36C78619B0021-015.pdf
PDF 13 MB Posted
- Solicitation number
- 36C78619B0021
About this file
36C78619B0021 190820 CNC 835-036 Bid Drawings Final_3of3.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C78619B0021-0006001.jpg | JPG image | |
| 36C78619B0021-0006000.docx | DOCX document | |
| 36C78619B0021-0005000.docx | DOCX document | |
| 36C78619B0021-0005001.xlsx | XLSX spreadsheet | |
| 36C78619B0021-0004000.docx | DOCX document | |
| 36C78619B0021-0004001.docx | DOCX document | |
| 36C78619B0021-0003001.pdf | ||
| 36C78619B0021-0003000.docx | DOCX document | |
| 36C78619B0021-0002000.docx | DOCX document | |
| 36C78619B0021-0001000.docx | DOCX document | |
| 36C78619B0021-013.pdf | ||
| 36C78619B0021-009.pdf | ||
| 36C78619B0021-006.docx | DOCX document | |
| 36C78619B0021-016.pdf | ||
| 36C78619B0021-011.pdf | ||
| 36C78619B0021-014.pdf | ||
| 36C78619B0021-008.pdf | ||
| 36C78619B0021-012.pdf | ||
| 36C78619B0021-007.pdf | ||
| 36C78619B0021-010.docx | DOCX document | |
| 36C78619B0021-000.docx | DOCX document |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SURFACE MOUNTED PANELBOARD.
SURFACE MOUNTED DUAL CHANNEL RACEWAY WIREMOLD SERIES 5400, 120VAC,
20A. MOUNT 48" AFF TO TOP OF RACEWAY. ONE OUTLET EVERY 24".
MOTOR, HORSEPOWER AS INDICATED.
FLUSH MOUNTED DUPLEX CONVENIENCE OUTLET NEMA 5-20R, 120V, 20 AMP,
3 WIRE, MOUNTED 18" AFF, "*" IF SUBSCRIPT APPLIES, SEE BELOW:
- INDICATES GROUND FAULT INTERRUPTING TYPE.
- INDICATES COUNTER TOP RECEPTACLE MOUNTED 6" ABOVE
"GFI"
"WP"
"C"
- INDICATES WEATHERPROOF COVER.
COUNTER TOP.
JUNCTION BOX, CEILING MOUNTED
5 HP
MAGNETIC MOTOR STARTER, "*" SUBSCRIPT INDICATES STARTER SIZE.
COMBINATION MAGNETIC MOTOR STARTER, RATINGS AS INDICATED (AMPS/POLES/
HEAVY DUTY DISCONNECT SWITCH, RATINGS AS INDICATED (AMPS/POLES/
DRY TYPE TRANSFORMER WITH VOLTAGES, KVA, AND PHASES AS
NAMEPLATE DATA. "*" SUBSCRIPT INDICATES STARTER SIZE.
"HOA" - INDICATES "HAND-OFF-AUTO" SELECTOR SWITCH MOUNTED ON DOOR.
/ENCLOSURE). NON-FUSED SWITCH TYPE. OVERLOADS SIZED PER MOTOR
"00" - INDICATES "ON-OFF" SELECTOR SWITCH MOUNTED ON DOOR.
HOMERUN TO PANEL INDICATED (XX) AND CIRCUIT NUMBER INDICATED (YY).
ELECTRICAL SYMBOL LEGEND
CONDUIT TURNING UP
CONDUIT ROUTED EXPOSED
CONDUIT TURNING DOWN
EQUIPMENT AS NOTED.
/ENCLOSURE) FUSED IF INDICATED.
EXAMPLE OF WIRING AND CONDUIT NOTATION.
3#10, #10G, 1"C
30/3/3R
HOA
SHOWN ON DRAWINGS.
SYMBOL
T
DESCRIPTION
CONDUIT ROUTED CONCEALED ABOVE DROPPED CEILING AND/OR WALLS.
XX-YY
- INDICATES DEDICATED CIRCUIT."D"
ONE CIRCUIT: PROVIDE 2#12, #12G, 3/4"C, UNO
TWO CIRCUITS: PROVIDE 3#12, #12G, 3/4"C, UNO
THREE CIRCUITS: PROVIDE 4#12, #12G, 3/4"C, UNO
30/3/1
"a" - LOWER CASE LETTER INDICATES SWITCHING ARRANGEMENT
SINGLE FACE EXIT LIGHT CEILING OR PENDANT MOUNTED W/ BATTERY BACKUP.
LIGHTED FACE. MATCH EXISTING.
DOUBLE FACE EXIT LIGHT CEILING OR PENDANT MOUNTED W/ BATTERY BACKUP.
SAME AS ABOVE, EXCEPT WALL MOUNTED
(ARROWS INDICATE DIRECTION OF TRAFFIC). MATCH EXISTING.
(ARROWS INDICATE DIRECTION OF TRAFFIC). SHADED SIDE INDICATES SIDE WITH
* IF SUBSCRIPT APPLIES, SEE BELOW:
SINGLE POLE LIGHT SWITCH, FLUSH MOUNTED 48" AFF, 120/277V, 20AMP.
ON STRIKE SIDE OF DOOR OR WHERE OTHERWISE INDICATED ON PLANS.
A1
"K" - KEY OPERATED SINGLE POLE SWITCH. SWITCH SHALL INTERRUPT
UNSWITCHED PHASE CONDUCTOR SERVING EMERGENCY LIGHTING
UNITS FOR TESTING PURPOSES.
18" AFF
18"AFF
48" AFF
18" AFF
48" AFF
TYPICAL DEVICE MOUNTING HEIGHT
1' ABOVE DOOR
7'-6" AFF (UNO)
MATCH EXISTING
48" AFF
18" AFF
MATCH EXISTINGFIRE ALARM PULL STATION
UNLESS NOTED OTHERWISE.
EXIT LIGHTS (WALL MTD.)
AUDIO/VIDEO OUTLETS
ANNUNCIATOR PANELS
FIRE ALARM AUDIO/VISUAL ALARM
EMERGENCY LIGHTS (WALL MTD.)
NOTE: DIMENSIONS ARE TO DEVICE CENTERLINE
LIGHT SWITCHES
RECEPTACLES (OFFICE AREA)
COMPUTER OUTLETS
TELEPHONE OUTLETS
TELEPHONE OUTLET (WALL MTD.)
PUSHBUTTON
B1
OR
RECESSED MOUNTED PANELBOARD.
2'X4' LED TROFFER. "A1" INDICATES FIXTURE TYPE FROM FIXTURE SCHEDULE.
SAME AS ABOVE, EXCEPT RECEPTACLE IS QUADRAPLEX TYPE.
LED STRIP FIXTURE "B1" INDICATES FIXTURE TYPE FROM FIXTURE SCHEDULE.
A2
SAME AS ABOVE EXCEPT FIXTURE TO BE USED FOR EGRESS.
OR
B2
JUNCTION BOX FOR DATA/TELEPHONE OUTLET WITH 3/4" EMPTY CONDUIT
STUBBED INTO ACCESSIBLE CEILING. PROVIDE PULL STRING.
GENERAL ELECTRICAL RENOVATION NOTES
(GENERAL NOTES APPLY TO ALL DRAWINGS AND SPECIFICATIONS)
GENERAL ELECTRICAL CONSTRUCTION NOTES
1. THE ELECTRICAL INSTALLATION SHALL CONFORM TO THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, THE
AMERICANS WITH DISABILITIES ACT, AND OTHER APPLICABLE STATE AND LOCAL CODES.
2. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE WORK OF THEIR TRADE WITH THAT OF THE OTHER TRADES
INVOLVED IN THE PROJECT. CONFLICTS WITH OTHER TRADES SHALL BE BROUGHT TO THE ATTENTION OF THE
PROJECT MANAGER PRIOR TO INSTALLATION. WORK SHOULD ALSO BE COORDINATED AROUND PORTABLE AND
MOBILE EQUIPMENT.
3. THE ELECTRICAL CONTRACTOR SHALL SCHEDULE THEIR WORK SO THAT THE CONSTRUCTION SCHEDULE IS
MAINTAINED.
4. THE ELECTRICAL CONTRACTOR SHALL REQUEST A COMPLETE SET OF THE HVAC, PLUMBING, AND FIRE PROTECTION
DRAWINGS TO VERIFY CONNECTIONS TO THE EQUIPMENT.
5. THE ELECTRICAL CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS PRIOR TO INSTALLING ANY EQUIPMENT
ABOVE CEILINGS AND IN MECHANICAL ROOMS.
6. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. THE ELECTRICAL CONTRACTOR SHALL VERIFY EXACT FIELD
CONDITIONS AND DIMENSIONS PRIOR TO COMMENCING WORK.
