36C78619B0021-015.pdf

PDF 13 MB Posted

Attached to
835-036 Chattanooga TN Renovate Admin, Maint. (VA-19-00078715)
Solicitation number
36C78619B0021
Issued by

About this file

36C78619B0021 190820 CNC 835-036 Bid Drawings Final_3of3.pdf

View the file

Other files

File Type Posted
36C78619B0021-0006001.jpg JPG image
36C78619B0021-0006000.docx DOCX document
36C78619B0021-0005000.docx DOCX document
36C78619B0021-0005001.xlsx XLSX spreadsheet
36C78619B0021-0004000.docx DOCX document
36C78619B0021-0004001.docx DOCX document
36C78619B0021-0003001.pdf PDF
36C78619B0021-0003000.docx DOCX document
36C78619B0021-0002000.docx DOCX document
36C78619B0021-0001000.docx DOCX document
36C78619B0021-013.pdf PDF
36C78619B0021-009.pdf PDF
36C78619B0021-006.docx DOCX document
36C78619B0021-016.pdf PDF
36C78619B0021-011.pdf PDF
36C78619B0021-014.pdf PDF
36C78619B0021-008.pdf PDF
36C78619B0021-012.pdf PDF
36C78619B0021-007.pdf PDF
36C78619B0021-010.docx DOCX document
36C78619B0021-000.docx DOCX document
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SURFACE MOUNTED PANELBOARD.

SURFACE MOUNTED DUAL CHANNEL RACEWAY WIREMOLD SERIES 5400, 120VAC,

20A. MOUNT 48" AFF TO TOP OF RACEWAY. ONE OUTLET EVERY 24".

MOTOR, HORSEPOWER AS INDICATED.

FLUSH MOUNTED DUPLEX CONVENIENCE OUTLET NEMA 5-20R, 120V, 20 AMP,

3 WIRE, MOUNTED 18" AFF, "*" IF SUBSCRIPT APPLIES, SEE BELOW:

- INDICATES GROUND FAULT INTERRUPTING TYPE.

- INDICATES COUNTER TOP RECEPTACLE MOUNTED 6" ABOVE

"GFI"

"WP"

"C"

- INDICATES WEATHERPROOF COVER.

COUNTER TOP.

JUNCTION BOX, CEILING MOUNTED

5 HP

MAGNETIC MOTOR STARTER, "*" SUBSCRIPT INDICATES STARTER SIZE.

COMBINATION MAGNETIC MOTOR STARTER, RATINGS AS INDICATED (AMPS/POLES/

HEAVY DUTY DISCONNECT SWITCH, RATINGS AS INDICATED (AMPS/POLES/

DRY TYPE TRANSFORMER WITH VOLTAGES, KVA, AND PHASES AS

NAMEPLATE DATA. "*" SUBSCRIPT INDICATES STARTER SIZE.

"HOA" - INDICATES "HAND-OFF-AUTO" SELECTOR SWITCH MOUNTED ON DOOR.

/ENCLOSURE). NON-FUSED SWITCH TYPE. OVERLOADS SIZED PER MOTOR

"00" - INDICATES "ON-OFF" SELECTOR SWITCH MOUNTED ON DOOR.

HOMERUN TO PANEL INDICATED (XX) AND CIRCUIT NUMBER INDICATED (YY).

ELECTRICAL SYMBOL LEGEND

CONDUIT TURNING UP

CONDUIT ROUTED EXPOSED

CONDUIT TURNING DOWN

EQUIPMENT AS NOTED.

/ENCLOSURE) FUSED IF INDICATED.

EXAMPLE OF WIRING AND CONDUIT NOTATION.

3#10, #10G, 1"C

30/3/3R

HOA

SHOWN ON DRAWINGS.

SYMBOL

T

DESCRIPTION

CONDUIT ROUTED CONCEALED ABOVE DROPPED CEILING AND/OR WALLS.

XX-YY

- INDICATES DEDICATED CIRCUIT."D"

ONE CIRCUIT: PROVIDE 2#12, #12G, 3/4"C, UNO

TWO CIRCUITS: PROVIDE 3#12, #12G, 3/4"C, UNO

THREE CIRCUITS: PROVIDE 4#12, #12G, 3/4"C, UNO

30/3/1

"a" - LOWER CASE LETTER INDICATES SWITCHING ARRANGEMENT

SINGLE FACE EXIT LIGHT CEILING OR PENDANT MOUNTED W/ BATTERY BACKUP.

LIGHTED FACE. MATCH EXISTING.

DOUBLE FACE EXIT LIGHT CEILING OR PENDANT MOUNTED W/ BATTERY BACKUP.

SAME AS ABOVE, EXCEPT WALL MOUNTED

(ARROWS INDICATE DIRECTION OF TRAFFIC). MATCH EXISTING.

(ARROWS INDICATE DIRECTION OF TRAFFIC). SHADED SIDE INDICATES SIDE WITH

* IF SUBSCRIPT APPLIES, SEE BELOW:

SINGLE POLE LIGHT SWITCH, FLUSH MOUNTED 48" AFF, 120/277V, 20AMP.

ON STRIKE SIDE OF DOOR OR WHERE OTHERWISE INDICATED ON PLANS.

A1

"K" - KEY OPERATED SINGLE POLE SWITCH. SWITCH SHALL INTERRUPT

UNSWITCHED PHASE CONDUCTOR SERVING EMERGENCY LIGHTING

UNITS FOR TESTING PURPOSES.

18" AFF

18"AFF

48" AFF

18" AFF

48" AFF

TYPICAL DEVICE MOUNTING HEIGHT

1' ABOVE DOOR

7'-6" AFF (UNO)

MATCH EXISTING

48" AFF

18" AFF

MATCH EXISTINGFIRE ALARM PULL STATION

UNLESS NOTED OTHERWISE.

EXIT LIGHTS (WALL MTD.)

AUDIO/VIDEO OUTLETS

ANNUNCIATOR PANELS

FIRE ALARM AUDIO/VISUAL ALARM

EMERGENCY LIGHTS (WALL MTD.)

NOTE: DIMENSIONS ARE TO DEVICE CENTERLINE

LIGHT SWITCHES

RECEPTACLES (OFFICE AREA)

COMPUTER OUTLETS

TELEPHONE OUTLETS

TELEPHONE OUTLET (WALL MTD.)

PUSHBUTTON

B1

OR

RECESSED MOUNTED PANELBOARD.

2'X4' LED TROFFER. "A1" INDICATES FIXTURE TYPE FROM FIXTURE SCHEDULE.

SAME AS ABOVE, EXCEPT RECEPTACLE IS QUADRAPLEX TYPE.

LED STRIP FIXTURE "B1" INDICATES FIXTURE TYPE FROM FIXTURE SCHEDULE.

A2

SAME AS ABOVE EXCEPT FIXTURE TO BE USED FOR EGRESS.

OR

B2

JUNCTION BOX FOR DATA/TELEPHONE OUTLET WITH 3/4" EMPTY CONDUIT

STUBBED INTO ACCESSIBLE CEILING. PROVIDE PULL STRING.

GENERAL ELECTRICAL RENOVATION NOTES

(GENERAL NOTES APPLY TO ALL DRAWINGS AND SPECIFICATIONS)

GENERAL ELECTRICAL CONSTRUCTION NOTES

1. THE ELECTRICAL INSTALLATION SHALL CONFORM TO THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, THE

AMERICANS WITH DISABILITIES ACT, AND OTHER APPLICABLE STATE AND LOCAL CODES.

2. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE WORK OF THEIR TRADE WITH THAT OF THE OTHER TRADES

INVOLVED IN THE PROJECT. CONFLICTS WITH OTHER TRADES SHALL BE BROUGHT TO THE ATTENTION OF THE

PROJECT MANAGER PRIOR TO INSTALLATION. WORK SHOULD ALSO BE COORDINATED AROUND PORTABLE AND

MOBILE EQUIPMENT.

3. THE ELECTRICAL CONTRACTOR SHALL SCHEDULE THEIR WORK SO THAT THE CONSTRUCTION SCHEDULE IS

MAINTAINED.

4. THE ELECTRICAL CONTRACTOR SHALL REQUEST A COMPLETE SET OF THE HVAC, PLUMBING, AND FIRE PROTECTION

DRAWINGS TO VERIFY CONNECTIONS TO THE EQUIPMENT.

5. THE ELECTRICAL CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS PRIOR TO INSTALLING ANY EQUIPMENT

ABOVE CEILINGS AND IN MECHANICAL ROOMS.

6. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. THE ELECTRICAL CONTRACTOR SHALL VERIFY EXACT FIELD

CONDITIONS AND DIMENSIONS PRIOR TO COMMENCING WORK.

