This is an Asbestos Reinspection Report documenting a comprehensive survey of 15 buildings at Cheyenne VA Medical Center in Cheyenne, Wyoming, conducted December 4-6, 2023 by Castle Hill Associates, LLC under VA Contract 36C25923Q0452. The inspection identified asbestos-containing materials (ACM) in 11 of the surveyed buildings, including pipe insulation, hard ceiling and wall plaster, drywall joint compound, floor tiles, linoleum, transite cement sheets, window glazing/putty, and window caulking. Building 1 contained the most significant ACM findings with contaminated soil containing pipe insulation debris (37,500 square feet) in crawl spaces and multiple friable and non-friable materials throughout. Other buildings with notable ACM included Building 4 (contaminated soil in crawl spaces and hard ceiling plaster on multiple floors), Building 13 (pipe insulation and skim coating on concrete walls), and Buildings 19, 20, 25, and 26 (window caulking and glazing). The report establishes hazard rankings based on AHERA protocol, recommending removal, encapsulation, or repair actions prioritized by damage condition and potential for human exposure. The inspection was conducted by certified asbestos inspectors Brett Brumbaugh (REPA, CESCO) and Samuel Ansara, with certifications valid through October 2024.
The report includes detailed architectural plans with ACM locations marked across all building floors, asbestos laboratory analysis results confirming chrysotile asbestos in samples ranging from 4-45% concentration, and an Operations and Maintenance (O&M) plan for managing identified ACM in good condition until abatement. The O&M plan outlines procedures for routine maintenance, emergency response protocols for fiber release episodes, worker protection requirements including medical surveillance and respiratory protection, training requirements for building staff and contractors, and recordkeeping procedures. Prior asbestos surveys from 2013 and 2018 were reviewed and incorporated into the current assessment. The report notes that roofing materials and electrical components were not specifically examined and should be sampled prior to any renovation activities that may disturb these materials.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS REINSPECTION REPORT
LOCATION:
CHEYENNE VA MEDICAL CENTER
2360 E PERSHING BLVD.
CHEYENNE, WY 82001
CONTRACT NO.: 36C25923Q0452
INSPECTION DATES:
DECEMBER 4-6, 2023
CONTRACTOR:
CASTLE HILL ASSOCIATES, LLC
1197 FARNSWORTH – SUITE E
WATERVILLE, OH 43566
567-952-0212
CHEYENNE VA MEDICAL CENTER - CHEYENNE, VA
DECEMBER 2023
TABLE OF CONTENTS
1.0 ASBESTOS INSPECTION REPORT
• Table 1 – List of Acronyms
• Table 2 - Removal Priority Protocols
2.0 APPENDICES
Appendix A – Asbestos Sampling Data 2018
Appendix B – Asbestos Quantities, Assessments, & Remediation Cost Estimate
Appendix C – Photographs Asbestos Materials
Appendix D – Asbestos Laboratory Reports
Appendix E - Inspector Certifications
Appendix F – Asbestos Material Locations & Sample Location Drawings
Appendix G – O&M Plan (Operations & Maintenance)
DECEMBER 2023
1.0 EXECUTIVE SUMMARY
On December 4-6, 2023, Castle Hill Associates, LLC was contracted by the US Department of Veterans Affairs (VA) to perform asbestos re-inspections of 15 buildings on the site of the Cheyenne VA Medical Center in Cheyenne, VA. The survey was performed as part of the VA Contract Number 36C25923Q0452. The buildings that were surveyed as part of this project included:
Building Number
Building Name/Description
ASBESTOS
PRESENT?
1 Main Hospital Yes 1-CA Main Hospital – Clinical Addition No 1-CX Main Hospital – Physical Therapy No
4 Offices – Fiscal and AM&M Yes 5 Office – Human Resources Yes 6 Former Quarters/Offices Yes 7 Former Quarters/Offices Yes 8 Offices Yes
11 Engineering & Shops Yes 12 Supply Warehouse No 13 Boiler Plant Yes 18 Garage No 19 Storage-Grounds Yes 20 Storage Garages Yes 23 Grounds Shop No 25 Garage Yes 26 Garage Yes
The inspection was conducted by Brett Brumbaugh and Samuel Ansara. The project manager was Mr.
Brumbaugh who has been conducting asbestos surveys, sampling, and consulting work since 1987.
Sam Ansara has been conducting asbestos surveys, sampling, and consulting work since 1989. There was a previous asbestos reinspection/sampling conducted at the facility in 2013 and 2018. These previous inspections were reviewed by Castle Hill prior to this inspection and incorporated into this report. There were no limitations or exceptions to the PWS for the surveys conducted. Roofing materials were not tested and must be assumed to be present on all buildings until tested prior to future renovations.
All accessible functional areas in the facilities were surveyed. All previous asbestos survey information and sampling conducted at the facilities were evaluated and incorporated into this survey. All confirmed asbestos-containing materials were verified. This report can be incorporated into the facility’s management plan for asbestos-containing materials.
2.0 STATE AND LOCAL REGULATIONS
The State of Wyoming asbestos licensing regulations are similar to the Federal regulations. State asbestos regulations include requirements for licensing and certification of personnel who will perform asbestos-related work activities. All personnel who engage in asbestos-related activities must comply with the state licensing/certification requirements as well as with all Federal requirements.
3.0 SUMMARY OF FINDINGS
3.1 Asbestos-Containing Building Materials
The following is a summary of the asbestos containing materials, locations, quantities of materials in each inspected building for this project:
Building 1 – Main Hospital
Asbestos Containing Materials Locations Quantity Contaminated soil with pipe insulation debris
Crawl Spaces under building 37,500 sf
Pipe insulation CL-02C hallway, pipe chases by CL-04 and CL-17, C1-102, D1-36A closet, D1-47, D1-50G, D1-50J
68 lf
Hard ceiling plaster C1-92 Entry & C1-95 Lobby 1,440 sf
9” floor tile D1-36A closet, D1-15 storage, D1-41 80 sf
Ebony cement countertops & shelves D1-53 Dental Lab 90 sf
Drywall joint compound Attic 4-OL & 4-OK divider wall 628 sf
Black tar on FG Duct Insulation D1-15, N. basement Crawl 560 sf
Cove base mastic (brown cove base) D2-38 80 lf
Building 1-CA Clinical Addition
No asbestos containing materials identified in building.