7. THE ELECTRICAL CONTRACTOR SHALL FURNISH MATERIALS AND LABOR FOR A COMPLETE ELECTRICAL INSTALLATION
AS INDICATED IN THESE DOCUMENTS. MATERIAL, APPARATUS, AND EQUIPMENT SHALL BE NEW AND SHALL BEAR THE
UNDERWRITERS LABEL WHERE APPLICABLE.
8. THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY LIGHTING AND POWER SERVICE WHILE THE
BUILDING/RENOVATION AREA IS UNDER CONSTRUCTION ACCORDING TO CURRENT OSHA STANDARDS.
9. ALL CIRCUITS SHALL CONTAIN AN EQUIPMENT GROUNDING CONDUCTOR (GREEN COLORED INSULATION) ROUTED IN
CONDUIT AND SIZED AS INDICATED.
10. THE ELECTRICAL CONTRACTOR SHALL BE ALLOWED TO USE 3/4" MINIMUM ELECTRIC METALLIC TUBING (EMT) IN ALL
AREAS NOT EXPOSED TO PHYSICAL DAMAGE. COMPRESSION FITTINGS WITH INSULATED THROATS SHALL BE USED
FOR EMT CONDUITS 1-1/4" AND SMALLER. LARGER CONDUITS (1-1/2" AND GREATER) SHALL UTILIZE SET SCREW TYPE
FITTINGS.
11. ALL CONDUIT EXPOSED TO PHYSICAL DAMAGE (15'-0" AFF & BELOW) SHALL BE INTERMEDIATE METAL CONDUIT (IMC).
12. ALL CONDUITS BELOW GRADE SHALL BE PVC. ALL ELBOWS TURNING UP TOWARD ABOVE GRADE, AND ALL CONDUITS
EXPOSED ABOVE GRADE SHALL BE IMC.
13. FLEXIBLE (TYPE MC) CABLE SHALL BE ALLOWED FOR THE FLEXIBLE CONNECTIONS TO VIBRATING EQUIPMENT AND
RECESSED LIGHTING FIXTURES IN LAY-IN TYPE CEILINGS. A GROUNDING CONDUCTOR SHALL BE INCLUDED WITH THE
POWER CONDUCTORS INSIDE THE FLEXIBLE CONNECTION.
14. THE ELECTRICAL CONTRACTOR SHALL BE ALLOWED TO RUN LOW VOLTAGE (UNDER 100V) CONDUCTORS AND
COMMUNICATIONS OR FIRE ALARM CABLING EXPOSED, BUNDLED, AND TIE WRAPPED BY USING PLENUM RATED
CABLES. ALL DROPS TO DEVICES SHALL BE IN ACCORDANCE WITH NOTE 10 ABOVE.
15. ALL CONDUIT RUNS SHALL BE MADE EITHER PARALLEL OR PERPENDICULAR TO STRUCTURAL MEMBERS.
16. THE ELECTRICAL CONTRACTOR SHALL UTILIZE TYPE THHN/THWN-2 CONDUCTORS IN ALL AREAS EXCEPT WHERE
SERVICE ENTRANCE CONDUCTORS ARE PROVIDED AS PART OF THE SCOPE OF WORK. WHERE SERVICE ENTRANCE
CONDUCTORS ARE PROVIDED AS PART OF THE SCOPE OF WORK THEY SHALL UTILIZE TYPE XHHW INSULATION.
17. THE ELECTRICAL CONTRACTOR SHALL PROVIDE COPPER CONDUCTORS. CONDUCTORS SHALL BE SOLID FOR SIZES
#10 AWG AND SMALLER. CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED.
18. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A SEPARATE RACEWAY SYSTEM FOR THE 208Y/120V
CIRCUITS/FEEDERS AND CONTROL CIRCUITS.
19. THE ELECTRICAL CONTRACTOR SHALL LIMIT LIGHTING AND RECEPTACLE BRANCH CIRCUIT HOMERUNS TO 5
CONDUCTORS: 3 PHASE CONDUCTORS, 1 NEUTRAL CONDUCTOR, AND 1 EQUIPMENT GROUNDING CONDUCTOR.
20. WIRES AND CABLES SHALL BE PULLED UTILIZING AN APPROVED PULLING LUBRICANT. OIL OR GREASE NOT
SPECIFICALLY LISTED FOR USE AS A CABLE PULLING LUBRICANT IS NOT PERMITTED.
21. WIRES AND CABLES SHALL BE INSTALLED WITHOUT JOINTS OR SPLICES INSOFAR AS PRACTICAL. WRITTEN APPROVAL
SHALL BE REQUESTED FROM THE ENGINEER PRIOR TO APPLICATION OF ANY SPLICES OR JOINTS.
22. THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE FOLLOWING COLOR CODING OF CIRCUITS/FEEDERS.
CIRCUITS/FEEDERS RATED 208Y/120V: PHASE "A" = BLACK
PHASE "B" = RED
PHASE "C" = BLUE
NEUTRAL = WHITE
GROUNDING = GREEN
ISOLATED G = GREEN/YELLOW STRIPE
23. RECESSED TYPE LIGHTING FIXTURES SHALL BE LOCATED AS INDICATED ON THE ARCHITECTURAL REFLECTED
CEILING PLAN.
24. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL CEILING CONSTRUCTION BEFORE ORDERING LIGHTING FIXTURES
AND SHALL PROVIDE CORRECT MOUNTING HARDWARE WITHOUT ADDITIONAL COST. LIGHTING FIXTURES SHALL BE AS
SCHEDULED, INCLUDING LAMPS.
25. ALL DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE, AND FUSIBLE WHERE INDICATED.
26. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ADDITIONAL SUPPORT FOR ALL ELECTRICAL
EQUIPMENT WHERE THE BUILDING STRUCTURE IS NOT SUITABLE FOR A PROPERLY SUPPORTED INSTALLATION.
27. THE ELECTRICAL CONTRACTOR SHALL PROVIDE AN OUTLET BOX FOR EACH LIGHTING FIXTURE, WIRING DEVICE, OR
JUNCTION POINT. ELECTRICAL BOXES SHALL BE OF SUFFICIENT CAPACITY FOR THE NUMBER OF CONDUCTORS AND
SPLICES WITHIN THE BOX; IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE.
28. DEVICE PLATES SHALL BE INSTALLED ON OUTLETS FOR ALL SWITCHES, RECEPTACLES, ETC. AND COLOR SHALL BE
AS SELECTED BY ARCHITECT. WHERE MORE THAN ONE SWITCH IS INDICATED IN THE SAME LOCATION, SWITCHES
SHALL BE GANGED UNDER A COMMON ONE-PIECE PLATE. MULTIPIECE COVER PLATES ARE NOT ACCEPTABLE.
29. HVAC SYSTEM DUCT SMOKE DETECTORS SHALL BE PROVIDED WHERE INDICATED ON THE SYSTEM DRAWINGS. DUCT
SMOKE DETECTORS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, INSTALLED BY THE CONTRACTOR
RESPONSIBLE FOR THE HVAC WORK, AND CONNECTED TO THE FIRE ALARM SYSTEM BY THE ELECTRICAL
CONTRACTOR.
30. ALL RECEPTACLES INSTALLED ON WALLS WHERE WINDOWS INHIBIT NORMAL INSTALLATION AT 18" AFF, SHALL BE
MOUNTED AT A LESSER HEIGHT ABOVE THE FINISHED FLOOR OR HORIZONTALLY ORIENTED IN THE BASEBOARD.
31. THE ELECTRICAL CONTRACTOR SHALL FIRESTOP, DRAFT STOP, AND/OR PROTECT THE ANNULAR SPACE AROUND ALL
RACEWAY, CONDUIT, WIRE, AND CABLE PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS AND
ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE
AND UL LISTING REQUIREMENTS.
32. THE ELECTRICAL CONTRACTOR SHALL SEAL ALL PENETRATIONS AND OPENINGS AROUND ALL RACEWAY, CONDUIT, WIRE, AND CABLE IN EXISTING AND NEW WALLS WHERE THERE IS AN HVAC PRESSURE DIFFERENTIAL REQUIREMENT.
33. THE ELECTRICAL CONTRACTOR SHALL NOT INSTALL OUTLET BOXES "BACK-TO-BACK". PROVIDE A MINIMUM OF 8"
HORIZONTAL SEPARATION BETWEEN OUTLET BOXES.
34. ALL INTERIOR BRANCH CIRCUITS SHALL BE INSTALLED OVERHEAD INSIDE BUILDINGS.
35. UNDERGROUND EXTERIOR BRANCH CIRCUITS SHALL BE RAN OVERHEAD INSIDE BUILDINGS TO AN EXTERIOR WALL, THEN DOWN BEFORE PENETRATING THE EXTERIOR WALL AND LEAVING THE BUILDING UNDERGROUND.
