S06 - 0003 - Att 3 - Addendum 1- Drawings Combined.pdf
PDF 22 MB Posted
- Attached to
- Construct EHRM Infrastructure Upgrades | Lebanon, PA Federal contract opportunity
- Solicitation number
- 36C77625R0055_1
About this file
This file contains door schedule and technical specifications for a telecommunications room upgrade at the Lebanon VA Medical Center. The detailed drawing provides comprehensive information about door types, frame types, hardware requirements, and security specifications for multiple buildings across the facility.
Key details include door dimensions predominantly at 3' wide by 7' or 8' tall, with specific requirements for fire ratings, hardware, and security features. Each door is assigned a unique identifier and must adhere to VA infrastructure standards, such as telecommunications space doors being a minimum of 8' tall (with some approved exceptions). Security requirements mandate dual authentication card readers, door contacts, fixed and pan/tilt/zoom cameras, duress alarms, and integration with physical access control systems. The document covers door specifications for Buildings 01, 02, 17, 18, 19, 22, 23, 35, and 37, with meticulous attention to installation details, frame types, and security protocols.
View the file
Other files for this federal contract opportunity
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DOOR TYPES
FRAME TYPES
AS SCHEDULED
A S
S C
H E
D U
LE
D
TYPE F
GENERAL NOTE:
1. SEE DOOR SCHEDULE FOR FIRE RATING
2. PAINT ALL HOLLOW METAL DOOR AND FRAME
AS SCHEDULED
A S
S C
H E
D U
LE
D
TYPE 1
2" T
Y P
AS SCHEDULED
A S
S C
H E
D U
LE
D
TYPE 2
4" T
Y P
AS SCHEDULED
A S
S C
H E
D U
LE
D
TYPE FG
1. COORDINATE ALL DOOR HARDWARE AND DOOR SECURITY REQUIREMENTS LISTED IN
HARDWARE SCHEDULE WITH TECHNOLOGY, SECURITY, AND ELECTRICAL DRAWINGS.
DOORS SHALL HAVE 1/2" UNDERCUT UNLESS NOTED OTHERWISE IN THE CONSTRUCTION
DOCUMENTS.
2. FRAME OPENINGS INDICATED FINISHED SIZE OF FRAMES. COORDINATE ROUGH OPENINGS
TO INCLUDE INSTALLATION TOLERANCES.
3. SEE HOLLOW METAL FRAME TYPES AND DOOR TYPES ON THIS SHEET FOR ELEVATIONS
OF FRAMES, DOORS AND GLAZING IN DOOR OPENINGS.
4. "C" LABEL FIRE RATED DOORS SHALL BE RATED FOR 45 MINUTES
5. DOOR CLOSERS SHALL BE ADJUSTED TO REQUIRE NO MORE THAN 5 POUNDS PER
SQUARE FOOT OF OPENINGS FORCE TO OPEN DOORS.
DOOR SCHEDULE GENERAL NOTES
PER THE INFRASTRUCTURE STANDARDS FOR TELECOMMUNICATIONS SPACES VERSION 3.1,
TABLE 4.1.1- DOORS TO TELECOMMUNICATION SPACES SHALL BE 8'-0" IN HEIGHT MINIMUM. NEW
DOORS SHOWN IN DOOR SCHEDULE AS 7'-0" HAVE BEEN APPROVED BY AN EXCEPTION MEMO
AND CAN BE REFERENCED IN THE EXCEPTION MEMORANDUM OF THE CONTRACT DOCUMENTS.
DOOR HEIGHT EXCEPTION NOTE
1. ALL LOCKS FOR DOORS INTO NEW MCR AND NEW SWITCHGEAR SHALL BE FIELD
SELECTABLE FAIL SAFE/FAIL SECURE. THE TERM FAIL SECURE INDICATES THE LOCK WILL
REMAIN SECURE WHEN IN FAIL MODE. FAIL SECURE SHALL ALWAYS PERMIT EMERGENCY
EGRESS FUNCTIONS OF THE LOCK. IN THESE CIRCUMSTANCES A BYPASS FEATURE SHALL
BE PROVIDED TO ALLOW ACCESS FROM THE UNSECURE SIDE. MAGNETIC LOCKS SHALL
NOT FAIL SECURE.
DOOR HARDWARE GENERAL NOTE
WALL THICKNESS
COORD W/
2"
VARIES
SCHEDULED
PARTITION TYPE
METAL TRACK
METAL STUD BOX
HEADER
SEALANT TYP. BOTH
SIDES, FULL PERIMETER
JAMB ANCHOR
W A
LL
T
H
IC
K N
E S
S
C O
O R
D W
MIN
4"
2"
V A
R
IE
S
SEALANT TYP. BOTH SIDES,
FULL PERIMETER
JAMB ANCHOR
DOOR
DOOR FRAME
SCHEDULED PARTITION
TYPE SEE PLAN AND
WALL TYPE SHEET
EXISTING CMU WALL AND
LINTEL- VERIFY IN FIELD
5/ 8"
S E
E F
R A
M E
T Y
P E
VARIES
COORD. W/ WALL THICKNESS
BACKER ROD & SEALANT- BOTH
SIDES, TYP
HOLLOW METAL FRAME
EXISTING CMU WALL AND
LINTEL- VERIFY IN FIELD
C O
O R
D . W
/ W A
LL
T
H
IC
K N
E S
S
2" 5/8"
4" MIN. UON
SEALANT, BOTH SIDES, TYP-
FULL PERIMETER
JAMB ANCHOR
HOLLOW METAL FRAME
SDO217
• CARD READER- W/ BIOMETRIC OR PIN
IDENTIFICATION RETRACTS ELECTRIC STRIKE
• DOOR CLOSER
• CONTINUOUS HINGE
• DOOR CONTACT
• ELECTRIC STRIKE
• FLUSH BOLTS (IF DOUBLE DOORS- SEE SCHED)
• MORTISE LOCK- LOCKSET TYPE SHALL BE IN
ACCORDANCE WITH ANSI/BMHA F07
STOREROOM FUNCTION
• DOOR MONITOR SHALL BE ALARMED TO
CENTRAL MONITORING SYSTEM
• KICK PLATE
• SILENCERS
DOOR HARDWARE SCHEDULE & SECURITY REQUIREMENTS
SDO218
• CONTINUOUS HINGE
• FLUSH BOLTS (IF DOUBLE DOORS- SEE SCHED)
• MORTISE LOCK- LOCKSET SHALL BE IN
ACCORDANCE WITH ANSI/BMHA F07
STOREROOM FUNCTION
• DOOR CLOSER
• KICK PLATE
• SILENCERS
SDO228
• CARD READER- RELEASES STRIKE OR
COMBINATION LOCK RETRACKS LATCHBOLT
• CLOSER
• CONTINUOUS HINGE
• DOOR CONTACT
• ELECTRIC STRIKE
• FLUSH BOLTS (IF DOUBLE DOORS- SEE SCHED)
• MORTISE LOCK
• DOOR MONITOR ALARMED TO CENTRAL
MONITORING STATION
• SILENCERS
• KICK PLATE
SECURITY REQUIREMENTS PER VA PHYSICAL SECURITY & RESILIENCY DESIGN MANUAL (SEE ALL CONSULTANTS SHEETS FOR ADDITIONAL REQUIREMENTS & DETAILS)
ALL NEW DOORS TO NEW TR ROOMS AND NEW MCR SHALL BE PROVIDED WITH THE VA REQUIRED MINIMUM SECURITY SYSTEMS:
1. DUAL AUTHENTICATION CARD READER (CARD AND PIN)
2. DOOR CONTACT
3. FIXED CAMERA, PAN/TILT/ZOOM, PASSIVE INFRARED CAMERA- DUAL TECHNOLOGY
4. DURRESS/PANIC ALARM/ MONEY CLIP
5. PUBLIC ADDRESS/ MASS NOTIFICATION SYSTEM
6. SCC/IOC/EOC MONITORING (LOCAL OR REGIONAL) OF PHYSICAL ACCESS CONTROL SYSTEM (PACS), INTRUSION DETECTION SYSTEM (IDS), SECURITY SURVEILLANCE TELEVISION (SSTV), DURESS SECURITY PHONES AND INTERCOM SYSTEM (DSPI)
PER VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL
PROVIDE HORIZONTAL BRACE IF
SCREEN HEIGHT EXCEEDS 52"
2 1/2" OPENING WIDTH 2 1/2"
FRAME WIDTH
1/
2" O
P E
N
IN
G H
E
IG
H T
1/
2"
FR
A
M E
H E
IG
H
T
12 X 12 SCREEN MESH,
SS 304, 0.028" THICK, TYP
12 GA. STEEL FRAME, TYP
WELDED CORNERS, TYP
13 GA. CONCEALED HINGES
@ 24" O.C. MAX (2 HINGES
MIN.), TYP
BIT KEY LOCK, TYP
FRAME WIDTH
2 1/2" OPENING WIDTH 2 1/2"
FR
A
M E
H E
IG
H
T
1/ 2"
O P
E N
IN
G
H E
IG
H
T
1/
2"
SINGLE WINDOW FRAME W/ MULLION-
WHERE REQUIRED
EXTERIOR
INTERIOR
12 GA. STEEL MAIN FRAME, TYP
FASTENER PER MANUF'S
RECOMMENDATIONS, TYP
12 X 12 SCREEN MESH, SS
304, 0.028" THICK, TYP
2 1/2"
O P
E N
IN
G
H E
IG
H
T
1/ 2"
1/
2"
PROVIDE HORIZONTAL BRACE IF
SCREEN HEIGHT EXCEEDS 52"
SILL
HEAD
BRACE
FASTENER PER MANUF'S
RECOMMENDATIONS, TYP
12 GA. STEEL SUB-FRAME, TYP
2 1/2"
12 GA. STEEL SUB-FRAME
12 X 12 SCREEN MESH, SS
304, 0.028" THICK, TYP
12 GA. STEEL MAIN FRAME
EXISTING WINDOW, TYP- VERIFY
IN FIELD
EXISTING EXTERIOR WALL
CONSTRUCTION, TYP- VERIFY IN
FIELD
EXISTING EXTERIOR WALL
CONSTRUCTION, TYP- VERIFY IN
FIELD
EXISTING WINDOW, TYP-
VERIFY IN FIELD
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
15 SUNNEN DR. SUITE 104
ST. LOUIS, MO 63143
314-951-2535
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
LTCAL
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
DOOR SCHEDULES AND OPENING
DETAILS
AE600
-2
-7
A E
.p d f
DOOR SCHEDULE
DOOR NO.