7. THE ELECTRICAL CONTRACTOR SHALL FURNISH MATERIALS AND LABOR FOR A COMPLETE ELECTRICAL INSTALLATION

AS INDICATED IN THESE DOCUMENTS. MATERIAL, APPARATUS, AND EQUIPMENT SHALL BE NEW AND SHALL BEAR THE

UNDERWRITERS LABEL WHERE APPLICABLE.

8. THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY LIGHTING AND POWER SERVICE WHILE THE

BUILDING/RENOVATION AREA IS UNDER CONSTRUCTION ACCORDING TO CURRENT OSHA STANDARDS.

9. ALL CIRCUITS SHALL CONTAIN AN EQUIPMENT GROUNDING CONDUCTOR (GREEN COLORED INSULATION) ROUTED IN

CONDUIT AND SIZED AS INDICATED.

10. THE ELECTRICAL CONTRACTOR SHALL BE ALLOWED TO USE 3/4" MINIMUM ELECTRIC METALLIC TUBING (EMT) IN ALL

AREAS NOT EXPOSED TO PHYSICAL DAMAGE. COMPRESSION FITTINGS WITH INSULATED THROATS SHALL BE USED

FOR EMT CONDUITS 1-1/4" AND SMALLER. LARGER CONDUITS (1-1/2" AND GREATER) SHALL UTILIZE SET SCREW TYPE

FITTINGS.

11. ALL CONDUIT EXPOSED TO PHYSICAL DAMAGE (15'-0" AFF & BELOW) SHALL BE INTERMEDIATE METAL CONDUIT (IMC).

12. ALL CONDUITS BELOW GRADE SHALL BE PVC. ALL ELBOWS TURNING UP TOWARD ABOVE GRADE, AND ALL CONDUITS

EXPOSED ABOVE GRADE SHALL BE IMC.

13. FLEXIBLE (TYPE MC) CABLE SHALL BE ALLOWED FOR THE FLEXIBLE CONNECTIONS TO VIBRATING EQUIPMENT AND

RECESSED LIGHTING FIXTURES IN LAY-IN TYPE CEILINGS. A GROUNDING CONDUCTOR SHALL BE INCLUDED WITH THE

POWER CONDUCTORS INSIDE THE FLEXIBLE CONNECTION.

14. THE ELECTRICAL CONTRACTOR SHALL BE ALLOWED TO RUN LOW VOLTAGE (UNDER 100V) CONDUCTORS AND

COMMUNICATIONS OR FIRE ALARM CABLING EXPOSED, BUNDLED, AND TIE WRAPPED BY USING PLENUM RATED

CABLES. ALL DROPS TO DEVICES SHALL BE IN ACCORDANCE WITH NOTE 10 ABOVE.

15. ALL CONDUIT RUNS SHALL BE MADE EITHER PARALLEL OR PERPENDICULAR TO STRUCTURAL MEMBERS.

16. THE ELECTRICAL CONTRACTOR SHALL UTILIZE TYPE THHN/THWN-2 CONDUCTORS IN ALL AREAS EXCEPT WHERE

SERVICE ENTRANCE CONDUCTORS ARE PROVIDED AS PART OF THE SCOPE OF WORK. WHERE SERVICE ENTRANCE

CONDUCTORS ARE PROVIDED AS PART OF THE SCOPE OF WORK THEY SHALL UTILIZE TYPE XHHW INSULATION.

17. THE ELECTRICAL CONTRACTOR SHALL PROVIDE COPPER CONDUCTORS. CONDUCTORS SHALL BE SOLID FOR SIZES

#10 AWG AND SMALLER. CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED.

18. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A SEPARATE RACEWAY SYSTEM FOR THE 208Y/120V

CIRCUITS/FEEDERS AND CONTROL CIRCUITS.

19. THE ELECTRICAL CONTRACTOR SHALL LIMIT LIGHTING AND RECEPTACLE BRANCH CIRCUIT HOMERUNS TO 5

CONDUCTORS: 3 PHASE CONDUCTORS, 1 NEUTRAL CONDUCTOR, AND 1 EQUIPMENT GROUNDING CONDUCTOR.

20. WIRES AND CABLES SHALL BE PULLED UTILIZING AN APPROVED PULLING LUBRICANT. OIL OR GREASE NOT

SPECIFICALLY LISTED FOR USE AS A CABLE PULLING LUBRICANT IS NOT PERMITTED.

21. WIRES AND CABLES SHALL BE INSTALLED WITHOUT JOINTS OR SPLICES INSOFAR AS PRACTICAL. WRITTEN APPROVAL

SHALL BE REQUESTED FROM THE ENGINEER PRIOR TO APPLICATION OF ANY SPLICES OR JOINTS.

22. THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE FOLLOWING COLOR CODING OF CIRCUITS/FEEDERS.

CIRCUITS/FEEDERS RATED 208Y/120V: PHASE "A" = BLACK

PHASE "B" = RED

PHASE "C" = BLUE

NEUTRAL = WHITE

GROUNDING = GREEN

ISOLATED G = GREEN/YELLOW STRIPE

23. RECESSED TYPE LIGHTING FIXTURES SHALL BE LOCATED AS INDICATED ON THE ARCHITECTURAL REFLECTED

CEILING PLAN.

24. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL CEILING CONSTRUCTION BEFORE ORDERING LIGHTING FIXTURES

AND SHALL PROVIDE CORRECT MOUNTING HARDWARE WITHOUT ADDITIONAL COST. LIGHTING FIXTURES SHALL BE AS

SCHEDULED, INCLUDING LAMPS.

25. ALL DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE, AND FUSIBLE WHERE INDICATED.

26. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ADDITIONAL SUPPORT FOR ALL ELECTRICAL

EQUIPMENT WHERE THE BUILDING STRUCTURE IS NOT SUITABLE FOR A PROPERLY SUPPORTED INSTALLATION.

27. THE ELECTRICAL CONTRACTOR SHALL PROVIDE AN OUTLET BOX FOR EACH LIGHTING FIXTURE, WIRING DEVICE, OR

JUNCTION POINT. ELECTRICAL BOXES SHALL BE OF SUFFICIENT CAPACITY FOR THE NUMBER OF CONDUCTORS AND

SPLICES WITHIN THE BOX; IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE.

28. DEVICE PLATES SHALL BE INSTALLED ON OUTLETS FOR ALL SWITCHES, RECEPTACLES, ETC. AND COLOR SHALL BE

AS SELECTED BY ARCHITECT. WHERE MORE THAN ONE SWITCH IS INDICATED IN THE SAME LOCATION, SWITCHES

SHALL BE GANGED UNDER A COMMON ONE-PIECE PLATE. MULTIPIECE COVER PLATES ARE NOT ACCEPTABLE.

29. HVAC SYSTEM DUCT SMOKE DETECTORS SHALL BE PROVIDED WHERE INDICATED ON THE SYSTEM DRAWINGS. DUCT

SMOKE DETECTORS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, INSTALLED BY THE CONTRACTOR

RESPONSIBLE FOR THE HVAC WORK, AND CONNECTED TO THE FIRE ALARM SYSTEM BY THE ELECTRICAL

CONTRACTOR.

30. ALL RECEPTACLES INSTALLED ON WALLS WHERE WINDOWS INHIBIT NORMAL INSTALLATION AT 18" AFF, SHALL BE

MOUNTED AT A LESSER HEIGHT ABOVE THE FINISHED FLOOR OR HORIZONTALLY ORIENTED IN THE BASEBOARD.

31. THE ELECTRICAL CONTRACTOR SHALL FIRESTOP, DRAFT STOP, AND/OR PROTECT THE ANNULAR SPACE AROUND ALL

RACEWAY, CONDUIT, WIRE, AND CABLE PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS AND

ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE

AND UL LISTING REQUIREMENTS.

32. THE ELECTRICAL CONTRACTOR SHALL SEAL ALL PENETRATIONS AND OPENINGS AROUND ALL RACEWAY, CONDUIT, WIRE, AND CABLE IN EXISTING AND NEW WALLS WHERE THERE IS AN HVAC PRESSURE DIFFERENTIAL REQUIREMENT.

33. THE ELECTRICAL CONTRACTOR SHALL NOT INSTALL OUTLET BOXES "BACK-TO-BACK". PROVIDE A MINIMUM OF 8"

HORIZONTAL SEPARATION BETWEEN OUTLET BOXES.

34. ALL INTERIOR BRANCH CIRCUITS SHALL BE INSTALLED OVERHEAD INSIDE BUILDINGS.

35. UNDERGROUND EXTERIOR BRANCH CIRCUITS SHALL BE RAN OVERHEAD INSIDE BUILDINGS TO AN EXTERIOR WALL, THEN DOWN BEFORE PENETRATING THE EXTERIOR WALL AND LEAVING THE BUILDING UNDERGROUND.

