This document is a set of electrical and telecommunications drawings and specifications for the Beaufort National Cemetery Expansion project. The drawings provide details on the existing and new electrical and telecommunications systems for the administration building, maintenance building, and temporary office trailer. Key details include:
The electrical scope includes new panels, transformers, lighting, power, grounding, and lightning protection systems. The telecommunications scope includes new server racks, cabling, and outlets. The project also involves modifications to the existing underground electrical and irrigation control systems serving the well pumps. The drawings provide detailed ductbank routing, conduit sizes, cable types, and equipment specifications. The overall goal is to provide a complete and functioning electrical and telecommunications system for the cemetery expansion.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL SYMBOLS ELECTRICAL ABBREVIATIONS
SINGLE POLE TOGGLE SWITCH - 20 AMP, 120V OR 277V, M.H. 48"
AFF, UON.
THREE WAY TOGGLE SWITCH - 20 AMP, 120V OR 277V, M.H. 48"
AFF, UON.
LIGHT SWITCH WITH BUILT-IN OCCUPANCY SENSOR.
OCCUPANCY SENSOR
MOTION SENSOR
MOTOR OPERATED SWITCH
SINGLE/DUPLEX TYPE RECEPTACLE - 20 AMP, 120 VOLT, NEMA 5-20R,
M.H. 18" AFF, UON.
QUADRUPLEX TYPE RECEPTACLE - 20 AMP, 120 VOLT, NEMA 5-20R,
M.H. 18" AFF, UON.
DUPLEX WEATHER PROOF RECEPTACLE WITH GROUND FAULT CIRCUIT
INTERRUPTER PROTECTION - 20 AMP, 120 VOLT, NEMA 5-20R, M.H. 18"
AFF, UON.
QUADRUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT
INTERRUPTER PROTECTION - 20 AMP, 120 VOLT, NEMA 5-20R, M.H. 18"
AFF, UON.
DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER
PROTECTION - 20 AMP, 120 VOLT, NEMA 5-20R, M.H. 18" AFF, UON.
SPECIAL TYPE RECEPTACLE - 240 VOLT , 1PHASE
CEILING MOUNTED DUPLEX GROUNDING TYPE RECEPTACLE - 20 AMP,
120 VOLT, NEMA 5-20R.
FLOOR BOX WITH (4) POWER, (2) CAT 6E, (1) HDMI AND (1) DUAL USB
PORT TYPE OUTLET
DISCONNECT SWITCH, AMP/ POLES / ENCLOSURE NEMA RATING / FUSE
PER NAME PLATE.
COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH
MOTOR STARTER
ELECTRIC MOTOR
FIRE ALARM MANUAL PULL STATION, M.H. 48" AFF.
FIRE ALARM AUDIO/VISUAL SIGNAL DEVICE, M.H. 96" AFF.
FIRE ALARM VISUAL ONLY SIGNAL DEVICE, M.H. 96" AFF.
SMOKE DETECTOR
DUCT SMOKE DETECTOR - PROVIDED UNDER DIVISION 15 AND WIRED
UNDER DIVISION 16.
PANELBOARD
JUNCTION BOX, PULL BOX WALL/CEILING MOUNTED
LINE BREAK.
HOMERUN WIRING WITH A DEDICATED EQUIPMENT GROUND WIRE TO
THE REFERENCED PANELBOARD. ARROW HEADS AND NUMERALS
INDICATE THE CIRCUIT NUMBERS.
CONDUIT DOWN OR AWAY
CONDUIT UP OR TOWARD VIEWER
CONDUIT, STUBBED AND CAPPED AS SHOWN
GROUND GRID CABLE
UNDERGROUND ELECTRIC
CIRCUIT BREAKER, THERMAL MAGNETIC TRIP SHOWN,
3 POLE UON.
FUSE - RATING INDICATED
DELTA CONNECTION, THREE PHASE
DELTA CONNECTION, SINGLE PHASE
WYE CONNECTION - UNGROUNDED, GROUNDED, THREE PHASE
WYE CONNECTION - UNGROUNDED, GROUNDED, SINGLE PHASE
FUSED SWITCH, MEDIUM VOLTAGE
SURGE ARRESTER/LIGHTNING ARRESTER
DRY CONTACTS - NO, NC
GROUND
POTENTIAL TRANSFORMER
TRANSFORMER
CURRENT TRANSFORMER,
NUMBER INDICATED
CORE BALANCE CURRENT TRANSFORMER
EXISTING, NEW ELECTRIC MANHOLE OR
HANDHOLE AND NUMBER
INTERLOCKED RECEPTACLE WITH
DISCONNECT SWITCH
FIELD PHOTOGRAPH
TERMINATION
GROUNDING RESISTOR
A
AC
AF
AFF
AFG
AHU
AIC
AL
AM
AT
ATS
AUTO
AUX
AWG
BAT
BKR
BLDG
BOCA
C
CB
CC
CH
CIR,CKT
CLR
COMB
CONT'D
CPT
CR
CT
CU
DC
DIA
DIST
DIV
DN
DP
DSW
DWG
E
EA
EC
ECB
EF
EL
EMH
EO
ER
ETM
ETR
EX
F
FA
FAAP
FACP
FDR
FLR
FSS
FUT
G
GALV
GC
GFI
GFP
GFR
GND
HH
HP
HVAC
HZ
IC
ICCB
I & C
ID
IG
INST
ITC
JB
K
KCMIL
KVA
KW
LA
LB
LO
LCP
LOS
LVL
AMPERE
ALTERNATING CURRENT
AMPERE FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERES INTERRUPTING
CAPACITY (SYM, RMS, AMPS)
ALUMINIUM
AMMETER
AMPERE TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AMERICAN WIRE GAUGE
BATTERY
BREAKER
BUILDING
BUILDING OFFICIALS AND
CODE ADMINISTRATORS
CONDUIT
CIRCUIT BREAKER
CONTROL CABLE
CABINET HEATER
CIRCUIT
CLEAR
COMBINATION
CONTINUED
CONTROL POWER TRANSFORMER
CONTROL RELAY
CURRENT TRANSFORMER
COPPER, COMPRESSOR UNIT
DIRECT CURRENT
DIAMETER
DISTRIBUTION
DIVISION
DOWN
DISTRIBUTION PANEL
DISCONNECTING SWITCH
DRAWING
EMPTY, ELECTRICAL INTERLOCK,
EXISTING
EACH
EMPTY CONDUIT
ENCLOSED CIRCUIT BREAKER
EXHAUST FAN
ELEVATION
ELECTRIC MANHOLE
ELECTRIC OPERATOR
EXISTING RELOCATED
ELAPSED TIME METER
EXISTING TO REMAIN
EXISTING
FUSE, FRAME, FRONT
FRAME AMPS
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FEEDER
FLOOR
FUSED SAFETY SWITCH
FUTURE
GREEN, GROUND, GROUND GRID
GALVANIZED
GENERATOR CONTACTOR,
GENERATOR CONTROL PANEL
GROUND FAULT INTERRUPTER
GROUND FAULT PROTECTION
GROUND FAULT RELAY
GROUND
HANDHOLE
HORSE POWER
HEATING VENTILATION AND AIR
CONDITION
HERTZ
INTERRUPTING CAPACITY
INSULATED CASE CIRCUIT BREAKER
INSTRUMENTATION & CONTROL
IDENTIFICATION
ISOLATED GROUND
INSTANTANEOUS
INTERFACE TERMINAL CABINET
JUNCTION BOX
KEY INTERLOCK
KILO CIRCULAR MILS
KILOVOLT-AMPERE
KILOWATT
LIGHTNING ARRESTER
CONDUIT BOX, RIGHT ANGLE
LOCKOUT
LOCAL CONTROL PANEL
LOCKOUT STOP PUSH BUTTON
LEVEL
MAIN CIRCUIT BREAKER
MACHINE
MULTIFUNCTION RELAY
MANHOLE, MOUNTING HEIGHT
MINIMUM
MAIN LUG ONLY
MOUNT
MOUNTED
NEUTRAL
NON-AUTOMATIC
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NON-FUSED SAFETY SWITCH
NORMALLY OPEN
NUMBER
NAMEPLATE
NOT TO SCALE
OVERLOAD
POLE OR POLES
PULL BOX, PUSH BUTTON
POWER FACTOR
PHASE
PILOT LIGHT
MICROPROCESSOR BASED METERING
PHASE MONITOR RELAY
POWER MONITORING DEVICE
PANEL
POWER QUALITY MONITOR
PAIR
PRIMARY
POTENTIAL TRANSFORMER
REMOVE, RED, REAR, RUN CONTRACTORS
RIGID GALVANIZED STEEL / GALVANIZED RIGID
CONDUIT
RECEPTACLE
REQUIRED
ROOT MEAN SQUARE
ROOM
ROOF TOP UNIT
SURGE ARRESTOR
SURGE PROTECTION DEVICE
SWITCH
SYMMETRICAL
TRIP AMPS
TERMINAL BOARD, TERMINAL BLOCK
TIME DELAY RELAY
TERMINAL JUNCTION BOX
TWISTED SHIELDED PAIR
HIGH-TEMP RELAY
TEST SWITCH
TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYPICAL
UNDERGROUND
UNDERWRITERS LABORATORY
UNLESS OTHERWISE NOTED
VOLTS OR VOLTAGE
VOLTAMPS
MB,MCB
M/C
MFR
MH
MIN
MLO
MT
MTD
N
NA
NC
NEC
NEMA
NFPA
NFSS
NO
NO.
NP
NTS
OL
P
PB
PF
PH
PL
PM
PMR
PMT
PNL
PQM
PR
PRI
PT
R
RGS,GRC
RECPT
REQ'D
RMS
RM
RTU
SA
SPD
SW
SYM
TA
TB
TDR
TJB
TSP
TSH
TS
TVSS
TYP
UG
UL
UON
V
VA
W W/
WH
WP
WR
XFMR
Z
O
WATTS, WIRE
WITH
WATTHOUR
WEATHERPROOF
WELDING RECEPTACLE
TRANSFORMER
IMPEDANCE
PHASE, DIAMETER
NUMBER
ELECTRICAL GENERAL NOTES
1. IT IS THE INTENT OF THESE DRAWINGS AND OTHER RELATED DOCUMENTS TO PRODUCE A
COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM. PROVIDE ALL LABOR, MATERIAL, TESTS,
AND OTHER SERVICES AS MAY BE NECESSARY TO ACHIEVE THIS PRODUCT. ACKNOWLEDGE
ACCEPTANCE OF THE PLANS AS AN ADEQUATE DEFINITION OF THE SCOPE OF WORK. EXTRA
COST CLAIMS BASED ON DISCREPANCIES ON THE PLANS WILL NOT BE CONSIDERED.
2. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE
(NEC) AND ALL LOCAL CODES HAVING JURISDICTION. ALL EQUIPMENT, DEVICES, AND
MATERIAL SHALL BE LISTED WITH UNDERWRITERS LABORATORIES FOR ITS APPLICATION AS
INSTALLED AND SHALL BEAR THE UL LABEL.
3. OBTAIN THE REQUIRED BUILDING AND TRADES PERMIT AND COORDINATE WITH THE
GOVERNMENT.
4. VISIT THE SITE AND EXAMINE CONDITIONS OF THE PREMISES AND THE CHARACTER AND
EXTENT OF WORK REQUIRED PRIOR TO CONSTRUCTION. BRING TO THE ATTENTION OF
GOVERNMENT FOR FURTHER DIRECTIONS, IF THERE ARE DIFFICULTIES IN COMPLYING WITH
DRAWINGS/SPECIFICATIONS.
5. ELECTRICAL PLANS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS.
6. CONSULT PLANS, IF ANY, OF ALL OTHER AFFECTED AREAS FOR COORDINATION AND RELATED
WORK.
7. CONSULT EXISTING AS BUILT ARCHITECTURAL AND STRUCTURAL PLANS AND DETAILS FOR
CONSTRUCTION TYPE, HEADROOM, ROOM FINISHES, CEILINGS, ETC. COORDINATE WITH
GOVERNMENT, AS REQUIRED.
8. CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. CONTRACTOR SHALL BE
RESPONSIBLE FOR CORRECTLY SPACING THE CIRCUITS IN THE PANEL AND BALANCE THE
LOAD ON THE PHASES UNDER NORMAL OPERATING CONDITIONS.
9. SUBMIT SHOP DRAWINGS FOR ALL ELECTRICAL EQUIPMENT, FIXTURES, DEVICES AND
MATERIALS TO OBTAIN COR'S APPROVAL BEFORE DELIVERY TO THE JOB SITE. REPLACE ALL
NON-CONFIRMING EQUIPMENT AND DEVICES, AT NOT EXTRA CHARGE TO GOVERNMENT.
10. VERIFY WIRE SIZES, CB AND FUSE RATINGS FOR ALL EQUIPMENT, AND BRING TO THE
ATTENTION OF THE GOVERNMENT ANY DISCREPANCIES AFFECTING THE WORK PRIOR TO
PROCEEDING.
11. ALL WORK SHALL BE DONE AT SUCH TIMES AND IN SUCH A MANNER AS WILL LEAST
INTERFERE WITH THE MAINTENANCE AND OPERATION OF ALL RELATED OR AFFECTED
SYSTEMS. COORDINATE ALL POWER OUTAGES, FIRE ALARM SHUT DOWNS, ETC. WITH
GOVERNMENT.
12. WHERE APPLICABLE, CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SIZING OF ALL
MOTOR OVERLOAD DEVICES (HEATERS) IN STARTERS BASED ON ACTUAL NAMEPLATE
RATINGS ON THE MOTORS BEING INSTALLED.
13. HORSEPOWER / WATTAGE INDICATED ON DRAWINGS MAY DIFFER FROM ACTUAL
EQUIPMENT FURNISHED. IF FURNISHED EQUIPMENT DIFFERS FROM RATINGS ON
DRAWINGS, MARK THE DRAWINGS FOR AS BUILT CONDITION.
14. THE EXACT NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE
WHERE CLARIFICATION IS NECESSARY. PROVIDE ALL WIRES NECESSARY FOR THE PROPER
FUNCTIONING OF THE SYSTEM WHETHER INDICATED ON DRAWINGS OR NOT.
15. PROVIDE PULL WIRE AND FISH CORD FOR ALL NEW EMPTY CONDUIT RUNS IN EXCESS OF 10
FEET.
1. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO COORDINATE EXACT REQUIREMENTS FOR INCOMING SERVICE OF LOCAL UTILITIES FOR POWER AND TELEPHONE, PAY ALL
FEES, AND INSTALL A COMPLETE AND FUNCTIONAL SYSTEM.
2. COORDINATE INSTALLATION OF TELEPHONE SYSTEM INCLUDING TELEPHONE WIRING AND TELEPHONE
OUTLETS WITH THE GOVERNMENT/ENGINEER.
3. REFER TO BASE BUILDING DRAWINGS FOR LOCATION OF UTILITY SERVICE JUNCTION BOX.
COORDINATION WITH POWER AND TELEPHONE COMPANIES:
1. COORDINATE ALL MOUNTING HEIGHTS FOR SWITCHES, RECEPTACLES, WALL MOUNTED LIGHT
FIXTURES, AND TELEPHONE OUTLETS BY THE USE OF THE ARCHITECTURAL AND ENGINEERING
DRAWINGS. SHOULD ANY CONFLICTS BECOME APPARENT, REQUEST CLARIFICATION PRIOR TO
INSTALLATION. IF THE WORK IS NOT COORDINATED, PROVIDE ANY REMEDIAL WORK, AS
APPROVED BY COR, AT NO ADDITIONAL COST TO THE GOVERNMENT.
WIRING DEVICES
1. BALLAST FOR LIGHTING FIXTURES SHALL OPERATE THE SPECIFIED LAMPS. ELECTRONIC BALLAST
SHALL HAVE A POWER FACTOR GREATER THAN .95, LESS THAN 10% HARMONIC DISTORTION.
LIGHT FIXTURES:
16. CONCEAL ALL CONDUCTORS, RACEWAYS AND CABLES IN CEILING OR WALL UNLESS OTHERWISE
INDICATED.
17. DO NOT CUT OPENINGS IN EXISTING BUILDING STRUCTURE FOR PASSAGE OF CONDUITS/CABLES
WITHOUT WRITTEN APPROVAL FROM THE GOVERNMENT.
18. FURNISH AND INSTALL NEW LIGHTING FIXTURES COMPLETE WITH ALL ACCESSORIES (INCLUDING
LAMPS).
19. SYMBOLS SHOWN ON THIS SHEET ARE STANDARD SYMBOLS. ALL OF THEM MAY NOT BE
APPLICABLE TO THIS PROJECT.
20. GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE BY
GOVERNMENT.
21. FIRE STOP ALL NEW PENETRATIONS THROUGH FLOOR AND WALLS IN ACCORDANCE WITH BOCA, NEC, AND NFPA.
22. INSTALL CONDUCTORS CONTINUOUS BETWEEN DEVICES, WITH SPLICES LOCATED ONLY IN
JUNCTION BOXES OR IN CABINETS, AS SHOWN. CONDUCTORS SHALL BE OF SUFFICIENT LENGTH
TO REACH THE FARTHEST POINT. A MINIMUM OF 6" LOOPS SHALL REMAIN WHERE
CONNECTIONS OR TAPS ARE TO BE MADE.
23. PROVIDE AN UPDATED TYPEWRITTEN PANEL DIRECTORY IN THE PANEL AFTER COMPLETION OF
WORK.
24. PROVIDE AS BUILT DRAWINGS, ALL MANUFACTURERS' DATA AND WARRANTY LITERATURE AT THE
COMPLETION OF THE CONTRACT.
P
XX/X/XX/FPN
AV
ELECTRICAL COVER SHEET
E-001
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
DocuSign Envelope ID: 0D7387B3-F84A-43BC-8271-5EA4D34073CB
3/7/2024
TOP OF EXISTING
FLOOR SLAB.
CORE DRILL THROUGH
EX. FLOOR SLAB AS
REQUIRED.
CONDUIT
PENETRATION SEE
PLANS FOR SIZE AND TYPE.
GALVANIZED STEEL
PIPE STRAP (TYP)
FIRE RATED FLOOR CONDUIT PENETRATION
NTS
FIRE RATED WALL
MINIMUM OF 2 HR RATED
FIRE STOP MATERIAL
SLEEVE
CONDUIT
FIRE RATED WALL CONDUIT PENETRATION
NTS
CONDUIT PENETRATION WALL ASSEMBLY
ANNULAR SLEEVE
MIN. 3" OF THERMAFIBER
SAFING INSULATION WITH
A MIN. DENSITY OF 3.5 PCF
- U.L. R-10905 LABEL.
FIRE RATED WALL
FIRE RATED WALL SLEEVE PENETRATION
NTS
OUTLET BOX
WITH BUSHED
OPENING
(TYPICAL)
FULL HEIGHT PARTITION
CONDUIT WITH DRAG
WIRE (TYPICAL)
CEILING
HIGH
PARTITION
SLAB
HUNG
CEILING
BUSHING BUSHING
SLAB
TYPICAL EMPTY CONDUITS STUB-UP FOR
TELEPHONE & DATA OUTLETS NTS
TYPICAL DEVICE MOUNTING HEIGHTS
NTS
2"
1'-6"
2"
4'-0"
4'-6"
6'-8"
8'-6"
FIRE ALARM
PULL STATIONS
WALL PHONE
OUTLETS
LIGHTING
CONTROL DEVICES
RECEPTACLES,
TELECOMM / DATA
OUTLETS
FIRE ALARM AUDIO/VISUAL
DEVICES IN MULTIPLE
CONFIGURATIONS. SEE NOTE #4.
EXIT SIGN
FINISHED FLOOR
PROVIDE STEM FOR PENDANT
MOUNTING WHEN PROVIDED IN
AN OPEN CEILING SPACE 1.
2.
3.
4.
NOTES:
SECTION "A-A"
TYPICAL EQUIPMENT GROUND BUS DETAIL
NTS
A
2"
1/4"
EXOTHERMIC WELD CONNECTION (TYP)
GROUND CONNECTION FOR
EQUIPMENT. COMPRESSION
LUG BOLTS, WIRE ETC. BY
EQUIPMENT INSTALLER.
1/4" X 4" X 20" COPPER GROUND BUS WITH (27) SETS OF
5/16" HOLES AND (3) SETS OF 7/16" HOLES. HARGER
#GBi14420TMGB OR APPROVED EQUAL.
A
A FRONT ELEVATION
TO BUILDING SYSTEM GROUND BUS
TO TEL/COMM. ROOM EQUIPMENT
GROUND BUS ON LEVEL ABOVE
TO TEL/COMM. ROOM EQUIPMENT
GROUND BUS ON SAME LEVEL
STAINLESS STEEL
MOUNTING
BRACKET, 1"
OFFSET
3/8" MOUNTING BOLT
RED STANDOFF INSULATOR,
POLYESTER/FIBERGLASS
4TYPICAL LIGHTING FIXTURE CIRCUITING DETAIL
NTS
LIGHTING
FIXTURE (TYPICAL)
FLEXIBLE METAL
CONDUIT (MAX. 6 FEET
LONG)
EMT - HOMERUNEMTTO NEXT
JUNCTION BOX
TO NEXT
JUNCTION BOX
EMT
LIGHTING
FIXTURE (TYPICAL)
FLEXIBLE METAL
CONDUIT (MAX. 6 FEET
LONG)
EMT - HOMERUN
J J
JJ
3DEVICE LABELING DETAIL
NTS
TYPICAL NEMA
5-20R, 120V, 20A
RECEPTACLE
R2P1(3) R2P1(21,23,25)
NEMA 18-30R
R2P1(3,5)
NEMA 6-50R
R2P1(3,5)
NEMA L6-30R
PANEL NAME AND
CIRCUIT NUMBER
TYPICAL LABELING FOR
RECEPTACLE TYPES OTHER
THAN NEMA 5-15R OR 5-20R
2PANEL / DISTRIBUTION BOARD LABELING
NTS
A.
B.
PANEL NAME / ID
SOURCE OF SUPPLY. NEC 408.4(B).
LP1
POWERED FROM H1, CIRCUIT 2,4,6
VIA TRANSFORMER T-LP1
MINIMUM OF 2 HR
RATED INFILL MATERIAL
TYPICAL ALL SIDES OF
PENETRATION
MINIMUM OF 2 HR RATED
INFILL MATERIAL TYPICAL ALL
SIDES OF PENETRATION
AND ANNULAR SLEEVE
LOCATIONS OF OUTLETS AND EQUIPMENT AS INDICATED ON THE DRAWINGS ARE
APPROXIMATE. PLACE THE EXACT CENTER OF ALL OUTLETS IN COOPERATION WITH THE
COR. EXAMINE ALL INTERIOR DETAILS OF THE CONSTRUCTION DRAWINGS FOR OUTLET
LOCATIONS NOT CONFORMING TO THE DETAIL ABOVE. WHERE DETAILED TO SPECIFIC
LOCATIONS, THE ARCHITECTURAL DRAWINGS SHALL TAKE PRECEDENCE. IF AN OUTLET IS
INSTALLED IN SUCH A LOCATION AS TO BE OUT OF PROPER RELATION TO WALLS OR
DETAILS OF THE BUILDING, CORRECT ITS LOCATION AT THE EXPENSE OF THE
CONTRACTOR UNDER THE DIRECTION OF THE COR.
VERIFY THE DEVICE LOCATIONS AND MOUNTING HEIGHTS AGAINST THE ARCHITECTURAL
PLANS AND ELEVATIONS PRIOR TO ROUGH-IN IN ORDER TO AVOID INTERFERENCES WITH
CASEWORK, FURNITURE, WINDOWS, MIRRORS, EQUIPMENT, ETC.
CENTER THE DEVICES IN A COMMON VERTICAL PLANE. MEASURE THE HEIGHT FROM
FINISHED FLOOR TO CENTERLINE OF DEVICE EXCEPT EXIT SIGNS, AND FIRE ALARM
SIGNALS. COORDINATE LOCATION WITH MATERIALS SUCH AS MASONRY UNITS.
LOCATE THE ENTIRE LENS OF A FIRE ALARM A/V SIGNAL OR VISUAL-ONLY SIGNAL
BETWEEN 6'-8" A.F.F. AND 8'-0" A.F.F. OR 6" BELOW CEILING (WHICHEVER IS LOWER).
ELEVATION SHALL BE CONSISTENT THROUGHOUT PROJECT. WHEN A CEILING DEVICE IS
SPECIFIED, INSTALL THE DEVICE ON A HUNG CEILING OR PROVIDE WITH A STEM FOR
PENDANT MOUNTING IN AN OPEN CEILING SPACE. HEIGHT OF DEVICE SHALL MATCH
LOCAL LIGHTING FIXTURE HEIGHTS OR BE INSTALLED AT 10-0" MAX, WHICHEVER IS
LOWER.
PERMANENTLY AFFIXED ENGRAVED NAME PLATE SHALL BE
HEAVY DUTY, MINIMUM 1/16" THICK PLASTIC, UV STABLE FOR
LONG-LASTING AND BLACK BACKGROUND WITH WHITE TEXT.
ELECTRICAL DETAILS
E-002
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
#4/0 B.C. STRANDED
GROUND GRID
24" MIN.
CONNECT GROUND ROD TO GROUND
GRID WITH EXOTHERMIC WELD
FINISHED GRADE
12" MIN.
GROUND
GAW910-TEST WELL
GROUND ROD CLAMP
CLASS II COPPER GROUNDING CONDUCTOR
GROUND ROD
3/4" DIA. x 10' LONG
COPPER CLAD ROUND
STEEL GROUND ROD
GROUNDING SYSTEM
GROUND ROD
GROUND ROD CLAMP
BRONZE BONDING PLATE
CLASS II CONDUCTOR
SURFACE
WELDED BASE BRONZE
BONDING PLATE
CLASS II COPPER CONDUCTOR
CLASS II COPPER
AIR TERMINAL
FLAT MOUNT POINT BASE WITH
SWIVEL ADAPTER
BARE COPPER
CONDUCTOR
LOOP CABLE HOLDER AT
3'-0" O.C.
SCALE: NONE
COPPER CLAD STEEL GROUD ROD DETAIL
BSCALE: NONE
GROUNDING TEST WELL
A
SCALE: NONE
GROUDING CONDUCTOR BONDED TO EQUIPMENT
C
SCALE: NONE
AIR TERMINAL BONDED TO STRUCTURE
E
SCALE: NONE
GROUNDING ROD BONDED TO STRUCTURE
FCLAMP TYPE BONDING
PLATE
BONDING STRAP
BONDING PLATE
BONDING CLAMP
SECONDARY SIZE
BONDING CLAMP
BONDING LUG
FLAT METAL
BONDING CLAMP
PARALLEL SPLICER
U-BOLT CLAMP
SCALE: NONE
TYPICAL BONDING AND SPLICE DETAIL
G
EXOTHERMIC WELD
CONNECTION TO
COUNTERPOISE
#4/0 AWG BARE
CLASS II COPPER
CONDUCTOR 30" BELOW
FINISHED GRADE
SCALE: NONE
GROUNDING "T" JOINT CONNECTION DETAIL
D
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
LIGHTNING PROTECTION
DETAILS
E-003
GENERAL NOTES
1. INTERCONNECT THE TELEPHONE AND ELECTRICAL SERVICE
ENTRANCE GROUNDS TO ONE LIGHTNING PROTECTION GROUND
OR WATER PIPE.
2. GROUND ALL ELECTRICAL EQUIPMENT, ENCLOSURE, FRAMES AND
STRUCTURES.
3. INTERCONNECT THE METAL BODIES OF INDUCTANCE LOCATED
ABOUT THE ROOF SUCH AS METAL FLASHING, GRAVEL STOPS,
ROOF DRAINS, SOIL PIPE VENTS, INSTALLATION VENTS, LOUVERS
AND DOOR FRAMES SITUATED WITHIN 6'-0" OF A LIGHTNING
CONDUCTOR OR BONDED METAL BODY TO THE LIGHTNING
CONDUCTOR SYSTEM.
4. MAKE ALL UNDERGROUND OR EMBEDDED GROUNDING
CONNECTIONS BY EXOTHERMIC FUSION WELDING PROCESS, UON.
5. NO BENDS OF A CONDUCTOR SHALL FORM A FINAL INCLUDED
ANGLE OF LESS THAN 90 DEGREES NOR SHALL HAVE A RADIUS OF
BEND LESS THAN 8".
6. WHERE DOUBLE CONNECTIONS ARE REQUIRED, ATTACH AT
DIAGONALLY OPPOSITE POINTS OF THE EQUIPMENT, AND EXTEND
EACH CONNECTION INDEPENDENTLY TO DIFFERENT SEGMENTS
OF THE GROUNDING SYSTEM.
7. INTERCONNECT ALL AIR TERMINALS AND SHALL FORM A
TWO-WAY PATH FROM EACH AIR TERMINAL HORIZONTALLY OR
DOWNWARD TO CONNECTIONS WIT GROUND TERMINALS.
8. FASTEN ALL LIGHTNING PROTECTION CONDUCTORS NOT MORE
THAN 3'-0" MAXIMUM SPACING.
9. DRIVE GROUND RODS SO THAT THE TOP OF THE GROUND RODS IS
TO A MINIMUM DEPTH OF 12" BELOW GRADE AND 2'-0" FROM
FOUNDATION WALL.
10. MAKE CONNECTORS TO GROUND LOOP CONDUCTOR AT A POINT
NOT LESS THAN 24" BELOW GRADE AND 2'-0" FROM
FOUNDATION WALL.
11. PLACE THE AIR TERMINALS AT ALL UNPROTECTED OUTSIDE
CORNERS AND 20'-0" MAXIMUM SPACING AROUND THE ROOF
PERIMETER OR RIDGE AND WITHIN 2'-0" OF OUTSIDE EDGE.
12. PROVIDE ALL BURIED GROUND CABLES WITH A MINIMUM OF 18"
OF EARTH COVER.
13. CLEAN BARE CABLE AT ALL CONNECTIONS TO A BRIGHT SURFACE,
MAKE CONNECTIONS ONLY WHEN THOROUGHLY DRY.
14. AFTER COMPLETION OF THE GROUND GRID, MEASURE AND
RECORD THE RESISTANCE TO EARTH. MEASUREMENTS SHALL BE
MADE AS PER IEEE STD. 81. THE RESISTANCE SHALL BE 5 OHMS
OR LESS.
15. DO NOT INSTALL BARE COPPER LIGHTNING PROTECTION
MATERIALS ON ALUMINUM ROOF OR SIDING OR OTHER
ALUMINUM SURFACES AND VICE VERSA, DO NOT INSTALL
ALUMINUM LIGHTNING PROTECTION MATERIALS ON COPPER
ROOF OR SIDING OR OTHER COPPER SURFACES.
16. INSTALL THE LIGHTNING PROTECTION SYSTEM IN A NEAT AND
INCONSPICUOUS MANNER SO THAT ALL COMPONENTS WILL
BLEND IN WITH THE APPEARANCE OF THE BUILDING.
17. INSTALL THE LIGHTNING PROTECTION SYSTEM IN A NEAT AND
INCONSPICUOUS MANNER SO THAT IT WILL NOT ALTER ANY
EXISTING WATERPROOFING COMPONENT OF BUILDING.
18. ACTUAL JOB SITE CONDITIONS MAY NECESSITATE SLIGHT
ALTERATIONS IN AIR TERMINAL AND GROUND ROD LOCATIONS.
19. THE PLAN AND LAYOUT SHOWN FOR THESE SYSTEMS ARE
SCHEMATIC AND ARE INTENDED TO SHOW BASIC SYSTEM
LAYOUT. VERIFY DIMENSIONS AND SITE CONDITIONS AND
PROVIDE SYSTEMS THAT COMPLY TO CODE REQUIREMENTS.
20. INSTALL DOWN CONDUCTORS FOR GROUNDING AND LIGHTNING
PROTECTIONS IN RIGID CONDUITS 8' FROM GROUND UP AND
EXPOSED, MOUNTED ON WALL.
21. SUBMIT A SIGNED AND SEALED BY A STATE-LICENSED ELECTRICAL
ENGINEER LIGHTNING PROTECTION SUBMITTAL DRAWING THAT
MEETS OR EXCEEDS THE REQUIREMENTS HEREIN, FOR OWNER'S
APPROVAL BEFORE CONSTRUCTION.
EX PANEL LA
UP
UP
BASEMENT
STORAGE
EXIT
STAIR
002EX
AHU-BASE
EX DSW
FOR AHU-BASE
EX REMOTE
TERMINAL
UNIT
EX ATS
EX UTILITY
METER
EX PANEL MLA
EX
TELECOMMUNICATION
BOX
SD
IT
RACK
DN
DN
DN
UP
KITCHEN
OPEN
OFFICE
RECEPTION
STORAGE
VESTIBULE
ACCESS
STAIR
TOILET
Wp
EX HP-
BASE
EX HP-
ATTIC SD
DN
TOILET
205HALL
OFFICE
OFFICE
203 CONF
ROOM
CLOSET
CLOSET
202A
CLOSET
204A
CLOSET
203A
CLOSET
204B
CLOSET
203B
EXISTING
DEMOLITION
NEW WORK
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH GFCI PROTECTION
IN WEATHERPROOF ENCLOSURE
QUADRUPLE RECEPTACLE
SPECIAL TYPE RECEPTACLE
FLOOR BOX
DISCONNECT SWITCH
AV
Wp
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
EXIST/DEMO BASEMENT LEVEL - POWER PLAN1 SCALE : 1/4" = 1'-0"
0 2' 4' 8' 12'
SCALE : 1/4" = 1'-0"
ADMINISTRATION BUILDING
EXIST/DEMO -
POWER PLANS
ED-101
EXIST/DEMO GROUND LEVEL - POWER PLAN2 SCALE : 1/4" = 1'-0"
EXIST/DEMO SECOND LEVEL - POWER PLAN3 SCALE : 1/4" = 1'-0"
KEY NOTES
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND
GENERAL NOTES, SEE DRAWING E-001.
2. FOR ELECTRICAL NEW WORK POWER PLAN, SEE DRAWING
EN-101.
3. FOR ELECTRICAL POWER RISER DIAGRAM AND SCHEDULES,
SEE DRAWINGS EN-121 AND EN-131.
GENERAL NOTES
01 EXISTING ELECTRICAL EQUIPMENT TO REMAIN-IN PLACE.
PROTECT DURING CONSTRUCTION.
REPLACE EXISTING RECEPTACLE WITH NEW GROUNDING TYPE
RECEPTACLE. PULL EXISTING WIRING BACK TO SOURCE AND
DISPOSE OFF. EXISTING CONDUIT TO REMAIN-IN PLACE FOR
RE-USE.
REPLACE EXISTING RECEPTACLE WITH NEW GROUND FAULT
CIRCUIT INTERRUPTER (GFCI) TYPE RECEPTACLE. EXISTING
WIRING AND CONDUIT TO REMAIN-IN PLACE.
EXISTING RECEPTACLE TO REMAIN-IN PLACE. PROTECT
DURING CONSTRUCTION.
DISCONNECT AND REMOVE EXISTING RECEPTACLE.
DISCONNECT AND REMOVE EXISTING SMOKE DETECTOR
INCLUDING WIRING AND CONDUIT.
DISCONNECT AND REMOVE EXISTING ELECTRICAL
CONNECTION TO MECHANICAL EQUIPMENT INCLUDING
WIRING AND CONDUIT. PULL WIRING BACK TO SOURCE AND
DISPOSE OFF.
EXISTING ELECTRICAL POWER CONNECTIONS TO EXISTING
MECHANICAL EQUIPMENT TO REMAIN-IN PLACE. PROTECT
DURING CONSTRUCTION.
LEGENDS
MS
S3
S
STORAGE
EXIT
STAIR
BASEMENT
18' - 5" 18' - 4"
18' - 5"
18' - 5" 18' - 5"
16' - 8 1/2"
18' - 5 1/2"
18' - 5 1/2"
28' - 0"
S S
S
S
S3
S
S3
S
S
S3S
S
O S
MS
M S
KITCHEN
OPEN
OFFICE
RECEPTION
STORAGE
VESTIBULE
ACCESS
STAIR
TOILET
MS
S
S
S3
S D
S
S
MS
MS
M S
MS
MS
TOILET
HALL
OFFICE
OFFICE
CONF
ROOM
CLOSET
204B
EXISTING
DEMOLITION
NEW WORK
SINGLE POLE TOGGLE SWITCH
THREE WAY TOGGLE SWITCH
LIGHT SWITCH WITH BUILT-IN OCCUPANCY SENSOR
OCCUPANCY SENSOR
MOTION SENSOR
S
S3
SOS
OS
MS
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
EXIST/DEMO BASEMENT LEVEL - LIGHTING PLAN1 SCALE : 1/4" = 1'-0"
0 2' 4' 8' 12'
SCALE : 1/4" = 1'-0"
ADMINISTRATION BUILDING
EXIST/DEMO -
LIGHTING PLAN
ED-102
EXIST/DEMO GROUND LEVEL - LIGHTING PLAN2 SCALE : 1/4" = 1'-0"
EXIST/DEMO SECOND LEVEL - LIGHTING PLAN3 SCALE : 1/4" = 1'-0"
KEY NOTES
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND
GENERAL NOTES, SEE DRAWING E-001.
2. FOR ELECTRICAL NEW WORK LIGHTING PLAN, SEE DRAWING
EN-102.
3. FOR ELECTRICAL POWER RISER DIAGRAM AND SCHEDULES,
SEE DRAWINGS EN-121 AND EN-131.
GENERAL NOTES
01 EXISTING LIGHTING FIXTURE, SWITCH AND MOTION SENSOR
TO REMAIN-IN PLACE. PROTECT DURING CONSTRUCTION.
DISCONNECT AND REMOVE EXISTING INTERIOR LIGHTING
FIXTURE AND SWITCH INCLUDING WIRING AND CONDUIT
BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EXTERIOR LIGHTING
FIXTURE INCLUDING WIRING AND CONDUIT BACK TO
SOURCE.
01 01
01 01
01 01
01 01
01 01
02 02
01 01
01 01
LEGENDSLEGENDS
TELEPHONE
TERMINATION BLOCKS
BASEMENT
SERVER CLOSET
/STORAGE
EXIT
STAIR
EX
PANEL LA
LA-17
LA-1
EX
AHU-BASE
EX DSW
FOR AHU-BASE
MLA-20
MLA-18
+48"
+48"
MLA-22
MLA-24
DN
DN
DN
UP
Wp EX REMOTE
TERMINAL UNIT
EX ATS
EX UTILITY
METER &
PANEL MLA
EX
TELECOMMUNICATION
BOX
KITCHEN
TOILET
OPEN
OFFICE
RECEPTION
OFFICE
VESTIBULE
ACCESS
STAIR
CLOSET
LA-10
LA-7
LA-13
LA-5
LA-3
LA-9
LA-15
LA-8
LA-11
+48"
+48"
NEW
HP-A
EX
HP-ATTIC
NEW 240V/30A/2P/
NEMA 3R DSW
MLA-21,23
+48"
+48"
+48"
+36"
EX HP-
BASE
DN
CLOSET
202A
TOILET
HALL
OFFICE
CONF
ROOM
OFFICE
CLOSET
205A
CLOSET
204A
SAFE
CLO
203A
AV
LA-18
LA-19
+48"
+48"
+48"
+60"
EXISTING
DEMOLITION
NEW WORK
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH GFCI PROTECTION
IN WEATHERPROOF ENCLOSURE
QUADRUPLE RECEPTACLE
SPECIAL TYPE RECEPTACLE
FLOOR BOX
DISCONNECT SWITCH
AV
Wp
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
NEW WORK BASEMENT LEVEL - POWER PLAN1 SCALE : 1/4" = 1'-0"
0 2' 4' 8' 12'
SCALE : 1/4" = 1'-0"
ADMINISTRATION BUILDING
NEW WORK -
POWER PLANS
EN-101
NEW WORK GROUND LEVEL - POWER PLAN2 SCALE : 1/4" = 1'-0"
NEW WORK SECOND LEVEL - POWER PLAN3 SCALE : 1/4" = 1'-0"
KEY NOTES
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND
GENERAL NOTES, SEE DRAWING E-001.
2. FOR ELECTRICAL POWER RISER DIAGRAM AND SCHEDULES,
SEE DRAWINGS EN-121 AND EN-131.
GENERAL NOTES
01 PROVIDE NEW RECEPTACLES INCLUDING WIRING AND CONDUIT
AS INDICATED.
PROVIDE NEW RECESSED FLOOR BOX WITH QUADRUPLE
ELECTRICAL RECEPTACLES, 2 - CAT 6a, 1 - HDMI PORT AND 1 -
DUAL USB PORT TYPE OUTLET.
a. CORE DRILL FOR POKE THROUGH FLOOR DEVICE. PROVIDE
REQUIRED WIRING ACCORDING TO MANUFACTURER'S
WIRING DIAGRAM. ALL CORE DRILLING AND UNDERFLOOR
CONDUIT ROUTING MUST BE SUBMITTED TO COR FOR
REVIEW PRIOR. OBTAIN COR'S APPROVAL PRIOR TO WORK.
b. CONDUIT ROUTING IS SHOWN FOR INDICATIVE PURPOSE
ONLY. PROVIDE UNDERFLOOR CONDUITS FOR 120V POWER,
TELECOMMUNICATION CABLES, AV CABLES AND USB POWER
FROM POKE THROUGH FLOOR DEVICE TO NEAREST WALL AS
SHOWN.
c. PROVIDE NEW JUNCTION BOX OR ACCESS BOX AT THE
WALL/FLOOR INTERFACE TO FACILITATE THE INSTALLATION
OF ELECTRICAL, TELECOMMUNICATION AND AV. EXTEND
THE CONDUITS FROM JUNCTION BOX OR ACCESS BOX TO
THE SPACE ABOVE CEILING.
d. PROVIDE NEW WIRING AND CONDUITS FOR RECEPTACLES UP
TO THE ELECTRICAL PANEL .
e. PROVIDE NEW WIRING AND CONDUIT FOR DATA &
TELEPHONE OUTLETS UP TO THE IT RACK LOCATED IN
SERVER CLOSET.
f. RUN HDMI CABLE AND USB CABLE FROM FLOOR BOX TO
WALL MOUNT TV IN THAT ROOM.
REPLACE EXISTING RECEPTACLES WITH NEW GROUNDING TYPE
RECEPTACLES, UNLESS OTHERWISE SPECIFIED. PROVIDE NEW
WIRING USING EXISTING CONDUIT. PROVIDE NEW CONDUIT, IF
EXISTING IS FOUND DEFICIENT. SUBMIT DEFICIENCY REPORT TO
COR, BEFORE COMMENCING ANY WORK.
PROVIDE NEW ELECTRICAL CONNECTIONS TO NEW MECHANICAL
EQUIPMENT INCLUDING WIRING AND CONDUIT. FOR EXACT
LOCATION, SEE MECHANICAL DRAWINGS.
PROVIDE NEW (2) L5-30 POWER RECEPTACLES FOR IT RACK. FEED
RECEPTACLES FROM SEPARATE DEDICATED POWER CIRCUITS,
INTO A SINGLE JUNCTION BOX.
01 01
03 03
03 03
LEGENDSLEGENDS
S
BASEMENT
STORAGE
EXIT
STAIR
MS
Y
Z
Y
18' - 5" 18' - 4"
18' - 5"
18' - 5" 18' - 5"
16' - 8 1/2"
18' - 5 1/2"
18' - 5 1/2"
28' - 0"
18' - 4"
S
S3
S
S3
S
S
S3S
S
KITCHEN
TOILET
OPEN
OFFICE
RECEPTION
OFFICE
VESTIBULE
ACCESS
STAIR
SERVER
CLO
O S
MS
M S
MS
SO
S
S3
S3S F
F F
A
Z
A
AA XA
A A
Y
Y
Z
Z
Y Y
MLA-13
S
S
S3
S
TOILET
HALL
OFFICE
CONF
ROOM
OFFICE
CLOSET
204A
SAFE
CLO
203A
MS
M S
MS
MS
MS
S
SD SD
S
S
A A
A
A Y
A
AA
A
A
A A
Y
X Y
Y A A
AA
EXISTING
DEMOLITION
NEW WORK
SINGLE POLE TOGGLE SWITCH
THREE WAY TOGGLE SWITCH
LIGHT SWITCH WITH BUILT-IN OCCUPANCY SENSOR
OCCUPANCY SENSOR
MOTION SENSOR
S
S3
SOS
OS
MS
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
NEW WORK BASEMENT LEVEL - LIGHTING PLAN1 SCALE : 1/4" = 1'-0"
0 2' 4' 8' 12'
SCALE : 1/4" = 1'-0"
ADMINISTRATION BUILDING
NEW WORK -
LIGHTING PLAN
EN-102
NEW WORK GROUND LEVEL - LIGHTING PLAN2 SCALE : 1/4" = 1'-0"
NEW WORK SECOND LEVEL - LIGHTING PLAN3 SCALE : 1/4" = 1'-0"
KEY NOTES
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND
GENERAL NOTES, SEE DRAWING E-001.
2. FOR ELECTRICAL POWER RISER DIAGRAM AND SCHEDULES,
SEE DRAWINGS EN-121 AND EN-131.
GENERAL NOTES
01 PROVIDE NEW LIGHTING FIXTURES, SWITCHES, WIRING AND
CONDUIT AS INDICATED. CONNECT TO EXISTING LIGHTING
POWER CIRCUIT FEEDING EXISTING LIGHTING, PRIOR TO
DEMOLITION. REFER ARCHITECTURAL DRAWINGS FOR EXACT
LOCATION OF LIGHTING FIXTURES.
PROVIDE EXIT AND EMERGENCY LIGHTING FIXTURES WITH
MINIMUM 90 MINUTE BATTERY BACKUP. CONNECT
EMERGENCY LIGHTING FIXTURES AHEAD OF SWITCH.
PROVIDE NEW OUTDOOR LIGHTING FIXTURES WITH BUILT-IN
PHOTOCELL FEATURE. MOUNT NEW LIGHTING FIXTURE AT
SIMILAR HEIGHT AS EXISTING LIGHTING FIXTURE. EXTERIOR
CONDUIT SHALL BE MOUNTED AT THE SAME HEIGHT AS THE
LIGHTING FIXTURE. PROVIDE NECESSARY WIRING AND
CONNECTIONS WITH LIGHT SWITCH AND FIXTURES. THE
INTENT IS TO KEEP THE LIGHT SWITCH ALWAYS 'ON' TO
ALLOW THE SERIES CONNECTED PHOTOCELL TO PERFORM
SWITCHING ACCORDING TO AMBIENT LIGHT. LIGHT SWITCH
TO BE USED TO OVERRIDE THE PHOTOCELL, WHEN REQUIRED.
01 02
01 02
01 02
01 (TYP.)
01 02
02 01
01 02
(TYP.)
01 02
01 02
01 02 01
01 02
(TYP.)
LEGENDSLEGENDS
G
TW
G
TW
GROUNDING
TEST WELL
A E-003
GROUND ROD
(TYP)
GROUNDING
TEST WELL
G
G
SCALE: 1/4" = 1'-0"
LIGHTNING PROTECTION - NEW WORK
RUN DOWN CONDUCTOR DOWN AND
BOND TO BUILDING GROUND ROD. (TYP.)
RUN DOWN CONDUCTOR IN RIGID
CONDUIT 8' FROM GROUND UP AND
EXPOSED, MOUNTED ON WALL.
LIGHTNING
CONDUCTOR
AIR TERMINAL (TYP)
A
C E-003
LIGHTNING CONDUCTOR
RUN ALONG ROOF,
FASTENED EVERY
3 FEET MAX.
AA
VENT PIPE
(TYP)
BONDING PLATE
(TYP)
E E-003
B E-003
"T" JOINT
CONNECTION
(TYP.)