Building 1-CX Physical Therapy Addition
Building 4 – Offices (Fiscal and AM&M)
Contaminated soil under concrete cap Crawl Spaces 2,860 sf
Pipe insulation Basement Storage Rooms B1, B2, and B4 415 lf
Skim coating on concrete walls Basement rooms B1, B1A, B2, B3, B4 and
1,440 sf
Hard ceiling & wall plaster
1st & 2nd floor rooms 100, 101, 102, 103, 104, 105, 106, 107, 108, 109, 110, 111, 112, 113, 114, 115, S1F1, 200, 201, 203, S1F2
11,220 sf
Building 5 – Offices (Human Resources)
Transite cement sheets Basement furnace room B1 16 sf
Drywall joint compound First floor rooms 101, 102, 103, 104, 105, 106, 107, 108, C1, C2, S1F1
4,160 sf
Building 6 – Offices (former quarters)
Contaminated soil under concrete cap 2 Crawl Spaces 776 sf
Pipe insulation Basement Storage Room 001 20 lf
Building 7 – Offices (former quarters)
Hard ceiling & wall plaster Basement, 1st & 2nd floor rooms B01, B02, 100, 101, 102, 103, 104, 105, 106, 107, 108, 109, 110, S1F2, 201
3,430 sf
Linoleum sheet flooring Kitchen 104 168 sf
Building 8 – Offices (former quarters)
9” floor tile Basement Storage B01 80 sf
Drywall joint compound 1st floor entry 100 846 sf
Building 11 – Engineering and Shops
Pipe insulation (remaining stubs in sleeves) Elect. shop 103 (S.W. corner) 2 lf
Hard ceiling plaster Paint shops 105, 106, 107, and closet
770 sf
Glue pods for non-ACM 12” ceiling tiles (above 2x4 lay-in ceiling tile)
2nd floor offices 212 and 212A 384 sf
Building 12 – Supply Warehouse
Building 13 – Boiler Plant
Pipe insulation Tunnel under driveway to Building 11 90 lf
Skim coating on concrete walls Basement Room B-107 320 sf
Building 18 – Garage
Building 19 – Storage/Grounds
Window Glazing/Putty Metal Windows 4 windows
Building 20 – Storage Garages
Window Caulking Metal Windows 10 windows
Building 23 – Grounds Shop
Building 25 –Garage
Window Caulking Metal Windows 1 window
Building 26 –Garage
Window Caulking Metal Windows 2 windows
Building 42 – Storage Building
Building 45 – VBA Veterans Benefits
4.0 Explanation of Assessment of Asbestos Containing Materials
Re-inspection protocol is based on the Asbestos Hazard Emergency Response Act (AHERA), Environmental Protection Act’s (EPA’s) revised Asbestos Model Accreditation Plan (MAP) mandated by the Asbestos School Hazard Abatement Reauthorization Act (ASHARA), and the Department of Veterans Affairs (VA) Directive 7700. The tabular listing included in this report contains Building Number, Floor, Room Number, Material Category (i.e., TSI, SM or MM), Material Type, quantity, a numerical priority ranking, condition, potential for damage, potential for human exposure, drawing number, hazard ranking, recommended response action and associated cost estimate for implementation of those response actions.
The material assessment categories of the ACM identified in the building is formatted in the following order for the summary tables enclosed in this report:
• Material Category - Surfacing Material (SUR); Thermal System Insulation (TSI); Miscellaneous (MM)
• Material Type - Friable (F); Non-Fable (NF)
• Condition of Material - Good; Fair; Poor
• Potential for Damage - Low; Medium; High
• Physical Assessment - Low; Medium; High
• Recommended Response Action - 1 through 7
Material category is the type of material such as surfacing material (SUR), thermal system insulation (TSI), and miscellaneous (MM)
• Surfacing Material (SUR) - Surfacing ACM means surfacing material that is ACM. Surfacing material means material in a school building that is sprayed-on, troweled-on, or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, or other purposes.
• Thermal System Insulation (TSI) - Thermal system insulation ACM means thermal system insulation that is ACM. Thermal system insulation means material in a school building applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes.
• Miscellaneous (MM) - Miscellaneous ACM means miscellaneous material that is ACM Miscellaneous material means interior building material on structural components, structural members or fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation.
Material type refers to the hardness of a material to be crumbled, pulverized, or reduced to powder by hand pressure as friable (F), and includes previously non-friable (NF) material after such previously non-friable material becomes damaged to the extent that when dry it may be crumbled, pulverized, or reduced to powder by hand pressure.
• Condition of Material - Good; Fair; Poor
• Potential for Damage - Low; Medium; High
• Physical Assessment - Low; Medium; High
Seven Assessment Categories defined in the AHERA regulation, one of which must be assigned to each friable surfacing and miscellaneous ACBM and each asbestos-containing TSI during the inspection/re-inspection.
1. Damaged or significantly damaged TSI ACBM - Damaged or significantly damaged thermal system insulation ACM means thermal system insulation ACM on pipes, boilers, tanks, ducts, and other thermal system insulation equipment where the insulation has lost its structural integrity, or its covering, in whole or in part, is crushed, water-stained, gouged, punctured, missing, or not intact such that it is not able to contain fibers. Damage may be further illustrated by occasional punctures, gouges or other signs of physical injury to ACM; occasional water damage on the protective coverings/jackets; or exposed ACM ends or joints. Asbestos debris originating from the ACBM in question may also indicate damage.