DOOR FRAME DOOR
LABEL
FIRE
RATING
HARDWARE
SET REMARKS
NOMINAL SIZE
TYPE MATL MATL TYPE
SECTIONS
WIDTH HEIGHT THK. JAMB HEAD
BUILDING 01
230A 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G13/01-AE604 A7/01-AE604 SDO218 SECURITY REQS IN HARDWARE SCHED
340A 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G13/01-AE604 A13/01-AE604 SDO218 SECURITY REQS IN HARDWARE SCHED
400C 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G13/01-AE604 A13/01-AE604 SDO218 SECURITY REQS IN HARDWARE SCHED
539 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G13/01-AE604 A13/01-AE604 SDO218 SECURITY REQS IN HARDWARE SCHED
6B 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
27A 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
155 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
16A 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 NEW DOOR TO EXISTING STORAGE ROOM
BUILDING 02
103 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
BUILDING 10
106B 3' - 0" 8' - 0" 1 3/4" F HM HM 1 D10/AE600 D7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
BUILDING 17
236A 3' - 0" 7' - 0" 1 3/4" F HM HM 1 A10/17-AE603 E10/17-AE603 SDO218 SECURITY REQS IN HARDWARE SCHED
442F 3' - 0" 7' - 0" 1 3/4" F HM HM 1 A10/17-AE603 E10/17-AE603 SDO218 SECURITY REQS IN HARDWARE SCHED
549B 3' - 0" 7' - 0" 1 3/4" F HM HM 1 A10/17-AE603 E10/17-AE603 SDO218 SECURITY REQS IN HARDWARE SCHED
122A 3' - 0" 8' - 0" 1 3/4" F HM HM 2 A5/17-AE603 E5/17-AE603 SDO218 SECURITY REQS IN HARDWARE SCHED
339B 3' - 0" 7' - 0" 1 3/4" F HM HM 1 A10/17-AE603 E5/17-AE603 SDO218 SECURITY REQS IN HARDWARE SCHED
102A 6' - 0" 7' - 0" 1 3/4" HM HM 2 A15/17-AE603 E15/17-AE603 NEW DOUBLE DOOR TO BASEMENT. ONE PANEL SHALL BE
4'-0" (W) AND ONE PANEL SHALL BE 2-0" (W)
BUILDING 18
123 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
350 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
402 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
530 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
280 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
14 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
349A 2' - 6" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 NEW DOOR TO EXISTING CLOSET
BUILDING 19
132F 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
227 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
323 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
BUILDING 22
317 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
106A 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
244 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
BUILDING 23
101A 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
BUILDING 35
C119 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
BUILDING 37
1A23 3' - 0" 7' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
2A08K 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
BUILDING 104
1404 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
272 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/AE600 SDO218 SECURITY REQS IN HARDWARE SCHED
BUILDING 136
136A 6' - 0" 8' - 0" 1 3/4" HM HM 2 C5/136-AE401b A8/136-AE502 45 MIN. SDO217 SECURITY REQS IN HARDWARE SCHED
136B 6' - 0" 8' - 0" 1 3/4" HM HM 2 C5/136-AE401b A8/136-AE502 45 MIN. SDO217 SECURITY REQS IN HARDWARE SCHED
136C 3' - 0" 8' - 0" 1 3/4" F HM HM 1 G10/AE600 G7/E600 45 MIN SDO217 SECURITY REQS IN HARDWARE SCHED
3" = 1'-0"G7
NEW DOOR HEAD IN MTL STUD WALL
3" = 1'-0"G10
NEW DOOR JAMB IN MTL STUD WALL
3" = 1'-0"D7
NEW DOOR HEAD DETAIL IN EXISTING CMU
3" = 1'-0"D10
NEW DOOR JAMB DETAIL IN EXISTING CMU
3/4" = 1'-0"A9
WINDOW SECURITY SCREEN- ELEVATION
6" = 1'-0"A16
WINDOW SECURITY MESH DETAILS
Revisions: Date
ADDENDUM 1 07.03.2025
IT CLOSET
G011
M
IT CLOSET
G011
IT
CLOSET
25B
M
IT
CLOSET
25B
01-TD400
G5
EXISTING TTB
2- POST EQUIPMENT RACK
VERTICAL WIRE MANAGER
(TYP.)
EXISTING WALL MOUNTED
SWITCHES
KEYNOTES:
1. RE-CABLE EXISTING TELECOM OUTLETS AND NETWORK DEVICES FED FROM THIS ROOM WITH NEW CAT6A CABLES FROM NEW TELECOM ROOM. AFTER NEW EQUIPMENT IS ACTIVE AND DEVICES RE-CABLED, REMOVE EXISTING VOICE AND DATA CABLING FROM OUTLETS AND NETWORK DEVICES COMPLETE BACK TO WALL/RACK MOUNTED TELECOM EQUIPMENT IN THIS ROOM. REMOVE EXISTING EQUIPMENT RACK, FIBER DISTRIBUTION, CABLE MANAGERS, PATCH PANELS, PUNCHDOWN BLOCKS, PDUs, ETC. COMPLETE.
DELIVER NETWORK SWITCHES AND UPSs TO OWNER AS SPARES.
2. AFTER ACTIVATION OF TELECOM ROOM, REMOVE EXISTING FIBER BACKBONE CABLING COMPLETE BACK TO DATA CENTER.
3. PROVIDE NEW TEMPORARY OPTICAL FIBER JUMPERS FROM FIBER DISTRIBUTION PANEL IN NEW RACK TO SWITCHES IN EXISTING
RACKS.
4. MAINTAIN OPERATION OF EXISTING ACCESS CONTROL PANEL, CARD READERS AND DEVICES. PROVIDE NEW NETWORK CONNECTION
FROM NEW TR SERVING THIS AREA.
5. MANTAIN EXISTING PLYWOOD BACKBOARDS, SLEEVES, AND PATHWAYS. PATCH ALL HOLES AND OPENINGS IN WALLS/FLOORS TO
MATCH EXISTING SURFACE.
6. EXISTING VIDEO SURVEILLANCE, ACCESS CONTROL, FIRE ALARM, CATV AND BAS SYSTEMS AND DEVICES LOCATED WITHIN EXISTING
TELECOM ROOM SHALL REMAIN, INCLUDING ALL BACKBONE AND INTERCONNECTING CABLES REQUIRED TO MAINTAIN FULL OPERATIONS OF THESE SYSTEMS. COORDINATE WORK WITH EACH SYSTEM'S VENDOR AND VA PRIOR TO DISCONNECTING ANY
CABLING IN THIS ROOM.
6 1
EXISTING LADDER RACK
(TYP.)