36. ALL EXTERIOR UNDERGROUND BRANCH CIRCUITS SHALL BE INSTALLED LAST AFTER ALL OTHER UNDERGROUND
UTILITY WORK ASSOCIATED WITH THIS PROJECT IS COMPLETE.
37. THE ELECTRICAL CONTRACTOR SHALL BE ALLOWED TO ROUTE FEEDERS FROM SERVICE SWITCHBOARDS TO
PANELBOARDS, BELOW SLAB INSIDE EACH BUILDING. THEY SHALL KEEP AN ACCURATE SET OF AS-BUILT DRAWINGS
INDICATING DIMENSIONED LOCATIONS OF ALL FEEDERS ROUTED BELOW SLAB.
38. THE ELECTRICAL CONTRACTOR SHALL LABEL EACH RECEPTACLE, DISCONNECT, AND MISCELLANEOUS EQUIPMENT
WITH BOTH THE PANELBOARD AND CIRCUIT NUMBER. PROVIDE SELF ADHESIVE LABEL TO DEVICE COVERPLATE.
39. THE CONTRACTOR SHALL COORDINATE THE SHUTDOWNS WITH OWNER TO SURVEY THE EXISTING CONDITIONS OF
THE ELECTRICAL EQUIPMENT PRIOR TO ORDERING REPLACEMENT PARTS. CONTRACTOR SHALL VERIFY ALL
NECESSARY PARTS, ACCESSORIES, AND TERMINATIONS REQUIRED TO COMPLETE INSTALLATIONS. CONTRACTOR
SHALL PROVIDE A METHOD OF PROCEDURE AND TIMELINE FOR CONSTRUCTION PHASING. CONTRACTOR SHALL
INCLUDE DURATION OF SHUTDOWN FOR EACH PHASE REFERENCED IN THE CONSTRUCTION SCHEDULE
DOCUMENTATION.
(GENERAL NOTES APPLY TO ALL DRAWINGS AND SPECIFICATIONS)
DOUBLE TWIN TUBE
ELECTRICAL
EXHAUST FAN
EMERGENCY
EQUIPMENT
EMPTY CONDUIT
DRAWING(S)
EXISTING
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FIRE ALARM
FURNISHED BY OTHERS
GROUND
HORSEPOWER
ELECTRONIC BALLAST
GROUND FAULT GFI
HP
GND
EXIST
FBO
FACP
EF
EMT
EQUIP
EWH
EWC
EM
DTT
DWG
EC
EB
ASYMMETRICAL
AMPERES
CONDUIT
CATALOG
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
C
CAT
AIC
AFF
AHU
A
INTERRUPTING CURRENT
ABBREVIATIONS
HID HIGH INTENSITY DISCHARGE
EACHEA
ENCLOSED ECB
BELOW FINISHED GRADEBFG
IMC INTERMEDIATE
JB JUNCTION BOX
R1. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR BIDDING ON THIS WORK TO VISIT THE
PROJECT TO FAMILIARIZE THEMSELVES WITH THE FIELD CONDITIONS WHICH MAY INHIBIT OR HINDER THE
EXECUTION OF THEIR WORK. THEY SHALL FIELD VERIFY THE BRANCH CIRCUITS ASSOCIATED WITH THE DEMOLITION
WORK INVOLVED AND THE NEW WORK THAT SHALL BE INVOLVED WITH THE PORTION OF THE CIRCUITS TO BE
DISCONNECTED; WHILE MAINTAINING POWER TO OTHER PORTIONS OF THAT SAME EXISTING CIRCUIT. SUBMITTAL
OF BID SHALL INDICATE THAT A THOROUGH SITE SURVEY HAS BEEN PERFORMED AND THAT THE WORK DESCRIBED
CAN BE PERFORMED AS DESIGNED ON THESE DRAWINGS. IF A DISCREPANCY IS REALIZED AS A RESULT OF THIS
ELECTRICAL CONTRACTOR SITE SURVEY, CONTACT THE PROJECT MANAGER FOR CLARIFICATION PRIOR TO
SUBMITTING BID. SUBMITTAL OF BID SHALL INDICATE THAT A THOROUGH SITE SURVEY HAS BEEN PERFORMED.
NO FUTURE CHANGE ORDERS RELATED TO UNKNOWN DIFFICULTIES OR UNANTICIPATED FIELD CONDITIONS WILL
BE CONSIDERED.
R2. THE DEMOLITION WORK SHALL FOLLOW THE FOLLOWING GUIDELINES AS WELL AS THOSE INDICATED IN
THE SPECIFICATIONS:
A. MAKE NECESSARY MODIFICATIONS AND ADJUSTMENTS TO ALL ELECTRICAL ITEMS AND EQUIPMENT;
BOTH NEW AND EXISTING, AS MAY BE REQUIRED BY THESE ALTERATIONS AND ADDITIONS.
B. DISCONNECT AT THE SOURCE AND REMOVE EXISTING ELECTRICAL MATERIALS AND EQUIPMENT;
INCLUDING BUT NOT LIMITED TO LIGHTING FIXTURES, WIRING DEVICES, SIGNAL EQUIPMENT, CONDUIT
AND WIRES, AND ALL OTHER ELECTRICAL ITEMS WHICH ARE RENDERED OBSOLETE BY THESE ALTERATIONS
AND ADDITIONS. THESE ARE THE PROPERTY OF THE OWNER AND SHALL BE EITHER REMOVED FROM THE SITE
OR RETURNED TO THE OWNER'S STOCK AT THE DISCRETION OF THE OWNER.
C. DISCONNECT, REMOVE, AND RELOCATE EXISTING ELECTRICAL MATERIALS AND EQUIPMENT;INCLUDING
BUT NOT LIMITED TO LIGHTING FIXTURES, WIRING DEVICES, SIGNAL EQUIPMENT, CONDUIT AND WIRES, AND
ALL OTHER ELECTRICAL ITEMS WHICH INTERFERE WITH, OBSTRUCT, OR ARE OBSTRUCTED BY THESE
ALTERATIONS AND ADDITIONS. PERMANENTLY INSTALL SUCH ITEMS IN NEW LOCATIONS AS DIRECTED.
D. ANY EQUIPMENT TO BE RELOCATED AND RECONNECTED SHALL BE CAREFULLY EXAMINED FOR ANY DEFECTS
AND TESTED FOR ELECTRICAL CONTINUITY PRIOR TO RELOCATION. ANY DEFECTS OR MALFUNCTIONS
DETECTED SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE PROJECT MANAGER. AFTER THE
EQUIPMENT HAS BEEN CERTIFIED TO BE IN GOOD ELECTRO/MECHANICAL CONDITION, THE EQUIPMENT MAY BE
RELOCATED AND THOROUGHLY CLEANED AND RETESTED FOR ELECTRICAL CONTINUITY. THE ELECTRICAL
CONTRACTOR SHALL BEAR ALL EXPENSES FOR ANY EQUIPMENT DAMAGED IN THE PROCESS OF
REINSTALLATION AND RELOCATION; AND SHALL REPLACE WITH NEW EQUIPMENT OR PROPERLY REPAIR
ANY DAMAGED EQUIPMENT TO THE SATISFACTION OF THE ENGINEER.
E. IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO MAINTAIN THE EXISTING BUILDING
IN ELECTRICAL OPERATION AT ALL TIMES DURING THE ENTIRE CONSTRUCTION PERIOD. IF IT IS ABSOLUTELY
NECESSARY TO SHUT DOWN THE ELECTRICAL POWER TO THE BUILDING; THE ELECTRICAL CONTRACTOR SHALL
CONSULT WITH THE OWNER AND THE PROJECT MANAGER TO MAKE ARRANGEMENTS TO DO SO AT THE
OWNER'S CONVENIENCE, INCLUDING WEEKENDS. PRIOR NOTICE SHALL BE GIVEN TO THE OWNER AND THE
PROJECT MANAGER 48 HOURS IN ADVANCE OF THE DESIRED SHUT DOWN TIME. ANY PREMIUM OR OVERTIME
COSTS NECESSARY TO ACCOMPLISH THE ABOVE SHALL BE INCLUDED IN BID.
F. ANY ELECTRICAL DEVICE NOT COMPLETELY REMOVED SHALL NOT BE LEFT WITHOUT POWER. THE ELECTRICAL
CONTRACTOR SHALL RECONNECT ANY DEVICE LEFT WITHOUT POWER DUE TO THIS SCOPE OF WORK TO THE
SAME SIZE CIRCUIT(S) AS PREVIOUSLY SERVED.