2. Damaged friable surfacing ACBM - Damaged friable surfacing ACM means friable surfacing ACM which has deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or which has delaminated such that its bond to the substrate (adhesion) is inadequate, or which, for any other reason, lacks fiber cohesion or adhesion qualities. Such damage or deterioration may be illustrated by the separation of ACM into layers; separation of ACM from the substrate; flaking, blistering, or crumbling of the ACM surface; water damage; significant or repeated water stains, scrapes, gouges, mars or other signs of physical injury on the ACM. Asbestos debris originating from the ACBM in question may also indicate damage.
3. Significantly damaged friable surfacing ACBM - Significantly damaged friable surfacing ACM means damaged friable surfacing ACM in a functional space where the damage is extensive and severe.
4. Damaged or significantly damaged friable miscellaneous ACBM - Damaged friable miscellaneous ACM means friable miscellaneous ACM which has deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or, if applicable, which has delaminated such that its bond to the substrate (adhesion) is inadequate or which for any other reason lacks fiber cohesion or adhesion qualities. Such damage or deterioration may be illustrated by the separation of ACM into layers; separation of ACM from the substrate; flaking, blistering, or crumbling of the ACM surface; water damage; significant or repeated water stains, scrapes, gouges, mars or other signs of physical injury on the ACM. Asbestos debris originating from the ACBM in question may also indicate damage.
5. ACBM with Potential for Damage - Potential damage means circumstances in which:
(1) Friable ACBM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.
(2) There are indications that there is a reasonable likelihood that the material or its covering will become damaged, deteriorated, or delaminated due to factors such as changes in building use, changes in operations and maintenance practices, changes in occupancy, or recurrent damage.
6. ACBM with potential for significant damaged - Potential significant damage means circumstances in which:
(1) Friable ACBM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.
(2) There are indications that there is a reasonable likelihood that the material or its covering will become significantly damaged, deteriorated, or delaminated due to factors such as changes in building use, changes in operations and maintenance practices, changes in occupancy, or recurrent damage.
7. Any remaining friable ACBM or Friable Suspected ACBM
5.0 EXPLANATION OF REMEDIATION COST ESTIMATES
All remediation cost (removal and repair) estimates are based upon RS Means data. Since RS Means does not account for work in a VA Medical Center, all cost estimates are adjusted to reflect the VA specific requirements for abatement. In addition, the cost estimates reflect the quantity and location of the asbestos materials. For example, abatement work in crawl spaces is expected to be much more costly than work in more accessible areas of building. Also, the costs for each material in each building are intended to be for “stand alone” projects and the combination of areas for removal will reduce the costs due to an economy of scale.
6.0 CONCLUSION/RECOMMENDATIONS
An operations and maintenance (O&M) program has been developed by the VAMC specifically for the positively identified ACBM in the facilities. Any renovation/demolition work which may impact these positive materials should be conducted in accordance with the O&M program and all applicable Federal, state, and local regulations by appropriately trained and VA-approved personnel and contractors. Since demolition was not performed as part of the inspection work at the facilities, certain areas such as pipe chases and areas above fixed permanent ceilings, fire-door interiors, and vault/safe wall and door linings were not inspected or tested. Prior to renovation and alteration work which could impact these areas, Castle Hill recommends that exploratory demolition be performed and a qualified inspector be utilized to examine the areas and collect samples as needed. Castle Hill recommends sampling of roofing materials and electrical components (not specifically examined as part of this survey) if renovation activities are planned which may disturb these materials.
Inspector Signature:
Brett L. Brumbaugh, REPA, CESCO
Asbestos Bldg. Inspector & Management Planner
Samuel D. Ansara
TABLE 1
LIST OF ACRONYMS
ACBM Asbestos Containing Building Material ACM Asbestos Containing Material AHERA Asbestos Hazard Emergency Response Act AIHA American Industrial Hygiene Association CAA Clean Air Act CFR Code of Federal Regulations EPA United States Environmental Protection Agency HazCom Hazard Communication HEPA High Efficiency Particulate Air Filter HVAC Heating, Ventilation, and Air Conditioning MISC Miscellaneous Asbestos Containing Material NESHAP National Emission Standards for Hazardous Air Pollutants NIOSH National Institute for Occupational Safety and Health NIST National Institute of Standards and Technology NOB Non-friable Organically Bound NVLAP National Voluntary Laboratory Accreditation Program OSHA Occupational Safety and Health Administration PAT AIHA Proficiency Analytical Testing Program PCM Phase Contrast Microscopy PEL Permissible Exposure Limit PLM Polarized Light Microscopy TEM Transmission Electron Microscopy TSCA Toxic Substances Control Act TSI Thermal Systems Insulation Castle Hill Castle Hill Associates, LLC VA United States Department of Veterans Affairs VAMC VA Medical Center XRD X-Ray Diffraction
TABLE 2
ASBESTOS REMOVAL PRIORITY PROTOCOLS
HAZARD
RANK
REMOVAL
PRIORITY
AHERA
CATEGORY
RESPONSE ACTION
RECOMMENDATION
7 1 Significantly Damaged
Evacuate or isolate the area.
Remove or repair if feasible. O&M for all friable ACM.
6 2 Damaged with potential for significant damage
Evacuate or isolate the area.
Remove, encapsulate, or repair if feasible. O&M for all friable ACM.
5 3 Damaged with potential for damage
Remove, encapsulate, or repair.
O&M for all friable ACM.
4 4 Damaged Remove, encapsulate, or repair.
O&M for all friable ACM.
3 5 Potential for significant damage
Take steps to reduce potential for damage. O&M for all friable ACM.
2 6 Potential for damage O&M for all friable ACM.
1 7 No problem O&M for all friable ACM.