36. ALL EXTERIOR UNDERGROUND BRANCH CIRCUITS SHALL BE INSTALLED LAST AFTER ALL OTHER UNDERGROUND

UTILITY WORK ASSOCIATED WITH THIS PROJECT IS COMPLETE.

37. THE ELECTRICAL CONTRACTOR SHALL BE ALLOWED TO ROUTE FEEDERS FROM SERVICE SWITCHBOARDS TO

PANELBOARDS, BELOW SLAB INSIDE EACH BUILDING. THEY SHALL KEEP AN ACCURATE SET OF AS-BUILT DRAWINGS

INDICATING DIMENSIONED LOCATIONS OF ALL FEEDERS ROUTED BELOW SLAB.

38. THE ELECTRICAL CONTRACTOR SHALL LABEL EACH RECEPTACLE, DISCONNECT, AND MISCELLANEOUS EQUIPMENT

WITH BOTH THE PANELBOARD AND CIRCUIT NUMBER. PROVIDE SELF ADHESIVE LABEL TO DEVICE COVERPLATE.

39. THE CONTRACTOR SHALL COORDINATE THE SHUTDOWNS WITH OWNER TO SURVEY THE EXISTING CONDITIONS OF

THE ELECTRICAL EQUIPMENT PRIOR TO ORDERING REPLACEMENT PARTS. CONTRACTOR SHALL VERIFY ALL

NECESSARY PARTS, ACCESSORIES, AND TERMINATIONS REQUIRED TO COMPLETE INSTALLATIONS. CONTRACTOR

SHALL PROVIDE A METHOD OF PROCEDURE AND TIMELINE FOR CONSTRUCTION PHASING. CONTRACTOR SHALL

INCLUDE DURATION OF SHUTDOWN FOR EACH PHASE REFERENCED IN THE CONSTRUCTION SCHEDULE

DOCUMENTATION.

(GENERAL NOTES APPLY TO ALL DRAWINGS AND SPECIFICATIONS)

DOUBLE TWIN TUBE

ELECTRICAL

EXHAUST FAN

EMERGENCY

EQUIPMENT

EMPTY CONDUIT

DRAWING(S)

EXISTING

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FIRE ALARM

FURNISHED BY OTHERS

GROUND

HORSEPOWER

ELECTRONIC BALLAST

GROUND FAULT GFI

HP

GND

EXIST

FBO

FACP

EF

EMT

EQUIP

EWH

EWC

EM

DTT

DWG

EC

EB

ASYMMETRICAL

AMPERES

CONDUIT

CATALOG

ABOVE FINISHED FLOOR

AIR HANDLING UNIT

C

CAT

AIC

AFF

AHU

A

INTERRUPTING CURRENT

ABBREVIATIONS

HID HIGH INTENSITY DISCHARGE

EACHEA

ENCLOSED ECB

BELOW FINISHED GRADEBFG

IMC INTERMEDIATE

JB JUNCTION BOX

R1. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR BIDDING ON THIS WORK TO VISIT THE

PROJECT TO FAMILIARIZE THEMSELVES WITH THE FIELD CONDITIONS WHICH MAY INHIBIT OR HINDER THE

EXECUTION OF THEIR WORK. THEY SHALL FIELD VERIFY THE BRANCH CIRCUITS ASSOCIATED WITH THE DEMOLITION

WORK INVOLVED AND THE NEW WORK THAT SHALL BE INVOLVED WITH THE PORTION OF THE CIRCUITS TO BE

DISCONNECTED; WHILE MAINTAINING POWER TO OTHER PORTIONS OF THAT SAME EXISTING CIRCUIT. SUBMITTAL

OF BID SHALL INDICATE THAT A THOROUGH SITE SURVEY HAS BEEN PERFORMED AND THAT THE WORK DESCRIBED

CAN BE PERFORMED AS DESIGNED ON THESE DRAWINGS. IF A DISCREPANCY IS REALIZED AS A RESULT OF THIS

ELECTRICAL CONTRACTOR SITE SURVEY, CONTACT THE PROJECT MANAGER FOR CLARIFICATION PRIOR TO

SUBMITTING BID. SUBMITTAL OF BID SHALL INDICATE THAT A THOROUGH SITE SURVEY HAS BEEN PERFORMED.

NO FUTURE CHANGE ORDERS RELATED TO UNKNOWN DIFFICULTIES OR UNANTICIPATED FIELD CONDITIONS WILL

BE CONSIDERED.

R2. THE DEMOLITION WORK SHALL FOLLOW THE FOLLOWING GUIDELINES AS WELL AS THOSE INDICATED IN

THE SPECIFICATIONS:

A. MAKE NECESSARY MODIFICATIONS AND ADJUSTMENTS TO ALL ELECTRICAL ITEMS AND EQUIPMENT;

BOTH NEW AND EXISTING, AS MAY BE REQUIRED BY THESE ALTERATIONS AND ADDITIONS.

B. DISCONNECT AT THE SOURCE AND REMOVE EXISTING ELECTRICAL MATERIALS AND EQUIPMENT;

INCLUDING BUT NOT LIMITED TO LIGHTING FIXTURES, WIRING DEVICES, SIGNAL EQUIPMENT, CONDUIT

AND WIRES, AND ALL OTHER ELECTRICAL ITEMS WHICH ARE RENDERED OBSOLETE BY THESE ALTERATIONS

AND ADDITIONS. THESE ARE THE PROPERTY OF THE OWNER AND SHALL BE EITHER REMOVED FROM THE SITE

OR RETURNED TO THE OWNER'S STOCK AT THE DISCRETION OF THE OWNER.

C. DISCONNECT, REMOVE, AND RELOCATE EXISTING ELECTRICAL MATERIALS AND EQUIPMENT;INCLUDING

BUT NOT LIMITED TO LIGHTING FIXTURES, WIRING DEVICES, SIGNAL EQUIPMENT, CONDUIT AND WIRES, AND

ALL OTHER ELECTRICAL ITEMS WHICH INTERFERE WITH, OBSTRUCT, OR ARE OBSTRUCTED BY THESE

ALTERATIONS AND ADDITIONS. PERMANENTLY INSTALL SUCH ITEMS IN NEW LOCATIONS AS DIRECTED.

D. ANY EQUIPMENT TO BE RELOCATED AND RECONNECTED SHALL BE CAREFULLY EXAMINED FOR ANY DEFECTS

AND TESTED FOR ELECTRICAL CONTINUITY PRIOR TO RELOCATION. ANY DEFECTS OR MALFUNCTIONS

DETECTED SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE PROJECT MANAGER. AFTER THE

EQUIPMENT HAS BEEN CERTIFIED TO BE IN GOOD ELECTRO/MECHANICAL CONDITION, THE EQUIPMENT MAY BE

RELOCATED AND THOROUGHLY CLEANED AND RETESTED FOR ELECTRICAL CONTINUITY. THE ELECTRICAL

CONTRACTOR SHALL BEAR ALL EXPENSES FOR ANY EQUIPMENT DAMAGED IN THE PROCESS OF

REINSTALLATION AND RELOCATION; AND SHALL REPLACE WITH NEW EQUIPMENT OR PROPERLY REPAIR

ANY DAMAGED EQUIPMENT TO THE SATISFACTION OF THE ENGINEER.

E. IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO MAINTAIN THE EXISTING BUILDING

IN ELECTRICAL OPERATION AT ALL TIMES DURING THE ENTIRE CONSTRUCTION PERIOD. IF IT IS ABSOLUTELY

NECESSARY TO SHUT DOWN THE ELECTRICAL POWER TO THE BUILDING; THE ELECTRICAL CONTRACTOR SHALL

CONSULT WITH THE OWNER AND THE PROJECT MANAGER TO MAKE ARRANGEMENTS TO DO SO AT THE

OWNER'S CONVENIENCE, INCLUDING WEEKENDS. PRIOR NOTICE SHALL BE GIVEN TO THE OWNER AND THE

PROJECT MANAGER 48 HOURS IN ADVANCE OF THE DESIRED SHUT DOWN TIME. ANY PREMIUM OR OVERTIME

COSTS NECESSARY TO ACCOMPLISH THE ABOVE SHALL BE INCLUDED IN BID.

F. ANY ELECTRICAL DEVICE NOT COMPLETELY REMOVED SHALL NOT BE LEFT WITHOUT POWER. THE ELECTRICAL

CONTRACTOR SHALL RECONNECT ANY DEVICE LEFT WITHOUT POWER DUE TO THIS SCOPE OF WORK TO THE

SAME SIZE CIRCUIT(S) AS PREVIOUSLY SERVED.

G. ALL ELECTRICAL EQUIPMENT NOTED TO BE REMOVED SHALL BE DISPOSED OF ACCORDING TO THE

LOCAL AUTHORITY GUIDELINES.