KEYNOTES:
1. MAINTAIN CEILING AND WALL MOUNTED LADDER RUNWAYS, CABLE PATHWAYS, SLEEVES AND ALL MOUNTED
HARDWARE. PATCH ALL HOLES AND OPENING TO MATCH EXISTING SURFACE.
VA NETWORK SW.
EX. FIBER DISTR
EX. PATCH PANEL
EX. PATCH PANEL
EX. PATCH PANEL
CABLE MGR
EX. PATCH PANEL
EX. PATCH PANEL
CABLE MGR
EX. NETWRK SW
EX. NETWRK SW
EX. NETWRK SW
EX. UPS/BATT
SPACE
KEYNOTES:
1. RE-CABLE EXISTING TELECOM OUTLETS AND NETWORK DEVICES FED FROM THIS ROOM WITH NEW CAT6A CABLES FROM NEW TELECOM ROOM. AFTER NEW EQUIPMENT IS ACTIVE AND DEVICES RE-CABLED, REMOVE EXISTING VOICE AND DATA CABLING FROM OUTLETS AND NETWORK DEVICES COMPLETE BACK TO WALL/RACK MOUNTED TELECOM EQUIPMENT IN THIS ROOM.
REMOVE EXISTING EQUIPMENT RACK, FIBER DISTRIBUTION, CABLE MANAGERS, PATCH PANELS, PUNCHDOWN BLOCKS, PDUs, ETC. COMPLETE. DELIVER NETWORK SWITCHES AND UPSs TO OWNER AS SPARES.
2. AFTER ACTIVATION OF #TR-6A, REMOVE EXISTING FIBER BACKBONE CABLING COMPLETE BACK TO DATA CENTER.
3. PROVIDE NEW TEMPORARY OPTICAL FIBER JUMPERS FROM FIBER DISTRIBUTION PANEL IN NEW RACK TO SWITCHES IN
EXISTING RACKS.
4. MAINTAIN OPERATION OF EXISTING ACCESS CONTROL PANEL, CARD READERS AND DEVICES. PROVIDE NEW NETWORK
CONNECTION FROM NEW TR SERVING THIS AREA.
5. MANTAIN EXISTING PLYWOOD BACKBOARDS, SLEEVES, AND PATHWAYS. PATCH ALL HOLES AND OPENINGS IN WALLS/FLOORS
TO MATCH EXISTING SURFACE.
6. EXISTING VIDEO SURVEILLANCE, ACCESS CONTROL, FIRE ALARM, CATV AND BAS SYSTEMS AND DEVICES LOCATED WITHIN
EXISTING TELECOM ROOM SHALL REMAIN, INCLUDING ALL BACKBONE AND INTERCONNECTING CABLES REQUIRED TO MAINTAIN FULL OPERATIONS OF THESE SYSTEMS. COORDINATE WORK WITH EACH SYSTEM'S VENDOR AND VA PRIOR TO DISCONNECTING
ANY CABLING IN THIS ROOM.
-T
D
B5
VERTICAL WIRE MANAGER
(TYP.)
EXISTING WALL MOUNTED
SWITCHES
EXISTING EQUIPMENT RACK
EXISTING TTB
KEYNOTES:
1. MAINTAIN EXISTING CEILING AND WALL MOUNTED LADDER RUNWAYS, CABLE PATHWAYS, SLEEVES AND ALL MOUNTED HARDWARE COMPLETE. PATCH ALL HOLES AND OPENING TO MATCH EXISTING SURFACE.
18"x4"
LADDER RACK (TYP.)
"x
EX. FIBER DISTR.
EX. PATCH PANEL
EX. PATCH PANEL
EX. PATCH PANEL
CABLE MGR
EX. PATCH PANEL
EX. PATCH PANEL
CABLE MGR
EX. PATCH PANEL
EX. PATCH PANEL
EX. NETWRK SW
EX. NETWRK SW
EX. NETWRK SW
EX. UPS/BATT
SPACE
SPACE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
101 NORTH SEVENTH STREET
LOUISVILLE, KY 40202
440-262-3063
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
ECWACA
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
BUILDING 01 - TECHNOLOGY DEMO
ENLARGED PLANS
01-TD400
-2
-7
-T
D
/2
/2
.p d f
N O R
HT
1/4" = 1'-0"
EXISTING EQUIPMENT ENLARGEMENT ROOM TR-#GO11
G15
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #G011 PATHWAY
G11
1" = 1'-0"
EXISTING RACK ELEVATION TR-#G011
G5
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #25B ENLARGEMENT
B15
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #25B PATHWAY
B11
1" = 1'-0"
EXISTING RACK ELEVATION TR-#25B
B5
ADDENDUM #1 06/27/2025
CHASE
M
CHASE
CHASE
200A
UTILITY RM
IT
CLOSET
UTILITY RM
IT
CLOSET
200A
D
200A
UTILITY RM
IT
CLOSET
UTILITY RM
IT
CLOSET
200A
01-TD401
G5
EXISTING TTB
2-POST EQUIPMENT RACK
VWM (TYP.)
EXISTING ACCESS
CONTROL PANEL
110 BLOCKS
FIBER CABINETS
FIBER CABINETS
WALL MOUNTED
SWITCHES
EXISTING FIRE ALARM
CONTROL PANEL
EXISTING ACCESS
CONTROL PANEL
2 3
KEYNOTES:
1. RE-CABLE EXISTING TELECOM OUTLETS AND NETWORK DEVICES FED FROM THIS ROOM WITH NEW CAT6A CABLES FROM NEW TELECOM ROOM. AFTER NEW TELECOM ROOM IS ACTIVE AND RE-CABLED, REMOVE EXISTING VOICE AND DATA CABLING FROM OUTLETS AND NETWORK DEVICES COMPLETE BACK TO WALL/RACK MOUNTED TELECOM EQUIPMENT IN THIS ROOM.
REMOVE EXISTING EQUIPMENT RACK, FIBER DISTRIBUTION, CABLE MANAGERS, PATCH PANELS, PUNCHDOWN BLOCKS, PDUs, ETC. COMPLETE. DELIVER NETWORK SWITCHES AND UPSs TO OWNER AS SPARES.
2. AFTER ACTIVATION OF #TR-155, REMOVE FIBER BACKBONE CABLING COMPLETE BACK TO DATA CENTER.
3. PROVIDE NEW TEMPORARY OPTICAL FIBER JUMPERS FROM FIBER DISTR. PANEL IN NEW EQUIPMENT RACKS TO NETWORK
SWITCHES IN EXISTING RACKS.
4. MAINTAIN OPERATION OF EXISTING ACCESS CONTROL PANEL, CARD READER. AND DEVICES.
5. MAINTAIN EXISTING PLYWOOOD BACKBOARDS. PATCH ALL HOLES, CEILING/WALL OPENINGS TO MATCH EXISTING SURFACES.
6. EXISTING VIDEO SURVEILLANCE, ACCESS CONTROL, FIRE ALARM, CATV AND BAS SYSTEMS AND DEVICES LOCATED WITHIN
EXISTING TELECOM ROOM SHALL REMAIN, INCLUDING ALL BACKBONE AND INTERCONNECTING CABLES REQUIRED TO MAINTAIN FULL OPERATIONS OF THESE SYSTEMS. COORDINATE WORK WITH EACH SYSTEM'S VENDOR AND VA PRIOR TO
DISCONNECTING ANY CABLING IN THIS ROOM.
KEYNOTES:
1. MAINTAIN EXISTING CEILING AND WALL MOUNTED LADDER RUNWAY, CABLE PATHWAYS AND SLEEVES. PATCH
ALL HOLES AND WALL/CEILING OPENINGS TO MATCH EXISTING SURFACE
EXISTING 12" WIDE
LADDER RUNWAY
EX. CABLE MGR
EX. CABLE MGR
VA NETWORK SW.
VA NETWORK SW.
VA NETWORK SW.
VA NETWORK SW.
EX. UPS/BATT
EX. FIBER DISTR.
EX. FIBER DISTR.
EX. CABLE MGR
EX. PATCH PANEL
EX. CABLE MGR
EX. PATCH PANEL
EX. PATCH PANEL
EX. CABLE MGR
EX. PATCH PANEL
EX. PATCH PANEL
EX. PATCH PANEL
VA NETWORK SW.
VA NETWORK SW.
EX. CABLE MGR
EX. PATCH PANEL
VA NETWORK SW.
VA NETWORK SW.
SPACE
EX. PATCH PANEL
EX. CABLE MGR
EX. PATCH PANEL
EX. PATCH PANEL
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
01-TD401
B5
EXISTING TTB
KEYNOTES:
1. RE-CABLE EXISTING TELECOM OUTLETS AND NETWORK DEVICES FED FROM THIS ROOM WITH NEW CAT6A CABLES FROM NEW TELECOM ROOM. AFTER NEW TELECOM ROOM IS ACTIVE AND RE-CABLED, REMOVE EXISTING VOICE AND DATA CABLING FROM OUTLETS AND NETWORK DEVICES COMPLETE BACK TO WALL/RACK MOUNTED TELECOM EQUIPMENT IN THIS ROOM.
REMOVE EXISTING EQUIPMENT RACK, FIBER DISTRIBUTION, CABLE MANAGERS, PATCH PANELS, PUNCHDOWN BLOCKS, PDUs, ETC. COMPLETE. DELIVER NETWORK SWITCHES AND UPSs TO OWNER AS SPARES.
2. AFTER ACTIVATION OF #TR-155, REMOVE COPPER AND FIBER BACKBONE CABLING COMPLETE BACK TO DATA CENTER.
3. PROVIDE NEW TEMPORARY OPTICAL FIBER JUMPERS FROM FIBER DISTR. PANEL IN NEW EQUIPMENT RACKS TO NETWORK
SWITCHES IN EXISTING RACKS.
4. MAINTAIN OPERATION OF EXISTING ACCESS CONTROL PANEL, CARD READER. AND DEVICES.
5. MAINTAIN EXISTING PLYWOOOD BACKBOARDS. PATCH ALL HOLES, CEILING/WALL OPENINGS TO MATCH EXISTING SURFACES.
6. EXISTING VIDEO SURVEILLANCE, ACCESS CONTROL, FIRE ALARM, CATV AND BAS SYSTEMS AND DEVICES LOCATED WITHIN
EXISTING TELECOM ROOM SHALL REMAIN, INCLUDING ALL BACKBONE AND INTERCONNECTING CABLES REQUIRED TO MAINTAIN FULL OPERATIONS OF THESE SYSTEMS. COORDINATE WORK WITH EACH SYSTEM'S VENDOR AND VA PRIOR TO
DISCONNECTING ANY CABLING IN THIS ROOM.
EXISTING PAT.
MONITOR EQ.
1 2 3
110 BLOCKS
EXISTING WALL
MTD SWITCHES
EXISTING FIRE ALARM
CONTROL PANEL
2-POST RACKS
EXISTING 12" WIDE
LADDER RUNWAY
KEYNOTES:
1. MAINTAIN EXISTING CEILING AND WALL MOUNTED LADDER RUNWAY, CABLE PATHWAYS AND SLEEVES. PATCH
ALL HOLES AND WALL/CEILING OPENINGS TO MATCH EXISTING SURFACE
EX. FIBER DISTR
EX. CABLE MGR
CABLE MGR
EX. PATCH PANEL
EX. PATCH PANEL
EX. PATCH PANEL
EX. CABLE MGR
VA NETWORK SW.
VA NETWORK SW.
VA NETWORK SW.
SPACE
EX. UPS/BATT
EX. FIBER DISTR
EX. PATCH PANEL
EX. PATCH PANEL
EX. CABLE MGR
EX. PATCH PANEL
EX. PATCH PANEL
VA NETWORK SW.
SPACE
SPACE
SPACE
SPACE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
101 NORTH SEVENTH STREET
LOUISVILLE, KY 40202
440-262-3063
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
ECWACA
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
BUILDING 01 - TECHNOLOGY DEMO
ENLARGED PLANS
01-TD401
-2
-7
-T
D
/2
/2
.p d f
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #129 ENLARGEMENT
G15
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #129 PATHWAY
G10 1" = 1'-0"
EXISTING RACK ELEVATION TR-#129
G5
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #261 ENLARGEMENT
B15
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #261 PATHWAY
B10 1" = 1'-0"
EXISTING RACK ELEVATION TR-#261
D
D
M
UNISEX TOILET
HAC
IT
CLOSET
UNISEX TOILET
UNISEX TOILET
HAC
UNISEX TOILET
HAC
D
V
D
M
D
UNISEX TOILET
HAC
01-TD402
G5
EXISTING TTB
(2) EXISTING WALL MOUNTED
RACKS
KEYNOTES:
1. RE-CABLE EXISTING TELECOM OUTLETS AND NETWORK DEVICES FED FROM THIS ROOM WITH NEW CAT6A CABLES FROM NEW TELECOM ROOM. AFTER NEW TELECOM ROOM IS ACTIVE AND RE-CABLED, REMOVE EXISTING VOICE AND DATA CABLING FROM OUTLETS AND NETWORK DEVICES COMPLETE BACK TO WALL/RACK MOUNTED TELECOM EQUIPMENT IN THIS ROOM.
REMOVE EXISTING EQUIPMENT RACK, FIBER DISTRIBUTION, CABLE MANAGERS, PATCH PANELS, PUNCHDOWN BLOCKS, PDUs, ETC. COMPLETE. DELIVER NETWORK SWITCHES AND UPSs TO OWNER AS SPARES.
2. AFTER ACTIVATION OF #TR-300A, REMOVE FIBER BACKBONE CABLING COMPLETE BACK TO DATA CENTER.
3. PROVIDE NEW TEMPORARY OPTICAL FIBER JUMPERS FROM FIBER DISTR. PANEL IN NEW EQUIPMENT RACKS TO NETWORK
SWITCHES IN EXISTING RACKS.
4. MAINTAIN OPERATION OF EXISTING ACCESS CONTROL PANEL, CARD READER. AND DEVICES.
5. MAINTAIN EXISTING PLYWOOOD BACKBOARDS. PATCH ALL HOLES, CEILING/WALL OPENINGS TO MATCH EXISTING SURFACES.
6. MAINTAIN OPERATION OF EXISTING FIRE ALARM CONTROL PANEL AND DEVICES.
7. EXISTING VIDEO SURVEILLANCE, ACCESS CONTROL, FIRE ALARM, CATV AND BAS SYSTEMS AND DEVICES LOCATED WITHIN
EXISTING TELECOM ROOM SHALL REMAIN, INCLUDING ALL BACKBONE AND INTERCONNECTING CABLES REQUIRED TO MAINTAIN FULL OPERATIONS OF THESE SYSTEMS. COORDINATE WORK WITH EACH SYSTEM'S VENDOR AND VA PRIOR TO
DISCONNECTING ANY CABLING IN THIS ROOM.
EXISTING FIRE ALARM
CONTROL PANEL
EXISTING WALL MOUNTED
SWITCHES 110 BLOCKS
EXISTING CATV
1 2 3
EXISTING 12" WIDE
LADDER RUNWAY
KEYNOTES:
1. MAINTAIN EXISTING CEILING AND WALL MOUNTED LADDER RUNWAY, CABLE PATHWAYS AND SLEEVES. PATCH
ALL HOLES AND WALL/CEILING OPENINGS TO MATCH EXISTING SURFACE
01-TD402
B5
EXISTING TTB
KEYNOTES:
1. RE-CABLE EXISTING TELECOM OUTLETS AND NETWORK DEVICES FED FROM THIS ROOM WITH NEW CAT6A CABLES FROM NEW TELECOM ROOM. AFTER NEW TELECOM ROOM IS ACTIVE AND RE-CABLED, REMOVE EXISTING VOICE AND DATA CABLING FROM OUTLETS AND NETWORK DEVICES COMPLETE BACK TO WALL/RACK MOUNTED TELECOM EQUIPMENT IN THIS ROOM. REMOVE EXISTING EQUIPMENT RACK, FIBER DISTRIBUTION, CABLE MANAGERS, PATCH PANELS, PUNCHDOWN BLOCKS, PDUs, ETC. COMPLETE. DELIVER NETWORK SWITCHES AND UPSs TO OWNER AS SPARES.
2. AFTER ACTIVATION OF #TR-400A, REMOVE FIBER BACKBONE CABLING COMPLETE BACK TO DATA CENTER.
3. PROVIDE NEW TEMPORARY OPTICAL FIBER JUMPERS FROM FIBER DISTR. PANEL IN NEW EQUIPMENT RACKS TO NETWORK
SWITCHES IN EXISTING RACKS.
4. MAINTAIN OPERATION OF EXISTING ACCESS CONTROL PANEL, CARD READER. AND DEVICES.
5. MAINTAIN EXISTING PLYWOOOD BACKBOARDS. PATCH ALL HOLES, CEILING/WALL OPENINGS TO MATCH EXISTING SURFACES.
6. MAINTAIN OPERATION OF EXISTING FIRE ALARM CONTROL PANEL AND DEVICES.
7. EXISTING VIDEO SURVEILLANCE, ACCESS CONTROL, FIRE ALARM, CATV AND BAS SYSTEMS AND DEVICES LOCATED WITHIN
EXISTING TELECOM ROOM SHALL REMAIN, INCLUDING ALL BACKBONE AND INTERCONNECTING CABLES REQUIRED TO MAINTAIN FULL OPERATIONS OF THESE SYSTEMS. COORDINATE WORK WITH EACH SYSTEM'S VENDOR AND VA PRIOR TO
DISCONNECTING ANY CABLING IN THIS ROOM.
EXISTING FIRE ALARM
CONTROL PANEL
EXISTING NURSE CALL
1 2 3
(2) EXISTING WALL MOUNTED RACKS
12"x4"
"x
EXISTING 12" WIDE
LADDER RUNWAY
KEYNOTES:
1. MAINTAIN EXISTING CEILING AND WALL MOUNTED LADDER RUNWAY, CABLE PATHWAYS AND SLEEVES. PATCH
ALL HOLES AND WALL/CEILING OPENINGS TO MATCH EXISTING SURFACE
EX. PATCH PANEL
EX. PATCH PANEL
VA NETWORK SW.
VA NETWORK SW.
VA NETWORK SW.
SPACE
VA NETWORK SW.
SPACE
VA NETWORK SW.
SPACE
EX. CABLE MGR
EX. PATCH PANEL
EX. PATCH PANEL
VA NETWORK SW.
VA NETWORK SW.
SPACE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
101 NORTH SEVENTH STREET
LOUISVILLE, KY 40202
440-262-3063
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
ECWACA
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
BUILDING 01 - TECHNOLOGY DEMO
ENLARGED PLANS
01-TD402
-2
-7
-T
D
/2
/2
.p d f
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #353 ENLARGEMENT
G15
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #353 PATHWAY
G10
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #461 ENLARGEMENT
B15
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #461 PATHWAY
B10
1" = 1'-0"
EXISTING RACK ELEVATION TR-#353
G5
1" = 1'-0"
EXISTING RACK ELEVATION TR-#461
UNISEX TOILET
D
V
M
UNISEX TOILET
CHASE
HAC
616ACSS
CHASE
HAC
616A
01-TD403
G5
EXISTING TTB
KEYNOTES:
1. RE-CABLE EXISTING TELECOM OUTLETS AND NETWORK DEVICES FED FROM THIS ROOM WITH NEW CAT6A CABLES FROM NEW TELECOM ROOM. AFTER NEW TELECOM ROOM IS ACTIVE AND RE-CABLED, REMOVE EXISTING VOICE AND DATA CABLING FROM OUTLETS AND NETWORK DEVICES COMPLETE BACK TO WALL/RACK MOUNTED TELECOM EQUIPMENT IN THIS ROOM.
REMOVE EXISTING EQUIPMENT RACK, FIBER DISTRIBUTION, CABLE MANAGERS, PATCH PANELS, PUNCHDOWN BLOCKS, PDUs, ETC. COMPLETE. DELIVER NETWORK SWITCHES AND UPSs TO OWNER AS SPARES.
2. AFTER ACTIVATION OF #TR-572A, REMOVE FIBER BACKBONE CABLING COMPLETE BACK TO DATA CENTER.
3. PROVIDE NEW TEMPORARY OPTICAL FIBER JUMPERS FROM FIBER DISTR. PANEL IN NEW EQUIPMENT RACKS TO NETWORK
SWITCHES IN EXISTING RACKS.
4. MAINTAIN OPERATION OF EXISTING ACCESS CONTROL PANEL, CARD READER. AND DEVICES.
5. MAINTAIN EXISTING PLYWOOOD BACKBOARDS. PATCH ALL HOLES, CEILING/WALL OPENINGS TO MATCH EXISTING SURFACES.
6. EXISTING VIDEO SURVEILLANCE, ACCESS CONTROL, FIRE ALARM, CATV AND BAS SYSTEMS AND DEVICES LOCATED WITHIN
EXISTING TELECOM ROOM SHALL REMAIN, INCLUDING ALL BACKBONE AND INTERCONNECTING CABLES REQUIRED TO MAINTAIN FULL OPERATIONS OF THESE SYSTEMS. COORDINATE WORK WITH EACH SYSTEM'S VENDOR AND VA PRIOR TO
DISCONNECTING ANY CABLING IN THIS ROOM.
EXISTING FIRE ALARM
CONTROL PANEL
EXISTING FIBER
PANEL/110 BLOCKS
EXISTING ACCESS
CONTROL PANEL
(2) EXISTING
EQUIPMENT RACK 1 2 3
KEYNOTES:
1. REMOVE EXISTING PATHWAYS AND SLEEVES. PATCH ALL HOLES AND WALL/CEILING OPENINGS TO MATCH
EXISTING SURFACE.
-T
D
B5
EXISTING TTB
EXISTING EQUIPMENT RACK
KEYNOTES:
1. RE-CABLE EXISTING TELECOM OUTLETS AND NETWORK DEVICES FED FROM THIS ROOM WITH NEW CAT6A CABLES FROM NEW TELECOM ROOM. AFTER NEW TELECOM ROOM IS ACTIVE AND RE-CABLED, REMOVE EXISTING VOICE AND DATA CABLING FROM OUTLETS AND NETWORK DEVICES COMPLETE BACK TO WALL/RACK MOUNTED TELECOM EQUIPMENT IN THIS ROOM. REMOVE EXISTING EQUIPMENT RACK, FIBER DISTRIBUTION, CABLE MANAGERS, PATCH PANELS, PUNCHDOWN BLOCKS, PDUs, ETC. COMPLETE. DELIVER NETWORK SWITCHES AND UPSs TO OWNER AS SPARES.
2. AFTER ACTIVATION OF #TR-572A, REMOVE FIBER BACKBONE CABLING COMPLETE BACK TO DATA CENTER.
3. PROVIDE NEW TEMPORARY OPTICAL FIBER JUMPERS FROM FIBER DISTR. PANEL IN NEW EQUIPMENT RACKS TO NETWORK
SWITCHES IN EXISTING RACKS.
4. MAINTAIN OPERATION OF EXISTING ACCESS CONTROL PANEL, CARD READER. AND DEVICES.
5. MAINTAIN EXISTING PLYWOOOD BACKBOARDS. PATCH ALL HOLES, CEILING/WALL OPENINGS TO MATCH EXISTING
SURFACES.
6. EXISTING VIDEO SURVEILLANCE, ACCESS CONTROL, FIRE ALARM, CATV AND BAS SYSTEMS AND DEVICES LOCATED WITHIN
EXISTING TELECOM ROOM SHALL REMAIN, INCLUDING ALL BACKBONE AND INTERCONNECTING CABLES REQUIRED TO MAINTAIN FULL OPERATIONS OF THESE SYSTEMS. COORDINATE WORK WITH EACH SYSTEM'S VENDOR AND VA PRIOR TO
DISCONNECTING ANY CABLING IN THIS ROOM.
1 2 3
EXISTING FIRE ALARM
CONTROL PANEL
KEYNOTES:
1. REMOVE EXISTING PATHWAYS AND SLEEVES. PATCH ALL HOLES AND WALL/CEILING OPENINGS TO MATCH
EXISTING SURFACE.
VA NETWORK SW.
VA NETWORK SW.
EX. PATCH PANEL
EX. PATCH PANEL
VA NETWORK SW.
VA NETWORK SW.
VA NETWORK SW.
VA NETWORK SW.
EX. PATCH PANEL
EX. PATCH PANEL
VA NETWORK SW.
VA NETWORK SW.
SPACE
SPACE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
101 NORTH SEVENTH STREET
LOUISVILLE, KY 40202
440-262-3063
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
ECWACA
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
BUILDING 01 - TECHNOLOGY DEMO
ENLARGED PLANS
01-TD403
-2
-7
-T
D
/2
/2
.p d f
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #561 ENLARGEMENT
G15
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #561 PATHWAY
G10
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #616A ENLAREMENT
B15
N O R
HT
1/4" = 1'-0"
EXISTING TELECOM ROOM TR #616A PATHWAY
B10
1" = 1'-0"
EXISTING RACK ELEVATION TR-#561
G5
1" = 1'-0"
EXISTING RACK ELEVATION TR-#616A
Telecom
M
Telecom01-TD404 G5
VERTICAL WIRE MANAGER
(TYP.)
EXISTING WALL MOUNTED
SWITCHES
EX. FIBER DISTR.