APPENDIX A
ASBESTOS BULK SAMPLING DATA
NOVEMBER 2018
ASBESTOS BULK SAMPLING INFORMATION
Facility: Cheyenne VA Medical Center – Cheyenne, VA Building: 1 Sampling Date: November 5, 2018 Analysis Date: November 12, 2018 Laboratory: EMLab P&K – Marlton, NJ Accreditation: NVLAP Asbestos Bulk Accredited Laboratory # 200844-0 Sampler: Brett Brumbaugh Certification: EPA Accredited Asbestos Inspector/Management Planner
PLM Laboratory Analysis Result
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
1 Asphalt tar paper under slate shingle Attic No asbestos detected
2a 9” tan vinyl floor tile D2-38 mechanical room No asbestos detected
2b Black tar paper under tile “” No asbestos detected
2c Yellow mastic under tar paper “” No asbestos detected
3a 9” green floor tile D1-36 conf. room closet 4% Chrysotile Asbestos
3b Black mastic “” No asbestos detected
4a 9” tan floor tile D1-15 food storage room 6% Chrysotile Asbestos
4b Black mastic “” No asbestos detected
C3 Pipe insulation debris in soil Crawl space 45% Chrysotile Asbestos
C4 Pipe insulation debris in soil Crawl space 40% Chrysotile Asbestos
C6 Pipe insulation debris in soil Crawl space 30% Chrysotile Asbestos
C7 Pipe insulation debris in soil Crawl space 45% Chrysotile Asbestos
C8 Pipe insulation debris in soil Crawl space 40% Chrysotile Asbestos
EPA Definition of an asbestos containing material: Greater than 1% asbestos
ASBESTOS BULK SAMPLING INFORMATION
Facility: Cheyenne VA Medical Center – Cheyenne, VA Building: 1 Sampling Date: November 5, 2018 Analysis Date: November 21, 2018 Laboratory: EMLab P&K – Arvada, CO Accreditation: NVLAP Asbestos Bulk Accredited Laboratory # 500053-0 Sampler: Brett Brumbaugh Certification: EPA Accredited Asbestos Inspector/Management Planner
PLM Point Count Laboratory Analysis Result (CARB 435)
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
C1 Loose soil in crawl space Crawl space 1-A No Asbestos Detected
C2 Loose soil in crawl space Crawl space 1 <0.25% Chrysotile Asbestos
C5 Loose soil in crawl space Crawl space 1-B No Asbestos Detected
APPENDIX B
Asbestos Quantities, Assessments, & Remediation Cost Estimates
APPENDIX C
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 1
Photo 1-1
Pipe insulation debris in crawl space on loose soil
Photo 1-2
Photo 1-3
Photo 1-4
Photo 1-5
Ebony cement lab table tops and shelves in Dental Lab D1-
Photo 1-6
9” tan floor tile in Canteen storage room D1-15
Photo 1-7
9” green floor tile in conference room closet D1-36
Photo 1-8
Pipe insulation in basement
Photo 1-9
Hard plaster ceiling in Cowboy Building Lobby
Photo 1-10
Drywall joint compound in Attic
BUILDING 4
Photo 4-1 storage rooms
Photo 4-2
Asbestos debris in crawl space under concrete cap
Photo 4-3
Skim coat on concrete walls in basement
Photo 4-4
Hard plaster on ceilings and walls
BUILDING 5
Photo 5-1
Transite cement sheets above furnace in basement storage room B1
Photo 5-2
Drywall joint compound on 1st floor
BUILDING 6
Photo 6-1 storage room 001
Photo 6-2
BUILDING 7
Photo 7-1
Linoleum sheet flooring in kitchen/break room
Photo 7-2
Hard plaster on walls and ceilings
BUILDING 8
Photo 8-1
9” floor tile in basement storage room B01
Photo 8-2 entry
BUILDING 11
Photo 11-1
Pipe iinsulation in electrical shop
Photo 11-2 Hard ceiling plaster
Photo 11-3 Glue pods for 12” ceiling tile
BUILDING 13
Photo 13-1
Steam pipe insulation in tunnel from basement to
Building 11 under driveway
Photo 13-2
Skim coating on concrete walls in basement storage
BUILDING 19
Photo 19-1
Window glazing/putty on metal windows
BUILDINGS 20, 25, AND 26
Photo 1
Window frame caulking on
Photo 2
Photo 3
APPENDIX D
ASBESTOS LABORATORY REPORTS
APPENDIX E
INSPECTOR CERTIFICATIONS
APPENDIX F
ASBESTOS MATERIAL LOCATIONS & SAMPLE LOCATION
DRAWINGS
APPENDIX G
O&M PLAN
(OPERATIONS & MAINTENANCE)
ASBESTOS O&M PLAN
NOVEMBER 2018
ASBESTOS O&M PLAN
Page 1 of
4.0 Explanation of Assessment of Asbestos Containing Materials
Re-inspection protocol is based on the Asbestos Hazard Emergency Response Act (AHERA), Environmental Protection Act’s (EPA’s) revised Asbestos Model Accreditation Plan (MAP) mandated by the Asbestos School Hazard Abatement Reauthorization Act (ASHARA), and the Department of Veterans Affairs (VA) Directive 7700. The tabular listing included in this report contains Building Number, Floor, Room Number, Material Category (i.e., TSI, SM or MM), Material Type, quantity, a numerical priority ranking, condition, potential for damage, potential for human exposure, drawing number, hazard ranking, recommended response action and associated cost estimate for implementation of those response actions.
The material assessment categories of the ACM identified in the building is formatted in the following order for the summary tables enclosed in this report:
• Material Category - Surfacing Material (SUR); Thermal System Insulation (TSI); Miscellaneous (MM)
• Material Type - Friable (F); Non-Fable (NF)
• Condition of Material - Good; Fair; Poor
• Potential for Damage - Low; Medium; High
• Recommended Response Action - 1 through 7
Material category is the type of material such as surfacing material (SUR), thermal system insulation (TSI), and miscellaneous (MM)
• Surfacing Material (SUR) - Surfacing ACM means surfacing material that is ACM. Surfacing material means material in a school building that is sprayed-on, troweled-on, or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, or other purposes.