R3. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO COORDINATE ELECTRICAL WORK WITH

OTHER TRADES. PARTICULAR ATTENTION SHOULD BE PAID TO HVAC, PLUMBING, AND FIRE PROTECTION.

WORK SHOULD ALSO BE COORDINATED AROUND PORTABLE AND MOBILE EQUIPMENT.

R4. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR UPDATING THE EXISTING PANELBOARD SCHEDULES

TO REFLECT CHANGES, DELETIONS, AND ADDITIONS BY THE SCOPE OF THIS WORK. ALSO REMOVE ANY NAME

PLATES OR LABELS THAT INCORRECTLY MARK A CIRCUIT. PROVIDE NEW TYPED SCHEDULES FOR EACH

PANELBOARD AFFECTED. PROVIDE NEW SCHEDULES ON #110 CARD STOCK. HANDWRITTEN SCHEDULES ARE

NOT ACCEPTABLE.

R5. ALL EQUIPMENT AND DEVICES SHOWN IN LIGHT LINEWEIGHT ARE EXISTING TO REMAIN. ALL ITEMS SHOWN IN

BOLD/DASHED LINEWEIGHT ARE EXISTING TO BE REMOVED. ALL EQUIPMENT AND DEVICES SHOWN IN BOLD LINEWEIGHT

ARE NEW .

XFMR

WP

VA

V

UH

UNO

TYP

REQD

RTU

RGS

RM

RECEPT

PNL

PB

NEC

NTS

OFCI

NF

NIC

MTG

N

MLO

MT

MTD

MCB

MCCB

LTG

UNLESS NOTED OTHERWISE

VOLT-AMPERE(S)

WEATHERPROOF

TRANSFORMER

VOLT(S)

UNIT HEATER

TYPICAL

RIGID GALVANIZED

REQUIRED

ROOF TOP UNIT

ROOM

PUSH BUTTON

CONTRACTOR INSTALLED

RECEPTACLE

PANEL(S)

OWNER FURNISHED,

NATIONAL ELECTRICAL CODE

NON FUSED

NOT TO SCALE

NOT IN CONTRACT

MOUNTING

MAIN LUGS ONLY

NEUTRAL

MOUNT

MOUNTED

MOLDED CASE

MAIN CIRCUIT BREAKER

LIGHTING

CONDUIT WITH THREE CONDUCTORS, ONE NEUTRAL AND ONE GROUND

F

SD

SD

FIRE ALARM MANUAL PULL STATION, PROVIDE CONDUIT DROP AND JUNCTION BOX.

FIRE ALARM AUDIBLE AND VISUAL SIGNAL DEVICE, PROVIDE CONDUIT DROP AND

JUNCTION BOX.

FIRE ALARM VISUAL STROBE LIGHT, PROVIDE CONDUIT DROP AND JUNCTION BOX.

FIRE ALARM DUCT MOUNTED SMOKE DETECTOR, PROVIDE CONDUIT DROP AND

JUNCTION BOX.

FIRE ALARM AREA SMOKE DETECTOR, PROVIDE CONDUIT DROP AND JUNCTION BOX.

F

CIRCUIT BREAKER

CIRCUIT BREAKER

METALLIC TUBING

CONTROL PANEL

INTERRUPTER

METAL CONDUIT

STEEL CONDUIT

JUNCTION BOX, WALL MOUNTED

J

J

F

"OC"- DUAL TECHNOLOGY WALL OCCUPANCY SENSOR, WATTSTOPPER #DW-100-W

POWER POLE

PP

CEILING MOUNTED DUPLEX RECEPTACLE.

F

FIRE ALARM AUDIBLE AND VISUAL SIGNAL DEVICE, CEILING MOUNTED.

VAV VARIABLE AIR VOLUME

THERMOSTAT BY OTHERS

T

NATIONAL CEMETERY

ADMINISTRATION

OFFICE OF DESIGN

AND CONSTRUCTION

John Gallup & Associates, LLC

3225 Shallowford Rd NE

Marietta, GA 30062

770-321-4040

Atriax Pllc

102 3rd Avenue N.E.

Hickory, NC 28601

Renovation of Administration and

Maintenance Buildings

835CM3036

June 28, 2019

Chattanooga National Cemetery

1200 Bailey Avenue, Chattanooga, TN 37404

Environment & Infrastructure Solutions, Inc.

1075 Big Shanty Road, NW Suite 100

Kennesaw, GA 30144

(770) 421-3400

E-001

ELECTRICAL LEGEND,

ABBREVIATIONS AND NOTES

41MAG AS

RETROFITR

LP-1a

NL

"NL" DENOTES ALWAYS ON NIGHT LIGHTING FIXTURE

"LP" INDICATES POWER CIRCUIT

"1a"SWITCHING CIRCUIT

- INDICATES TAMPER - RESISTANT RECEPTACLE."TR"

DF

DRINKING FOUNTAIN

DC

DOOR CONTACT

MS

MOTION SENSOR

PUSH BUTOON

CARD READER

KEYPAD

CCTV CAMERA

MAGNETIC LOCK

ELECTRONIC LOCK

REQUEST TO EXIT MOTION DEVICE

SECURITY SYMBOL LEGEND

SYMBOL DESCRIPTION

EP

EXPLOSION PROOF

PHOTOCELL

PC

DUAL TECHNOLOGY MOTION SENSOR

TV

WALL MOUNTED POWER AND DATA OUTLET

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Sheet of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PB

AutoCAD SHX Text

CR

AutoCAD SHX Text K

AutoCAD SHX Text

ML

AutoCAD SHX Text

EL

AutoCAD SHX Text

RX

AutoCAD SHX Text

MS

KEY NOTES :

1. PROVIDE (2) 100A/3P/100AF/3R FUSED DISCONNECT SWITCH FOR THE ADMIN AND

RESTROOM TEMPORARY TRAILERS.

2. PROVIDE FEEDER CONSISTING OF (4) #3, (1) #8G, 1-1/4”C BETWEEN FUSED

DISCONNECT SWITCH AND TEMPORARY TRAILER ELECTRICAL SERVICE ENTRANCE

EQUIPMENT. FIELD COORDINATE EXACT FEEDER ROUTING WITH FINAL LOCATION

OF TEMPORARY TRAILER AND THE EXISTING SITE CONDITIONS AS REQUIRED. FIELD

COORDINATE FINAL FEEDER TERMINATIONS WITH TEMPORARY TRAILER

ELECTRICAL SERVICE ENTRANCE EQUIPMENT AS REQUIRED FOR A COMPLETE

INSTALLATION. ASSUME MAXIMUM FEEDER LENGTH OF 100 LINEAR FEET.

ELECTRICAL SITE PLAN

SCALE: 1" = 30'

E-101

NATIONAL CEMETERY

ADMINISTRATION

OFFICE OF DESIGN

AND CONSTRUCTION

John Gallup & Associates, LLC

3225 Shallowford Rd NE

Marietta, GA 30062

770-321-4040

Atriax Pllc

102 3rd Avenue N.E.

Hickory, NC 28601

Renovation of Administration and

Maintenance Buildings

835CM3036

June 28, 2019

Chattanooga National Cemetery

1200 Bailey Avenue, Chattanooga, TN 37404

Environment & Infrastructure Solutions, Inc.

1075 Big Shanty Road, NW Suite 100

Kennesaw, GA 30144

(770) 421-3400

E-101

ELECTRICAL SITE PLAN

42MAG AS

ADMIN BUILDING

TEMPORARY ADMIN TRAILER

RESTROOM BUILDING

TEMPORARY RESTROOM TRAILER

0 30' 60'

Scale: 1" = 30'-0"

SEQUENCE OF CONSTRUCTION NOTES

A. CONTRACTOR TO PREPARE FEEDER BETWEEN EXISTING PANEL 'A' AND

TEMPORARY TRAILERS DISCONNECT SWITCHES PRIOR TO DISABLING ELECTRICAL

SERVICE (TYPICAL FOR TWO INSTALLATIONS).

B. CONTRACTOR SHALL DISABLE EXISTING ELECTRICAL SERVICE AND REMOVE

EXISTING SERVICE ENTRANCE DISCONNECT SWITCH AND EXISTING PANEL 'A'.

C. INSTALL NEW DISCONNECT SWITCH AND NEW PANEL 'A" IN PLACE OF ORIGINAL

CONSTRUCTION. COMPLETE FINAL CONNECTION OF TEMPORARY TRAILERS

DISCONNECT SWITCHES' FEEDERS.

D. RESTORE ELECTRICAL SERVICE. THE BREAKERS AT PANEL 'A' SERVING THE

FOLLOWING LOADS SHALL REMAIN ENERGIZED THROUGHOUT THE DURATION OF

CONSTRUCTION.