EXISTING TTB
KEYNOTES:
1. RE-CABLE EXISTING TELECOM OUTLETS AND NETWORK DEVICES FED FROM THIS ROOM WITH NEW CAT6A CABLES FROM NEW TELECOM ROOM. AFTER NEW EQUIPMENT IS ACTIVE AND DEVICES RE-CABLED, REMOVE EXISTING VOICE AND DATA CABLING FROM OUTLETS AND NETWORK DEVICES COMPLETE BACK TO WALL/RACK MOUNTED TELECOM EQUIPMENT IN THIS ROOM. REMOVE EXISTING EQUIPMENT RACK, FIBER DISTRIBUTION, CABLE MANAGERS, PATCH PANELS, PUNCHDOWN BLOCKS, PDUs, ETC. COMPLETE. DELIVER NETWORK SWITCHES AND UPSs TO OWNER AS SPARES.
2. AFTER ACTIVATION OF #TR-6A, REMOVE EXISTING COPPER AND FIBER BACKBONE CABLING COMPLETE BACK TO ANALOG PHONE DISTRIBUTION EQUIPMENT AND
DATA CENTER, RESPECTIVELY.
3. PROVIDE NEW TEMPORARY OPTICAL FIBER JUMPERS FROM FIBER DISTRIBUTION PANEL IN NEW RACK TO SWITCHES IN EXISTING RACKS.
4. REMOVE ACCESS CONTROL CARD READER, RTE, PTE, DOOR CONTACTS AND CABLES COMPLETE BACK TO ACCESS CONTROL SYSTEM PANELS THAT SERVES
THIS ROOM. DELIVER ALL COMPONENTS TO OWNER AS SPARES.
5. REMOVE EXISTING PLYWOOOD BACKBOARDS, CABLE SLEEVES AND PATHWAYS COMPLETE. PATCH ALL HOLES, CEILING/WALL OPENINGS TO MATCH EXISTING
SURFACES.
6. EXISTING VIDEO SURVEILLANCE, ACCESS CONTROL, FIRE ALARM, CATV AND BAS SYSTEMS AND DEVICES LOCATED WITHIN EXISTING TELECOM ROOM SHALL
REMAIN, INCLUDING ALL BACKBONE AND INTERCONNECTING CABLES REQUIRED TO MAINTAIN FULL OPERATIONS OF THESE SYSTEMS. COORDINATE WORK WITH EACH SYSTEM'S VENDOR AND VA PRIOR TO DISCONNECTING ANY CABLING IN THIS ROOM.
EXISTING LADDER
RACK (TYP.)
KEYNOTES:
1. REMOVE EXISTING CEILING AND WALL MOUNTED LADDER RUNWAYS, CABLE PATHWAYS, SLEEVES AND ALL MOUNTED HARDWARE
COMPLETE. PATCH ALL HOLES AND OPENING TO MATCH EXISTING SURFACE.
EX. FIBER DISTR.
EX. PATCH PANEL
EX. PATCH PANEL
EX. PATCH PANEL
EX. PATCH PANEL
EX. PATCH PANEL
CABLE MGR
EX. NETWRK SW
EX. NETWRK SW
EX. NETWRK SW
EX. UPS/BATT
EX. PATCH PANEL
EX. NETWRK SW
EX. NETWRK SW
EX. NETWRK SW
CABLE MGR
SPACE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
101 NORTH SEVENTH STREET
LOUISVILLE, KY 40202
440-262-3063
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
ECWACA
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
BUILDING 01 - TECHNOLOGY DEMO
ENLARGED PLANS
01-TD404
-2
-7
-T
D
/2
/2
.p d f
N O R
HT
1/4" = 1'-0"
EXISTING EQUIPMENT ENLARGEMENT TR-GROUND FLOOR AREA C
G15
N O R
HT
1/4" = 1'-0"
PATHWAY ENLARGEMENT TR-GROUND FLOOR AREA C
G10 1" = 1'-0"
EXISTING RACK ELEVATION TR-GROUND FLOOR AREA-C
G5
F.A.C
CABINET
ELECTRICAL
400C1C 400C1B 247
C4-15
400C3
400C5
480A
480 479
C4-13 C4-13A
479A 478A
477A
476A 476
474474A
473A
C4-10 C4-10A
466A
467A
NO. 3
NO.
455A
457A
452A
453B 453C
453A
460 461
400C4
485A
490B
429 428
400C1D
418 417
411 410
408 407
406 405
438 443
445 446
NO. 2
400C2
400C1A
C4-11
C4-12C4-14489
440439
C4-1F
C4-1E
490A
470469
CORRIDOR CORRIDOR CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
DAY ROOM
THERAPY
STORAGE
WAITING
EQUIP STORAGE
HAC
LAUNDRY
BATH RM
BED RM - 2BED BED RM - 1BED
HAC HAC
BATH RM BATH RM
BED RM - 2BED
BATH RM
BED RM - 2BED
BATH RM BED RM - ISOLATION
ANTE RM
BED RM - ISOLATIONBATH RM
BED RM - 2BED
BATH RM
CLEAN
UTILITY
STAIR HALL SOILED UTILITY
ALCOVE ALCOVE
BED RM - 2BED
BATH RM
MEDICATION RM
NURSE
STATION
NOURISHMENT
CONFERENCESTAFF
LOUNGE
STAIR HALL
BATH RM
BED RM - 2BED
SERVICE
ELEVATOR
PUBLIC
ELEVATOR
STAIR HALL
STAIR HALL
WOMEN TOILET
VESTIBULE
MEN
LOCKER
ENTRY
MENS
TOILET
PIPE CHASE
HAC
CONFERENCE
OFFICE
HAC HAC
OFFICE
STAIR
OFFICE
HOSPICE
PATIENT RM
UNISEX TOILET
HAC
CORRIDOR
EQUIP
STORAGE
HOSPICE
PATIENT ROOM
BED RM - 1BED
BATH RM
BED RM - 1BED
BED RM - 1BED
BATH RM
BED RM - 1BED BED RM - 1BED
BATH RM BED RM - 1BED
NURSE STATION
LOUNGE
MEDICATION RM
BED RM - 1BED
CORRIDOR
BATH RM
BED RM - 2BED
BATH RM
BED RM - 1BED BED RM - 1BED
BATH RM
BATH RM
BED RM - 1BED
STORAGE
BED RM - 1BED BATH RM
LAUNDRY
NURSE
OFFICE
CLEAN
STORAGE
CLEAN
UTILITY SOILED UTILITY
STAFF
TOILET
BREAK RM
VESTIBULE
STAFF
LOCKERS
OFFICE
BED RM - 1BED
BATH RM
BATH RM
BED RM - 2BED DAY ROOM
BED RM - 1BED BATH RM
SERVICE LOBBY
CLEAN
UTILITY
BED RM - 1BED
PUBLIC
ELEVATOR
ELEVATOR LOBBY
CORRIDOR
BED RM - 2BED
CHARTING
CHARTINGCHARTING
STAFF
TOILET
ELECTRICAL CLOSETELECTRICAL CLOSET
ELECTRICAL CLOSET
ELECTRICAL CLOSET
PATIENT TOILET
ELECTRICAL CLOSETELECTRICAL CLOSET
UPUP
DN
UP DN
UP
DN
UP UP
DN
NEW TR-
PROPOSED
TOWER
ADDITION
400C1C 400C1B 247
C4-15
400C3
400C5
480A
480 479
C4-13 C4-13A
479A 478A
477A
476A 476
474474A
473A
C4-10 C4-10A
466A
467A
NO. 3
NO.