• Thermal System Insulation (TSI) - Thermal system insulation ACM means thermal system insulation that is ACM. Thermal system insulation means material in a school building applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes.
• Miscellaneous (MM) - Miscellaneous ACM means miscellaneous material that is ACM Miscellaneous material means interior building material on structural components, structural members or fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation.
Material type refers to the hardness of a material to be crumbled, pulverized, or reduced to powder by hand pressure as friable (F), and includes previously non-friable (NF) material after such previously non-friable material becomes damaged to the extent that when dry it may be crumbled, pulverized, or reduced to powder by hand pressure.
• Condition of Material - Good; Fair; Poor
• Potential for Damage - Low; Medium; High
Seven Assessment Categories defined in the AHERA regulation, one of which must be assigned to each friable surfacing and miscellaneous ACBM and each asbestos-containing TSI during the inspection/re-inspection.
1. Damaged or significantly damaged TSI ACBM - Damaged or significantly damaged thermal system insulation ACM means thermal system insulation ACM on pipes, boilers, tanks, ducts, and other thermal system insulation equipment where the insulation has lost its structural integrity, or its covering, in whole or in part, is crushed, water-stained, gouged, punctured, missing, or not intact such that it is not able to contain fibers. Damage may be further illustrated by occasional punctures, gouges or other signs of physical injury to ACM; occasional water damage on the protective coverings/jackets; or exposed ACM ends or joints. Asbestos debris originating from the ACBM in question may also indicate damage.
2. Damaged friable surfacing ACBM - Damaged friable surfacing ACM means friable surfacing ACM which has deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or which has delaminated such that its bond to the substrate (adhesion) is inadequate, or which, for any other reason, lacks fiber cohesion or adhesion qualities. Such damage or deterioration may be illustrated by the separation of ACM into layers; separation of ACM from the substrate; flaking, blistering, or crumbling of the ACM surface; water damage; significant or repeated water stains, scrapes, gouges, mars or other signs of physical injury on the ACM. Asbestos debris originating from the ACBM in question may also indicate damage.
3. Significantly damaged friable surfacing ACBM - Significantly damaged friable surfacing ACM means damaged friable surfacing ACM in a functional space where the damage is extensive and severe.
4. Damaged or significantly damaged friable miscellaneous ACBM - Damaged friable miscellaneous ACM means friable miscellaneous ACM which has deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or, if applicable, which has delaminated such that its bond to the substrate (adhesion) is inadequate or which for any other reason lacks fiber cohesion or adhesion qualities. Such damage or deterioration may be illustrated by the separation of ACM into layers; separation of ACM from the substrate; flaking, blistering, or crumbling of the ACM surface; water damage; significant or repeated water stains, scrapes, gouges, mars or other signs of physical injury on the ACM. Asbestos debris originating from the ACBM in question may also indicate damage.
5. ACBM with Potential for Damage - Potential damage means circumstances in which:
(1) Friable ACBM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.
(2) There are indications that there is a reasonable likelihood that the material or its covering will become damaged, deteriorated, or delaminated due to factors such as changes in building use, changes in operations and maintenance practices, changes in occupancy, or recurrent damage.
6. ACBM with potential for significant damaged - Potential significant damage means circumstances in which:
(1) Friable ACBM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.
(2) There are indications that there is a reasonable likelihood that the material or its covering will become significantly damaged, deteriorated, or delaminated due to factors such as changes in building use, changes in operations and maintenance practices, changes in occupancy, or recurrent damage.
7. Any remaining friable ACBM or Friable Suspected ACBM
5.0 EXPLANATION OF REMEDIATION COST ESTIMATES
All remediation cost (removal and repair) estimates are based upon RS Means data. Since RS Means does not account for work in a VA Medical Center, all cost estimates are adjusted to reflect the VA specific requirements for abatement. In addition, the cost estimates reflect the quantity and location of the asbestos materials. For example, abatement work in crawl spaces is expected to be much more costly than work in more accessible areas of building. Also, the costs for each material in each building are intended to be for “stand alone” projects and the combination of areas for removal will reduce the costs due to an economy of scale.
6.0 CONCLUSION/RECOMMENDATIONS
An operations and maintenance (O&M) program has been developed by the VAMC specifically for the positively identified ACBM in the facilities. Any renovation/demolition work which may impact these positive materials should be conducted in accordance with the O&M program and all applicable Federal, state, and local regulations by appropriately trained and VA-approved personnel and contractors. Since demolition was not performed as part of the inspection work at the facilities, certain areas such as pipe chases and areas above fixed permanent ceilings, fire-door interiors, and vault/safe wall and door linings were not inspected or tested. Prior to renovation and alteration work which could impact these areas, Castle Hill recommends that exploratory demolition be performed and a qualified inspector be utilized to examine the areas and collect samples as needed. Castle Hill recommends sampling of roofing materials and electrical components (not specifically examined as part of this survey) if renovation activities are planned which may disturb these materials.
