND CAUTIONS REGARDING
THE USE AND PLACEMENT OF VAPOR BARRIER.
REFERENCE GEOTECH REPORT FOR PREPARED
SUBGRADE REQUIREMENTS.
STEEL BASEPLATE SCHEDULE
NOTES:
1. ALL HOLES SHALL BE DRILLED WITH NO LARGER THAN 1/2" DIAMETER
GREATER THAN THE SPECIFIED BOLT DIAMETER.
2. PLATES AND COLUMNS SHALL BE SET ON 1 1/2" NON-SHRINK DRY PACK
GROUT SATISFYING THE MINIMUM SPECIFICATIONS SET FORTH IN THE SGN.
3. COLUMNS SHALL BE CONNECTED TO PLATES WITH 1/4" FILLET WELD FOR
3/4" THICK PLATES AND SMALLER AND A 5/16" FILLET WELD FOR PLATES
THICKER THAN 3/4". WELD ALL THE WAY AROUND THE BASE OF THE
COLUMNS.
4. MOMENT FRAMES ONLY- FLANGE WELD WITH 1/2" E70 DOUBLE FLLET. WEB
WELD WITH 4/16" E70 DOUBLE FILLET.
5. SHIMS MAY BE LEFT IN PLACE BELOW COLUMNS AT CONTRACTOR'S
DISCRETION.
6. BOLTS SHALL BE THREADED RODS WITH NUTS EXTENDING A MINIMUM OF 8"
INTO THE CONCRETE FOOTING UNO. BOLTS SHALL PROJECT A MINIMUM OF
3" FROM THE TOP LEVEL OF THE BASEPLATE.
BP-1
USE (4)1/2" DIA BOLTS
1/2" STEEL PLATE
1/
2" 6"
1/
2" 9"
1 1/2" 6"
1 1/2"9"
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
WFS U
N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
N
C
A
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
Revisions Date
Drawing Title
Approved:
Approved:
Project Title
Building Number Checked Drawn
Location
Date
Project No.
DRAWING NO.
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Bid Documents
NOTES
CEMETERY EXPANSION
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
PRIME CONSULTANT
EMETERY
ATIONAL
DMINISTRATION
BEAUFORT NATIONAL CEMETERY
CONSULTANTS
FOUNDATION PLAN
831CM3016
CABER
S-101
March 8, 2024
SCALE: 1/4" = 1'-0"
1 FOUNDATION PLAN
3. EQUALLY SPACE SPECIFIED REINFORCING BARS IN THE CONTINUOUS FOOTING.
NOT THE EMBEDMENT INTO GRADE.
2. TOF AS INDICATED IN THE PLANS NOTES THE TOP OF THE CONTINUOUS CONCRETE FOOTING, STRUCTURAL GENERAL NOTES.
1. ASSURE PROPER CONCRETE CLEARANCES AROUND REINFORCING STEEL PER THE
NOTES:
CONTINUOUS FOOTING SCHEDULE
MARK
DIMENSIONS REINFORCEMENT
REMARKSWIDTH THICKNESS TOP BOTTOM
WF2 2'-0" 10" (4) #4 (4) #5
WF2.5 2'-6" 1'-0" (5) #4 (5) #5
Dwg. 189 Of 194
B B
A A
S-201
8" 13'-4" 13'-6" 13'-6" 13'-4" 8"
W14x26
1.5B 20 GA METAL
ROOF DECK
W
4x
W
4x
W
4x
W
4x
W
4x
W
4x
W
4x
S-201
SC1
R1
S-201
1'-0" 55'-0" 1'-0"
1' -0
'-6
2' -2
[118'-8"] W14x26 [118'-8"]
6'-7" 6'-9" 6'-9" 6'-9" 6'-9" 6'-9" 6'-9" 6'-7"
SC1 SC1
S-601
1. REF TO S001 AND S002 FOR STRUCTURAL GENERAL NOTES AND DESIGN
CRITERIA AND ABBREVIATIONS.
2. VERIFY DIMENSIONS AND ELEVATIONS WITH ALL OTHER DISCIPLINES. SEE
S003 FOR ADDITIONAL LEGENDS AND SCHEDULES.
3. VERIFY ALL ELEVATIONS WITH APPROVED ARCHITECTURAL.
4. ROOF DECK PER STEEL ROOF DECK SCHEDULE AND SGN.
CONTINUOUS (3) SPAN
3'-0" WIDTH
DECK TYPE:
FINISH:
SUPPORT ATTACHMENT:
ATTACHMENT PATTERN:
SIDE LAP FASTENERS:
* EQUALLY SPACED, NOT TO EXCEED 3'-0" OC
1 1/2" x 20 GA B DECK
3/4" PUDDLE WELDS
36/7
(7) 3/4" SPOT WELDS
NOTES:
1. DECK SHALL BE MANUFACTURED BY VULCRAFT OR AN APPROVED
EQUIVALENT.
2. ANY POTENTIAL FASTENER SUBSTITUTION REQUIRE PRIOR WRITTEN
APPROVAL OF COR.
GALVANIZED
R1
MARK
W14x35(15)c=3/4"
STEEL BEAM LEGEND
NUMBER OF STUDS
MEMBER PROFILE
CAMBER
(5) (7) (5)
UNEVEN STUD
DISTRUBUTION
V10
V10 M150
SHEAR
REACTION
MOMENT
REACTION
MOMENT CONNECTION
DRAG STRUT/COLLECTOR CONNECTION
STEEL EMBED AND CALLOUTEM3
[119'-6"]
T/BEAM ELEVATION
NOTES:
1. REFER TO AISC MANUAL OF STEEL CONSTRUCTION FOR MINIMUM
FRAMED BEAM CONNECTION REQUIREMENTS.
5500 Greenwood Plaza Blvd., Suite 200
Greenwood Village, CO 80111
303.770.8884
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
WFS U
N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
U N I T
E D
STATES OF
A M E
R I C A
E
N T
OF
VETERANS
A F F A I R S
N
C
A
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
© COPYRIGHT 2022, Walker Federal Services, LLC
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
Revisions Date
1 2 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A B
C D
E F
A B
C D
E F
Revisions Date
Drawing Title
Approved:
Approved: