This file package relates to a federal construction contract opportunity. The solicitation seeks bids for renovations, improvements, and repairs at the Long Island National Cemetery in Farmingdale, New York under project number 815CM3041. Key work includes renovations and upgrades to buildings, facilities, grounds, and infrastructure with an estimated value over $5 million. Bids are due by September 15, 2024 and the contract is expected to be awarded by October 31, 2024. The opportunity is designated for small businesses under NAICS code 238210 - Electrical Contractors and Other Wiring Installation Contractors and is being conducted by the Department of Veterans Affairs National Cemetery Administration.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

K

( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS MAY NOT APPEAR ON THIS SET OF DRAWINGS. )ELECTRICAL SYMBOLS

ABOVE FINISHED FLOOR TO CENTERLINE OF DEVICE.

EMPTY CONDUIT.

JUNCTION BOX SIZED PER NEC.

NATIONAL ELECTRICAL CODE

NIGHT LIGHTING, 24 HOUR, OPERATION. WIRE AHEAD OF ALL LOCAL SWITCHES.

ON CENTER.

TELEPHONE TERMINAL BOARD.

DIMENSION INDICATES HEIGHT, AFF, AT WHICH DEVICE IS TO BE MOUNTED.

HEADWALL. SEE PLAN FOR NUMBER.

POWER COLUMN. SEE PLAN FOR NUMBER.

SURGE PROTECTIVE DEVICE

VARIABLE SPEED DRIVE

PNEUMATIC TUBE STATION

SYMBOL LOCATION LEADER

ABBREVIATIONS

AFF

TELEPHONE OUTLET, FLUSH FLOOR MOUNTED.

TELEPHONE OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE.

SECURITY SYSTEM CLOSED CIRCUIT T.V. CAMERA. SUBSCRIPT INDICATES PAN/TILT/ZOOM CONTROL.

SECURITY SYSTEM PUSHBUTTON STATION. SURFACE MOUNTED 48" AFF.

PUBLIC ADDRESS SYSTEM MICROPHONE OUTLET, WALL MOUNTED 18" AFF. COORDINATE TYPE OF

PUBLIC ADDRESS SYSTEM HORN, WALL MOUNTED 7'-6" AFF. UNLESS OTHERWISE INDICATED.

PUBLIC ADDRESS SYSTEM SPEAKER, CEILING MOUNTED.

OUTLET WITH OWNER'S EQUIPMENT.

W = WALL MOUNTED STATION

INTERCOM OUTLET WALL MOUNTED 48" AFF TO TOP OF DEVICE, WITH DESK MOUNTED STATION UNLESS

INTERCOM WALL MOUNTED 18" AFF TO CENTER OF DEVICE, WITH DESK MOUNTED STATION.

MODIFIERS FOR INTERCOM:

S = SUB STATION

M = MASTER STATION

OR 6" FROM BOTTOM OF OUTLET TO COUNTERTOP.

TELEPHONE OUTLET WALL MOUNTED 48" AFF, 2" FROM BOTTOM OF OUTLET TO BACKSPLASH,

PROVIDE FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE. PROVIDE 1 1/4" EMPTY CONDUIT WITH NYLON PULL CORD FROM JUNCTION BOX TO ABOVE ACCESSIBLE CEILING FOR VOICE/DATA WIRING TO

PRE WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT

MODIFIERS FOR VOICE/DATA & TELEPHONE OUTLETS: (DEVICE AND CONDUCTORS BY TELECOM VENDOR) a = VOICE ONLY b = STANDARD (2 DATA / 1 VOICE SPLIT) c = 1 DATA ONLY d = 4 DATA / 1 VOICE SPLIT

COMMUNICATIONS

VOICE/DATA OUTLET, FLUSH FLOOR MOUNTED.

GROUND BAR - 1/8"x1"x12" COPPER BUS IN NEMA 1 ENCLOSURE. LOCATE ABOVE SUSPENDED CEILING.

PUBLIC ADDRESS SYSTEM VOLUME CONTROL SWITCH, WALL MOUNTED 48" AFF.

CONDUIT SLEEVES. SEE PLANS FOR SIZE AND QUANTITY.

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER CABINET, CONNECTED TO NORMAL POWER.

LED LIGHTING FIXTURE, CEILING OR WALL MOUNTED,

POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).

DRAWINGS. SEE SCHEDULE FOR TYPE (*). CONNECT UNSWITCHED.

CEILING OR WALL MOUNTED EXIT SIGN. PROVIDE NUMBER OF FACES AND CHEVRONS AS INDICATED ON

EMERGENCY LIGHTING FIXTURE, CEILING-MOUNTED OR WALL-MOUNTED AT 7'-6" AFF UNLESS NOTED

OTHERWISE. CONNECT UNSWITCHED.

LIGHTING

LED LIGHTING WALLWASH FIXTURE, CEILING MOUNTED.

TRACK LIGHTING FIXTURE. SEE PLANS/SCHEDULE FOR TRACK LENGTH AND NUMBER OF TRACK HEADS.

EQUIPMENT IDENTIFICATION

HORSEPOWER RATING

MOTOR CONNECTION. SPECIAL VOLTAGES AS SHOWN ON DRAWING.

ENCLOSED CIRCUIT BREAKER. NUMERAL INDICATES TRIP AMPERE RATING.

FUSED SAFETY SWITCH. NUMERAL INDICATES FUSE RATING.

NON-FUSIBLE SAFETY SWITCH. NUMERAL INDICATES AMPERE RATING.

SIZE AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.

COMBINATION MOTOR STARTER WITH CIRCUIT BREAKER. TOP NUMERAL INDICATES CIRCUIT BREAKER

MOTOR STARTER. NUMERAL INDICATES NEMA SIZE.

AMPACITY. SEE FEEDER SCHEDULE.

ON RISERS, DESIGNATION DENOTES QUANTITY OF CURRENT CARRYING CONDUCTORS AND FEEDER

WIRING SYSTEM CONCEALED IN OR ABOVE CEILING OR IN WALL.

WIRING SYSTEM BELOW FLOOR OR BELOW GRADE.

DESIGNATION DENOTES PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC., AND OVERCURRENT BRANCH OR FEEDER CIRCUIT HOMERUN TO PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC.

WIRING SYSTEM TURNED UP.

WIRING SYSTEM TURNED DOWN.

WIRING SYSTEM EXPOSED.

PROTECTION DEVICE NUMBER.

DRY TYPE TRANSFORMER.

NEC REQUIRED GROUND.

EF-1, 10 HP.460V, 3∅

208V, 3∅

120V, 1∅

MOTOR RATED SWITCH. AMPS/POLES TO MATCH UPSTREAM BREAKER.

CONNECTION TO WALL MOUNTED FILM ILLUMINATOR. PROVIDE RECEPTACLE IN FLUSH OUTLET BOX AT

LOWER RIGHT HAND CORNER OF UNIT IF SURFACE MOUNTED. HARD WIRE IF RECESSED.

JUNCTION BOX AND CONNECTION TO EQUIPMENT OR TERMINAL STRIPS.

CEILING FAN 120V. MANUFACTURER (HUNTER#21252 GREEN FINISH W/ INTEGRATED 240W LIGHT FIXTURE)

CONNECTION TO HEADWALL UNIT. ONE NORMAL POWER CIRCUIT. ONE CRITICAL POWER CIRCUIT, CONNECTION TO FAN COIL UNIT. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.

AND ONE DEDICATED CRITICAL POWER CIRCUIT FOR VENTILATOR.

CONNECTION TO EXHAUST FAN. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.

PANELBOARD SURFACE MOUNTED.

REMOTE ALARM PANEL FOR ISOLATED POWER PANEL BOARD WALL MOUNTED AT 5'-0" AFF.

GENERATOR REMOTE ALARM ANNUNCIATOR. WALL MOUNTED AT 5'-0" AFF.

N = NORMAL BRANCH

U = UNGROUNDED (ISOLATION) PANEL

Q = EQUIPMENT BRANCH

C = CRITICAL BRANCH

L = LIFE SAFETY BRANCH

M = MOTOR CONTROL CENTER

L = 120/208 VOLT

H = 277/480 VOLT

PANELBOARD FLUSH MOUNTED.

1,2,3 = FLOOR

A,B,C = LOCATION

PANELBOARD NAMING CONVENTION

JUNCTION OR PULL BOX. W = WEATHERPROOF.

CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE.

HARDWIRE CONNECTION FROM FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE AND 3/4" LIQUID TIGHT FLEXIBLE METALLIC WHIP TO PRE-WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT SUPPLIER/INSTALLER. EIGHT(8) WIRE SYSTEM PROVIDES FOUR(4) CIRCUITS.

POWER

SURFACE MOUNTED MULTIOUTLET ASSEMBLY. 48" AFF OR 8" ABOVE COUNTER

TV = TELEVISION, SEE DETAIL.

G = GROUND FAULT CIRCUIT INTERRUPTER.

EWC = ELECTRIC WATER COOLER POWER CONNECTION, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER

P = PEDESTAL

WP = WEATHERPROOF "IN-USE" COVER, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER DEVICE.

DUPLEX RECEPTACLE, MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE

OR 2" ABOVE BACKSPLASH. SHADED AREA INDICATES RECEPTACLE.

DUPLEX RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED.

SIMPLEX RECEPTACLE MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 48" AFF TO TOP OF OUTLET

OR 2" FROM BOTTOM OF OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES

OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES CONNECTED TO THE EMERGENCY

DUPLEX RECEPTACLE, MOUNTED 48" AFF TO TOP OF OUTLET OR 2" FROM BOTTOM OF

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 18" AFF TO CENTER OF DEVICE. SLASH

DUPLEX RECEPTACLE OUTLET. CEILING MOUNTED.

SPECIAL RECEPTACLE OUTLET. NEMA CONFIGURATION AS INDICATED. PROVIDE MATCHING CORD & PLUG AS

NEEDED.

MODIFIERS FOR RECEPTACLES:

SPECIAL RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED. NEMA CONFIGURATION AS INDICATED. PROVIDE

MATCHING CORD & PLUG AS NEEDED.

LH2A-1

CH2A

POWER POLE. DEVICE CONFIGURATION AND COLOR AS INDICATED. PROVIDE POLE HEIGHT AS REQUIRED.

EQUIPMENT CONNECTION DESIGNATION, SEE SCHEDULE FOR DETAILS.

M

RATING AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.

COMBINATION MOTOR STARTER WITH FUSED SWITCH. TOP NUMERAL INDICATES FUSETRON AMPERE

LIGHTNING PROTECTION SYSTEM GROUND ROD.

75KVA T

LIGHTNING PROTECTION SYSTEM AIR TERMINAL.

TR = TAMPER RESISTANT

3 = THREE WAY

MODIFIERS FOR SWITCHES:

SINGLE POLE SWITCH, MOUNTED 48" AFF TO TOP OF DEVICE.

THREE SINGLE POLE SWITCHES IN A 3-GANG BOX, MOUNTED 48" AFF TO TOP OF DEVICE.

PHOTO ELECTRIC CELL MOUNTED ON CONDUIT STUBBED 6" ABOVE ROOF, FACING NORTH.

SWITCHES

TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO TOP OF DEVICE.

PROVIDE DIVIDER FOR DIFFERENT VOLTAGES OR BRANCHES.

4 = FOUR WAY

D = DIMMER

DT = DOUBLE THROW

LV = LOW VOLTAGE

TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO TOP OF DEVICE, TO COMPLY WITH ENERGY CODE. EITHER SWITCH INBOARD AND OUTBOARD LAMPS SEPARATELY OR STEP-DIM BOTH

PROVIDE DIVIDER(S) FOR DIFFERENT VOLTAGES OR BRANCHES.

OS = OCCUPANCY SENSOR

TIME CLOCK. PROVIDE POWER CIRCUIT AND 3/4" CONDUIT TO ACCESSIBLE CEILING SPACE.

a,b,c = MULTIPLE SWITCH LEGS

T = TIMER

INDICATED.

INDICATED. SLASH INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

CONNECTED TO NORMAL POWER. SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT

LUMINAIRE, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED).

SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION AND CEILING TYPE.

LOCATION AND CEILING TYPE. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

SEE SCHEDULE FOR TYPE (*).

SEE SCHEDULE FOR TYPE (*).

REMOTE EMERGENCY EGRESS TWIN-LAMP UNIT.

HALF-SHADED INDICATES CONNECTED TO LIFE SAFETY BRANCH.

LAMPS TO 50%.

NOTED OTHERWISE.

SUPPLIER/INSTALLER.

PTZ

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. SEE SCHEDULE FOR TYPE (*).

POWER SYSTEM.

CONNECTED TO THE EMERGENCY POWER SYSTEM.

LED STRIP LUMINAIRE. CEILING MOUNTED OR SUSPENDED 8'-0" AFF TO BOTTOM OF LUMINAIRE, CONNECTED TO NORMAL POWER. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY

GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

CARD READER. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

ELECTRIC STRIKE. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

REMOTE LINE ISOLATION MONITOR.

CABLE TV OUTLET, MOUNTED ADJACENT TO TV RECEPTACLE, UNLESS NOTED OTHERWISE.

PUSHPAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

EXPEDITOR SYSTEM

WIRELESS TELEMETRY ANTENNA

WIRELESS TELEMETRY DEVICE

EXPEDITER BUTTON PANEL

EXAM LIGHT CONTROLLER

EMERGENCY EGRESS PUSH BUTTON

KEY PAD CARD READER

EMERGENCY RELEASE SWITCH. PROVIDE TAMPER RESISTANT COVER WITH A SOUNDING HORN.

BUTTON RELEASE.

BADGE ACCESS.

NURSE LOCATOR.

EMERGENCY MANUAL OVERRIDE.

DEVICE. INSTALL DEVICE SO IT IS CONCEALED BEHIND ENCLOSURE, COORDINATE WITH PLUMBING.

SHOWN TO CLARIFY THAT DEVICES/LUMINAIRES ON THE SAME CIRCUIT ARE CONTROLLED SEPARATELY.

POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).

4/350

XXXX

ERS

GENERAL PROJECT NOTES

LIM

RA

GA

J

E

C

M

H

F

P

P

S

P

J

SS

SS

ELC

EXIT

KPCR

PP

ES

CR

ES

BR

BA

NL

EMO

SS

V

M

H

GB

PS

C

TC

PE

SS

SSS

SS

S

DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR. PROVIDE ONE POWER PACK FOR EACHOS

SENSOR. COORDINATE WIRING REQUIREMENTS WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.

WIRELESS ACCESS POINTWAP

DEMOLITION NOTES

A.

FIRE ALARM

FIRE ALARM CONTROL PANEL. MOUNT AT 6'-6" AFF TO TOP. PROVIDE SMOKE DETECTOR ABOVE PANEL.FACP

REMAINDER

VOLTS DISTANCE HOMERUN OF CIRCUIT

120/208 0' - 50' #12 #12

50' - 100' #10 #12 100 - 150' #8 #10

REMAINDER

VOLTS DISTANCE HOMERUN OF CIRCUIT

277/480 0' - 125' #12 #12

125' - 220' #10 #12 220 - 330' #8 #10

COMMUNICATIONS

LIGHTNING PROTECTION AIR TERMINAL

PUSH BUTTON DOOR RELEASE WITH SOUNDER COVER.

MAGNETIC LOCK FOR DOOR.

PB

ML

KEY PAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.KP

1. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE WHEN INDICATED IS INTENDED FOR GENERAL

REFERENCE ONLY.

2. ALL OUTAGES SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS' REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND SHALL BE AT THE OWNER'S DISCRETION.

3. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY AND LEGALLY DISPOSED OFF-SITE.

4. ALL FIXED ELECTRICAL EQUIPMENT FURNISHED BY ELECTRICAL CONTRACTOR SHALL BE LISTED AND LABELED BY A U.S. NATIONALLY RECOGNIZED TESTING LABORATORY. FACTORY ASSEMBLED LISTED COMPONENTS SHALL BE LISTED AND LABELED AS AN ASSEMBLY.

ANY ELECTRICAL EQUIPMENT NOT LISTED OR LABELED MUST BE APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION AND HAVE

A THIRD PARTY TESTING LABEL.

5. FIRE ALARM APPLIANCES AND DEVICES SHOWN INDICATE TO PROVIDE COVERAGE IN THAT AREA. ELECTRICAL CONTRACTOR SHALL PROVIDE APPLIANCES AND DEVICES AS REQUIRED BY THE LATEST EDITION OF NFPA 72 AND THE BUILDING CODE. NO CHANGE ORDERS WILL BE ALLOWED FOR APPLIANCES AND DEVICES REQUIRED BY NFPA 72 AND THE BUILDING CODE.

6. COMPLETE EXISTING ELECTRICAL WORK AS INDICATED ON THE PLANS. CONNECTIONS OF FEEDERS AND BRANCH CIRCUITS TO NEW

PANELS SHALL BE DONE TO KEEP DOWNTIME TO AN ABSOLUTE MINIMUM.

7. ALL TERMINATIONS, CONDUCTORS, AND DEVICES SHALL BE 75 DEGREE C RATED.

8. UNLESS NOTED OTHERWISE, ELECTRICAL CONTRACTOR SHALL INSTALL ALL RACEWAY, BOXES, AND CABLES.

9. A MAXIMUM OF THREE 20A, 1 POLE BRANCH CIRCUITS MAY BE COMBINED IN A COMMON HOMERUN SHARING A COMMON NEUTRAL OR WITH SEPARATE NEUTRALS, FOR A TOTAL OF SIX CURRENT CARRYING CONDUCTORS. ALL BRANCH CIRCUITS LARGER THAN 20A SHALL BE

SEPARATELY HOMERUN TO PANEL.

10. CONDUCTORS SHALL BE COPPER, RATED AT NOT LESS THAN 600 VOLTS. MINIMUM SIZE SHALL BE NO. 12 AWG UNLESS OTHERWISE NOTED ON THE DRAWINGS. ALL WIRE #8 AWG AND LARGER SHALL BE STRANDED. #10 THRU #12 AWG CONDUCTORS SHALL BE SOLID. ALL

INSULATION TYPES SHALL BE THWN OR THHN.

11. ELECTRICAL CONTRACTOR SHALL USE MULTI-POLE BREAKERS FOR ALL SHARED NEUTRALS OR PROVIDE SEPARATE NEUTRALS FOR EACH

BRANCH CIRCUIT. ADJUST PANEL SCHEDULES ACCORDINGLY TO MEET NEC 210.4.

12. BRANCH CIRCUIT WIRE SIZING WILL BE IN ACCORDANCE WITH THE FOLLOWING TABLES:

13. ADJUST ELECTRONIC TRIP FUNCTIONS FOR LOW-VOLTAGE CIRCUIT BREAKERS SO AS TO ACHIEVE SELECTIVE COORDINATION.

14. LIGHTING LAYOUTS ARE BASED ON IES STANDARD RECOMMENDED LIGHTING LEVELS. LIGHT LEVELS ARE AFFECTED BY ENVIRONMENTAL CONDITIONS SUCH AS FINISH COLOR, WINDOW TREATMENTS, AND FINAL LUMINAIRE SELECTIONS. FINAL INFORMATION IS NOT ALWAYS ESTABLISHED AT THE TIME OF CALCULATION. DESIGN BASIS LIGHT LEVEL CALCULATIONS FOR SPECIFIC AREAS CAN BE PROVIDED UPON

REQUEST.

15. LEAD PAINT IS FOUND TO EXIST ON EXISTING EXPOSED PAINTED SURFACES. REFER TO ECS HAZARDOUS MATERIALS SURVEY, DATED JULY 28, 2021, PROJECT MANUAL, APPENDIX II, AND SPECIFICATION(S) 02 28 33 - LEAD-BASED PAINT REMOVAL.

16. ASBESTOS CONTAINING MATERIALS FOUND TO EXIST IN EXISTING DIRECTOR LODGE BOILER ROOM CEILING PLASTER. REFER TO ECS HAZARDOUS MATERIALS SURVEY, DATED JULY 28, 2021, PROJECT MANUAL, APPENDIX II, AND SPECIFICATION(S) 02 28 33 - LEAD-BASED

PAINT REMOVAL.

17. ELECTRICAL CONTRACTOR SHALL BE ABLE TO DEMONSTRATE RESTORATION EXPERIENCE PER THE SECRETARY OF THE INTERIOR

HISTORICAL RESTORATION STANDARDS.

USB = RECEPTACLE WITH USB CHARGING PORT.

VOICE/DATA OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE. PROVIDE BACKBOX, COVERPLATE AND 3/4"C WITH PULL CORD FROM OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN CEILING.

VOICE/DATA OUTLET, WALL MOUNTED 48" AFF, 2" FROM BOTTOM OF OUTLET TO BACKSPLASH. PROVIDE BACKBOX, COVERPLATE AND 3/4"C WITH PULL CORD FROM OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN

CEILING.

SMOKE DETECTOR, CEILING MOUNTED.

AFF

EC

J-BOX

NEC

NL

OC

TTB

+60"

HW#

PC#

SPD

VSD

PTS

A. COORDINATE ALL DEMOLITION WORK WITH OWNER PRIOR TO BEGINNING WORK.

B. REMOVE ALL ELECTRICAL DEVICES, WIRING AND RACEWAYS IN WALLS AND CEILINGS BEING DEMOLISHED UNLESS NOTED OTHERWISE. RECONNECT DEVICES AND FIXTURES DOWNSTREAM OF REMOVED WORK.

UNLESS OTHERWISE NOTED, WIRING AND RACEWAYS ARE TO BE REMOVED BACK TO THEIR SOURCE.

C. RELOCATE EXISTING WORK TO REMAIN WHICH INTERFERES WITH RENOVATION.

D. ELECTRICAL DEMOLITION WORK SHALL BE PHASED IN ACCORDANCE WITH PROJECT "GENERAL CONDITIONS". ELECTRICAL CONTRACTOR SHALL DEVELOP A PHASING SCHEME WHICH WILL WORK WITH

THE ARCHITECT'S OVERALL PHASING PLAN AND WITH WORK TO BE DONE BY OTHER TRADES.

E. CONTRACTOR SHALL PROVIDE TEMPORARY POWER WHERE NECESSARY AT NO EXTRA COST TO THE OWNER IN ORDER TO KEEP THE BUILDING IN OPERATION DURING EACH PHASE OF THE RENOVATION.

F. REMOVE EXISTING ELECTRICAL WORK AS INDICATED. TRANSFER OF FEEDERS AND BRANCH CIRCUITS TO NEW PANELS SHALL BE DONE IN A MANNER THAT WILL KEEP DOWNTIME TO AN ABSOLUTE MINIMUM.

G. ALL OUTAGES SHALL BE COORDINATED WITH OWNER AT LEAST 72 HOURS IN ADVANCE. OUTAGES WHICH ARE ANTICIPATED TO LAST LONGER THAN 1 HOUR SHALL BE COORDINATED WITH OWNER AT LEAST 1

WEEK IN ADVANCE.

H. ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL WORK ASSOCIATED WITH WORK INDICATED TO BE REMOVED ON THE ARCHITECTURAL, PLUMBING, MECHANICAL AND FIRE PROTECTION DRAWINGS.

I. ELECTRICAL WORK SHOWN IS BASED ON FIELD OBSERVATIONS AND EXISTING DRAWINGS AND IS

PROVIDED TO CONVEY THE GENERAL SCOPE OF DEMOLITION WORK TO BE ACCOMPLISHED. THE

ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND OBSERVE EXISTING CONDITIONS PRIOR TO

BIDDING.

J. SEE SHEET A-001 FOR ALL HAZARDOUS MATERIALS NOTES FOR THIS PROJECT.

REFER TO FIRE ALARM DRAWING SET FOR FULL LIST OF SYMBOLS AND FIRE ALARM SCOPE OF WORK.

SYMBOLS, LEGENDS, NOTES

AND DRAWING INDEX

E-001

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2021, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION

LONG ISLAND NATIONAL CEMETERY

815CM3041

Final Construction Documents - Issued for Construction

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Project No. 4624

JCE CDH

May 22, 2023

296199

AutoCAD SHX Text

PB

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

AutoCAD SHX Text

CONSULTANTS

10" 1"

.625" 2"

1.125"

3 PLS

.25" DIA

12 PLS

.50" DIA

4 PLS

3.75"

.25"

COMBINATION DUPLEX

RECEPTACLE/USB CHARGER

USB CHARGING PORT

HOSPITAL GRADE 20 AMP

125 VOLT AC DUPLEX

RECEPTACLE

EQUAL TO TD HUBBELL

USB8300 SERIES

USB

TYPICAL TELECOMMUNICATIONS

GROUNDING BAR DETAILS

NOTES:

3. ALL GROUNDING BARS SHALL BE COPPER.

TGB

TELECOMMUNICATIONS GROUNDING LEGEND

ALL CONDUCTORS SHALL BE GREEN INSULATED SOLID COPPER CONDUCTORS.

TELECOMMUNICATIONS GROUND BAR MOUNTED ON BACKBOARD.TGB

SEE DETAIL.

1. TYPICAL BUSBARS, INSULATIONS AND BACKBOARD MOUNT BRACKETS

SHOWN HERE REFLECT TIA STANDARDS-COMPLIANT DIMENSIONS.

2. MOUNT BACKBOARD-MOUNTED BUSBARS AT 6'-6" AFF UNLESS DIRECTED

OTHERWISE BY OWNER.

FEATURES

PATTERN: 180 DEGREES

COVERAGE: UP TO 900 SF

TIME DELAY: ADJUSTABLE 1 TO 30 MINUTES

OPTIONS

CONTROL: MANUAL OFF, DUAL TECHNOLOGY LIGHTING CONTROL

GENERAL DESCRIPTION

HOUSING: MEDIUM IMPACT INJECTION MOLDED ABS

MOUNTING: WALL MOUNT AT 48" AFF TO CENTER OF DEVICE.

ELECTRICAL: 120 OR 277 VOLT

FINISH: MATCH FACILITY'S STANDARDS

NOM. DIMENSIONS: 119 mm X 75 mm (4 11/16" X 2 15/16")

WALL MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR WITH DIMMER SWITCH

CEILING HANGER

WIRE, TYP.

RECESSED

CAN

LUMINAIRE

FIXTURE WHIP FROM JUNCTION

BOX (1829mm (6') LONG MAX)

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING RECOMMENDED MOUNTING HARDWARE

DOWNLIGHT MOUNTING - LAY-IN CEILING

ACOUSTICAL

CEILING TILE

(TYP)

RECESSED CAN

LUMINAIRE

ARCHITECTURAL

CEILING GRID

LUMINAIRE SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION 26 51 00

LUMINAIRE

BAR HANGERS

ARCHITECTURAL

CEILING GRID

WIRE TIE OR SCREW

BAR HANGER TO

ARCHITECTURAL

CEILING GRID TYP.

CEILING HANGER WIRE

ARCHITECTURAL

CEILING GRID

ARCHITECTURAL

CEILING GRID

ACOUSTICAL

CEILING TILE

(TYP)

HANGER WIRE AND

MOUNTING CHANNEL

ATTACHED TO STRUCTURE

REFER TO SPECIFICATION

SECTION 26 51 00

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

JUNCTION BOX

LOCKING

SQUARE

WASHER & NUT

6.35mm (1/4") SCREW

ARCHITECTURAL

CEILING

WIRE TIE THROUGH

MOUNTING CHANNEL &

CROSS BEAM, TYP.

FIXTURE WHIP FROM

JUNCTION BOX (1829mm

(6') LONG MAX)

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

EXIT SIGN MOUNTING - LAY-IN CEILING

GRID

ACOUSTICAL CEILING TILE (TYP)

ARCHITECTURAL

CEILING

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND

USING THE RECOMMENDED MOUNTING HARDWARE.

LUMINAIRE MOUNTING - LAY-IN CEILING

LUMINAIRE

SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION 26 51 00

3 TWIST MINIMUM

(TYP)

FIXTURE WHIP FROM JUNCTION

BOX (1829mm (6') LONG MAX.)

LUMINAIRE. REFER

TO SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE. REFER TO

SPECIFICATION SECTION 26 51 00

CEILING CROSS

BEAM

LUMINAIRE. REFER TO SCHEDULE

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND

USING THE RECOMMENDED MOUNTING HARDWARE.

DOWNLIGHT MOUNTING - GYP. BOARD CEILING

CEILING HANGER

WIRE, TYP.

RECESSED CAN

LUMINAIRE

REFER TO

SCHEDULE.

CEILING MAIN BEAM

GYPSUM

BOARD (TYP)

WIRE TIE OR SCREW

BAR HANGER TO

CROSS BEAM TYP.

LUMINAIRE

BAR HANGERS

LUMINAIRE SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION 26 51 00

CEILING CROSS

BEAM

RECESSED CAN

LUMINAIRE

CEILING BEAM

FIXTURE WHIP FROM JUNCTION

BOX (1829mm (6') LONG MAX)

GRID

IT GROUNDING BAR CABLE LUG DETAIL

A

A

Section A-A

1. RATED WALL OR FLOOR ASSEMBLY - PROVIDE FIRE STOPPING ASSEMBLY FOR

PARTITION TYPE & RATING ENCOUNTERED.

2. THROUGH PENETRATION - PROVIDE FIRE STOPPING ASSEMBLY FOR SIZE &

MATERIAL OF THROUGH PENETRATION UTILIZED.

3. FIRE STOPPING MATERIAL - PROVIDE FIRE STOPPING MATERIAL FOR WALL

ASSEMBLY & THROUGH PENETRATION MATERIAL ENCOUNTERED. FILL VOIDS OR

CAVITY ACCORDING TO THE REQUIREMENTS OF THE FIRE STOPPING SYSTEM

UTILIZED.

ALL RATED WALLS, PARTITIONS OR FLOORS SHALL BE PROVIDED WITH A UL LISTED

FIRE STOP SYSTEM. THE SYSTEM UTILIZED SHALL MATCH THE SEPARATION

PENETRATED AND THE THROUGH PENETRATION MATERIAL.

DETAILS FOR THE INSTALLATION OF SYSTEM TYPE UTILIZED SHALL BE AVAILABLE AT

THE PROJECT SITE FOR THE DURATION OF CONSTRUCTION AND SHALL BE PROVIDED

TO THE AUTHORITY HAVING JURISDICTION AND TO THE BUILDING OWNER AT THE

PROJECT COMPLETION.

PROVIDE WALL OR FLOOR LABELS INDICATING THE SYSTEM MANUFACTURER AND UL

LISTED ASSEMBLY NUMBER AT EACH LOCATION WHERE THE FIRE STOPPING SYSTEM

IS INSTALLED.

THROUGH PENETRATION FIRESTOP SYS.

(PROVIDE UL LISTED SYSTEM)

LUMINAIRE

SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION 26 51 00

3 TWIST MINIMUM

(TYP)

FIXTURE WHIP FROM JUNCTION

BOX (1829mm (6') LONG MAX.)

CEILING MAIN

BEAM

GYPSUM BOARD

(TYP)

LUMINAIRE. REFER

TO SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE. REFER TO

SPECIFICATION SECTION 26 51 00

CEILING CROSS

BEAM

GYPSUM BOARD

CEILING CROSS

BEAM

LUMINAIRE. REFER TO SCHEDULE

DRYWALL

BORDER

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND

USING THE RECOMMENDED MOUNTING HARDWARE.

LUMINAIRE MOUNTING - GYP. BOARD CEILING

DEVICE MOUNTING DETAIL

TOP PLATE

STUDS

JUNCTION BOX ABOVE

CEILING MOUNTED ON

BRACKET, TOP PLATE,

OR BY THREADED

ROD FROM STRUCTURE.

HOMERUN

IN EMT.

EMT

CADDY STRAP.

MOUNT TO

STUDS ON BOTH

SIDES.

SWITCH OR

RECEPTACLE.

FEATURES

PATTERN: 360 DEGREES

COVERAGE: 46-186 SQ M (500-2000SF)

TIME DELAY: ADJUSTABLE 30 SECONDS TO 30 MINUTES

OPTIONS

PROVIDE DUAL RELAY IN SPACES WITH MULTIPLE SWITCHING.

CONTROL: MANUAL OFF, DUAL TECHNOLOGY LIGHTING CONTROL

GENERAL DESCRIPTION

HOUSING: IMPACT RESISTANT INJECTION MOLDED ABS

MOUNTING: CEILING BETWEEN 2440-3050 mm (8'-10') H

ELECTRICAL: 24 VOLT DC (FROM POWER PACK), 120 OR 277

VOLT AC

INPUT

FINISH: MATCH FACILITY'S STANDARDS

NOM. DIMENSIONS: 121 mm X 102 mm (4 3/4" DIA X 4"D)

CEILING MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR

EXIT

12", UNLESS CEILING IS HIGHER

THAN 12'-0", THEN 24" ABOVE DOOR.

CEILING

FLOOR

WALL MOUNTED

TELEPHONE

2" TO

TOP OF

COUNTER OR

BACKSPLASH

18"

RECEPTACLE

LIGHT SWITCH

OR DIMMER

ALIGN WHERE

POSSIBLE

TELEPHONE OR

VOICE DATA OUTLET

TV OUTLET

OR CLOCK

OUTLET

FIRE ALARM DEVICES

" A

BO

VE

F

LO

O R

T O

B O

TT

O

M O

F D

EV

IC

E O

N C

O

LU

M N

S

MOUNTING HEIGHTS OF DEVICES

FOR WALL MOUNTED UNITS:

BOTTOM

OF DEVICE

N O

T

TO

E

XC

EE

D

6"

T O

B O

TT

O

M

GENERAL DETAIL NOTES:

A. PARTICULAR ATTENTION SHALL BE GIVEN TO THE ALIGNMENT OF DEVICES.

WHEREVER DEVICES, ON THIS SHEET OR OTHER SHEETS, ARE SHOWN AT

GIVEN LOCATION WITH DIFFERENT MOUNTING HEIGHTS THEY SHALL BE

ALIGNED VERTICALLY. IF THEY ARE SHOWN AT THE SAME MOUNTING HEIGHT

THEY SHALL BE ALIGNED HORIZONTALLY. REFER TO THE ARCHITECTURAL

PLANS, ELEVATIONS AND DETAILS. COORDINATE WITH ARCHITECT PRIOR TO

ROUGH-IN.

B. ALL DIMENSIONS ARE TO THE CENTER LINE OF DEVICE UNLESS INDICATED

OTHERWISE.

C. MOUNTING HEIGHTS SHOWN HERE ARE TYPICAL. PRIOR TO ROUGH-IN,

COORDINATE WITH ARCHITECTURAL PLANS, ELEVATIONS, AND DETAILS. IF A

CONFLICT OCCURS, REQUEST CLARIFICATION FROM ARCHITECT/ENGINEER

PRIOR TO ROUGH-IN.