ATS
(EXTERIOR WALL)
PANEL MLA
(EXTERIOR WALL)
TELECOMMUNICATION BOX
(EXTERIOR WALL)
GROUNDING GRID
CONDUCTOR (TYP)
GROUNDING CONDUCTOR
LIGHTNING CONDUCTOR
GROUND ROD
GROUNDING TEST WELL
AIR TERMINAL
G
TW
A
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set 0 2' 4' 8' 12'
SCALE : 1/4" = 1'-0"
ADMINISTRATION BUILDING
NEW WORK -
LIGHTNING PROTECTION PLAN
EN-103
1. FOR LIGHTNING PROTECTION GENERAL NOTES, SEE DRAWING
E-003.
LEGENDS
GENERAL NOTES
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND GENERAL
NOTES, SEE DRAWING E-001.
01 EXISTING ELECTRICAL EQUIPMENT TO REMAIN IN-PLACE. PROTECT
DURING CONSTRUCTION.
SCALE: NONE
POWER RISER DIAGRAM - EXISTING
KEY NOTES
GENERAL NOTES
EX UTILITY POLE
EX POLE MOUNTED
UTILITY
TRANSFORMER
OHE OHE
EXTERIOR WALL OF ADMIN BUILDING
EX METER
200A E
EX ATS CABINET
100A 2P
EX PANEL MLA
240/120V, 3Ø, 4W, 200A MAIN
M
OHE
125A
L
EX GENERATOR
60KW, 75KVA,
120/240V, 3PH
EXTERIOR OF MAINTENANCE BUILDING
200A
MAIN
100A
MAIN
EX PANEL LA
240/120V, 1Ø, 3W, 100A MAIN
BASEMENT
N
EX 3-#3/0 AWG, 2"C
EX 3-#2 AWG,
1 1/4"C
SPECIFIC NOTES FOR RISER DIAGRAM:
1. ALL ELECTRICAL EQUIPMENT SHOWN HERE, IS EXISTING.
2. POWER RISER DIAGRAM FOR EXISTING SYSTEM IS REPRODUCED BASED ON VISUAL, NON-INVASIVE FIELD SURVEY ONLY, WITH LIMITED OR NO ACCESS TO ENCLOSED AND CONCEALED SPACES. FIELD VERIFY THE SYSTEM CONFIGURATION. NOTIFY COR IMMEDIATELY OF ANY DISCREPANCY, AND SEEK DIRECTION BEFORE MAKING ANY MODIFICATIONS.
LEGENDS
NEW WORK
DEMOLITION
EXISTING
ADMINISTRATION BUILDING
POWER RISER DIAGRAM -
EXISTING
EN-121
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
ADMINISTRATION BUILDING
ELECTRICAL SCHEDULES
EN-131
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
KEY NOTES
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND GENERAL
NOTES, SEE DRAWING E-001.
2. FOR ELECTRICAL POWER RISER DIAGRAM, SEE DRAWING EN-121.
GENERAL NOTES
01 PROVIDE NEW CIRCUIT BREAKER, COMPATIBLE WITH EXISTING PANEL AT
AVAILABLE SPACE TO FEED THE NEW LOAD AS INDICATED.
AFTER DEMOLITION OF EXISTING LOADS, USE EXISTING AVAILABLE SPARE
CIRCUIT BREAKER TO FEED NEW LOAD AS SHOWN.
PANEL B
EMERGENCY SHUT
OFF & ALARM PANEL
FOR FUEL PUMPS
ELECTRIC METER
FIRE ALARM
CONTROL DEVICE
ATS
PANEL A
ECB FOR PANEL B
DSW - H
FOR FUEL PUMPS
DSW - L
FOR TRANSFORMER
TRANSFORMER
STORAGE
GARAGE
STORAGE
STORAGE
GARAGE
HALL
SHOWER
JAN
CLO
MALE
RESTROOM
FEMALE
RESTROOM
STORAGE
106A
CLOSET
102A
CLOSET
101A
PANEL
FOR AHU
EXISTING
DEMOLITION
NEW WORK
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH GFCI PROTECTION
IN WEATHERPROOF ENCLOSURE
QUADRUPLE RECEPTACLE
SPECIAL TYPE RECEPTACLE
FLOOR BOX
DISCONNECT SWITCH
AV
Wp
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid SetEXIST/DEMO GROUND LEVEL - POWER PLAN1 SCALE : 1/4" = 1'-0" 0 2' 4' 8' 12'
SCALE : 1/4" = 1'-0"
MAINTENANCE BUILDING
EXIST/DEMO -
POWER PLAN
ED-201
KEY NOTES
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND
GENERAL NOTES, SEE DRAWING E-001.
2. FOR ELECTRICAL POWER RISER DIAGRAM AND SCHEDULES,
SEE DRAWINGS EN-121 AND EN-231.
GENERAL NOTES
01 EXISTING ELECTRICAL EQUIPMENT TO REMAIN-IN PLACE.
PROTECT DURING CONSTRUCTION.
DISCONNECT AND REMOVE EXISTING ELECTRICAL PANEL.
PROTECT ALL EXISTING BRANCH WIRING AND CONDUIT FOR
RE-USE. FOR MORE DETAILS, SEE POWER RISER DIAGRAM,
DRAWING EP-221.
DISCONNECT AND REMOVE EXISTING RECEPTACLE INCLUDING
WIRING AND CONDUIT.
EXISTING RECEPTACLE TO REMAIN-IN PLACE. PROTECT
DURING CONSTRUCTION.
DISCONNECT AND REMOVE ALL EXISTING FIRE ALARM DEVICE
INCLUDING WIRING AND CONDUIT.
DISCONNECT AND REMOVE EXISTING ELECTRICAL
CONNECTION TO MECHANICAL EQUIPMENT INCLUDING
WIRING AND CONDUIT. PULL WIRING BACK TO SOURCE AND
DISPOSE OFF.
04 04 04
LEGENDSLEGENDS
S
SS
SS
S
S
S
S
S
S
S
SS
SS S
SSSS
MS
MS
M S
MS
STORAGE
GARAGE
STORAGE
STORAGE
GARAGE
HALL
SHOWER
JAN
CLO
MALE
RESTROOM
FEMALE
RESTROOM
STORAGE
106A
CLOSET
102A
CLOSET
101A
EXISTING
DEMOLITION
NEW WORK
SINGLE POLE TOGGLE SWITCH
THREE WAY TOGGLE SWITCH
LIGHT SWITCH WITH BUILT-IN OCCUPANCY SENSOR
OCCUPANCY SENSOR
MOTION SENSOR
S
S3
SOS
OS
MS
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid SetEXIST/DEMO GROUND LEVEL - LIGHTING PLAN1 SCALE : 1/4" = 1'-0" 0 2' 4' 8' 12'
SCALE : 1/4" = 1'-0"
MAINTENANCE BUILDING
EXIST/DEMO -
LIGHTING PLAN
ED-202
KEY NOTES
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND
GENERAL NOTES, SEE DRAWING E-001.
2. FOR ELECTRICAL POWER RISER DIAGRAM AND SCHEDULES,
SEE DRAWINGS EN-121 AND EN-231.
GENERAL NOTES
01 DISCONNECT AND REMOVE EXISTING INTERIOR LIGHTING
FIXTURE, SWITCH AND MOTION SENSOR INCLUDING WIRING
AND CONDUIT BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING EXTERIOR LIGHTING
FIXTURE INCLUDING WIRING AND CONDUIT BACK TO
SOURCE.
(TYP.)
(TYP.) 01
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
LEGENDSLEGENDS
NEW
PANEL B
EMERGENCY SHUT
OFF & ALARM PANEL
FOR FUEL PUMPS
EX ELECTRIC METER
EX ATS
NEW PANEL A
EX ENCLOSED CIRCUIT
BREAKER
EX DSW FOR FUEL
PUMPS
EX DSW FOR
TRANSFORMER
EX TRANSFORMER
MECH
GARAGE
STORAGE
STORAGE
GARAGE
HALL
OFFICE
105 JAN
CLO
MALE
RESTROOM
FEMALE
RESTROOM
+48"
+48"
Wp
Wp Wp
Wp
Wp
Wp
Wp
Wp Wp
A-5
A-12 A-6
B-4
B-13
B-6
B-2
ERV-1
PTAC-1
HP-1
NEW 240V/60A/2P/
NEMA 3R DSW
NEW 240V/30A/2P/
NEMA 1 DSW NEW 240V/30A/2P/
NEMA 1 DSW
B-21,23B-17,19
B-8,10
EXISTING
DEMOLITION
NEW WORK
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE WITH GFCI PROTECTION
DUPLEX RECEPTACLE WITH GFCI PROTECTION
IN WEATHERPROOF ENCLOSURE
QUADRUPLE RECEPTACLE
SPECIAL TYPE RECEPTACLE
FLOOR BOX
DISCONNECT SWITCH
AV
Wp
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid SetNEW WORK GROUND LEVEL - POWER PLAN1 SCALE : 1/4" = 1'-0" 0 2' 4' 8' 12'
SCALE : 1/4" = 1'-0"
MAINTENANCE BUILDING
NEW WORK -
POWER PLAN
EN-201
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND
GENERAL NOTES, SEE DRAWING E-001.
2. FOR ELECTRICAL POWER RISER DIAGRAM AND SCHEDULES, SEE
DRAWINGS EN-121 AND EN-231.
GENERAL NOTES
KEY NOTES
01 PROVIDE NEW ELECTRICAL PANEL INCLUDING WIRING AND
CONDUIT AS SHOWN. RECONNECT EXISTING BRANCH CIRCUITS
NEW PANEL. FOR MORE DETAILS, SEE POWER RISER DIAGRAM,
DRAWING EP-221.