G. ALL ELECTRICAL EQUIPMENT NOTED TO BE REMOVED SHALL BE DISPOSED OF ACCORDING TO THE
LOCAL AUTHORITY GUIDELINES.
R3. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO COORDINATE ELECTRICAL WORK WITH
OTHER TRADES. PARTICULAR ATTENTION SHOULD BE PAID TO HVAC, PLUMBING, AND FIRE PROTECTION.
WORK SHOULD ALSO BE COORDINATED AROUND PORTABLE AND MOBILE EQUIPMENT.
R4. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR UPDATING THE EXISTING PANELBOARD SCHEDULES
TO REFLECT CHANGES, DELETIONS, AND ADDITIONS BY THE SCOPE OF THIS WORK. ALSO REMOVE ANY NAME
PLATES OR LABELS THAT INCORRECTLY MARK A CIRCUIT. PROVIDE NEW TYPED SCHEDULES FOR EACH
PANELBOARD AFFECTED. PROVIDE NEW SCHEDULES ON #110 CARD STOCK. HANDWRITTEN SCHEDULES ARE
NOT ACCEPTABLE.
R5. ALL EQUIPMENT AND DEVICES SHOWN IN LIGHT LINEWEIGHT ARE EXISTING TO REMAIN. ALL ITEMS SHOWN IN
BOLD/DASHED LINEWEIGHT ARE EXISTING TO BE REMOVED. ALL EQUIPMENT AND DEVICES SHOWN IN BOLD LINEWEIGHT
ARE NEW .
XFMR
WP
VA
V
UH
UNO
TYP
REQD
RTU
RGS
RM
RECEPT
PNL
PB
NEC
NTS
OFCI
NF
NIC
MTG
N
MLO
MT
MTD
MCB
MCCB
LTG
UNLESS NOTED OTHERWISE
VOLT-AMPERE(S)
WEATHERPROOF
TRANSFORMER
VOLT(S)
UNIT HEATER
TYPICAL
RIGID GALVANIZED
REQUIRED
ROOF TOP UNIT
ROOM
PUSH BUTTON
CONTRACTOR INSTALLED
RECEPTACLE
PANEL(S)
OWNER FURNISHED,
NATIONAL ELECTRICAL CODE
NON FUSED
NOT TO SCALE
NOT IN CONTRACT
MOUNTING
MAIN LUGS ONLY
NEUTRAL
MOUNT
MOUNTED
MOLDED CASE
MAIN CIRCUIT BREAKER
LIGHTING
CONDUIT WITH THREE CONDUCTORS, ONE NEUTRAL AND ONE GROUND
F
SD
SD
FIRE ALARM MANUAL PULL STATION, PROVIDE CONDUIT DROP AND JUNCTION BOX.
FIRE ALARM AUDIBLE AND VISUAL SIGNAL DEVICE, PROVIDE CONDUIT DROP AND
JUNCTION BOX.
FIRE ALARM VISUAL STROBE LIGHT, PROVIDE CONDUIT DROP AND JUNCTION BOX.
FIRE ALARM DUCT MOUNTED SMOKE DETECTOR, PROVIDE CONDUIT DROP AND
JUNCTION BOX.
FIRE ALARM AREA SMOKE DETECTOR, PROVIDE CONDUIT DROP AND JUNCTION BOX.
F
CIRCUIT BREAKER
CIRCUIT BREAKER
METALLIC TUBING
CONTROL PANEL
INTERRUPTER
METAL CONDUIT
STEEL CONDUIT
JUNCTION BOX, WALL MOUNTED
J
J
F
"OC"- DUAL TECHNOLOGY WALL OCCUPANCY SENSOR, WATTSTOPPER #DW-100-W
POWER POLE
PP
CEILING MOUNTED DUPLEX RECEPTACLE.
F
FIRE ALARM AUDIBLE AND VISUAL SIGNAL DEVICE, CEILING MOUNTED.
VAV VARIABLE AIR VOLUME
THERMOSTAT BY OTHERS
T
NATIONAL CEMETERY
ADMINISTRATION
OFFICE OF DESIGN
AND CONSTRUCTION
John Gallup & Associates, LLC
3225 Shallowford Rd NE
Marietta, GA 30062
770-321-4040
Atriax Pllc
102 3rd Avenue N.E.
Hickory, NC 28601
Renovation of Administration and
Maintenance Buildings
835CM3036
June 28, 2019
Chattanooga National Cemetery
1200 Bailey Avenue, Chattanooga, TN 37404
Environment & Infrastructure Solutions, Inc.
1075 Big Shanty Road, NW Suite 100
Kennesaw, GA 30144
(770) 421-3400
E-001
ELECTRICAL LEGEND,
ABBREVIATIONS AND NOTES
41MAG AS
RETROFITR
LP-1a
NL
"NL" DENOTES ALWAYS ON NIGHT LIGHTING FIXTURE
"LP" INDICATES POWER CIRCUIT
"1a"SWITCHING CIRCUIT
- INDICATES TAMPER - RESISTANT RECEPTACLE."TR"
DF
DRINKING FOUNTAIN
DC
DOOR CONTACT
MS
MOTION SENSOR
PUSH BUTOON
CARD READER
KEYPAD
CCTV CAMERA
MAGNETIC LOCK
ELECTRONIC LOCK
REQUEST TO EXIT MOTION DEVICE
SECURITY SYMBOL LEGEND
SYMBOL DESCRIPTION
EP
EXPLOSION PROOF
PHOTOCELL
PC
DUAL TECHNOLOGY MOTION SENSOR
TV
WALL MOUNTED POWER AND DATA OUTLET
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Sheet of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PB
AutoCAD SHX Text
CR
AutoCAD SHX Text K
AutoCAD SHX Text
ML
AutoCAD SHX Text
EL
AutoCAD SHX Text
RX
AutoCAD SHX Text
MS
KEY NOTES :
1. PROVIDE (2) 100A/3P/100AF/3R FUSED DISCONNECT SWITCH FOR THE ADMIN AND
RESTROOM TEMPORARY TRAILERS.
2. PROVIDE FEEDER CONSISTING OF (4) #3, (1) #8G, 1-1/4”C BETWEEN FUSED
DISCONNECT SWITCH AND TEMPORARY TRAILER ELECTRICAL SERVICE ENTRANCE
EQUIPMENT. FIELD COORDINATE EXACT FEEDER ROUTING WITH FINAL LOCATION
OF TEMPORARY TRAILER AND THE EXISTING SITE CONDITIONS AS REQUIRED. FIELD
COORDINATE FINAL FEEDER TERMINATIONS WITH TEMPORARY TRAILER
ELECTRICAL SERVICE ENTRANCE EQUIPMENT AS REQUIRED FOR A COMPLETE
INSTALLATION. ASSUME MAXIMUM FEEDER LENGTH OF 100 LINEAR FEET.
ELECTRICAL SITE PLAN
SCALE: 1" = 30'
E-101
NATIONAL CEMETERY
ADMINISTRATION
OFFICE OF DESIGN
AND CONSTRUCTION
John Gallup & Associates, LLC
3225 Shallowford Rd NE
Marietta, GA 30062
770-321-4040
Atriax Pllc
102 3rd Avenue N.E.
Hickory, NC 28601
Renovation of Administration and
Maintenance Buildings
835CM3036
June 28, 2019
Chattanooga National Cemetery
1200 Bailey Avenue, Chattanooga, TN 37404
Environment & Infrastructure Solutions, Inc.
1075 Big Shanty Road, NW Suite 100
Kennesaw, GA 30144
(770) 421-3400
E-101
ELECTRICAL SITE PLAN
42MAG AS
ADMIN BUILDING
TEMPORARY ADMIN TRAILER
RESTROOM BUILDING
TEMPORARY RESTROOM TRAILER
0 30' 60'
Scale: 1" = 30'-0"
SEQUENCE OF CONSTRUCTION NOTES
A. CONTRACTOR TO PREPARE FEEDER BETWEEN EXISTING PANEL 'A' AND
TEMPORARY TRAILERS DISCONNECT SWITCHES PRIOR TO DISABLING ELECTRICAL
SERVICE (TYPICAL FOR TWO INSTALLATIONS).
B. CONTRACTOR SHALL DISABLE EXISTING ELECTRICAL SERVICE AND REMOVE
EXISTING SERVICE ENTRANCE DISCONNECT SWITCH AND EXISTING PANEL 'A'.
C. INSTALL NEW DISCONNECT SWITCH AND NEW PANEL 'A" IN PLACE OF ORIGINAL
CONSTRUCTION. COMPLETE FINAL CONNECTION OF TEMPORARY TRAILERS
DISCONNECT SWITCHES' FEEDERS.