6"

NAMEPLATE DETAIL

NORMAL

BRANCH

PANEL 'X'

208Y/120V

ENGRAVED THREE-LAYER LAMINATED

PLASTIC WITH ADHESIVE BACKING

PROVIDE ALL ELECTRICAL DISTRIBUTION EQUIPMENT WITH A NAMEPLATE AS

FOLLOWS: (SWITCHBOARDS, PANELBOARDS, BUSWAYS, DISCONNECTS, AHU,

FANS, FCU, ETC)

1/4" LETTERING

(TYPICAL)

WHITE LETTERS ON BLACK BACKGROUND

WHITE LETTERS ON RED BACKGROUND

WHITE LETTERS ON RED BACKGROUND

WHITE LETTERS ON RED BACKGROUND

NORMAL:

LIFE SAFETY:

CRITICAL:

EQUIPMENT:

3/8" LETTERING

GENERAL DETAIL NOTES:

A. PROVIDE SAMPLE FOR APPROVAL BY ENGINEERS/OWNER.

B. COORDINATE NAMING CONVENTION AND DESCRIPTIONS WITH OWNER.

SOURCE

VOLTAGE

BRANCH

NAME OF

EQUIPMENT

OR LOAD

LOCATION

FED FROM PANEL 'MDP'

LOCATED IN F-WING

4TH FLR ELECTRICAL RM

7FCL-37FCL-1

DEVICE LABELING DETAIL

PROVIDE ALL WIRING DEVICES WITH A SELF-

ADHESIVE METALLIC LABEL WITH BLACK

LETTERING INDICATING PANEL AND CIRCUIT

NUMBER SERVING THE DEVICE. THE LABEL

SHALL MATCH THE CURRENT FACILITY'S

STANDARDS FOR NORMAL AND EMERGENCY

BRANCH CIRCUITS. 1/4 " MINIMUM LETTERING

HEIGHT.

GENERAL DETAIL NOTES:

A. COORDINATE LABELING WITH OWNER PRIOR TO INSTALLATION.

NTS 5

NTS

NTS

NTS

NTS

NTS 9

NTS 8NTS 12

NTS 13

NTS

NTS 15

NTS 17

NTS 1NTS 16

NTS

T

N

DEVICE LEGEND:

LIGHT SWITCH

RECEPTACLE

VOICE/DATA OUTLET

NURSE CALL DEVICES

THERMOSTAT

RECEPTACLE GROUNDING BOX DETAIL

METALLIC

BOXCONDUIT

CONDUIT

BUSHING

GROUNDING

SCREW

"GREEN"

GROUND

WIRE

NTS

PLASTIC

THROAT

BUSHING

GROUND WIRE

SURGE PROTECTIVE DEVICE (SPD) INSTALLATION 4

GENERAL NOTE:

1. LOCATE THE SPD AS CLOSE TO THE PANELBOARD BEING PROTECTED AS POSSIBLE.

2. MINIMIZE THE LENGTHS OF THE CONDUCTORS TO THE CIRCUIT BREAKER AND THE

NEUTRAL BUS, KEEPING ALL CONDUCTORS AS SHORT AS POSSIBLE AND CLOSE TO

THE SAME LENGTH.

3. LOCATE CIRCUIT BREAKER FOR THE SPD AS CLOSE TO THE MAIN CIRCUIT BREAKER,

OR MAIN LUGS, AS POSSIBLE.

4. USE STRANDED CONDUCTORS, IF RECOMMENDED BY THE MANUFACTURERS, TO

CONNECT TO THE SPD. AVOID SHARP BENDS, SHORT DIRECT CONNECTIONS ARE

PREFERRED.

PANELBOARD

SURGE PROTECTIVE DEVICE (SPD)

CHASE NIPPLE

MAIN CIRCUIT

BREAKER OR

MAIN LUGS

3 POLE

BRANCH

CIRCUIT

BREAKER

NEUTRAL BUS

GROUND BUS

BRANCH CIRCUIT

CONDUCTORS

ELECTRICAL - DETAILS

E-002

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2021, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION

LONG ISLAND NATIONAL CEMETERY

815CM3041

Final Construction Documents - Issued for Construction

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Project No. 4624

JCE CDH

May 22, 2023

296200

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

A

C

A C

A A

A

B

A

C

C

C

A A

CADWELD MOLD DETAIL

6 SCALE: NOT TO SCALE11

EXPOSED DOWNLEAD DETAIL

SCALE: NOT TO SCALE

12 SCALE: NOT TO SCALE

PVC CABLE GUARD SCALE: NOT TO SCALE

THRU-ROOF PENETRATION

SCALE: NOT TO SCALE

CADWELD MOLD - TA

MISCELLANEOUS

SCALE: NOT TO SCALE10

SCALE: NOT TO SCALE

THRU-ROOF CONNECTION

AIR TERMINAL

SCALE: NOT TO SCALE

TYPICAL DOWNLEAD DETAIL

SCALE: NOT TO SCALE5

TYPICAL DOWNLEAD DETAIL

SCALE: NOT TO SCALE1

CLASS I COPPER

LIGHTNING CONDUCTOR

AIR TERMINAL

SCALE: NOT TO SCALE

AIR TERMINAL

2 SCALE: NOT TO SCALE

AIR TERMINAL

SCALE: NOT TO SCALE3

AIR TERMINAL

SCALE: NOT TO SCALE

NOTE: ALL DETAILS MAY NOT APPLY TO THIS PROJECT.

3M VHB TAPE

SELF CONTAINED

STAINLESS STEEL NUT

AND LOCK WASHER

3M VHB TAPE

3M VHB TAPE

SELF CONTAINED

STAINLESS STEEL NUT

AND LOCK WASHER

SELF CONTAINED

STAINLESS STEEL NUT

AND LOCK WASHER

All fasteners shall have appropriate loop supports. No support penetrations shall be made in any sheet metal flashing or roof top equipment. Sheet metal screws shall not be used. Appropriate adhesive supports and construction mastic may be used on Membrane roof surfaces only.

Adhesive supports and construction mastic shall not be used on any sheet metal surfaces.

The contractor shall furnish 10 Year Adhesion Warranty on the fastener system.

1/2" X 12"

COPPER SAFETY TIPPED

AIR TERMINAL

COPPER

CABLE CLIP FASTENING SYSTEM

CLASS I

ALUMINUM MAIN CONDUCTOR

COPPER UNIVERSAL LIGHTNING ROD MOUNT

ASSEMBLY, SECURE WITH ADHESIVE

1/2" X 12"

COPPER SAFETY TIPPED

AIR TERMINAL

COPPER

ADHESIVE CABLE FASTENER

CLASS I

COPPER MAIN CONDUCTOR

COPPER 8"

SURFACE BONDING PLATE

UNIVERSAL LIGHTNING

ROD MOUNT ASSEMBLY

1/2" GALVANIZED STEEL TRIPOD

BASE

1/2" X 48"

COPPER AIR TERMINAL

COPPER ONE HOLE CABLE

STRAP

COPPER PIPE CLAMP

U-BOLT GROUND

ROD CLAMP

COPPER

CLASS I CONDUCTOR

COPPER U

BOLT CLAMP BASE

1/2" X 12"

COPPER SAFETY TIPPED

AIR TERMINAL

2 SCREW STANDING

SEAM SUPPORT

COPPER

CABLE CLIP

1/2" x 18"

COPPER CONCEALED BASE

CLASS I COPPER MAIN

CONDUCTOR

1/2" X 12" UNIVERSAL AIR

TERMINAL

SWIVEL ADAPTER, 1/2" TO 1/2"