Brett L. Brumbaugh, REPA, CESCO
TABLE 1
LIST OF ACRONYMS
ACBM Asbestos Containing Building Material ACM Asbestos Containing Material AHERA Asbestos Hazard Emergency Response Act AIHA American Industrial Hygiene Association CAA Clean Air Act CFR Code of Federal Regulations EPA United States Environmental Protection Agency HazCom Hazard Communication HEPA High Efficiency Particulate Air Filter HVAC Heating, Ventilation, and Air Conditioning MISC Miscellaneous Asbestos Containing Material NESHAP National Emission Standards for Hazardous Air Pollutants NIOSH National Institute for Occupational Safety and Health NIST National Institute of Standards and Technology NOB Non-friable Organically Bound NVLAP National Voluntary Laboratory Accreditation Program OSHA Occupational Safety and Health Administration PAT AIHA Proficiency Analytical Testing Program PCM Phase Contrast Microscopy PEL Permissible Exposure Limit PLM Polarized Light Microscopy TEM Transmission Electron Microscopy TSCA Toxic Substances Control Act TSI Thermal Systems Insulation Castle Hill Castle Hill Associates, LLC VA United States Department of Veterans Affairs VAMC VA Medical Center XRD X-Ray Diffraction
TABLE 2
ASBESTOS REMOVAL PRIORITY PROTOCOLS
HAZARD
RANK
REMOVAL
PRIORITY
AHERA
CATEGORY
RESPONSE ACTION
RECOMMENDATION
7 1 Significantly Damaged
Evacuate or isolate the area.
Remove or repair if feasible. O&M for all friable ACM.
6 2 Damaged with potential for significant damage
Evacuate or isolate the area.
Remove, encapsulate, or repair if feasible. O&M for all friable ACM.
5 3 Damaged with potential for damage
Remove, encapsulate, or repair.
O&M for all friable ACM.
4 4 Damaged Remove, encapsulate, or repair.
O&M for all friable ACM.
3 5 Potential for significant damage Take steps to reduce potential for damage. O&M for all friable ACM.
2 6 Potential for damage O&M for all friable ACM.
1 7 No problem O&M for all friable ACM.
DECEMBER 2023
APPENDIX A
ASBESTOS BULK SAMPLING DATA
DECEMBER 2023
ASBESTOS BULK SAMPLING INFORMATION
Facility: Cheyenne VA Medical Center – Cheyenne, VA Building: 1 Sampling Date: November 5, 2018 Analysis Date: November 12, 2018 Laboratory: EMLab P&K – Marlton, NJ Accreditation: NVLAP Asbestos Bulk Accredited Laboratory # 200844-0 Sampler: Brett Brumbaugh Certification: EPA Accredited Asbestos Inspector/Management Planner
PLM Laboratory Analysis Result
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
1 Asphalt tar paper under slate shingle Attic No asbestos detected
2a 9” tan vinyl floor tile D2-38 mechanical room No asbestos detected
2b Black tar paper under tile “” No asbestos detected
2c Yellow mastic under tar paper “” No asbestos detected
3a 9” green floor tile D1-36 conf. room closet 4% Chrysotile Asbestos
3b Black mastic “” No asbestos detected
4a 9” tan floor tile D1-15 food storage room 6% Chrysotile Asbestos
4b Black mastic “” No asbestos detected
C3 Pipe insulation debris in soil Crawl space 45% Chrysotile Asbestos
C4 Pipe insulation debris in soil Crawl space 40% Chrysotile Asbestos
C6 Pipe insulation debris in soil Crawl space 30% Chrysotile Asbestos
C7 Pipe insulation debris in soil Crawl space 45% Chrysotile Asbestos
C8 Pipe insulation debris in soil Crawl space 40% Chrysotile Asbestos
Facility:
Building:
Sampling Date:
Analysis Date:
Laboratory:
Accreditation:
Sampler:
Certification:
CHEYENNE VA MEDICAL CENTER - CHEYENNE, VA
ASBESTOS REINSPECTION REPORT
DECEMBER 2023
ASBESTOS BULK SAMPLING INFORMATION
Cheyenne VA Medical Center – Cheyenne, VA Bldg. 1 November 5, 2018 November 21, 2018 EMLab P&K – Arvada, CO NVLAP Asbestos Bulk Accredited Laboratory # 500053-0 Brett Brumbaugh EPA Accredited Asbestos Inspector/Management Planner
PLM Point Count Laboratory Analysis Result (CARB 435)
SAMPLE
NUMBER
MATERIAL SAMPLE LOCATION
LABORATORY ANALYSIS
RESULT
C1 Loose soil in crawl space Crawl space 1-A No Asbestos Detected
C2 Loose soil in crawl space Crawl space 1 <0.25% Chrysotile Asbestos
C5 Loose soil in crawl space Crawl space 1-B No Asbestos Detected
DECEMBER 2023
APPENDIX B
Asbestos Quantities, Assessments, & Remediation Cost Estimates
Cheyenne VAMC - Cheyenne, WY Building 1
Asbestos Assessments and Cost Estimates December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment
Recommendation Removal Priority
Repair Cost Estimate
Removal Cost Estimate
Contaminated soil from pipe insulation debris Crawl Spaces 35,500 sf TSI Friable 7 Isolate crawl spaces and place signs at all entrances. Require PPE for entrance to crawl. Encapsulate soil or remove.