D. RESTORE ELECTRICAL SERVICE. THE BREAKERS AT PANEL 'A' SERVING THE
FOLLOWING LOADS SHALL REMAIN ENERGIZED THROUGHOUT THE DURATION OF
CONSTRUCTION.
· COMMITTAL SHELTER B
· TEMPORARY ADMIN TRAILER
· TEMPORARY RESTROOM TRAILER
THREE ADDITIONAL 20A 1POLE BREAKERS ARE PERMITTED FOR USE TO SUPPORT
TEMPORARY POWER AND LIGHTING DURING CONSTRUCTION. THE REMAINING
BREAKERS SHALL REMAIN IN THE OFF POSITION.
UPON COMPLETION OF CONSTRUCTION IN ADMIN AND RESTROOM BUILDINGS
CONTRACTOR SHALL ENSURE THAT TEMPORARY POWER IS DISCONNECTED FROM
TEMPORARY TRAILER PRIOR TO ENERGIZING PERMANENT BUILDINGS' LOADS.
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text
WV
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Sheet of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
N x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
KEY NOTES :
1. PROVIDE (1) 100A/3P/100AF/3R FUSED DISCONNECT SWITCH FOR
MAINTENANCE TEMPORARY TRAILER.
2. PROVIDE FEEDER CONSISTING OF (4) #3, (1) #8G,1-1/4”C BETWEEN FUSED
DISCONNECT SWITCH AND TEMPORARY TRAILER ELECTRICAL SERVICE
ENTRANCE EQUIPMENT. FIELD COORDINATE EXACT FEEDER ROUTING WITH
FINAL LOCATION OF TEMPORARY TRAILER AND THE EXISTING SITE
CONDITIONS AS REQUIRED. FIELD COORDINATE FINAL FEEDER.
TERMINATIONS WITH TEMPORARY TRAILER ELECTRICAL SERVICE
ENTRANCE EQUIPMENT AS REQUIRED FOR A COMPLETE INSTALLATION.
ASSUME MAXIMUM FEEDER LENGTH OF 100 LINEAR FEET.
3. PROVIDE LED UPLIGHT TO REPLACE EXISTING WALL MOUNTED HID UPLIGHT.
NATIONAL CEMETERY
ADMINISTRATION
OFFICE OF DESIGN
AND CONSTRUCTION
John Gallup & Associates, LLC
3225 Shallowford Rd NE
Marietta, GA 30062
770-321-4040
Atriax Pllc
102 3rd Avenue N.E.
Hickory, NC 28601
Renovation of Administration and
Maintenance Buildings
835CM3036
June 28, 2019
Chattanooga National Cemetery
1200 Bailey Avenue, Chattanooga, TN 37404
Environment & Infrastructure Solutions, Inc.
1075 Big Shanty Road, NW Suite 100
Kennesaw, GA 30144
(770) 421-3400
E-102
ELECTRICAL SITE PLAN
43MAG AS
2 ELECTRICAL SITE PLAN
SCALE: 1" = 30'
E-102
MAINTENANCE BUILDING
MAINTENANCE TEMPORARY TRAILER
0 30' 60'
Scale: 1" = 30'-0"
AutoCAD SHX Text D
AutoCAD SHX Text
WV
AutoCAD SHX Text D
AutoCAD SHX Text
WV
AutoCAD SHX Text D
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Sheet of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
N
GFI
GFI
AH-1
AH-2
CU-1
J
J
WH EF
DIRECTOR
LOBBY
RECEPTION
CONFERENCE
UTILITY
MECH TOILET
OPEN OFFICE
HALL
G
DIRECTOR
LOBBY
RECEPTION
CONFERENCE
UTILITY
MECH TOILET
OPEN OFFICE
HALL
NATIONAL CEMETERY
ADMINISTRATION
OFFICE OF DESIGN
AND CONSTRUCTION
John Gallup & Associates, LLC
3225 Shallowford Rd NE
Marietta, GA 30062
770-321-4040
Atriax Pllc
102 3rd Avenue N.E.
Hickory, NC 28601
Renovation of Administration and
Maintenance Buildings
835CM3036
June 28, 2019
Chattanooga National Cemetery
1200 Bailey Avenue, Chattanooga, TN 37404
Environment & Infrastructure Solutions, Inc.
1075 Big Shanty Road, NW Suite 100
Kennesaw, GA 30144
(770) 421-3400
EA101
ADMINISTRATION BUILDING
POWER AND LIGHTING
DEMOLITION PLANS
Break Area
SCALE: 1/4" = 1'-0"
ADMINISTRATION BUILDING - LIGHTING DEMOLITION PLAN1
EA101
MAG AS
SCALE: 1/4" = 1'-0"
ADMINISTRATION BUILDING - POWER DEMOLITION PLAN
EA101
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
1. DISCONNECT AND REMOVE EXISTING PANEL 'A'. MAINTAIN ASSOCIATED
FEEDER CIRCUIT CONDUCTORS AND CONDUIT FOR RECONNECTION
UNLESS OTHERWISE NOTED.
2. DISCONNECT AND REMOVE EXISTING FUSED DISCONNECT SWITCH.
MAINTAIN ASSOCIATED FEEDER CIRCUIT CONDUCTORS AND CONDUIT
FOR RECONNECTION.
3. FIELD VERIFY EXISTING ELECTRICAL DEVICES IN THIS ROOM.
(ELECTRICAL DEVICES INCLUDE BUT ARE NOT LIMITED TO RECEPTACLES,
SWITCHES, DISCONNECT, DATA OUTLETS ETC.) DISCONNECT AND
REMOVE VERIFIED ELECTRICAL DEVICES. DISCONNECT AND REMOVE
ASSOCIATED BRANCH CIRCUIT CONDUCTORS BACK TO PANEL SOURCE.
REMOVE ASSOCIATED BRANCH CIRCUIT CONDUITS BETWEEN DEVICE
AND LOCAL JUNCTION BOX(ES) ABOVE LAY-IN CEILING OR HARD CEILING.
MAINTAIN CONDUITS BETWEEN CEILING MOUNTED JUNCTION BOX(ES)
AND PANEL SOURCE. REFER TO ARCHITECTURE DEMOLITION PLAN
AA-101 AND AA102.
4. EXISTING AIR HANDLING UNIT (AHU) SCHEDULED TO BE REMOVED.
DISCONNECT AND REMOVE EXISTING LOCAL DISCONNECT SERVING
EQUIPMENT (NOT SHOWN). DISCONNECT AND REMOVE ASSOCIATED
BRANCH CIRCUIT CONDUCTORS AND CONDUIT BETWEEN UNIT AND
PANEL SOURCE. DISCONNECT AND REMOVE ALL ASSOCIATED CONTROLS
CONDUCTORS AND CONDUIT WHEN APPLICABLE.
5. EXISTING EXHAUST FAN (EF) SCHEDULED TO BE REMOVED IN THIS
ROOM. REMOVE ASSOCIATED BRANCH CIRCUIT CONDUCTORS AND
CONDUIT BETWEEN UNIT AND LOCAL JUNCTION BOX. MAINTAIN BRANCH
CIRCUIT AT JUNCTION BOX FOR EXTENSION.
6. EXISTING CONDENSING UNIT (CU) SCHEDULED TO BE REMOVED.
DISCONNECT AND REMOVE EXISTING LOCAL DISCONNECT SERVING
EQUIPMENT. DISCONNECT AND REMOVE ASSOCIATED BRANCH CIRCUIT
CONDUCTORS AND CONDUIT BETWEEN UNIT AND PANEL SOURCE.
DISCONNECT AND REMOVE ALL ASSOCIATED CONTROLS CONDUCTORS
AND CONDUIT WHEN APPLICABLE.
7. EXISTING WATER HEATER (WH) SCHEDULED TO BE REMOVED IN THIS
ROOM. REMOVE ASSOCIATED BRANCH CIRCUIT CONDUCTORS AND
CONDUIT BETWEEN UNIT AND LOCAL JUNCTION BOX. MAINTAIN BRANCH
CIRCUIT AT JUNCTION BOX FOR EXTENSION.
1. DISCONNECT AND REMOVE EXISTING 2'X4' RECESSED LIGHT FIXTURE.
DISCONNECT AND REMOVE ASSOCIATED LIGHTING BRANCH CIRCUIT
CONDUCTORS AND CONDUIT BACK TO LOCAL JUNCTION BOX ABOVE
ACCESSIBLE CEILING. MAINTAIN LIGHTING BRANCH CIRCUIT(S) AT
JUNCTION BOX FOR REUSE.