UNIVERSAL PARALLEL CABLE SPLICER ASSEMBLY

USE TO SPLICE MAIN

SIZE CONDUCTOR TO

MAIN SIZE CONDUCTOR

BRONZE PARALLEL CLAMP

BRONZE CABLE TO FLAT

METAL CLAMP

CLASS I COPPER MAIN

CONDUCTOR

1" PVC CONDUIT

BRONZE

FLANGE BONDING

PLATE

1" PVC CONDUIT

CLASS I

COPPER MAIN CONDUCTOR

CLASS I

COPPER MAIN CONDUCTOR

BI-METAL

THRU-ROOF CONNECTOR

CLASS I

ALUMINUM MAIN CONDUCTOR

BRONZE

CROSS-RUN CABLE

CONNECTOR

BRONZE

FLANGE BONDING PLATE

BI-METAL

CONNECTOR

HEAVY

DUTY BONDING LUG

COPPER PIPE CLAMP

BONDING LUG

CABLE TO

FLAT METAL CLAMP

STRAP

TYPE PIPE CLAMP

COPPER

FLAT BONDING PLATE

COPPER

BONDING PLATE

GENERAL INSTALLATION NOTES

FINAL SYSTEM INSPECTION AND QUALITY CONTROL

CADWELD MOLD

CABLE TO CABLE CONNECTION

CLASS I

COPPER MAIN CONDUCTOR

CLASS I MAIN

CONDUCTOR COPPER

CLASS I MAIN

CONDUCTOR COPPER

FLANGE

BONDING PLATE

THRU-ROOF

ASSEMBLYCLASS I

COPPER MAIN CONDUCTOR

CLASS I

ALUMINUM MAIN CONDUCTOR

BI-METAL

CONNECTOR

PVC

CABLE GUARD

CLASS I

COPPER MAIN CONDUCTOR

PIPE GROUNDING

CLAMP

CLASS I COPPER

MAIN SIZE CONDUCTOR

BI-METAL

CONNECTOR

CLASS I

COPPER MAIN CONDUCTOR

CLASS I

COPPER MAIN CONDUCTOR

CADWELD MOLD

CABLE TO CABLE CONNECTION

CLASS I

COPPER MAIN CONDUCTOR

CADWELD MOLD

3/4" X 10 COPPER CLAD

GROUND ROD

AIR TERMINAL

MECHANICAL CONNECTION

MISC. BONDING

THRU-ROOF CONNECTOR

CLASS I ALUMINUM MAIN CONDUCTOR

CLASS I COPPER MAIN CONDUCTOR

COPPER CLAD GROUND ROD

WITH ULTRAWELD CONNECTION

TR

LEGEND

LOCATE AIR TERMINALS AS SHOWN. ENSURE THAT ALL

POINTS ARE WITHIN 2'-0" (609mm) OF OUTSIDE BUILDING

EDGE, OUTSIDE CORNERS, RIDGE ENDS, AND THAT MAX

SPACING DOES NOT EXCEED 20'-0" (6,096mm), AND THAT MIN PROJECTION ABOVE OBJECT PROTECTED IS 10" (254mm);

POINTS PROJECTING 24" (609mm) MAY BE SPACED @ 25'-0" (7,520mm) MAX.

MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN

CONDUCTOR. INSURE THAT ALL BENDS HAVE AT LEAST AN 8"

(203mm) RADIUS AND DO NOT EXCEED 90 DEGREES.

ATTACH ALL EXPOSED ROOF, DOWN LEAD AND BONDING CABLES

AT 3'-0" (914mm) ON CENTER MAX. VERIFY COMPATIBILITY OF

ADHESIVE ON MEMBRANE ROOF APPLICATION PRIOR TO

INSTALLATION.

GROUND ELECTRODES SHALL BE INSTALLED AS REQUIRED.

THEY SHALL NOT BE LESS THAN 1'-0" (304mm) BELOW GRADE AND 2'-0" (609mm) FROM FOUNDATION WALL. DRIVEN RODS SHALL PENETRATE THE EARTH AT LEAST 10'-0" (3,048mm).

BOND TO WATER SERVICE AND OTHER PIPING SYSTEMS AS

REQUIRED.

MAIN SIZE LIGHTNING CONDUCTOR BONDED TO MAIN GROUND

BUS FIELD. VERIFY LOCATION. PROVIDE 1" CONDUIT FOR

ACCESS. INTERCONNECT LIGHTNING PROTECTION GROUND TO

TELEPHONE AND OTHER BUILDING GROUND SYSTEMS LOCATION

FIELD. DETERMINE OR AS REQUIRED BY CODE.

SYSTEM SHALL BE INSTALLED AS TO ENSURE PROPER CODE

COMPLIANCE AND SYSTEM CERTIFICATION. SHOP DRAWINGS

SHALL BE SUBMITTED FOR APPROVAL.

ALL MATERIALS SHALL BE UNDERWRITER'S LABORATORIES

APPROVED WITH "A" LABELS ON CONDUCTORS @ 10'-0"

INTERVALS AND "B" LABELS ON ALL AIR TERMINALS.

A) THE CONTRACTOR SHALL FURNISH AN LPI-IP

CERTIFICATE OR A UL CERTIFICATE UPON COMPLETION

OF THE INSTALLATION.

B) LPI CERTIFICATION REQUIRES A SIGNATURE BY A

REPRESENTATIVE OF THE OWNER AT MULTIPLE

STAGES OF INSTALLATION & BY THEIR THIRD PARTY

FIELD STAFF. UL CERTIFICATION REQUIRES INSPECTION

BY THEIR THIRD-PARTY FIELD STAFF AFTER

COMPLETION OF THE INSTALLATION.

C) AS-BUILT DRAWINGS SHALL BE COMPLETED AND

STAMPED BY AN LPI CERTIFIED MASTER DESIGNER

- INSTALLER OF LIGHTNING PROTECTION

SYSTEMS.

D) FINAL INSPECTION REPORT - A FINAL INSPECTION AND

INSPECTION REPORT SHALL BE COMPLETED BASED ON

ANSI/TIA/EIA 607, NEC, NFPA 780, AND UL96A

INDUSTRY STANDARDS AS APPLICABLE. THE SCOPE OF

THE INSPECTION AND REPORT SHALL INCLUDE;

a. TEST AND EVALUATION THE GROUNDING SYSTEM.

RECORD FINAL SYSTEMS TO GROUND RESISTANCE

LEVEL.

b. EVALUATION AND TESTING OF THE INTERNAL

BONDING AND GROUNDING SYSTEMS.

c. EVALUATION AND TESTING OF EQUIPMENT

GROUNDING.

d. EVALUATION OF AC SURGE SUPPRESSION

INSTALLATION.

e. EVALUATION OF TELCO SURGE SUPPRESSION

INSTALLATION.

f. COPY OF THE LPI-IP LIGHTNING PROTECTION

CERTIFICATION.

g. FINAL AS-BUILT REVIEW AND SUBMISSION.

E) REPORT SHALL INCLUDE DETAILED REPORTING AND

TEST RESULTS WITH CORRESPONDING PHOTOS OF

EACH EVALUATION CATEGORY.

ELECTRICAL - DETAILS

LIGHTNING

E-003

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2021, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION

LONG ISLAND NATIONAL CEMETERY

815CM3041

Final Construction Documents - Issued for Construction

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Project No. 4624

JCE CDH

May 22, 2023

296201

AutoCAD SHX Text

6'-0" MIN.

AutoCAD SHX Text

12" MIN. BELOW FINISH GRADE

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

PANEL

"DLB-1"

200A MCB

208/120V

3PH 4W

(NEW)

BOILER

PANEL

"DLB-2"

100A MCB

120/208V

1PH 3W

(NEW)

SPD

3PH 4W

(NEW)

BASEMENT 4

DIRECTOR'S LODGE

BUILDING 2001 #2

PANEL

"DL1-1"

30A MCB

120/208V

1PH 3W

(NEW)

BASEMENT LEVEL

GROUND FLOOR

PANEL

"MDP"

400A

208/120V

3PH

(EXISTING TO

REMAIN)

ADMINISTRATION

BUILDING

MECHANICAL

ROOM

122 POWER RISER LEGEND

NEW

DEMO

EXISTING

LOBBY 2

20Y

30Y

50Y

60Y

80Y

100Y

125Y

150Y

175Y

200Y

225Y

250Y

300Y

400Y

500Y

600Y

800Y

1000Y

4 #12, 1#12 G, 3/4" C.

4 #10, 1#10 G, 3/4" C.

4 #6, 1#10 G, 1 1/4" C.

4 #2, 1#8 G, 1 1/2" C.

4 #4, 1#8 G, 1 1/4" C.

4 #6, 1#10 G, 1" C.

4 #1, 1#6 G, 2" C.

4 #1/0, 1#6 G, 2" C.

4 #2/0, 1#6 G, 2" C.

4 #3/0, 1#6 G, 2" C.

4 #4/0, 1#4 G, 2 1/2" C.

4-250 MCM, 1#4 G, 2 1/2" C.

4-350 MCM, 1#4 G, 3" C.

4-500 MCM, 1#3 G, 3 1/2"C.

2 SETS: 4-250 MCM, 1#2 G, 2 1/2" C.

2 SETS: 4-350 MCM, 1#1 G, 3" C.

2 SETS: 4-500 MCM, 1#1/0 G, 3" C.

3 SETS: 4-400 MCM, 1#2/0 G, 3" C.

BRANCH CIRCUIT AND FEEDER SCHEDULE

3-PHASE CIRCUITS + NEUTRAL + GROUND

SYMBOL

NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.

MINIMUM SIZE CONDUCTORS AND CONDUITS

3-PHASE CIRCUITS (NO NEUTRAL) + GROUND

3 #12, 1#12 G, 3/4" C.

3 #10, 1#10 G, 3/4" C.

3 #6, 1#10 G, 1" C.

3 #6, 1#10 G, 1" C.

3 #2, 1#8 G, 1 1/2" C.

3 #4, 1#8 G, 1" C.