· COMMITTAL SHELTER B

· TEMPORARY ADMIN TRAILER

· TEMPORARY RESTROOM TRAILER

THREE ADDITIONAL 20A 1POLE BREAKERS ARE PERMITTED FOR USE TO SUPPORT

TEMPORARY POWER AND LIGHTING DURING CONSTRUCTION. THE REMAINING

BREAKERS SHALL REMAIN IN THE OFF POSITION.

UPON COMPLETION OF CONSTRUCTION IN ADMIN AND RESTROOM BUILDINGS

CONTRACTOR SHALL ENSURE THAT TEMPORARY POWER IS DISCONNECTED FROM

TEMPORARY TRAILER PRIOR TO ENERGIZING PERMANENT BUILDINGS' LOADS.

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text

WV

AutoCAD SHX Text

WV

AutoCAD SHX Text

WV

AutoCAD SHX Text

WV

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text

WV

AutoCAD SHX Text

WV

AutoCAD SHX Text

WV

AutoCAD SHX Text

WV

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Sheet of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

N x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x

KEY NOTES :

1. PROVIDE (1) 100A/3P/100AF/3R FUSED DISCONNECT SWITCH FOR

MAINTENANCE TEMPORARY TRAILER.

2. PROVIDE FEEDER CONSISTING OF (4) #3, (1) #8G,1-1/4”C BETWEEN FUSED

DISCONNECT SWITCH AND TEMPORARY TRAILER ELECTRICAL SERVICE

ENTRANCE EQUIPMENT. FIELD COORDINATE EXACT FEEDER ROUTING WITH

FINAL LOCATION OF TEMPORARY TRAILER AND THE EXISTING SITE

CONDITIONS AS REQUIRED. FIELD COORDINATE FINAL FEEDER.

TERMINATIONS WITH TEMPORARY TRAILER ELECTRICAL SERVICE

ENTRANCE EQUIPMENT AS REQUIRED FOR A COMPLETE INSTALLATION.

ASSUME MAXIMUM FEEDER LENGTH OF 100 LINEAR FEET.

3. PROVIDE LED UPLIGHT TO REPLACE EXISTING WALL MOUNTED HID UPLIGHT.

NATIONAL CEMETERY

ADMINISTRATION

OFFICE OF DESIGN

AND CONSTRUCTION

John Gallup & Associates, LLC

3225 Shallowford Rd NE

Marietta, GA 30062

770-321-4040

Atriax Pllc

102 3rd Avenue N.E.

Hickory, NC 28601

Renovation of Administration and

Maintenance Buildings

835CM3036

June 28, 2019

Chattanooga National Cemetery

1200 Bailey Avenue, Chattanooga, TN 37404

Environment & Infrastructure Solutions, Inc.

1075 Big Shanty Road, NW Suite 100

Kennesaw, GA 30144

(770) 421-3400

E-102

ELECTRICAL SITE PLAN

43MAG AS

2 ELECTRICAL SITE PLAN

SCALE: 1" = 30'

E-102

MAINTENANCE BUILDING

MAINTENANCE TEMPORARY TRAILER

0 30' 60'

Scale: 1" = 30'-0"

AutoCAD SHX Text D

AutoCAD SHX Text

WV

AutoCAD SHX Text D

AutoCAD SHX Text

WV

AutoCAD SHX Text D

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Sheet of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

N

GFI

GFI

AH-1

AH-2

CU-1

J

J

WH EF

DIRECTOR

LOBBY

RECEPTION

CONFERENCE

UTILITY

MECH TOILET

OPEN OFFICE

HALL

G

DIRECTOR

LOBBY

RECEPTION

CONFERENCE

UTILITY

MECH TOILET

OPEN OFFICE

HALL

NATIONAL CEMETERY

ADMINISTRATION

OFFICE OF DESIGN

AND CONSTRUCTION

John Gallup & Associates, LLC

3225 Shallowford Rd NE

Marietta, GA 30062

770-321-4040

Atriax Pllc

102 3rd Avenue N.E.

Hickory, NC 28601

Renovation of Administration and

Maintenance Buildings

835CM3036

June 28, 2019

Chattanooga National Cemetery

1200 Bailey Avenue, Chattanooga, TN 37404

Environment & Infrastructure Solutions, Inc.

1075 Big Shanty Road, NW Suite 100

Kennesaw, GA 30144

(770) 421-3400

EA101

ADMINISTRATION BUILDING

POWER AND LIGHTING

DEMOLITION PLANS

Break Area

SCALE: 1/4" = 1'-0"

ADMINISTRATION BUILDING - LIGHTING DEMOLITION PLAN1

EA101

MAG AS

SCALE: 1/4" = 1'-0"

ADMINISTRATION BUILDING - POWER DEMOLITION PLAN

EA101

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

1. DISCONNECT AND REMOVE EXISTING PANEL 'A'. MAINTAIN ASSOCIATED

FEEDER CIRCUIT CONDUCTORS AND CONDUIT FOR RECONNECTION

UNLESS OTHERWISE NOTED.

2. DISCONNECT AND REMOVE EXISTING FUSED DISCONNECT SWITCH.

MAINTAIN ASSOCIATED FEEDER CIRCUIT CONDUCTORS AND CONDUIT

FOR RECONNECTION.

3. FIELD VERIFY EXISTING ELECTRICAL DEVICES IN THIS ROOM.

(ELECTRICAL DEVICES INCLUDE BUT ARE NOT LIMITED TO RECEPTACLES,

SWITCHES, DISCONNECT, DATA OUTLETS ETC.) DISCONNECT AND

REMOVE VERIFIED ELECTRICAL DEVICES. DISCONNECT AND REMOVE

ASSOCIATED BRANCH CIRCUIT CONDUCTORS BACK TO PANEL SOURCE.

REMOVE ASSOCIATED BRANCH CIRCUIT CONDUITS BETWEEN DEVICE

AND LOCAL JUNCTION BOX(ES) ABOVE LAY-IN CEILING OR HARD CEILING.

MAINTAIN CONDUITS BETWEEN CEILING MOUNTED JUNCTION BOX(ES)

AND PANEL SOURCE. REFER TO ARCHITECTURE DEMOLITION PLAN

AA-101 AND AA102.

4. EXISTING AIR HANDLING UNIT (AHU) SCHEDULED TO BE REMOVED.

DISCONNECT AND REMOVE EXISTING LOCAL DISCONNECT SERVING

EQUIPMENT (NOT SHOWN). DISCONNECT AND REMOVE ASSOCIATED

BRANCH CIRCUIT CONDUCTORS AND CONDUIT BETWEEN UNIT AND

PANEL SOURCE. DISCONNECT AND REMOVE ALL ASSOCIATED CONTROLS

CONDUCTORS AND CONDUIT WHEN APPLICABLE.

5. EXISTING EXHAUST FAN (EF) SCHEDULED TO BE REMOVED IN THIS

ROOM. REMOVE ASSOCIATED BRANCH CIRCUIT CONDUCTORS AND

CONDUIT BETWEEN UNIT AND LOCAL JUNCTION BOX. MAINTAIN BRANCH

CIRCUIT AT JUNCTION BOX FOR EXTENSION.

6. EXISTING CONDENSING UNIT (CU) SCHEDULED TO BE REMOVED.

DISCONNECT AND REMOVE EXISTING LOCAL DISCONNECT SERVING

EQUIPMENT. DISCONNECT AND REMOVE ASSOCIATED BRANCH CIRCUIT

CONDUCTORS AND CONDUIT BETWEEN UNIT AND PANEL SOURCE.

DISCONNECT AND REMOVE ALL ASSOCIATED CONTROLS CONDUCTORS

AND CONDUIT WHEN APPLICABLE.

7. EXISTING WATER HEATER (WH) SCHEDULED TO BE REMOVED IN THIS

ROOM. REMOVE ASSOCIATED BRANCH CIRCUIT CONDUCTORS AND

CONDUIT BETWEEN UNIT AND LOCAL JUNCTION BOX. MAINTAIN BRANCH

CIRCUIT AT JUNCTION BOX FOR EXTENSION.

1. DISCONNECT AND REMOVE EXISTING 2'X4' RECESSED LIGHT FIXTURE.

DISCONNECT AND REMOVE ASSOCIATED LIGHTING BRANCH CIRCUIT

CONDUCTORS AND CONDUIT BACK TO LOCAL JUNCTION BOX ABOVE

ACCESSIBLE CEILING. MAINTAIN LIGHTING BRANCH CIRCUIT(S) AT

JUNCTION BOX FOR REUSE.

2. DISCONNECT AND REMOVE EXISTING SURFACE STRIP LIGHT FIXTURE.

DISCONNECT AND REMOVE ASSOCIATED LIGHTING BRANCH CIRCUIT

CONDUCTORS AND CONDUIT BACK TO LOCAL JUNCTION BOX ABOVE

ACCESSIBLE CEILING. MAINTAIN LIGHTING BRANCH CIRCUIT(S) AT

JUNCTION BOX FOR REUSE.