2. DISCONNECT AND REMOVE EXISTING SURFACE STRIP LIGHT FIXTURE.
DISCONNECT AND REMOVE ASSOCIATED LIGHTING BRANCH CIRCUIT
CONDUCTORS AND CONDUIT BACK TO LOCAL JUNCTION BOX ABOVE
ACCESSIBLE CEILING. MAINTAIN LIGHTING BRANCH CIRCUIT(S) AT
JUNCTION BOX FOR REUSE.
3. DISCONNECT AND REMOVE EXISTING RECESSED DOWNLIGHT
FIXTURE. DISCONNECT AND REMOVE ASSOCIATED LIGHTING BRANCH
CIRCUIT CONDUCTORS AND CONDUIT BACK TO LOCAL JUNCTION BOX
ABOVE HARD CEILING. MAINTAIN LIGHTING BRANCH CIRCUIT(S) AT
JUNCTION BOX FOR REUSE.
4. DISCONNECT EXISTING RECESSED DOWNLIGHT FIXTURE. MAINTAIN
FIXTURE BRANCH CIRCUIT CONDUCTORS AND MOUNTING FRAME TO
BE RETROFITTED.
5. DISCONNECT AND REMOVE EXISTING " BUGEYE" EMERGENCY
FIXTURE. DISCONNECT AND REMOVE ASSOCIATED LIGHTING BRANCH
CIRCUIT CONDUCTORS AND CONDUIT BACK TO LOCAL JUNCTION BOX
ABOVE HARD CEILING.
6. FIELD VERIFY EXISTING LIGHTING CONTROL DEVICES. DISCONNECT
AND REMOVE VERIFIED LIGHTING CONTROL DEVICES. REMOVE
ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT
BETWEEN LIGHT FIXTURE AND LOCAL JUNCTION BOX ABOVE HARD
CEILING OR ACCESSIBLE CEILING. DISCONNECT AND REMOVE
ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT
BETWEEN LIGHTING CONTROL DEVICES AND PANEL SOURCE. REFER
TO ARCHITECTURE DEMOLITION PLAN AA-101 AND AA102.
GFI (WP)
GFI
(WP)
GFI
(WP)
GFI
(WP)
GFI
(WP)
GFI
(WP)
KEY NOTES LIGHTING DEMOLITION PLAN:
KEY NOTES POWER DEMOLITION PLAN
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Sheet of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text Scale: 1/4" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
Scale: 1/4" = 1'-0"
OC
S
B1B1
B3
B1
B1 B1E
B1
B1
B1
C1E
C1
C1E
C2
C2
C2
C2
A3E
A3E
B1
B3
B3
E1
X1
E1
X1
X1
X1
O C
S
O C
S O
C S
OCS
OC
OC
S
S
S
NL
NL
C1E
S
S
F2
C1
C1
C1C1
C1
C1C1
C1E
C1C1
C1
C1 a b a b
OC
OC
OC
NL
NL
S c c c c
B1 B1
C1
S a
W1
PC
PC
UTILITY
MECH
TOILET
FILES
OFFICE
BREAK AREA
DIRECTOR
RECEPTION
LOBBY
CONFERENCE
DF
LOCKERS
OPEN
OFFICE
CONFERENCE
HALL
F
F
F
F
F
F
F
F
F
F
SD
SD
F
F
F
T V
UTILITY
MECH
TOILET
FILES
OFFICE
BREAK AREA
DIRECTOR
RECEPTION
LOBBY
CONFERENCE
DF
LOCKERS
OPEN
OFFICE
CONFERENCE
HALL
NATIONAL CEMETERY
ADMINISTRATION
OFFICE OF DESIGN
AND CONSTRUCTION
John Gallup & Associates, LLC
3225 Shallowford Rd NE
Marietta, GA 30062
770-321-4040
Atriax Pllc
102 3rd Avenue N.E.
Hickory, NC 28601
Renovation of Administration and
Maintenance Buildings
835CM3036
June 28, 2019
Chattanooga National Cemetery
1200 Bailey Avenue, Chattanooga, TN 37404
Environment & Infrastructure Solutions, Inc.
1075 Big Shanty Road, NW Suite 100
Kennesaw, GA 30144
(770) 421-3400
EA102
ADMINISTRATION BUILDING
POWER AND LIGHTING NEW
WORK PLANS
Break Area
SCALE: 1/4" = 1'-0"
ADMINISTRATION BUILDING - POWER AND SYSTEM PLAN
EA102
0 2' 4' 8'
Scale: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
ADMINISTRATION BUILDING - LIGHTING PLAN
EA102
0 2' 4' 8'
Scale: 1/4" = 1'-0"
1. PROVIDE 2'X4' RECESSED LED LIGHT FIXTURE IN ROOM OR SPACE AS
INDICATED. EXTEND NEAREST LIGHTING BRANCH CIRCUIT CONDUCTORS
AND CONDUIT FROM LOCAL JUNCTION BOX ABOVE ACCESSIBLE CEILING
MAINTAINED FROM DEMOLITION TO LIGHT FIXTURE.
2. PROVIDE 4' NARROW STRIP LIGHT SURFACE MOUNTED IN THIS ROOM OR
SPACE AS INDICATED. EXTEND LIGHTING BRANCH CIRCUIT CONDUCTORS
AND CONDUIT FROM LOCAL JUNCTION BOX ABOVE ACCESSIBLE CEILING
MAINTAINED FROM DEMOLITION TO LIGHT FIXTURE.
3. PROVIDE WALL MOUNTED EXIT SIGN WITH BATTERY BACKUP. EXTEND
NEAREST LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT TO EXIT
SIGN.
4. PROVIDE 2'X2' RECESSED LED LIGHT FIXTURE IN ROOM OR SPACE AS
INDICATED. EXTEND NEAREST LIGHTING BRANCH CIRCUIT CONDUCTORS
AND CONDUIT FROM LOCAL JUNCTION BOX ABOVE ACCESSIBLE CEILING
MAINTAINED FROM DEMOLITION TO LIGHT FIXTURE.
5. PROVIDE LINE VOLTAGE WALL MOUNTED, LIGHT SWITCH WITH INFRARED
OCCUPANCY SENSOR. EXTEND LIGHTING BRANCH CIRCUIT CONDUCTOR
AND CONDUIT TO SWITCH.
6. PROVIDE LINE VOLTAGE CEILING MOUNTED, DUAL TECHNOLOGY
OCCUPANCY SENSOR. EXTEND LIGHTING BRANCH CIRCUIT CONDUCTOR
AND CONDUIT TO SENSOR.
7. PROVIDE EMERGENCY EGRESS LIGHT FIXTURE. EXTEND LIGHTING BRANCH
CIRCUIT CONDUCTORS AND CONDUIT FROM LOCAL JUNCTION BOX TO
EGRESS LIGHT FIXTURE.
8. PROVIDE RETROFIT DOWNLIGHT FIXTURES MOUNTED IN THE EXISTING
FRAME MAINTAINED FROM DEMOLITION.
9. PROVIDE LINE VOLTAGE WALL MOUNTED, LIGHT SWITCH WITH ULTRASOUND
OCCUPANCY SENSOR. EXTEND LIGHTING BRANCH CIRCUIT CONDUCTOR
AND CONDUIT TO SWITCH.
10. PROVIDE 4' STRIP LIGHT SURFACE MOUNTED . EXTEND LIGHTING BRANCH
CIRCUIT CONDUCTORS AND CONDUIT FROM LOCAL JUNCTION BOX ABOVE
ACCESSIBLE CEILING MAINTAINED FROM DEMOLITION TO LIGHT FIXTURE.
11. PROVIDE TOGGLE SWITCH. EXTEND LIGHTING BRANCH CIRCUIT
CONDUCTORS AND CONDUIT TO SWITCH.
12. PROVIDE RECESSED LED DOWNLIGHT FIXTURE IN ROOM OR SPACE AS
INDICATED. EXTEND NEAREST LIGHTING BRANCH CIRCUIT CONDUCTORS
AND CONDUIT FROM LOCAL JUNCTION BOX ABOVE ACCESSIBLE CEILING
MAINTAINED FROM DEMOLITION TO LIGHT FIXTURE. INTERFACE CONTROL
AS INDICATED. ADJUST WIRING OF FIXTURES WITH (NL) DESIGNATION TO
ENSURE THEY OPERATE AS NIGHT LIGHT (UNSWITCHED).
13. EXTERIOR LIGHT FIXTURES SHALL BE CONTROLLED BY NEW EXTERIOR
PHOTOCELL MOUNTED ON ROOF, FACING NORTH, WITH AN UNOBSTRUCTED
VIEW OF THE SKY.
14. PROVIDE WALLPACK FIXTURE FOR EXTERIOR LIGHTING MOUNTED ABOVE
DOOR . EXTEND LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT
FROM LOCAL JUNCTION BOX TO WALLPACK FIXTURE. WALLPACK FIXTURE
SHALL BE CONTROLLED VIA INTEGRATED PHOTOCELL AND POWERED BY
CIRCUIT INDICATED.