3 #1, 1#6 G, 2" C.

3 #1/0, 1#6 G, 2" C.

3 #2/0, 1#6 G, 2" C.

3 #3/0, 1#6 G, 2" C.

3 #4/0, 1#4 G, 2 1/2" C.

3-250 MCM, 1#4 G, 2 1/2" C.

3-350 MCM, 1#4 G, 3" C.

3-500 MCM, 1#3 G, 3"C.

2 SETS: 3-250 MCM, 1#2 G, 2 1/2" C.

2 SETS: 3-350 MCM, 1#1 G, 3" C.

2 SETS: 3-500 MCM, 1#1/0 G, 3" C.

3 SETS: 3-400 MCM, 1#2/0 G, 3" C.

BRANCH CIRCUIT AND FEEDER SCHEDULE

NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.

SYMBOL MINIMUM SIZE CONDUCTORS AND CONDUITS

KITCHEN

PANEL

"DL1-1"

30A MCB

120/208V

1PH 3W

(DEMO)

3#10, 1#10, ¾"C

3#2, 1#8, 1-½"C

3#12, 1#12, ¾"C

POWER RISER DIAGRAM

EXISTING TO REMAIN.

RECONNECT AND

EXTEND AS NEEDED

ELECTRICAL - LUMINAIRE

SCHEDULE & RISER DIAGRAM

DIRECTOR'S LODGE

E-004

ALL SURGE PROTECTION DEVICES SHALL BE REPLACED UNDER THIS

SCOPE OF WORK.

NEW WORK KEYED NOTES

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2021, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION

LONG ISLAND NATIONAL CEMETERY

815CM3041

Final Construction Documents - Issued for Construction

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Project No. 4624

JCE CDH

May 22, 2023

296202

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

20Y

30Y

50Y

60Y

80Y

100Y

125Y

150Y

175Y

200Y

225Y

250Y

300Y

400Y

500Y

600Y

800Y

1000Y

4 #12, 1#12 G, 3/4" C.

4 #10, 1#10 G, 3/4" C.

4 #6, 1#10 G, 1 1/4" C.

4 #2, 1#8 G, 1 1/2" C.

4 #4, 1#8 G, 1 1/4" C.

4 #6, 1#10 G, 1" C.

4 #1, 1#6 G, 2" C.

4 #1/0, 1#6 G, 2" C.

4 #2/0, 1#6 G, 2" C.

4 #3/0, 1#6 G, 2" C.

4 #4/0, 1#4 G, 2 1/2" C.

4-250 MCM, 1#4 G, 2 1/2" C.

4-350 MCM, 1#4 G, 3" C.

4-500 MCM, 1#3 G, 3 1/2"C.

2 SETS: 4-250 MCM, 1#2 G, 2 1/2" C.

2 SETS: 4-350 MCM, 1#1 G, 3" C.

2 SETS: 4-500 MCM, 1#1/0 G, 3" C.

3 SETS: 4-400 MCM, 1#2/0 G, 3" C.

BRANCH CIRCUIT AND FEEDER SCHEDULE

3-PHASE CIRCUITS + NEUTRAL + GROUND

SYMBOL

NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.

MINIMUM SIZE CONDUCTORS AND CONDUITS

3-PHASE CIRCUITS (NO NEUTRAL) + GROUNDING

3 #12, 1#12 G, 3/4" C.

3 #10, 1#10 G, 3/4" C.

3 #6, 1#10 G, 1" C.

3 #6, 1#10 G, 1" C.

3 #2, 1#8 G, 1 1/2" C.

3 #4, 1#8 G, 1" C.

3 #1, 1#6 G, 2" C.

3 #1/0, 1#6 G, 2" C.

3 #2/0, 1#6 G, 2" C.

3 #3/0, 1#6 G, 2" C.

3 #4/0, 1#4 G, 2 1/2" C.

3-250 MCM, 1#4 G, 2 1/2" C.

3-350 MCM, 1#4 G, 3" C.

3-500 MCM, 1#3 G, 3"C.

2 SETS: 3-250 MCM, 1#2 G, 2 1/2" C.

2 SETS: 3-350 MCM, 1#1 G, 3" C.

2 SETS: 3-500 MCM, 1#1/0 G, 3" C.

3 SETS: 3-400 MCM, 1#2/0 G, 3" C.

BRANCH CIRCUIT AND FEEDER SCHEDULE

NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.

SYMBOL MINIMUM SIZE CONDUCTORS AND CONDUITS

PANEL "PIC-1 "

150A MCB

120/208V

3PH 4W

PUBLIC INFORMATION

CENTER

BUILDING 1002 NO. 4

SPD

120/208V

3PH

BASEMENT

LEVEL

BASEMENT

POWER RISER LEGEND

NEW

DEMO

EXISTING

NEW NEW

METER

(EXISTING

TO

REMAIN)

ELECTRICAL - LUMINAIRE

SCHEDULE & RISER DIAGRAM

PUBLIC INFORMATION CENTER

E-005

ALL SURGE PROTECTION DEVICES SHALL BE REPLACED UNDER THIS

SCOPE OF WORK.

WIRE AND CONDUIT FEEDING THE PUBLIC INFORMATION CENTER IS

EXISTING TO REMAIN.

NEW WORK KEYED NOTES

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2021, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION

LONG ISLAND NATIONAL CEMETERY

815CM3041

Final Construction Documents - Issued for Construction

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Project No. 4624

JCE CDH

May 22, 2023

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

50Y

60Y

80Y

100Y

125Y

150Y

175Y

200Y

225Y

250Y

300Y

400Y

500Y

600Y

800Y

1000Y

4 #12, 1#12 G, 3/4" C.

4 #10, 1#10 G, 3/4" C.

4 #6, 1#10 G, 1 1/4" C.

4 #2, 1#8 G, 1 1/2" C.

4 #4, 1#8 G, 1 1/4" C.

4 #6, 1#10 G, 1" C.

4 #1, 1#6 G, 2" C.

4 #1/0, 1#6 G, 2" C.

4 #2/0, 1#6 G, 2" C.

4 #3/0, 1#6 G, 2" C.

4 #4/0, 1#4 G, 2 1/2" C.

4-250 MCM, 1#4 G, 2 1/2" C.

4-350 MCM, 1#4 G, 3" C.

4-500 MCM, 1#3 G, 3 1/2"C.

2 SETS: 4-250 MCM, 1#2 G, 2 1/2" C.

2 SETS: 4-350 MCM, 1#1 G, 3" C.

2 SETS: 4-500 MCM, 1#1/0 G, 3" C.

3 SETS: 4-400 MCM, 1#2/0 G, 3" C.

BRANCH CIRCUIT AND FEEDER SCHEDULE

3-PHASE CIRCUITS + NEUTRAL + GROUND

SYMBOL

NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.

MINIMUM SIZE CONDUCTORS AND CONDUITS

3-PHASE CIRCUITS (NO NEUTRAL) + GROUNDING

3 #12, 1#12 G, 3/4" C.

3 #10, 1#10 G, 3/4" C.

3 #6, 1#10 G, 1" C.

3 #6, 1#10 G, 1" C.

3 #2, 1#8 G, 1 1/2" C.

3 #4, 1#8 G, 1" C.

3 #1, 1#6 G, 2" C.

3 #1/0, 1#6 G, 2" C.

3 #2/0, 1#6 G, 2" C.

3 #3/0, 1#6 G, 2" C.

3 #4/0, 1#4 G, 2 1/2" C.

3-250 MCM, 1#4 G, 2 1/2" C.

3-350 MCM, 1#4 G, 3" C.

3-500 MCM, 1#3 G, 3"C.

2 SETS: 3-250 MCM, 1#2 G, 2 1/2" C.

2 SETS: 3-350 MCM, 1#1 G, 3" C.

2 SETS: 3-500 MCM, 1#1/0 G, 3" C.

3 SETS: 3-400 MCM, 1#2/0 G, 3" C.

BRANCH CIRCUIT AND FEEDER SCHEDULE

NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.

SYMBOL MINIMUM SIZE CONDUCTORS AND CONDUITS

PANEL PR

100A MCB

120/208V

3PH 4W

(NEW;

REPLACEMENT)

PUBLIC

RESTROOM

GROUND

FLOOR

MECHANICAL

ROOM

METER

(EXISTING

TO

REMAIN)

SPD

3PH 4W

(NEW)

POWER RISER LEGEND

NEW

DEMO

EXISTING

ELECTRICAL - LUMINAIRE

SCHEDULE & RISER DIAGRAM

PUBLIC RESTROOM

E-006

LOCATE SURGE PROTECTIVE DEVICE (SPD) ADJACENT TO

PANELBOARD AND CLOSE TO BOTH CIRCUIT BREAKER AND NEUTRAL

BUS TO MINIMIZE LEAD LENGTH.

WIRE AND CONDUIT FEEDING THE BUILDING IS EXISTING TO REMAIN.