3. DISCONNECT AND REMOVE EXISTING RECESSED DOWNLIGHT

FIXTURE. DISCONNECT AND REMOVE ASSOCIATED LIGHTING BRANCH

CIRCUIT CONDUCTORS AND CONDUIT BACK TO LOCAL JUNCTION BOX

ABOVE HARD CEILING. MAINTAIN LIGHTING BRANCH CIRCUIT(S) AT

JUNCTION BOX FOR REUSE.

4. DISCONNECT EXISTING RECESSED DOWNLIGHT FIXTURE. MAINTAIN

FIXTURE BRANCH CIRCUIT CONDUCTORS AND MOUNTING FRAME TO

BE RETROFITTED.

5. DISCONNECT AND REMOVE EXISTING " BUGEYE" EMERGENCY

FIXTURE. DISCONNECT AND REMOVE ASSOCIATED LIGHTING BRANCH

CIRCUIT CONDUCTORS AND CONDUIT BACK TO LOCAL JUNCTION BOX

ABOVE HARD CEILING.

6. FIELD VERIFY EXISTING LIGHTING CONTROL DEVICES. DISCONNECT

AND REMOVE VERIFIED LIGHTING CONTROL DEVICES. REMOVE

ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT

BETWEEN LIGHT FIXTURE AND LOCAL JUNCTION BOX ABOVE HARD

CEILING OR ACCESSIBLE CEILING. DISCONNECT AND REMOVE

ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT

BETWEEN LIGHTING CONTROL DEVICES AND PANEL SOURCE. REFER

TO ARCHITECTURE DEMOLITION PLAN AA-101 AND AA102.

GFI (WP)

GFI

(WP)

GFI

(WP)

GFI

(WP)

GFI

(WP)

GFI

(WP)

KEY NOTES LIGHTING DEMOLITION PLAN:

KEY NOTES POWER DEMOLITION PLAN

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Sheet of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text Scale: 1/4" = 1'-0"

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

Scale: 1/4" = 1'-0"

OC

S

B1B1

B3

B1

B1 B1E

B1

B1

B1

C1E

C1

C1E

C2

C2

C2

C2

A3E

A3E

B1

B3

B3

E1

X1

E1

X1

X1

X1

O C

S

O C

S O

C S

OCS

OC

OC

S

S

S

NL

NL

C1E

S

S

F2

C1

C1

C1C1

C1

C1C1

C1E

C1C1

C1

C1 a b a b

OC

OC

OC

NL

NL

S c c c c

B1 B1

C1

S a

W1

PC

PC

UTILITY

MECH

TOILET

FILES

OFFICE

BREAK AREA

DIRECTOR

RECEPTION

LOBBY

CONFERENCE

DF

LOCKERS

OPEN

OFFICE

CONFERENCE

HALL

F

F

F

F

F

F

F

F

F

F

SD

SD

F

F

F

T V

UTILITY

MECH

TOILET

FILES

OFFICE

BREAK AREA

DIRECTOR

RECEPTION

LOBBY

CONFERENCE

DF

LOCKERS

OPEN

OFFICE

CONFERENCE

HALL

NATIONAL CEMETERY

ADMINISTRATION

OFFICE OF DESIGN

AND CONSTRUCTION

John Gallup & Associates, LLC

3225 Shallowford Rd NE

Marietta, GA 30062

770-321-4040

Atriax Pllc

102 3rd Avenue N.E.

Hickory, NC 28601

Renovation of Administration and

Maintenance Buildings

835CM3036

June 28, 2019

Chattanooga National Cemetery

1200 Bailey Avenue, Chattanooga, TN 37404

Environment & Infrastructure Solutions, Inc.

1075 Big Shanty Road, NW Suite 100

Kennesaw, GA 30144

(770) 421-3400

EA102

ADMINISTRATION BUILDING

POWER AND LIGHTING NEW

WORK PLANS

Break Area

SCALE: 1/4" = 1'-0"

ADMINISTRATION BUILDING - POWER AND SYSTEM PLAN

EA102

0 2' 4' 8'

Scale: 1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

ADMINISTRATION BUILDING - LIGHTING PLAN

EA102

0 2' 4' 8'

Scale: 1/4" = 1'-0"

1. PROVIDE 2'X4' RECESSED LED LIGHT FIXTURE IN ROOM OR SPACE AS

INDICATED. EXTEND NEAREST LIGHTING BRANCH CIRCUIT CONDUCTORS

AND CONDUIT FROM LOCAL JUNCTION BOX ABOVE ACCESSIBLE CEILING

MAINTAINED FROM DEMOLITION TO LIGHT FIXTURE.

2. PROVIDE 4' NARROW STRIP LIGHT SURFACE MOUNTED IN THIS ROOM OR

SPACE AS INDICATED. EXTEND LIGHTING BRANCH CIRCUIT CONDUCTORS

AND CONDUIT FROM LOCAL JUNCTION BOX ABOVE ACCESSIBLE CEILING

MAINTAINED FROM DEMOLITION TO LIGHT FIXTURE.

3. PROVIDE WALL MOUNTED EXIT SIGN WITH BATTERY BACKUP. EXTEND

NEAREST LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT TO EXIT

SIGN.

4. PROVIDE 2'X2' RECESSED LED LIGHT FIXTURE IN ROOM OR SPACE AS

INDICATED. EXTEND NEAREST LIGHTING BRANCH CIRCUIT CONDUCTORS

AND CONDUIT FROM LOCAL JUNCTION BOX ABOVE ACCESSIBLE CEILING

MAINTAINED FROM DEMOLITION TO LIGHT FIXTURE.

5. PROVIDE LINE VOLTAGE WALL MOUNTED, LIGHT SWITCH WITH INFRARED

OCCUPANCY SENSOR. EXTEND LIGHTING BRANCH CIRCUIT CONDUCTOR

AND CONDUIT TO SWITCH.

6. PROVIDE LINE VOLTAGE CEILING MOUNTED, DUAL TECHNOLOGY

OCCUPANCY SENSOR. EXTEND LIGHTING BRANCH CIRCUIT CONDUCTOR

AND CONDUIT TO SENSOR.

7. PROVIDE EMERGENCY EGRESS LIGHT FIXTURE. EXTEND LIGHTING BRANCH

CIRCUIT CONDUCTORS AND CONDUIT FROM LOCAL JUNCTION BOX TO

EGRESS LIGHT FIXTURE.

8. PROVIDE RETROFIT DOWNLIGHT FIXTURES MOUNTED IN THE EXISTING

FRAME MAINTAINED FROM DEMOLITION.

9. PROVIDE LINE VOLTAGE WALL MOUNTED, LIGHT SWITCH WITH ULTRASOUND

OCCUPANCY SENSOR. EXTEND LIGHTING BRANCH CIRCUIT CONDUCTOR

AND CONDUIT TO SWITCH.

10. PROVIDE 4' STRIP LIGHT SURFACE MOUNTED . EXTEND LIGHTING BRANCH

CIRCUIT CONDUCTORS AND CONDUIT FROM LOCAL JUNCTION BOX ABOVE

ACCESSIBLE CEILING MAINTAINED FROM DEMOLITION TO LIGHT FIXTURE.

11. PROVIDE TOGGLE SWITCH. EXTEND LIGHTING BRANCH CIRCUIT

CONDUCTORS AND CONDUIT TO SWITCH.

12. PROVIDE RECESSED LED DOWNLIGHT FIXTURE IN ROOM OR SPACE AS

INDICATED. EXTEND NEAREST LIGHTING BRANCH CIRCUIT CONDUCTORS

AND CONDUIT FROM LOCAL JUNCTION BOX ABOVE ACCESSIBLE CEILING

MAINTAINED FROM DEMOLITION TO LIGHT FIXTURE. INTERFACE CONTROL

AS INDICATED. ADJUST WIRING OF FIXTURES WITH (NL) DESIGNATION TO

ENSURE THEY OPERATE AS NIGHT LIGHT (UNSWITCHED).

13. EXTERIOR LIGHT FIXTURES SHALL BE CONTROLLED BY NEW EXTERIOR

PHOTOCELL MOUNTED ON ROOF, FACING NORTH, WITH AN UNOBSTRUCTED

VIEW OF THE SKY.

14. PROVIDE WALLPACK FIXTURE FOR EXTERIOR LIGHTING MOUNTED ABOVE

DOOR . EXTEND LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT

FROM LOCAL JUNCTION BOX TO WALLPACK FIXTURE. WALLPACK FIXTURE

SHALL BE CONTROLLED VIA INTEGRATED PHOTOCELL AND POWERED BY

CIRCUIT INDICATED.