1. PROVIDE NEW 208/120V, 3PH, 4W , 225A MAIN LUG ONLY PANEL 'A'.
CONNECT TO EXISTING FEEDER MAINTAINED DURING DEMOLITION.
CONNECT EXISTING BRANCH CIRCUITS MAINTAINED DURING DEMOLITION
TO PANEL.
2. PROVIDE NEW 400A/3P/225AF/3R FUSED DISCONNECT SWITCH. CONNECT
TO EXISTING FEEDER MAINTAINED DURING DEMOLITION TO PANEL 'A'.
3. PROVIDE TWO (2) TEMPORARY FUSED DISCONNECT SWITCHES TO SERVE
ADMIN AND RESTROOM TEMPORARY TRAILERS. REFER TO RISER DIAGRAM
FOR ADDITIONAL INFORMATION.
4. PROVIDE (2) 2" CONDUITS TO RESTROOM BUILDING FOR INTERCONNECTION
OF FIRE ALARM.
5. PROVIDE NEW FEEDER CONDUCTOR AND CONDUIT. CONNECT TO PANEL 'T'
IN THE RESTROOM BUILDING. REFER TO RISER DIAGRAM ON SHEET E-601
FOR FEEDER CONDUCTOR AND CONDUIT SIZES.
6. PROVIDE DUPLEX RECEPTACLE(S) IN THIS ROOM OR SPACE AS INDICATED.
PROVIDE BRANCH CIRCUIT CONDUCTORS AND CONDUIT. CONNECT TO
PANEL AND CIRCUIT INDICATED.
7. PROVIDE GFI DUPLEX RECEPTACLE. PROVIDE BRANCH CIRCUIT
CONDUCTORS AND CONDUIT. CONNECT TO PANEL AND CIRCUIT INDICATED.
8. PROVIDE NEW FIRE ALARM CONTROL PANEL. CONNECT TO A DEDICATED
CIRCUIT AS INDICATED.
9. PROVIDE FIRE ALARM ANNUNCIATOR PANEL IN DIRECTOR'S OFFICE.
CONNECT TO A DEDICATED CIRCUIT.
10. PROVIDE FIRE ALARM INITIATION DEVICES. REFER TO DETAIL 1 ON E-502
FOR RISER DIAGRAM.
11. PROVIDE 208V, 60A, 2-POLE FUSED DISCONNECT SWITCH IN NEMA 3R
ENCLOSURE FOR CONDENSING UNIT. FIELD COORDINATE EXACT LOCATION
AND ELEVATION OF DISCONNECT PLACEMENT WITH EXISTING
CONSTRUCTION AND EQUIPMENT. PROVIDE BRANCH CIRCUIT
CONDUCTORS AND CONDUIT BETWEEN EQUIPMENT AND PANEL SOURCE.
CONNECT TO PANEL AND CIRCUITS INDICATED. PROVIDE ALL CONTROLS
WIRING AND RACEWAY AS REQUIRED FOR A COMPLETE INSTALLATION.
12. PROVIDE MOTOR RATED TOGGLE SWITCH FOR FAN COIL UNIT. PROVIDE
BRANCH CIRCUIT CONDUCTORS AND CONDUIT. CONNECT TO PANEL AND
CIRCUIT INDICATED.
13. PROVIDE BRANCH CIRCUIT CONDUCTORS AND CONDUIT FOR EXHAUST FAN.
CONNECT TO PANEL AND CIRCUIT INDICATED. INTERFACE CONTROLS WITH
LOCAL OCCUPANCY SENSOR. REFER TO ADMINISTRATION BUILDING -
LIGHTING PLAN FOR CIRCUITING. COORDINATE LOCATION WITH
MECHANICAL DRAWINGS AND MECHANICAL CONTRACTOR PRIOR TO
INSTALLATION.
14. PROVIDE FIRE ALARM NOTIFICATION APPLIANCE.REFER TO DETAIL 1 ON
E-502 FOR RISER DIAGRAM.
15. RECONNECT EXISTING FEEDER CONDUIT MAINTAINED DURING DEMOLITION
TO PANEL "CSP" IN COMMITTAL SHELTER B.
16. PROVIDE GFI DUPLEX RECEPTACLE. PROVIDE DEDICATED BRANCH CIRCUIT
CONDUCTORS AND CONDUIT FOR DRINKING FOUNTAIN. CONNECT TO
PANEL AND CIRCUIT INDICATED.
17. PROVIDE BRANCH CIRCUIT CONDUCTORS AND CONDUIT FOR INSTANT
WATER HEATER. CONNECT TO PANEL AND CIRCUIT INDICATED.
18. PROVIDE DEDICATED CIRCUIT FOR SECURITY PANEL. SEE PANEL
SCHEDULE FOR PANEL 'A'.
19. PROVIDE (2) 100A, 3-POLE BRANCH CIRCUIT BREAKER TO PROVIDE POWER
TO THE ADMIN AND RESTROOM TEMPORARY TRAILERS. REFER TO
SEQUENCE OF CONSTRUCTION NOTES ON SHEET E-101.
20. PROVIDE CAT-6 DATA OUTLET AND DEDICATED RECEPTACLE FOR WALL
MOUNTED FLAT PANEL TV.
PANEL 'A'
MAG AS
GFI
GFI
GFI (WP)
C
C
G F
I
W
P
C
GFI
(TYP.)
(TYP.)
(TYP)
CU-1
FCU-1
("15CD")
("15CD")
("15CD")
("15CD")
("15CD")
("15CD")
("15CD")
("15CD")
("15CD")
CU-2
FCU-2
EF-1
A-21
A-23
A-24
A- 39, 41
A- 40, 42
GFI
GFI
1 5 15
IWH-1
A- 17, 19
A-1 A-1
A-1
A-1
A-1 A-1
A-1
A-1
A-1
A-1 A-1
A-1 A-1
A-1 A-1
A-1
A-1
A-1
A-1
A-1
A-1
A-1
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2
A-2 A-2
A-2 A-2
A-2
D
TR
TR
A-3
A-3
A-4
A-3
A-3
A-3
A-4
A-4
A-4
A-4
A-4
A-6
A-15
A-15
A-14
A-14
A-5
A-5
A-7
A-7
A-7
A-7
A-7
A-9
A-9
A-9
A-9
A-9
A-9
A-11
A-8
A-8
A-8
GFI (WP)
GFI (WP)
GFI (WP)
GFI (WP)
A-3
A-13
A-13
A-13
A-8
A-7
(TYP)
(TYP.)
A-10
A-2
A-1
(TYP.)
(TYP)
A-2
KEY NOTES LIGHTING NEW WORK PLAN:
KEY NOTES POWER NEW WORK PLAN:
(TYP.)
(TYP.)
A-1
(TYP.)
A-16
GFI
A-2
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
A-18
AutoCAD SHX Text
FACP
AutoCAD SHX Text
FAA
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Sheet of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DF
LOCKERS
FX
MS
MS
MS
MS
MS
MS
MS
D C
C R
SD
SD
CR
E L
C R
DC
EL
D C
E L
ML
ML
ML
CR
DC
DC
DC
RX
RX
RX
R X
R X
PB
PB
D C
MS
MS
K
CR
UTILITY
MECH
TOILET
FILES
OFFICE
BREAK AREA
DIRECTOR
RECEPTION
LOBBY
CONFERENCE
DF
LOCKERS
OPEN
OFFICE
CONFERENCE
HALL
FX
NATIONAL CEMETERY
ADMINISTRATION
OFFICE OF DESIGN
AND CONSTRUCTION
John Gallup & Associates, LLC
3225 Shallowford Rd NE
Marietta, GA 30062
770-321-4040
Atriax Pllc
102 3rd Avenue N.E.
Hickory, NC 28601
Renovation of Administration and
Maintenance Buildings
835CM3036
June 28, 2019
Chattanooga National Cemetery
1200 Bailey Avenue, Chattanooga, TN 37404
Environment & Infrastructure Solutions, Inc.
1075 Big Shanty Road, NW Suite 100
Kennesaw, GA 30144
(770) 421-3400
EA103
ADMINISTRATION BUILDING
TELECOM PLAN
Break Area
SCALE: 1/4" = 1'-0"
ADMINISTRATION BUILDING - TELECOM AND SECURITY PLAN
EA103
0 2' 4' 8'
Scale: 1/4" = 1'-0"
KEY NOTES TELECOM AND SECURITY PLAN:
1. ALL CABLING TO BE PLENUM RATED. CABLING SHALL BE INSTALLED
IN J-HOOKS ABOVE THE DROP CEILING. CABLING TO BE SECURED TO
LADDER RACKS TRANSITIONING BELOW CEILING TO EQUIPMENT
ROOM.