455A
457A
452A
453B 453C
453A
460 461
400C4
485A
490B
429 428 427 426
400C1D
418 417
411 410
408 407
406 405
438 443
445 446
NO. 2
400C2
400C1A
C4-11
C4-12C4-14489
440439
C4-1F
C4-1E
490A
470469
UPUP
DN
UP DN
UP
DN
UP UP
DN
CORRIDOR CORRIDOR CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
DAY ROOM
THERAPY
STORAGE
WAITING
EQUIP STORAGE
HAC
LAUNDRY
BATH RM
BED RM - 2BED BED RM - 1BED
HAC HAC
BATH RM BATH RM
BED RM - 2BED
BATH RM
BED RM - 2BED
BATH RM BED RM - ISOLATION
ANTE RM
BED RM - ISOLATIONBATH RM
BED RM - 2BED
BATH RM
CLEAN
UTILITY
STAIR HALL SOILED UTILITY
ALCOVE ALCOVE
BED RM - 2BED
BATH RM
MEDICATION RM
NURSE
STATION
NOURISHMENT
CONFERENCESTAFF
LOUNGE
STAIR HALL
BATH RM
BED RM - 2BED
SERVICE
ELEVATOR
PUBLIC
ELEVATOR
STAIR HALL
STAIR HALL
WOMEN TOILET
VESTIBULE
MEN
LOCKER
ENTRY
MENS
TOILET
PIPE CHASE
HAC
CONFERENCE
OFFICE
HAC HAC
OFFICE
STAIR
OFFICE
HOSPICE
PATIENT RM
UNISEX TOILET
HAC
CORRIDOR
EQUIP
STORAGE
HOSPICE
PATIENT ROOM
BED RM - 1BED
BATH RM
BED RM - 1BED
BED RM - 1BED
BATH RM
BED RM - 1BED BED RM - 1BED
BATH RM BED RM - 1BED
NURSE STATION
LOUNGE
MEDICATION RM
BED RM - 1BED
CORRIDOR
BATH RM
BED RM - 2BED
BATH RM
BED RM - 1BED BED RM - 1BED
BATH RM
BATH RM
BED RM - 1BED
STORAGE
BED RM - 1BED BATH RM
LAUNDRY
NURSE
OFFICE
CLEAN
STORAGE
CLEAN
UTILITY SOILED UTILITY
STAFF
TOILET
BREAK RM
VESTIBULE
STAFF
LOCKERS
OFFICE
BED RM - 1BED
BATH RM
BATH RM
BED RM - 2BED DAY ROOM
BED RM - 1BED BATH RM
SERVICE LOBBY
CLEAN
UTILITY
BED RM - 1BED
PUBLIC
ELEVATOR
ELEVATOR LOBBY
CORRIDOR
BED RM - 2BED
CHARTING
CHARTINGCHARTING
STAFF
TOILET
ELECTRICAL CLOSETELECTRICAL CLOSET
ELECTRICAL CLOSET
ELECTRICAL CLOSET
PATIENT TOILET
ELECTRICAL CLOSETELECTRICAL CLOSET
F.A.C
CABINET
ELECTRICAL
TR #400A
ADDITION
01-TN402
B15
01-TN402
B10
OUTLINE OF TR #539
AT FLOOR ABOVE
(1) 4"C - 24-STRAND, OS2,
OPTICAL FIBER CABLE
(1) 4"C - 24-STRAND, OS2,
OPTICAL FIBER CABLE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
101 NORTH SEVENTH STREET
LOUISVILLE, KY 40202
440-262-3063
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
ECWACA
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
BUILDING 01 - 4TH FLOOR OVERALL
PLAN - TECHNOLOGY
01-TN205
-2
-7
-T
N
/2
/2
.p d f
N O R
HT
1/16" = 1'-0"
BUILDING 01 - 4TH FLOOR PLAN - TECHNOLOGY
A12
N
TRUE
NORTH
N
BUILDING
NORTH
KEY NOTES:
1. ROUTE CONDUITS UP TO CEILING HEIGHT.
PROVIDE PULL BOX AND PENETRATION THRU
CEILING TO ROUTE CONDUIT UP INTO TR #539 IN
NEW BUILDING ADDITION.
SITE KEY PLAN
N
TRUE NORTH
NOT TO SCALE
GENERAL NOTES:
1. ALL NEW CABLING SHALL BE INSTALLED IN
EXISTING CABLE TRAYS LOCATED IN
CORRIDORS OF FLOOR PLAN. PROVIDE J-HOOK
PATHWAYS FOR NEW CABLING FROM EXISTING
CABLE TRAY TO OUTLET LOCATIONS.
UP
UP
UP
DN.
UP DN.
UP
DN.
UP
DN
521C
521A
530 531 C5-10
533 560
C5-15
563 565
566A 567A
567 568
571 572 573A
C5-16
574A
576A
541A
540E 540D
540A540B
540F
577A
578A
580A
581A
C5-24
582A
585A
593593
500A
500C2-1 C5-14
C5-1
572X
517C 517D
518 519 520 521 522 523 525 526
517A 517
510511512513514515516 509
500C3-1
521B
517B
540C
C5-17 575
C5-18C5-19 C5-21
592A
504 591
C5-20
STAIR - 2
ELECTRICAL CLOSET
OFFICE
HEAD
NURSE
OFFICE
ELEVATOR LOBBY
SERVICE
ELEVATOR 3
PUBLIC
ELEVATOR
STAIR
UNISEX TOILET
IT CLOSET
MEDICATION RM
NOURISHMENT LOUNDRY
LOUNGE
BED RM - 2 BED
PATIENT
SHOWER
PATIENT
SHOWER
BED RM - 2 BED STAIR
STORAGE
SOILED UTILITY CLEAN UTILITY
PATIENT
SHOWER
BED RM - 2 BED
ALCOVE
PATIENT
SHOWER
BED RM - ISOLATION
PATIENT
SHOWER
BED RM - ISOLATION
HAC
PIPE CHASE
PATIENT TOILET
MENS LOCKER
STAIR
MECH
ENTRY PASSAGE
CLOSET
STAFF LOCKERS
OFFICE
OFFICE
STORAGE
BED RM - 2 BED
PATIENT
SHOWER
BED RM - 2 BEDPATIENT
SHOWER
EQUIP
STORAGEPATIENT
SHOWER
BATH RM
PATIENT TOILET
ALCOVE
BED RM - 1 BED
PATIENT
SHOWER
BED RM - 1 BED
BED RM - 2 BED
BATH RM
PATIENT
SHOWER
BED RM - 2 BED
PHYSICIAN OFFICE
PHYSICIAN OFFICE
PHYSICIAN OFFICE
PHYSICIAN OFFICE
HAC
BREAK RMBREAK RM
DINING
STORAGE
PATIENT TOILET
WAITING
HAC
OFFICE
BED RM - 2 BED
CORRIDOR
CORRIDOR
ELEVATOR LOBBY
CORRIDOR
OFFICE OFFICE
OFFICE OFFICE OFFICE
OFFICE OFFICE OFFICE OFFICE OFFICE
OFFICE
OFFICE OFFICE
OFFICEOFFICEOFFICEOFFICEOFFICEOFFICEOFFICE OFFICE
STAFF TOILET
KITCHENETTE
OFFICE
HAC
CORRIDOR
MECH
ELECTRICAL CLOSET
STORAGE
PATIENT TOILET
TELEPHONE CLOSET
CHARTING KITCHEN
CHARTINGALCOVE
HAC
HAC
UNISEX TOILET UNISEX TOILET
STORAGE
NEW TR
TR #539
ADDITION
01-TN403
G15
01-TN403
G10
(1) 4"C - 24-STRAND, OS2,
OPTICAL FIBER CABLE
(1) 4"C - 24-STRAND, OS2,
OPTICAL FIBER CABLE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
101 NORTH SEVENTH STREET
LOUISVILLE, KY 40202
440-262-3063
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
ECWACA
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
BUILDING 01 - 5TH FLOOR OVERALL
PLAN - TECHNOLOGY
01-TN206
-2
-7
-T
N
/2
/2
.p d f
N O R
HT
1/16" = 1'-0"
BUILDING 01 - 5TH FLOOR PLAN - TECHNOLOGY
A12
N
TRUE
NORTH
N
BUILDING
NORTH
KEY NOTES:
1. ROUTE CONDUITS UP TO CEILING HEIGHT.
PROVIDE PULL BOX AND PENETRATION THRU
CEILING TO ROUTE CONDUIT UP INTO TR #539 IN
NEW BUILDING ADDITION.
SITE KEY PLAN
N
TRUE NORTH
NOT TO SCALE
GENERAL NOTES:
1. ALL NEW CABLING SHALL BE INSTALLED IN
EXISTING CABLE TRAYS LOCATED IN
CORRIDORS OF FLOOR PLAN. PROVIDE J-HOOK
PATHWAYS FOR NEW CABLING FROM EXISTING
CABLE TRAY TO OUTLET LOCATIONS.
CHASE
CHASE
CHASE
CHASECHASE
ATTIC
CORRIDOR
CORRIDOR
CORRIDOR
ATTIC
STAIR
LOBBY
STORAGE
MECHSTAIR
STORAGE STORAGE
MEDICATION RM CHIEF OF
SURGICAL
HAC
ELEVATOR
SERVICE
ELEVATOR
STAIR
BATH RM
FEC
FOYER
BED RM -
ISOLATION HAC
CONFERENCE
COMPUTER RM
RESIDENT
ON-CALL BED
KITCHEN
SINK
OFFICE
ELECTRICAL
CLOSET
OFFICE
OFFICE
STAFF
TOILET
OFFICE
COMPUTER
RM
HAC
HAC
603A 617
610A
610 611A
611B
611C
611D
611E
601D
601A
601B
616A
UP DN
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
101 NORTH SEVENTH STREET
LOUISVILLE, KY 40202
440-262-3063
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
ECWACA
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
BUILDING 01 - 6TH FLOOR OVERALL
PLAN - TECHNOLOGY
01-TN207
-2
-7
-T
N
/2
/2
.p d f
N O R
HT
1/16" = 1'-0"
BUILDING 01 - 6TH FLOOR PLAN - TECHNOLOGY
A12
N
TRUE
NORTH
N
BUILDING
NORTH
GENERAL NOTES:
1. SIXTH FLOOR NETWORK DEVICES SHALL BE FED
FROM FIFTH FLOOR TR #539.