1. PROVIDE NEW 208/120V, 3PH, 4W , 225A MAIN LUG ONLY PANEL 'A'.

CONNECT TO EXISTING FEEDER MAINTAINED DURING DEMOLITION.

CONNECT EXISTING BRANCH CIRCUITS MAINTAINED DURING DEMOLITION

TO PANEL.

2. PROVIDE NEW 400A/3P/225AF/3R FUSED DISCONNECT SWITCH. CONNECT

TO EXISTING FEEDER MAINTAINED DURING DEMOLITION TO PANEL 'A'.

3. PROVIDE TWO (2) TEMPORARY FUSED DISCONNECT SWITCHES TO SERVE

ADMIN AND RESTROOM TEMPORARY TRAILERS. REFER TO RISER DIAGRAM

FOR ADDITIONAL INFORMATION.

4. PROVIDE (2) 2" CONDUITS TO RESTROOM BUILDING FOR INTERCONNECTION

OF FIRE ALARM.

5. PROVIDE NEW FEEDER CONDUCTOR AND CONDUIT. CONNECT TO PANEL 'T'

IN THE RESTROOM BUILDING. REFER TO RISER DIAGRAM ON SHEET E-601

FOR FEEDER CONDUCTOR AND CONDUIT SIZES.

6. PROVIDE DUPLEX RECEPTACLE(S) IN THIS ROOM OR SPACE AS INDICATED.

PROVIDE BRANCH CIRCUIT CONDUCTORS AND CONDUIT. CONNECT TO

PANEL AND CIRCUIT INDICATED.

7. PROVIDE GFI DUPLEX RECEPTACLE. PROVIDE BRANCH CIRCUIT

CONDUCTORS AND CONDUIT. CONNECT TO PANEL AND CIRCUIT INDICATED.

8. PROVIDE NEW FIRE ALARM CONTROL PANEL. CONNECT TO A DEDICATED

CIRCUIT AS INDICATED.

9. PROVIDE FIRE ALARM ANNUNCIATOR PANEL IN DIRECTOR'S OFFICE.

CONNECT TO A DEDICATED CIRCUIT.

10. PROVIDE FIRE ALARM INITIATION DEVICES. REFER TO DETAIL 1 ON E-502

FOR RISER DIAGRAM.

11. PROVIDE 208V, 60A, 2-POLE FUSED DISCONNECT SWITCH IN NEMA 3R

ENCLOSURE FOR CONDENSING UNIT. FIELD COORDINATE EXACT LOCATION

AND ELEVATION OF DISCONNECT PLACEMENT WITH EXISTING

CONSTRUCTION AND EQUIPMENT. PROVIDE BRANCH CIRCUIT

CONDUCTORS AND CONDUIT BETWEEN EQUIPMENT AND PANEL SOURCE.

CONNECT TO PANEL AND CIRCUITS INDICATED. PROVIDE ALL CONTROLS

WIRING AND RACEWAY AS REQUIRED FOR A COMPLETE INSTALLATION.

12. PROVIDE MOTOR RATED TOGGLE SWITCH FOR FAN COIL UNIT. PROVIDE

BRANCH CIRCUIT CONDUCTORS AND CONDUIT. CONNECT TO PANEL AND

CIRCUIT INDICATED.

13. PROVIDE BRANCH CIRCUIT CONDUCTORS AND CONDUIT FOR EXHAUST FAN.

CONNECT TO PANEL AND CIRCUIT INDICATED. INTERFACE CONTROLS WITH

LOCAL OCCUPANCY SENSOR. REFER TO ADMINISTRATION BUILDING -

LIGHTING PLAN FOR CIRCUITING. COORDINATE LOCATION WITH

MECHANICAL DRAWINGS AND MECHANICAL CONTRACTOR PRIOR TO

INSTALLATION.

14. PROVIDE FIRE ALARM NOTIFICATION APPLIANCE.REFER TO DETAIL 1 ON

E-502 FOR RISER DIAGRAM.

15. RECONNECT EXISTING FEEDER CONDUIT MAINTAINED DURING DEMOLITION

TO PANEL "CSP" IN COMMITTAL SHELTER B.

16. PROVIDE GFI DUPLEX RECEPTACLE. PROVIDE DEDICATED BRANCH CIRCUIT

CONDUCTORS AND CONDUIT FOR DRINKING FOUNTAIN. CONNECT TO

PANEL AND CIRCUIT INDICATED.

17. PROVIDE BRANCH CIRCUIT CONDUCTORS AND CONDUIT FOR INSTANT

WATER HEATER. CONNECT TO PANEL AND CIRCUIT INDICATED.

18. PROVIDE DEDICATED CIRCUIT FOR SECURITY PANEL. SEE PANEL

SCHEDULE FOR PANEL 'A'.

19. PROVIDE (2) 100A, 3-POLE BRANCH CIRCUIT BREAKER TO PROVIDE POWER

TO THE ADMIN AND RESTROOM TEMPORARY TRAILERS. REFER TO

SEQUENCE OF CONSTRUCTION NOTES ON SHEET E-101.

20. PROVIDE CAT-6 DATA OUTLET AND DEDICATED RECEPTACLE FOR WALL

MOUNTED FLAT PANEL TV.

PANEL 'A'

MAG AS

GFI

GFI

GFI (WP)

C

C

G F

I

W

P

C

GFI

(TYP.)

(TYP.)

(TYP)

CU-1

FCU-1

("15CD")

("15CD")

("15CD")

("15CD")

("15CD")

("15CD")

("15CD")

("15CD")

("15CD")

CU-2

FCU-2

EF-1

A-21

A-23

A-24

A- 39, 41

A- 40, 42

GFI

GFI

1 5 15

IWH-1

A- 17, 19

A-1 A-1

A-1

A-1

A-1 A-1

A-1

A-1

A-1

A-1 A-1

A-1 A-1

A-1 A-1

A-1

A-1

A-1

A-1

A-1

A-1

A-1

A-2

A-2

A-2

A-2

A-2

A-2

A-2

A-2

A-2

A-2

A-2

A-2 A-2

A-2 A-2

A-2

D

TR

TR

A-3

A-3

A-4

A-3

A-3

A-3

A-4

A-4

A-4

A-4

A-4

A-6

A-15

A-15

A-14

A-14

A-5

A-5

A-7

A-7

A-7

A-7

A-7

A-9

A-9

A-9

A-9

A-9

A-9

A-11

A-8

A-8

A-8

GFI (WP)

GFI (WP)

GFI (WP)

GFI (WP)

A-3

A-13

A-13

A-13

A-8

A-7

(TYP)

(TYP.)

A-10

A-2

A-1

(TYP.)

(TYP)

A-2

KEY NOTES LIGHTING NEW WORK PLAN:

KEY NOTES POWER NEW WORK PLAN:

(TYP.)

(TYP.)

A-1

(TYP.)

A-16

GFI

A-2

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

A-18

AutoCAD SHX Text

FACP

AutoCAD SHX Text

FAA

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Sheet of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DF

LOCKERS

FX

MS

MS

MS

MS

MS

MS

MS

D C

C R

SD

SD

CR

E L

C R

DC

EL

D C

E L

ML

ML

ML

CR

DC

DC

DC

RX

RX

RX

R X

R X

PB

PB

D C

MS

MS

K

CR

UTILITY

MECH

TOILET

FILES

OFFICE

BREAK AREA

DIRECTOR

RECEPTION

LOBBY

CONFERENCE

DF

LOCKERS

OPEN

OFFICE

CONFERENCE

HALL

FX

NATIONAL CEMETERY

ADMINISTRATION

OFFICE OF DESIGN

AND CONSTRUCTION

John Gallup & Associates, LLC

3225 Shallowford Rd NE

Marietta, GA 30062

770-321-4040

Atriax Pllc

102 3rd Avenue N.E.

Hickory, NC 28601

Renovation of Administration and

Maintenance Buildings

835CM3036

June 28, 2019

Chattanooga National Cemetery

1200 Bailey Avenue, Chattanooga, TN 37404

Environment & Infrastructure Solutions, Inc.

1075 Big Shanty Road, NW Suite 100

Kennesaw, GA 30144

(770) 421-3400

EA103

ADMINISTRATION BUILDING

TELECOM PLAN

Break Area

SCALE: 1/4" = 1'-0"

ADMINISTRATION BUILDING - TELECOM AND SECURITY PLAN

EA103

0 2' 4' 8'

Scale: 1/4" = 1'-0"

KEY NOTES TELECOM AND SECURITY PLAN:

1. ALL CABLING TO BE PLENUM RATED. CABLING SHALL BE INSTALLED

IN J-HOOKS ABOVE THE DROP CEILING. CABLING TO BE SECURED TO

LADDER RACKS TRANSITIONING BELOW CEILING TO EQUIPMENT

ROOM.