2. DATA OUTLETS TO BE INSTALLED WITH 2-CAT 6 DATA JACKS AND
1-CAT 6 PHONE JACK.
3. ALL CCTV AND INTRUSION DETECTION SYSTEM (IDS) JUNCTION
BOXES TO BE PAINTED BLUE.
4. MAIN CROSS CONNECT RACK 7'Hx19"Wx3D", ALL DATA ETHERNET
CABLES TO TERMINATE TO CONTRACTOR PROVIDED PATCH PANEL
USING T568B CONNECTION STANDARDS.
5. PROVIDE WALL MOUNTED LOCKABLE CCTV HEADEND, CCTV
NETWORK TO UTILIZE POE CAMERAS AND SHALL BE SEPARATE FROM
THE BUILDING HORIZONTAL CABLING. CCTV HEADEND TO HAVE
REMOTE MANAGEMENT. CCTV HEADEND TO BE INSTALLED WITH A
5KVA UPS. SERVER TO BE INSTALLED WITH 1U PULL OUT FLAT
SCREEN/KEYBOARD FOR LOCAL VIEWING.
6. PROVIDE INTRUSION DETECTION SYSTEM (IDS). IDS TO MONITOR
DOOR CONTACTS AND MOTION DETECTORS. IDS TO BE EQUIPPED
WITH AUTO DIALER TO BASE SECURITY AND 76 HOUR BATTERY
BACKUP.
7. PROVIDE PACS HEADEND AND DC POWER SUPPLY WITH 76 HOUR
BATTERY BACKUP. PACS SYSTEM TO BE MANAGED WITH AND USE
STANDARD FEDERAL GSA CARD TECHNOLOGY.
8. PROVIDE CEILING MOUNTED IP CAMERA. CAMERAS MOUNTED
EXTERIOR SHALL BE RATED FOR EXTERIOR USE. PROVIDE ETHERNET
SURGE PROTECTORS FOR ALL CABLE LEAVING BUILDING ENVELOPE.
9. PROVIDE DUAL TECHNOLOGY MOTION SENSORS TIED TO. IDS TO BE
EQUIPPED WITH AUTO DIALER TO BASE SECURITY. PHYSICAL
ACCESS CONTROL SYSTEM (PACS) DOOR CONTACTS TO INTERFACE
WITH IDS.
10. WIRELESS ACCESS POINT, PROVIDE TWO CAT 6 CABLES EACH UNIT,
COORDINATE WITH COR FOR EXACT PLACEMENT.
11. IDS REMOTE KEY PAD. MOUNTED AT 48" AFF. KEYPAD TO HAVE
DISPLAY SCREEN AND SYSTEM ARMED INDICATOR LIGHTS.
12. PROVIDE (2) SHEETS OF 48" X 96" X
", FIRE RATED, VOID FREE, AC
GRADE PLYWOOD. MOUNT WITH "A" SIDE OUT. PAINTED WITH A FIRE
RESISTANT PAINT, DO NOT PAINT OVER FIRE RATED LABEL. MOUNT
WITH THE PLYWOOD BOTTOM AT 8" AFF.
13. PROVIDE A 12" X 4" X
" COPPER GROUND BAR WITH 2" ISOLATORS
MOUNTED TO WALL PROVIDE TWO HOLE LUGS ON ALL
CONNECTIONS. HOMERUN #3/0 AWG CU CONDUCTOR TO THE PANEL
P-1 GROUND BAR IN UTILITY ROOM.
14. COORDINATE WITH TELECOM PROVIDER FOR THE RELOCATION AND
INSTALLATION OF DEMARCATION EQUIPMENT.
15. PROVIDE LADDER TYPE CABLE TRAY MOUNTED AT +7'-6" ABOVE
FINISHED FLOOR.
16. PROVIDE 1-4" PVC SCHD 80 BURIED CONDUIT FROM MECHANICAL
ROOM TO RESTROOM BUILDING FOR SECURITY CIRCUITS.
17. PROVIDE 1-2" PVC SCHD 80 BURIED CONDUIT FROM UTILITY ROOM TO
TEMPORARY TRAILER LOCATION FOR ISP CIRCUITS. INTERNET
SERVICE TO MAINTAIN FUNCTIONAL DURING CONSTRUCTION.
18. CARD READER. PROVIDE JUNCTION BOX WHERE SHOWN. INTERFACE
WITH DOOR HARDWARE. PROVIDE ALL NECESSARY DOOR
EQUIPMENT PROVIDE POWER FROM CENTRAL PACS POWER SUPPLY.
REFER TO DETAIL 07 ON SHEET E-602 FOR MORE INFORMATION.
MAG AS
6 7
AutoCAD SHX Text
IDS
AutoCAD SHX Text
CCTV HE
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Sheet of
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UTILITY
WOMEN'S
RESTROOM
MEN'S
RESTROOM
WP
GFI
HVAC
UNIT
PANEL T
100A/2P/SN/RT
NON-FUSED DISC
EF
WH
UTILITY
WOMEN'S
RESTROOM
MEN'S
RESTROOM
NATIONAL CEMETERY
ADMINISTRATION
OFFICE OF DESIGN
AND CONSTRUCTION
John Gallup & Associates, LLC
3225 Shallowford Rd NE
Marietta, GA 30062
770-321-4040
Atriax Pllc
102 3rd Avenue N.E.
Hickory, NC 28601
Renovation of Administration and
Maintenance Buildings
835CM3036
June 28, 2019
Chattanooga National Cemetery
1200 Bailey Avenue, Chattanooga, TN 37404
Environment & Infrastructure Solutions, Inc.
1075 Big Shanty Road, NW Suite 100
Kennesaw, GA 30144
(770) 421-3400
0 1' 2' 4'
Scale: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
RESTROOM BUILDING - LIGHTING DEMOLITION PLAN
EB101
EB101
PUBLIC RESTROOM BUILDING
POWER AND LIGHTING
DEMOLITION PLANS
47MAG AS
0 1' 2' 4'
Scale: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
RESTROOM BUILDING - POWER DEMOLITION PLAN
EB101
KEY NOTES LIGHTING DEMOLITION PLAN:
1. DISCONNECT AND REMOVE EXISTING 2'X4' RECESSED LIGHT FIXTURE. DISCONNECT AND REMOVE
ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT BACK TO SOURCE.
2. DISCONNECT AND REMOVE EXISTING PENDENT STRIP LIGHT FIXTURE. DISCONNECT AND REMOVE
ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT BACK TO SOURCE.
3. DISCONNECT EXISTING RECESSED DOWNLIGHT FIXTURES. DISCONNECT AND REMOVE
ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT BACK TO SOURCE.
4. DISCONNECT AND REMOVE EXISTING " BUGEYE" EMERGENCY FIXTURE. DISCONNECT AND
REMOVE ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT BACK TO LOCAL
JUNCTION BOX ABOVE HARD CEILING.
5. DISCONNECT AND REMOVE EXISTING LIGHT SWITCH. DISCONNECT AND REMOVE ASSOCIATED
LIGHTING BRANCH CIRCUIT AND CONDUCTORS AND CONDUIT BACK TO SOURCE.
KEY NOTES POWER DEMOLITION PLAN:
1. DISCONNECT AND REMOVE EXISTING PANEL 'T'. DISCONNECT AND
REMOVE ASSOCIATED FEEDER CIRCUIT CONDUCTORS AND CONDUIT.
RECONNECT EXISTING BRANCH CIRCUIT CONDUCTOR UNLESS
OTHERWISE NOTED.
2. DISCONNECT AND REMOVE EXISTING NON-FUSED DISCONNECT
SWITCH. DISCONNECT AND REMOVE ASSOCIATED FEEDER CIRCUIT
CONDUCTORS AND CONDUIT. UNLESS OTHERWISE NOTED.
3. EXISTING HVAC UNIT SCHEDULED TO BE REMOVED. DISCONNECT AND
REMOVE EXISTING LOCAL DISCONNECT SWITCH SERVING EQUIPMENT.
DISCONNECT AND REMOVE ASSOCIATED BRANCH CIRCUIT
CONDUCTORS AND CONDUIT BETWEEN UNIT AND PANEL SOURCE.
DISCONNECT AND REMOVE ALL ASSOCIATED CONTROLS
CONDUCTORS AND CONDUIT WHEN APPLICABLE.
4. EXISTING WATER HEATER (WH) SCHEDULED TO BE REMOVED.
DISCONNECT AND REMOVE ASSOCIATED BRANCH CIRCUIT
CONDUCTORS AND CONDUIT BETWEEN UNIT AND SOURCE.
5. EXISTING…