PROVIDE NEW RECEPTACLES INCLUDING WIRING AND CONDUIT
AS INDICATED. FOR EXTERIOR RECEPTACLES, EXTERIOR CONDUIT
SHALL BE MOUNTED AT THE SAME HEIGHT AS THE RECEPTACLES.
PROVIDE NEW ELECTRICAL CONNECTIONS TO NEW MECHANICAL
EQUIPMENT INCLUDING WIRING AND CONDUIT. FOR EXACT
LOCATION, SEE MECHANICAL DRAWINGS.
LEGENDSLEGENDS
MECH
GARAGE
STORAGE
STORAGE
GARAGE
HALL
OFFICE
JAN
CLO
MALE
RESTROOM
FEMALE
RESTROOM
S
G
F
F
B B
BEB
CE C CE
C
A1
A1
CE
C
Z
A2E
XX
X X
X
Y
A-8
S3
S3
S3
S
B-12
A-25
SSS
A-14
SOS
S3
S3
B-18
SOS SOS
B-16
SS3 S
S 3
X
X X
A1 A1 A1
A1A1E
A1E
A1E
A1E
A2
A2A2
A2
A2
A2 A2A2
A2A2 A2
A2 A2A2
A2A2A2
A2E
A2E A2E
A2E
A2E
A2E
A2E
EXISTING
DEMOLITION
NEW WORK
SINGLE POLE TOGGLE SWITCH
THREE WAY TOGGLE SWITCH
LIGHT SWITCH WITH BUILT-IN OCCUPANCY SENSOR
OCCUPANCY SENSOR
MOTION SENSOR
S
S3
SOS
OS
MS
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid SetNEW WORK GROUND LEVEL - LIGHTING PLAN1 SCALE : 1/4" = 1'-0" 0 2' 4' 8' 12'
SCALE : 1/4" = 1'-0"
MAINTENANCE BUILDING
NEW WORK -
LIGHTING PLAN
EN-202
KEY NOTES
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND
GENERAL NOTES, SEE DRAWING E-001.
2. FOR ELECTRICAL POWER RISER DIAGRAM AND SCHEDULES, SEE
DRAWINGS EN-121 AND EN-231.
GENERAL NOTES
01 PROVIDE NEW LIGHTING FIXTURE, SWITCH, OCCUPANCY
SENSOR, WIRING AND CONDUIT AS INDICATED. REFER
ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF
LIGHTING FIXTURES.
PROVIDE EXIT AND EMERGENCY LIGHTING FIXTURE WITH
MINIMUM 90 MINUTE BATTERY BACKUP. CONNECT
EMERGENCY AND EXIT LIGHTING FIXTURES AHEAD OF
SWITCH.
PROVIDE NEW OUTDOOR LIGHTING FIXTURE WITH BUILT-IN
PHOTOCELL FEATURE. MOUNT NEW LIGHTING FIXTURE AT
SIMILAR HEIGHT AS EXISTING LIGHTING FIXTURE. PROVIDE
NECESSARY WIRING AND CONNECTIONS WITH LIGHT SWITCH
AND FIXTURES. THE INTENT IS TO KEEP THE LIGHT SWITCH
ALWAYS 'ON' TO ALLOW THE SERIES CONNECTED PHOTOCELL
TO PERFORM SWITCHING ACCORDING TO AMBIENT LIGHT.
LIGHT SWITCH TO BE USED TO OVERRIDE THE PHOTOCELL,
WHEN REQUIRED.
(TYP.)
01 02
(TYP.)
01 02
01 02
(TYP.)
01 02 01 02
(TYP.)
(TYP.)
(TYP.)
02 02
01 02
LEGENDSLEGENDS
SCALE: 1/4" = 1'-0"
LIGHTNING PROTECTION - NEW WORK
G
G
G
G
GG
G
GG
G
G
G
G
GG
TW
TW
TW
TW
GROUND ROD
(TYP)
B E-003
GROUNDING
TEST WELL
A E-003
GROUNDING GRID
CONDUCTOR (TYP)
GROUNDING GRID
CONDUCTOR (TYP)
RUN DOWN CONDUCTOR DOWN AND
BOND TO BUILDING GROUND ROD. (TYP.)
RUN DOWN CONDUCTOR IN RIGID
CONDUIT 8' FROM GROUND UP AND
EXPOSED, MOUNTED ON WALL.
A
A
A
A A A
A A
AA
AIR TERMINAL (TYP)
C E-003
AIR TERMINAL (TYP)
C E-003
"T" JOINT
CONNECTION
(TYP.)
E E-003
LIGHTNING CONDUCTOR
RUN ALONG ROOF,
FASTENED EVERY
3 FEET MAX.
(TYP.)
LIGHTNING CONDUCTOR
RUN ALONG ROOF,
FASTENED EVERY
3 FEET MAX.
(TYP.)
LIGHTNING CONDUCTOR
RUN ALONG ROOF,
FASTENED EVERY
3 FEET MAX.
(TYP.)
LIGHTNING CONDUCTOR
RUN ALONG ROOF,
FASTENED EVERY
3 FEET MAX.
(TYP.)
BONDING PLATE
(TYP)
VENT PIPE
(TYP)
FIELD VERIFY
EXACT LOCATION.
BONDING PLATE
(TYP)
ATS
(INSIDE THE BUILDING)
GROUNDING CONDUCTOR
LIGHTNING CONDUCTOR
GROUND ROD
GROUNDING TEST WELL
AIR TERMINAL
G
TW
A
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set 0 2' 4' 8' 12'
SCALE : 1/4" = 1'-0"
MAINTENANCE BUILDING
NEW WORK -
LIGHTNING PROTECTION PLAN
EN-203
GENERAL NOTES
1. FOR LIGHTNING PROTECTION GENERAL NOTES, SEE DRAWING
E-003.
LEGENDS
LEGENDS
01 EXISTING ELECTRICAL EQUIPMENT TO REMAIN IN-PLACE.
DISCONNECT AND REMOVE EXISTING ELECTRICAL PANEL AS SHOWN.
a. EXISTING INCOMING AND BRANCH WIRING INCLUDING CONDUIT
TO REMAIN IN-PLACE. PROTECT DURING CONSTRUCTION.
b. COORDINATE WITH UTILITY COMPANY AND FACILITY MANAGER
FOR ANY POWER OUTAGE.
PROVIDE NEW ELECTRICAL PANEL, RATINGS AS SHOWN. RECONNECT
EXISTING INCOMING AND BRANCH WIRING TO NEW PANEL.
NEW WORK
DEMOLITION
EXISTING
KEY NOTES
GENERAL NOTES
UTILITY POLE
POLE MOUNTED
UTILITY
TRANSFORMER
OHE OHE
EXTERIOR OF MAINTENANCE BUILDING
SCALE: NONE
MAINTENANCE BUILDING - POWER RISER DIAGRAM - EXISTING AND DEMOLITION
UTILITY POLE
METER
GARAGE - MAINTENANCE BUILDING
400A E
ATS CABINET
175A
MAIN
4-#3/0 AWG
PANEL A
240/120V, 3Ø, 4W, 175A MAIN
JB
3-#3/0
200A
M
OHE OHE
200A
L
3-#3/0 AWG
ENCLOSED
CIRCUIT
BREAKER
(ECB) FOR
PANEL B
240/120V, 1Ø, 3W, 200A
DISCONNECT
SWITCH
(DSW) - L
240/120V, 3Ø, 4W, 200A
75KVA STEP-UP
TRANSFORMER
240V - 480V
DISCONNECT
SWITCH
(DSW) - H
600V, 3Ø, 4W, 100A
TO FUEL PUMPS
200A
MAIN
PANEL B
240/120V, 1Ø, 3W, 200A MAIN
CORRIDOR(OUTSIDE OF MEN'S RESTROOM)
- MAINTENANCE BUILDING
3-#3/0
4-350MCM
3-#3/0 AWG, #1/0 NEUTRAL
3-#3/0 AWG
GENERATOR
60KW, 75KVA,
120/240V, 3PH
OHE OHE OHE OHE
N
SCALE: NONE
MAINTENANCE BUILDING - POWER RISER DIAGRAM - EXISTING AND NEW WORK
SPECIFIC NOTES FOR RISER DIAGRAM:
1. POWER RISER DIAGRAM FOR EXISTING SYSTEM IS REPRODUCED BASED ON VISUAL, NON-INVASIVE FIELD SURVEY ONLY, WITH LIMITED OR NO ACCESS TO ENCLOSED AND CONCEALED SPACES. CONTRACTOR TO FIELD VERIFY THE SYSTEM CONFIGURATION. NOTIFY COR IMMEDIATELY OF ANY DISCREPANCY, AND SEEK DIRECTIONS BEFORE MAKING ANY MODIFICATIONS.
UTILITY POLE
POLE MOUNTED
UTILITY
TRANSFORMER
OHE OHE
EXTERIOR OF MAINTENANCE BUILDING
UTILITY POLE
METER
GARAGE - MAINTENANCE BUILDING
400A E
ATS CABINET
175A
MAIN
4-#3/0 AWG
NEW
PANEL A
208/120V, 3Ø, 4W, 175A MAIN
200A BUS,
NEMA 12,
22KAIC
JB
3-#3/0
200A
M
OHE OHE
200A
L
3-#3/0 AWG
ENCLOSED
CIRCUIT
BREAKER
(ECB) FOR
PANEL B
240/120V, 1Ø, 3W, 200A
DISCONNECT
SWITCH
(DSW) - L
240/120V, 3Ø, 4W, 200A
75KVA STEP-UP
TRANSFORMER
240V - 480V
DISCONNECT
SWITCH
(DSW) - H
600V, 3Ø, 4W, 100A
TO FUEL PUMPS
200A
MAIN
NEW
PANEL B
240/120V, 1Ø, 3W, 200A MAIN,
200A BUS,
NEMA 12,
22KAIC
CORRIDOR(OUTSIDE OF MEN'S RESTROOM)
- MAINTENANCE BUILDING
3-#3/0
4-350MCM
3-#3/0 AWG, #1/0 NEUTRAL
3-#3/0 AWG
GENERATOR
60KW, 75KVA,
120/240V, 3PH
OHE OHE OHE OHE
N
MAINTENANCE BUILDING
POWER RISER DIAGRAM -
EXIST/DEMO AND NEW WORK
EN-221
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
MAINTENANCE BUILDING
ELECTRICAL SCHEDULES
EN-231
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
KEY NOTES
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND GENERAL
NOTES, SEE DRAWING E-001.