2. DATA OUTLETS TO BE INSTALLED WITH 2-CAT 6 DATA JACKS AND

1-CAT 6 PHONE JACK.

3. ALL CCTV AND INTRUSION DETECTION SYSTEM (IDS) JUNCTION

BOXES TO BE PAINTED BLUE.

4. MAIN CROSS CONNECT RACK 7'Hx19"Wx3D", ALL DATA ETHERNET

CABLES TO TERMINATE TO CONTRACTOR PROVIDED PATCH PANEL

USING T568B CONNECTION STANDARDS.

5. PROVIDE WALL MOUNTED LOCKABLE CCTV HEADEND, CCTV

NETWORK TO UTILIZE POE CAMERAS AND SHALL BE SEPARATE FROM

THE BUILDING HORIZONTAL CABLING. CCTV HEADEND TO HAVE

REMOTE MANAGEMENT. CCTV HEADEND TO BE INSTALLED WITH A

5KVA UPS. SERVER TO BE INSTALLED WITH 1U PULL OUT FLAT

SCREEN/KEYBOARD FOR LOCAL VIEWING.

6. PROVIDE INTRUSION DETECTION SYSTEM (IDS). IDS TO MONITOR

DOOR CONTACTS AND MOTION DETECTORS. IDS TO BE EQUIPPED

WITH AUTO DIALER TO BASE SECURITY AND 76 HOUR BATTERY

BACKUP.

7. PROVIDE PACS HEADEND AND DC POWER SUPPLY WITH 76 HOUR

BATTERY BACKUP. PACS SYSTEM TO BE MANAGED WITH AND USE

STANDARD FEDERAL GSA CARD TECHNOLOGY.

8. PROVIDE CEILING MOUNTED IP CAMERA. CAMERAS MOUNTED

EXTERIOR SHALL BE RATED FOR EXTERIOR USE. PROVIDE ETHERNET

SURGE PROTECTORS FOR ALL CABLE LEAVING BUILDING ENVELOPE.

9. PROVIDE DUAL TECHNOLOGY MOTION SENSORS TIED TO. IDS TO BE

EQUIPPED WITH AUTO DIALER TO BASE SECURITY. PHYSICAL

ACCESS CONTROL SYSTEM (PACS) DOOR CONTACTS TO INTERFACE

WITH IDS.

10. WIRELESS ACCESS POINT, PROVIDE TWO CAT 6 CABLES EACH UNIT,

COORDINATE WITH COR FOR EXACT PLACEMENT.

11. IDS REMOTE KEY PAD. MOUNTED AT 48" AFF. KEYPAD TO HAVE

DISPLAY SCREEN AND SYSTEM ARMED INDICATOR LIGHTS.

12. PROVIDE (2) SHEETS OF 48" X 96" X

", FIRE RATED, VOID FREE, AC

GRADE PLYWOOD. MOUNT WITH "A" SIDE OUT. PAINTED WITH A FIRE

RESISTANT PAINT, DO NOT PAINT OVER FIRE RATED LABEL. MOUNT

WITH THE PLYWOOD BOTTOM AT 8" AFF.

13. PROVIDE A 12" X 4" X

" COPPER GROUND BAR WITH 2" ISOLATORS

MOUNTED TO WALL PROVIDE TWO HOLE LUGS ON ALL

CONNECTIONS. HOMERUN #3/0 AWG CU CONDUCTOR TO THE PANEL

P-1 GROUND BAR IN UTILITY ROOM.

14. COORDINATE WITH TELECOM PROVIDER FOR THE RELOCATION AND

INSTALLATION OF DEMARCATION EQUIPMENT.

15. PROVIDE LADDER TYPE CABLE TRAY MOUNTED AT +7'-6" ABOVE

FINISHED FLOOR.

16. PROVIDE 1-4" PVC SCHD 80 BURIED CONDUIT FROM MECHANICAL

ROOM TO RESTROOM BUILDING FOR SECURITY CIRCUITS.

17. PROVIDE 1-2" PVC SCHD 80 BURIED CONDUIT FROM UTILITY ROOM TO

TEMPORARY TRAILER LOCATION FOR ISP CIRCUITS. INTERNET

SERVICE TO MAINTAIN FUNCTIONAL DURING CONSTRUCTION.

18. CARD READER. PROVIDE JUNCTION BOX WHERE SHOWN. INTERFACE

WITH DOOR HARDWARE. PROVIDE ALL NECESSARY DOOR

EQUIPMENT PROVIDE POWER FROM CENTRAL PACS POWER SUPPLY.

REFER TO DETAIL 07 ON SHEET E-602 FOR MORE INFORMATION.

MAG AS

6 7

AutoCAD SHX Text

IDS

AutoCAD SHX Text

CCTV HE

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Sheet of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

UTILITY

WOMEN'S

RESTROOM

MEN'S

RESTROOM

WP

GFI

HVAC

UNIT

PANEL T

100A/2P/SN/RT

NON-FUSED DISC

EF

WH

UTILITY

WOMEN'S

RESTROOM

MEN'S

RESTROOM

NATIONAL CEMETERY

ADMINISTRATION

OFFICE OF DESIGN

AND CONSTRUCTION

John Gallup & Associates, LLC

3225 Shallowford Rd NE

Marietta, GA 30062

770-321-4040

Atriax Pllc

102 3rd Avenue N.E.

Hickory, NC 28601

Renovation of Administration and

Maintenance Buildings

835CM3036

June 28, 2019

Chattanooga National Cemetery

1200 Bailey Avenue, Chattanooga, TN 37404

Environment & Infrastructure Solutions, Inc.

1075 Big Shanty Road, NW Suite 100

Kennesaw, GA 30144

(770) 421-3400

0 1' 2' 4'

Scale: 1/2" = 1'-0"

SCALE: 1/2" = 1'-0"

RESTROOM BUILDING - LIGHTING DEMOLITION PLAN

EB101

EB101

PUBLIC RESTROOM BUILDING

POWER AND LIGHTING

DEMOLITION PLANS

47MAG AS

0 1' 2' 4'

Scale: 1/2" = 1'-0"

SCALE: 1/2" = 1'-0"

RESTROOM BUILDING - POWER DEMOLITION PLAN

EB101

KEY NOTES LIGHTING DEMOLITION PLAN:

1. DISCONNECT AND REMOVE EXISTING 2'X4' RECESSED LIGHT FIXTURE. DISCONNECT AND REMOVE

ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT BACK TO SOURCE.

2. DISCONNECT AND REMOVE EXISTING PENDENT STRIP LIGHT FIXTURE. DISCONNECT AND REMOVE

ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT BACK TO SOURCE.

3. DISCONNECT EXISTING RECESSED DOWNLIGHT FIXTURES. DISCONNECT AND REMOVE

ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT BACK TO SOURCE.

4. DISCONNECT AND REMOVE EXISTING " BUGEYE" EMERGENCY FIXTURE. DISCONNECT AND

REMOVE ASSOCIATED LIGHTING BRANCH CIRCUIT CONDUCTORS AND CONDUIT BACK TO LOCAL

JUNCTION BOX ABOVE HARD CEILING.

5. DISCONNECT AND REMOVE EXISTING LIGHT SWITCH. DISCONNECT AND REMOVE ASSOCIATED

LIGHTING BRANCH CIRCUIT AND CONDUCTORS AND CONDUIT BACK TO SOURCE.

KEY NOTES POWER DEMOLITION PLAN:

1. DISCONNECT AND REMOVE EXISTING PANEL 'T'. DISCONNECT AND

REMOVE ASSOCIATED FEEDER CIRCUIT CONDUCTORS AND CONDUIT.

RECONNECT EXISTING BRANCH CIRCUIT CONDUCTOR UNLESS

OTHERWISE NOTED.

2. DISCONNECT AND REMOVE EXISTING NON-FUSED DISCONNECT

SWITCH. DISCONNECT AND REMOVE ASSOCIATED FEEDER CIRCUIT

CONDUCTORS AND CONDUIT. UNLESS OTHERWISE NOTED.

3. EXISTING HVAC UNIT SCHEDULED TO BE REMOVED. DISCONNECT AND

REMOVE EXISTING LOCAL DISCONNECT SWITCH SERVING EQUIPMENT.

DISCONNECT AND REMOVE ASSOCIATED BRANCH CIRCUIT

CONDUCTORS AND CONDUIT BETWEEN UNIT AND PANEL SOURCE.

DISCONNECT AND REMOVE ALL ASSOCIATED CONTROLS

CONDUCTORS AND CONDUIT WHEN APPLICABLE.

4. EXISTING WATER HEATER (WH) SCHEDULED TO BE REMOVED.

DISCONNECT AND REMOVE ASSOCIATED BRANCH CIRCUIT

CONDUCTORS AND CONDUIT BETWEEN UNIT AND SOURCE.

5. EXISTING…