1 $220,000 $916,000
Pipe insulation CL-02C hallway, pipe chases by CL-04 and CL- 17, C1-102, D1-36A closet, D1-47, D1-50G, D1- 50J
68 lf TSI Friable 2 O&M; Remove at renovation or demolition 6 No damage $6,500
Hard ceiling plaster C1-92 Entry 1,440 sf SURFACING Non-friable 2 O&M; Remove at renovation or demolition 6 No damage $96,000
9” floor tile D1-36A closet, D1-15 storage, D1-41 80 sf MISC Non-friable 1 O&M; Remove at renovation or demolition 7 No damage $3,200
Ebony cement countertops & shelves D1-53 Dental Lab 90 sf MISC Non-friable 1 O&M; Remove at renovation or demolition 7 No damage $3,800
Drywall joint compound Attic 4-OL & 4-OK divider wall 628 sf MISC Non-friable 1 O&M; Remove at renovation or demolition 7 No damage $8,200
Black tar on FG Duct Insulation D1-15, N. basement Crawl 560 sf MISC Non-friable 1 O&M; Remove at renovation or demolition 7 No damage $22,500
Cove base mastic (brown cove base) D2-38 80 lf MISC Non-friable 1 O&M; Remove at renovation or demolition 7 No damage $4,500
Building 4
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation
Removal
Priority
Repair Cost
Estimate
Removal Cost
Estimate
Contaminated soil under concrete cap Crawl Spaces 2,860 sf TSI Non-friable 1 O&M; Remove at demolition 7 No damage $94,000
Pipe insulation Basement Storage Rooms B1, B2, and B4 415 lf TSI Friable 2 O&M; Remove at renovation or demolition 6 No damage $22,000
Skim coating on concrete walls Basement rooms B1, B1A, B2, B3, B4 and
1,440 sf SURFACING Non-friable 1
O&M; Remove at renovation or demolition 7 No damage $26,000
Hard ceiling & wall plaster
1st & 2nd floor rooms 100, 101, 102, 103, 104, 105, 106, 107, 108, 109, 110, 111, 112, 113, 114, 115, S1F1, 200, 201, 203, S1F2
11,220 sf SURFACING Non-friable 2 O&M; Remove at renovation or demolition 6 No damage $132,000
Building 5
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation
Removal
Priority
Repair Cost
Estimate
Removal Cost
Estimate
Transite cement sheets Basement furnace room B1 16 sf MISC Non-friable 1 O&M; Remove at renovation or demolition 7 No damage $3,200
Drywall joint compound First floor rooms 101, 102, 103, 104, 105, 106, 107, 108, C1, C2, S1F1 4,160 sf MISC Non-friable 2
O&M; Remove at renovation
6 No damage $28,000
Building 6
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation
Removal
Priority
Repair Cost
Estimate
Removal Cost
Estimate
Contaminated soil under concrete cap 2 Crawl Spaces 776 sf TSI Non-friable 1 O&M; Remove at renovation or demolition 7 No damage $58,000
Pipe insulation Basement Storage Room 001 20 lf TSI Friable 4 O&M; Remove at renovation
4 No damage $3,750
Building 7
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation
Removal
Priority
Repair Cost
Estimate
Removal Cost
Estimate
Hard ceiling & wall plaster
Basement, 1st & 2nd floor rooms B01, B02, 100, 101, 102, 103, 104, 105, 106, 107, 108, 109, 110, S1F2, 201
3,430 sf SURFACING Non-friable 2 O&M; Remove at renovation or demolition 6 No Damage $62,000
Linoleum sheet flooring Kitchen 104 168 sf MISC Non-friable 1 O&M; Remove at renovation
7 No Damage $3,200
Building 8
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation Removal Priority
Repair Cost
Estimate
Removal
Cost
Estimate
9” floor tile Basement Storage B01 80 sf MISC Non-friable 1 O&M; Remove at renovation or demolition 7 No damage $3,000
Drywall joint compound 1st floor entry 100 846 sf MISC Non-friable 2 O&M; Remove at renovation or demolition 6 No damage $8,460
Building 11
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation
Removal
Priority
Repair Cost
Estimate
Removal
Cost
Estimate
Pipe insulation (remaining stubs in sleeves) Elect. shop 103 (S.W. corner) 2 lf TSI Friable 1 O&M; Remove at renovation or demolition 7 No damage $2,500
Hard ceiling plaster Paint shops 105, 106, 107, and closet 214 770 sf SURFACING Non-friable 1 O&M; Remove at renovation or demolition 7 No damage $9,500
Glue pods for non-ACM 12” ceiling tiles (above 2x4 lay-in ceiling tile) 2nd floor offices 212 and 212A 384 sf MISC Non-friable 1
O&M; Remove at renovation or
7 No damage $7,200
Building 13
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation Removal Priority
Repair Cost
Estimate
Removal
Cost
Estimate
Pipe insulation Tunnel under driveway to Building
90 lf TSI Friable 2
Restrict access to tunnel with proper
PPE; O&M until removal at renovation or demolition
6 No damage $32,000
Skim coating on concrete walls Basement Room B-107 320 sf SURFACING Non-friable 2 O&M; Remove at renovation or
6 No damage $8,200
Building 19
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation Removal Priority
Repair Cost
Estimate
Removal
Cost
Estimate
Window Glazing/Putty Metal windows 4 windows MISC Non-friable 1 O&M; Remove at renovation or
7 No damage $4,000
Building 20
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation Removal Priority
Repair Cost
Estimate
Removal
Cost
Estimate
Window caulking Metal windows 10 windows MISC Non-friable 1 O&M; Remove at renovation or
7 No damage $5,000
Building 25
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation Removal Priority
Repair Cost
Estimate
Removal
Cost
Estimate
Window caulking Metal windows 1 window MISC Non-friable 1 O&M; Remove at renovation or
7 No damage $2,500
Building 26
Asbestos Assessments and Cost Estimates
December 2023
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation Removal Priority
Repair Cost
Estimate
Removal
Cost
Estimate
Window caulking Metal windows 2 windows MISC Non-friable 1 O&M; Remove at renovation or
7 No damage $2,500
DECEMBER 2023
APPENDIX C
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 1
Photo 1-1 Pipe insulation debris in crawl space on loose soil
Photo 1-2 Pipe insulation debris in crawl space on loose soil
Photo 1-3 Pipe insulation debris in crawl space on loose soil
Photo 1-4
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 1
Photo 1-5 Ebony cement lab table tops and shelves in Dental Lab D1-