EXISTING PANELBOARD IS TO BE REMOVED AND REPLACED. REFER TO

NEW PANELBOARD SCHEDULE ON THIS SHEET. EXTEND EXISTING

FEEDER AS REQUIRED, MATCHING EXISTING IN ALL CHARACTERISTICS.

(E) - EXISTING

NEW WORK KEYED NOTES

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2021, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION

LONG ISLAND NATIONAL CEMETERY

815CM3041

Final Construction Documents - Issued for Construction

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Project No. 4624

JCE CDH

May 22, 2023

LEGEND

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

50Y

60Y

80Y

100Y

125Y

150Y

175Y

200Y

225Y

250Y

300Y

400Y

500Y

600Y

800Y

1000Y

4 #12, 1#12 G, 3/4" C.

4 #10, 1#10 G, 3/4" C.

4 #6, 1#10 G, 1 1/4" C.

4 #2, 1#8 G, 1 1/2" C.

4 #4, 1#8 G, 1 1/4" C.

4 #6, 1#10 G, 1" C.

4 #1, 1#6 G, 2" C.

4 #1/0, 1#6 G, 2" C.

4 #2/0, 1#6 G, 2" C.

4 #3/0, 1#6 G, 2" C.

4 #4/0, 1#4 G, 2 1/2" C.

4-250 MCM, 1#4 G, 2 1/2" C.

4-350 MCM, 1#4 G, 3" C.

4-500 MCM, 1#3 G, 3 1/2"C.

2 SETS: 4-250 MCM, 1#2 G, 2 1/2" C.

2 SETS: 4-350 MCM, 1#1 G, 3" C.

2 SETS: 4-500 MCM, 1#1/0 G, 3" C.

3 SETS: 4-400 MCM, 1#2/0 G, 3" C.

BRANCH CIRCUIT AND FEEDER SCHEDULE

3-PHASE CIRCUITS + NEUTRAL + GROUND

SYMBOL

NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.

MINIMUM SIZE CONDUCTORS AND CONDUITS

3-PHASE CIRCUITS (NO NEUTRAL) + GROUNDING

3 #12, 1#12 G, 3/4" C.

3 #10, 1#10 G, 3/4" C.

3 #6, 1#10 G, 1" C.

3 #6, 1#10 G, 1" C.

3 #2, 1#8 G, 1 1/2" C.

3 #4, 1#8 G, 1" C.

3 #1, 1#6 G, 2" C.

3 #1/0, 1#6 G, 2" C.

3 #2/0, 1#6 G, 2" C.

3 #3/0, 1#6 G, 2" C.

3 #4/0, 1#4 G, 2 1/2" C.

3-250 MCM, 1#4 G, 2 1/2" C.

3-350 MCM, 1#4 G, 3" C.

3-500 MCM, 1#3 G, 3"C.

2 SETS: 3-250 MCM, 1#2 G, 2 1/2" C.

2 SETS: 3-350 MCM, 1#1 G, 3" C.

2 SETS: 3-500 MCM, 1#1/0 G, 3" C.

3 SETS: 3-400 MCM, 1#2/0 G, 3" C.

BRANCH CIRCUIT AND FEEDER SCHEDULE

NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.

SYMBOL MINIMUM SIZE CONDUCTORS AND CONDUITS

PANELBOARD

"CSA"

100A MCB

120/240V

1PH 3W

(EXISTING)

COMMITTAL SHELTER A

GROUND

PANELBOARD

"CSB"

100A MCB

COMMITTAL SHELTER B

GROUND

POWER RISER LEGEND

NEW

DEMO

EXISTING

SPD

1PH 3W

(NEW)

1 1

SPD

1PH 3W

(NEW)

120/240V

1PH 2P 3W

(EXISTING)

3#10, 1#10G, ¾"C 3#10, 1#10G, ¾"C

ELECTRICAL - LUMINAIRE

SCHEDULE & RISER DIAGRAM

COMMITTAL SHELTERS

E-009

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2021, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION

LONG ISLAND NATIONAL CEMETERY

815CM3041

Final Construction Documents - Issued for Construction

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Project No. 4624

JCE CDH

May 22, 2023

KEYED NOTES

1 TO EXISTING 24 kVA PAD MOUNTED TRANSFORMER LOCATED BETWEEN

COMMITTAL SHELTERS A & B AND FED FROM ADMINISTRATION BUILDING

(1001). 480V PRIMARY, 240/120V SECONDARY.

LEGEND

(E) EXISTING TO REMAIN

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

2M

2T

2T

W es te rn

D r.

West Fourth Dr.

West Fifth Dr.

OC

PUMP

HOUSE

PUBLIC

RESTROOMS

BUILDING

MAINTENANCE

BUILDING

NIC

NIC

NIC

NIC

NIC

(NIC)

FOR TELECOM

ROUTING

NEW

TEMPORARY

RESTROOMS

NEW WATER

WELL PUMP

NEW WATER

WELL CONTROL

SPOOL

FOR POWER

ROUTING

E

Main Portal Dr.

LODGE

EMPLOYEE

ONLY

EMPLOYEE

ONLY

EMPLOYEE

ONLY

EMPLOYEE

ONLY

EMPLOYEE

ONLY

EMPLOYEE

ONLY

EMPLOYEE

ONLY

EMPLOYEE

ONLY

EMPLOYEE

ONLYNO

PARKING

EM

PLOYEE

ONLY

EM

PLOYEE

ONLY

EM

PLOYEE

ONLY

EM

PLOYEE

ONLY

EM

PLOYEE

ONLY

EM

PLOYEE

ONLY

EM

PLOYEE

ONLY

EM

PLOYEE

ONLY

EM

PLOYEE

ONLY

EM

PLOYEE

ONLY

NO

PARKING

DIRECTOR'S

LODGE

PUBLIC

INFORMATION

CENTER

ADMINISTRATION

BUILDING (NIC)

NIC

FOR

CONTINUATION

K

D

3E

C

Memorial Dr. S.

Memorial Dr. N.

Memorial Dr. S.

C

COMMITTAL

SHELTER A

COMMITTAL

SHELTER B

ELECTRICAL - OVERALL

SITE PLAN

E-010

LEGEND

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2021, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION

LONG ISLAND NATIONAL CEMETERY

815CM3041

Final Construction Documents - Issued for Construction

KEY

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Project No. 4624

NOT TO SCALE

3B

2X

2Z2Y

2W 3D

2S

2R

2Q

2D

3F

3C

2U

2T

2M

2K

H

J

C

D

N O

M L

K A

B

G

F

2L

2P2N

2M2J

2E2G

2E2G

R

Q

P

Y Z

2A

X

V

T

US

2C

2B

2VW

3A

JCE CDH

May 22, 2023

0 15 30 60 90

TRUE

NORTHGRAPHICAL SCALE

GENERAL NOTES

A. REFER TO DRAWING SERIES OF RESPECTIVE BUILDING FOR SCOPE OF WORK.

B. ALL BUILDINGS LABELED 'NIC' ARE NOT IN CONTRACT.

C. ALL BUILDINGS / STRUCTURES ARE EXISTING, UNLESS OTHERWISE NOTED.

KEYED NOTES

1 APPROXIMATE ROUTING OF EXISTING UNDERGROUND TELECOMMUNICATION

PATHWAY. PROVIDE TWO (2) PLENUM RATED SINGLE MODE FIBER CABLES FROM

EXISTING ADMINISTRATION BUILDING TELECOM ROOM TO PUBLIC INFORMATION

CENTER BASEMENT VIA EXISTING RACEWAYS. VERIFY RACEWAY INTEGRITY AND

CLEAN PRIOR TO RE-USE. CONFIRM EXACT ROUTING IN THE FIELD. REFER TO

PUBLIC INFORMATION CENTER PLANS FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

1 STORY FRAME BUILDING

AutoCAD SHX Text

BUILDING FOOTPRINT AREA=1,015± S.F.

AutoCAD SHX Text

1 STORY FRAME BUILDING

AutoCAD SHX Text

BUILDING FOOTPRINT AREA=7,570± S.F.

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

FRAME SHED

AutoCAD SHX Text

TRAILER

AutoCAD SHX Text

1 STORY FRAME BUILDING

AutoCAD SHX Text

BUILDING FOOTPRINT AREA=2,009± S.F.

AutoCAD SHX Text

1 STORY FRAME BUILDING

AutoCAD SHX Text

BUILDING FOOTPRINT AREA=983± S.F.

AutoCAD SHX Text

1 STORY FRAME BUILDING

AutoCAD SHX Text

BUILDING FOOTPRINT AREA=5,325± S.F.

AutoCAD SHX Text

FRAME SHED

AutoCAD SHX Text

FRAME SHED

AutoCAD SHX Text

1 STORY FRAME BUILDING

AutoCAD SHX Text

BUILDING FOOTPRINT…