2. FOR POWER RISER DIAGRAM, SEE DRAWING EN-221.
GENERAL NOTES
01 PROVIDE NEW ELECTRICAL PANEL, RATINGS AS SHOWN.
J K
K
J
C8
C8 C8
C8
C7
C7
J
J K
TPF TPF
TP
F
TPF TPF TPF TPF TPF
TPF
ELECTRICAL SITE PLAN
EXISTING AND DEMOLITION
ES-101
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set 0 5' 10' 20' 30'
ELECTRICAL PARTIAL SITE PLAN - EXISTING AND DEMOLITION1 SCALE : 1" = 10'-0"
KEY NOTES
01 RELOCATE EXISTING GATE OPENER AS SHOWN ON LS-x PLANS.
DISCONNECT AND REMOVE EXISTING POWER FEED TO GATE
OPENER. PULL WIRING BACK TO SOURCE AND DISPOSE OFF.
DEMOLISH ALL EXPOSED CONDUITS. CUT UNDERGROUND
CONDUITS, CAP AND ABANDON IN-PLACE.
RELOCATE EXISTING WELL MAIN CONTROL PANEL AS SHOWN
ON NEW WORK SITE PLAN, INCLUDING ELECTRICAL PANEL,
TRANSFORMER, DISCONNECT SWITCH, LIGHTING, SWITCH
AND RECEPTACLES, LOCATED ON BACK SIDE OF CONTROL
PANEL.
a. TAKE PHOTOGRAPH AND DOCUMENT EXISTING WIRING
AND CONNECTIONS TO ALL EQUIPMENT PRIOR TO
DEMOLITION WORK.
b. PROVIDE SUBMITTAL FOR EXISTING CONDITION
SHOWING WIRING CONNECTIONS TO ALL EQUIPMENT
TO COR FOR REVIEW AND APPROVAL PRIOR TO
DEMOLITION WORK.
c. FOR MORE DETAILS, SEE IRRIGATION SYSTEM
DRAWINGS.
MODIFY EXISTING UNDERGROUND ELECTRICAL POWER FEED
TO RECOATED MAIN WELL CONTROL PANEL AS SHOWN ON
NEW SITE WORK PLAN. PULL WIRING BACK TO NEW HAND
HOLE(HH1) AS SHOWN ON NEW SITE PLAN.
MODIFY EXISTING UNDERGROUND ELECTRICAL POWER FEED
TO WELL PUMP#2 AND #3 AS SHOWN ON NEW SITE WORK
PLAN. PULL WIRING BACK TO NEW HAND HOLE(HH1) AND
PROTECT FOR RE-USE AS SHOWN ON NEW SITE PLAN.
FOR WELL PUMP #2, PERFORM FOLLOWING:
a. PULL IRRIGATION COMMUNICATION WIRING BACK TO
SOURCE AND DISPOSE OFF.
b. DEMOLISH ALL EXPOSED CONDUITS. CUT
UNDERGROUND CONDUITS, CAP AND ABANDON
IN-PLACE.
FOR WELL PUMP #3, PERFORM FOLLOWING:
a. MODIFY EXISTING UNDERGROUND IRRIGATION
COMMUNICATION CONDUIT AS SHOWN ON NEW SITE
WORK PLAN. PULL WIRING BACK TO SOURCE AND
DISPOSE OFF.
b. FOR MORE DETAILS, SEE IRRIGATION DRAWING.
1. FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, LEGENDS AND
GENERAL NOTES, SEE DRAWING E-001.
2. FOR MORE DETAILS FOR IRRIGATION CONTROL SYSTEM, SEE
IRRIGATION DRAWINGS.
3. FIELD VERIFY THE EXISTING ROUTING OF UNDERGROUND
CONDUITS BEFORE COMMENCING ANY NEW UNDERGROUND
WORK. PROTECT EXISTING STORM, SEWER AND WATER LINES.
4. REFER TO TP-XX PLANS AND SPECIFICATION 015639 FOR WORK
ADJACENT TO OR INSIDE THE TREE PROTECTION FENCES/ZONES.
GENERAL NOTES
EXISTING GATE
OPENER
EXISTING MAIN
ELECTRICAL SERVICE
TO MAINTENANCE
BUILDING
MAINTENANCE BUILDING
(3) UNDERGROUND
ELECTRICAL POWER
CONDUITS TO PANEL C
EXISTING WELL PUMP
#1, #2 AND #3
EXISTING WELL MAIN
CONTROL PANEL
PANEL W02
EXISTING
WELL PUMP #2
EXISTING
WELL PUMP #3
(1) UNDERGROUND
ELECTRICAL POWER
CONDUIT TO EXISTING
WELL PUMP #1
(2) UNDERGROUND
ELECTRICAL POWER
CONDUITS TO
EXISTING WELL PUMP
#2 AND #3
(2) UNDERGROUND
IRRIGATION
COMMUNICATION
CONDUITS FROM
WELL MAIN CONTROL
PANEL TO EXISTING
WELL PUMP #2 AND #3
(1) UNDERGROUND
ELECTRICAL POWER
CONDUIT TO EXISTING
WELL PUMP #3
(1) UNDERGROUND
IRRIGATION
COMMUNICATION
CONDUIT FROM
WELL MAIN CONTROL
PANEL TO EXISTING
WELL PUMP #3
EXISTING
WELL PUMP #1
TREE
PROTECTION FENCE
LEGENDS
EXISTING UNDERGROUND CONDUITS
TREE PROTECTION FENCE
J K
K
J
C8
C8 C8
C8
C7
C7
J
J K
TPF TPF
TP
F
TPF TPF TPF TPF TPF
TPF
ELECTRICAL SITE PLAN
EXISTING AND NEW WORK
ES-102
KEY
NOT TO SCALE
Project Title
Checked
Dwg.
2 7
B C
D E
Drawing Title
Approved:
Location
5 8
A
© COPYRIGHT 2023, Walker Federal Services, LLC
Approved:
Drawn
Date
Project No.
DRAWING NO.
Of
1 4 6 9
A F
NATIONAL
CEMETERY
ADMINISTRATION
Revisions Date
Building Number
1 2 4 6 7 8 9
B C
D E
F
Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701
WFS
CEMETERY EXPANSION
BEAUFORT NATIONAL CEMETERY
831CM3016
UB, HU NS
March 8, 2024
Bid Set
ELECTRICAL PARTIAL SITE PLAN - EXISTING AND NEW WORK1 SCALE : 1" = 10'-0"
KEY NOTES
01 RELOCATED EXISTING GATE OPENER. PROVIDE NEW WIRING AND
CONDUIT FROM PANEL W TO THIS RELOCATED GATE OPENER.
FOR PANEL SCHEDULE, SEE DRAWING ES-103.
NEW GATE OPENER. PROVIDE NEW WIRING AND CONDUIT FROM
PANEL W TO THIS GATE OPENER. COORDINATE WITH
MANUFACTURER FOR EXACT WIRING AND CONNECTIONS. FOR
PANEL SCHEDULE, SEE DRAWING ES-103.
RELOCATE EXISTING MAIN WELL CONTROL PANEL INCLUDING
ELECTRICAL PANEL, TRANSFORMER, DISCONNECT SWITCH,
LIGHTING, SWITCH AND RECEPTACLES. FOR MORE DETAILS, SEE
IRRIGATION SYSTEM DRAWINGS.
a. PROVIDE NEW HAND HOLE (HH1), SIZE AS REQUIRED TO
INTERCEPT EXISTING POWER FEED TO MAIN CONTROL
PANEL AND OTHER WELL PUMPS.
b. SPLICE NEW POWER WIRING (4-#4AWG, #8G) WITH
EXISTING IN NEW HANDHOLE (HH1) AND EXTEND UPTO
THE NEW LOCATION OF WELL CONTROL PANEL IN NEW
UNDERGROUND CONDUIT.
c. AFTER GETTING APPROVAL FROM COR FOR EXISTING
CONDITION SUBMITTAL, REWIRE ALL ELECTRICAL AND
CONTROL EQUIPMENT INCLUDING TRANSFORMER, PANEL,
DISCONNECT SWITCH, ETC. AS IT WAS WIRED BEFORE.
d. PROVIDE NEW UNDERGROUND CONDUIT FOR IRRIGATION
COMMUNICATION WIRE FROM WELL CONTROL PANEL TO
EXISTING WELL PUMP#1.
e. PROVIDE GROUNDING AND LIGHTNING PROTECTION AS
PER DETAILS SHOWN ON IRRIGATION DRAWINGS.
FOR WELL PUMP #2, PERFORM FOLLOWING:
a. SPLICE NEW POWER WIRING (4-#3AWG, #6G) WITH
EXISTING IN NEW HANDHOLE (HH1) AND EXTEND UPTO
THE EXISTING WELL PUMP #2 IN NEW AND EXISTING
CONDUITS AS SHOWN ON SITE PLAN.
b. PROVIDE NEW IRRIGATION COMMUNICATION WIRING IN
NEW UNDERGROUND CONDUIT FROM MAIN WELL
CONTROL PANEL TO EXISTING WELL PUMP #2.
c. FOR MORE DETAILS,…