Photo 1-6 9” tan floor tile in Canteen storage room D1-15
Photo 1-7 9” green floor tile in conference room closet D1-36
Photo 1-8
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 1
Photo 1-9 Hard plaster ceiling in
Cowboy Building Lobby
Photo 1-10
Attic
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 4
Photo 4-1 Pipe insulation in basement storage rooms
Photo 4-2 Asbestos debris in crawl space under concrete cap
Photo 4-3 Skim coat on concrete walls in basement
Photo 4-4 Hard plaster on ceilings and walls
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 5
Photo 5-1 Transite cement sheets above furnace in basement storage room B1
Photo 5-2 Drywall joint compound on 1st floor
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 6
Photo 6-1 Pipe insulation in basement storage room 001
Photo 6-2
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 7
Photo 7-1 Linoleum sheet flooring in kitchen/break room
Photo 7-2 Hard plaster on walls and ceilings
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 8
Photo 8-1 9” floor tile in basement storage room B01
Photo 8-2 entry
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 11
Photo 11-1 Pipe iinsulation in electrical shop
Photo 11-2 Hard ceiling plaster
Photo 11-3 Glue pods for 12” ceiling tile
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 13
Photo 13-1 Steam pipe insulation in tunnel from basement to
Building 11 under driveway
Photo 13-2 Skim coating on concrete walls in basement storage
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDING 19
Photo 19-1 Window glazing/putty on
DECEMBER 2023
PHOTOGRAPHS OF ASBESTOS MATERIALS
BUILDINGS 20, 25, AND 26
Photo 1 Window frame caulking on metal windows
Photo 2 Window frame caulking on metal windows
Photo 3
DECEMBER 2023
APPENDIX D
ASBESTOS LABORATORY REPORTS
Approved by:
Approved Signatory Balu Krishnan
Report for:
Mr. Brett Brumbaugh, REPA Castle Hill Associates PO Box 283 Waterville, OH 43566
Regarding: Project: Cheyenne VAMC - Cheyenne, WY; Asbestos Reinspection
EML ID: 2038295
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the items tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 11-12-2018
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EM-AS-S-1267)
EMLab ID: 2038295, Page 1 of 4EMLab P&K, LLC
EMLab P&K 3000 Lincoln Drive East, Suite A, Marlton, NJ 08053
(866) 871-1984 Fax (856) 334-1040 www.emlab.com Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Cheyenne VAMC - Cheyenne, WY; Asbestos Reinspection
Date of Sampling: 11-06-2018 Date of Receipt: 11-07-2018 Date of Report: 11-12-2018
ASBESTOS PLM REPORT
Total Samples Submitted: 9 Total Samples Analyzed: 9
Total Samples with Layer Asbestos Content > 1%: 7
Location: 1, Roofing Felt Lab ID-Version‡: 9619113-1
Sample Layers Asbestos Content Black Roofing Felt ND
Composite Non-Asbestos Content: 50% Cellulose Sample Composite Homogeneity: Good
Location: 2, Floor Tile & Mastic Lab ID-Version‡: 9619114-1
Sample Layers Asbestos Content Tan Floor Tile ND
Brown/Black Felt Padding ND Yellow Mastic ND
Composite Non-Asbestos Content: 70% Cellulose Sample Composite Homogeneity: Good
Location: 3, Floor Tile Lab ID-Version‡: 9619115-1
Sample Layers Asbestos Content Green Floor Tile 4% Chrysotile
Black Mastic ND Composite Non-Asbestos Content: 2% Cellulose Sample Composite Homogeneity: Good
EMLab ID: 2038295, Page 2 of 4EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(866) 871-1984 Fax (856) 334-1040 www.emlab.com Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Cheyenne VAMC - Cheyenne, WY; Asbestos Reinspection
Date of Sampling: 11-06-2018 Date of Receipt: 11-07-2018 Date of Report: 11-12-2018
ASBESTOS PLM REPORT
Location: 4, Floor Tile Lab ID-Version‡: 9619116-1
Sample Layers Asbestos Content Cream Floor Tile 6% Chrysotile
Black Mastic ND Sample Composite Homogeneity: Good
Location: C3, Debris in Crawl Lab ID-Version‡: 9619117-1
Sample Layers Asbestos Content White Insulation 45% Chrysotile
Peach Rock & Stick ND Composite Non-Asbestos Content: 25% Cellulose
20% Mineral Wool Sample Composite Homogeneity: Good
Location: C4, Debris in Crawl Lab ID-Version‡: 9619118-1
Sample Layers Asbestos Content Off-White Fibrous Material 40% Chrysotile
Composite Non-Asbestos Content: 50% Mineral Wool 2% Cellulose
Sample Composite Homogeneity: Good
EMLab ID: 2038295, Page 3 of 4EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 Fax (856) 334-1040 www.emlab.com Client: Castle Hill Associates C/O: Mr. Brett Brumbaugh, REPA Re: Cheyenne VAMC - Cheyenne, WY; Asbestos Reinspection
Date of Sampling: 11-06-2018 Date of Receipt: 11-07-2018 Date of Report: 11-12-2018
ASBESTOS PLM REPORT
Location: C6, Debris in Crawl Lab ID-Version‡: 9619119-1
Sample Layers Asbestos Content Beige Wrap Insulation 30% Chrysotile
Composite Non-Asbestos Content: 5% Cellulose Sample Composite Homogeneity: Good
Location: C7, Debris in Crawl Lab ID-Version‡: 9619120-1
Sample Layers Asbestos Content Off-White Fibrous Material 45% Chrysotile
Composite Non-Asbestos Content: 40% Mineral Wool 2% Cellulose
Sample Composite Homogeneity: Good
Location: C8, Debris in Crawl Lab ID-Version‡: 9619121-1
Sample Layers Asbestos Content White Insulation 40% Chrysotile
Composite Non-Asbestos Content: 50% Mineral Wool 3% Cellulose
Sample Composite Homogeneity: Good
EMLab ID: 2038295, Page 4 of 4EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
Approved by:
Technical Manager Noah Lazarte
Report for:
Mr. Brett Brumbaugh, REPA Castle Hill Associates PO Box 283 Waterville, OH 43566
Regarding: Project: Cheyenne VAMC- Cheyenne, WY; Asbestos Reinspection
EML ID: 2041579
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. Due to the nature of the analyses performed, field blank correction of results is not applied. The results relate only to the items tested.
EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results.
This is the start of the file's text. The full file is on GovTribe.