SITE KEY PLAN
N
TRUE NORTH
NOT TO SCALE
CHASE
CHASE
CHASE
CHASECHASE
ATTIC
CORRIDOR
CORRIDOR
CORRIDOR
ATTIC
LOBBY
STORAGE
STORAGE STORAGE
MEDICATION RM CHIEF OF
SURGICAL
HAC
ELEVATOR
SERVICE
ELEVATOR
STAIR
BATH RM
FEC
FOYER
BED RM -
ISOLATION HAC
CONFERENCE
COMPUTER RM
RESIDENT
ON-CALL BED
KITCHEN
SINK
OFFICE
ELECTRICAL
CLOSET
OFFICE
OFFICE
STAFF
TOILET
OFFICE
COMPUTER
RM
HAC
HAC
603A 617
610A
610 611A
611B
611C
611D
611E
601D
601A
601B
616A
UP DN
2D
2D
D
2D
D
D
D
D
D
D
1D
1D-WAP
1D-WAP
2D
D
D
D
D
/T V
6D2D 6D
D
2D 2D
2D
D
2D
2D 2D
2D
01-TN207C
01-TN207B
01-TN207C
01-TN207D01-TN207C01-TN207A
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
101 NORTH SEVENTH STREET
LOUISVILLE, KY 40202
440-262-3063
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
ECWACA
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
BUILDING 01 - 6TH FLOOR PLAN -
AREA C - TECHNOLOGY
01-TN207C
-2
-7
-T
N C
/2
/2
.p d f
N O R
HT
1/8" = 1'-0"
BUILDING 01 - 6TH FLOOR PLAN - AREA C - TECHNOLOGY
A11
N
TRUE
NORTH
N
BUILDING
NORTH
KEYNOTE :
1. ROUTE NEW CABLING FOR SIXTH FLOOR
NETWORK DEVICES DOWN THRU CHASE TO
ABOVE FIFTH FLOOR CEILING AND OVER TO TR #
539. PROVIDE PENETRATIONS THRU FLOOR AND
FIRE RATED PATHWAYS AS REQUIRED.
SITE KEY PLAN
N
TRUE NORTH
NOT TO SCALE
GENERAL NOTES:
1. REFER TO 00-TN000 TELECOMMUNICATIONS
SYMBOLS AND ABBREVIATIONS FOR TECHNOLOGY
NOTES, TECHNOLOGY INSTALLATION NOTES AND
SYMBOLS LIST NEW CABLING.
2. ALL INFORMATION OUTLETS ON THIS SHEET SHALL
BE SERVED FROM TELECOM ROOM TR #572A IN
BLDG #1 UNLESS OTHERWISE NOTED. REFER TO
00-TN000 FOR EXACT LOCATION.
3. REFER TO 00-TN602 FOR TELECOMMUNICATIONS
EQUIPMENT SCHEDULE.
4. CONTRACTOR SHALL INCLUDE AN ALLOWANCE
FOR 10 ADDITIONAL 2-PORT CAT6A OUTLETS IN
THEIR PROPOSAL FOR THIS SHEET. FUTURE
OUTLET LOCATIONS WILL BE DETERMINED BY VA
AT LATER DATE.
5. CONTRACTOR TO FIELD VERIFY CONDUIT RISER
ROUTE WITH OWNER PRIOR TO INSTALLATION.
6. CONTRACTOR TO PROVIDE NEW J-HOOKS ROUTES
FOR ALL NEW CABLING, J-HOOK SIZE AND
QUANTITY TO BE PER MANUFACTURER'S
RECOMMENDATIONS.
7. ALL INFORMATION OUTLETS ON THIS SHEET TO BE
CABLED ON A SCHEDULED BASIS WITH OWNER
WHILE OCCUPPIED WITH STAFF AND PATIENTS.
COORDINATE DEMO AND CABLE REPLACEMENT
WITH OWNER.
8. CONTRACTOR TO PROVIDE 1" OR 2" SLEEVE WITH
FIRE-STOPPING INTO EACH ROOM WITH NEW
CABLING.
C C
T V
M
CSS
MICROBIOLOGY
6A
CSS
C C
T V
M
WORK RM
NEW TR
6B
01-TN400
G5
SC-TTB
SC-PBB-1
(TYP.)
AC-SCP-1
R3 R2 R1
6B
/1
3'-9"
5'-10 1/4"
12"x4"
12"x4"
12"x4"
SC-CT-1
"x
"x
(TYP.)
PW-CPW-1
(TYP.)
(4) 4" CONDUIT SLEEVES
NOTES:
1. INSTALL CABLE TRAY AT 7'-6"AFF.
2. REFER TO 00-TN602 FOR TECHNOLOGY EQUIPMENT SCHEDULE.
SC-ER-1
(TYP.)
SC-BLK-1
SC-BLK-1
SC-MPP-2
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-HWM-1
VA NETWORK SW.
SC-HWM-2
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-UPS-1
SC-FDC-1
SC-BLK-1
SC-MPP-2
SC-MPP-2
SC-MPP-2
SC-MPP-2
SC-MPP-2
SC-MPP-2
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-HWM-1
VA NETWORK SW.
SC-HWM-2
VA NETWORK SW.
SC-HWM-2
VA NETWORK SW.
SC-HWM-2
VA NETWORK SW.
SC-HWM-2
VA NETWORK SW.
SC-HWM-2
VA NETWORK SW.
SC-HWM-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-UPS-1
SC-BLK-1
SC-BLK-1SC-BLK-1
R1 R2
SC-PDU-2
(TYP.)
SC-VWM-1
(TYP.)
NOTES:
1. REFER TO 00-TN602 FOR TECHNOLOGY EQUIPMENT
SCHEDULE.
2. INSTALL RACK BONDING BUSBAR AT TOP RMU ON BACK
SIDE OF EQUIPMENT RACK. REFER TO 17/00-TN504 FOR
ADDITIONAL INFORMATION.
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
NEW TR
27A 01-TN400
B5
SC-TTB
SC-SBB-1
(TYP.)
AC-SCP-1
R1R2
27A
/8
11'-11 1/2"
/1
6'-3 3/4" 2'-1 3/4"
12"x4"
12"x4"
12"x4"
"x
"x
SC-CT-1
(TYP.)
PW-CPW-1
(TYP.)
(4) 4" CONDUIT SLEEVES
NOTES:
1. INSTALL CABLE TRAY AT 7'-6"AFF.
2. REFER TO 00-TN602 FOR TECHNOLOGY EQUIPMENT SCHEDULE.
SC-BLK-1
SC-BLK-1
SC-MPP-2
SC-BLK-1
SC-BLK-1
SC-MPP-2
SC-MPP-2
SC-MPP-2
SC-MPP-2
SC-BLK-1
SC-FDC-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-HWM-1
SC-HWM-2
VA NETWORK SW.
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-HWM-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-UPS-1SC-UPS-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-HWM-1
VA NETWORK SW.
SC-HWM-2
VA NETWORK SW.
SC-HWM-2
VA NETWORK SW.
SC-HWM-2
VA NETWORK SW.
SC-HWM-2
VA NETWORK SW.
SC-HWM-2
VA NETWORK SW.
SC-HWM-2
SC-HWM-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-MPP-2
SC-MPP-2
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
R1 R2
SC-ER-1
(TYP.)
NOTES:
1. REFER TO 00-TN602 FOR TECHNOLOGY EQUIPMENT
SCHEDULE.
2. INSTALL RACK BONDING BUSBAR AT TOP RMU ON BACK
SIDE OF EQUIPMENT RACK. REFER TO 17/00-TN504 FOR
ADDITIONAL INFORMATION.
SC-VWM-1
(TYP.)
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
SC-BLK-1
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
Lebanon VA Medical Center 1700 S Lincoln Ave.
Lebanon, PA 17042
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT / ENGINEER OF RECORD:
CONSULTANT:
DAVID MCCOY
8734 GALLOWAY TRAIL
NOVELTY, OH. 44072
619-925-1647
ARCHITECT:
CB DESIGN GROUP
412 KING ST
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
CONSULTANT:
LENNY HENDRIX
101 NORTH SEVENTH STREET
LOUISVILLE, KY 40202
440-262-3063
CONSULTANT:
MARK DYCK
148 S. QUEEN ST. SUITE 201
MARTINSBURG, WV. 25401
304-266-3115
CONSULTANT:
MICHAEL SMITH
2815 DIRECTORS ROW
SUITE 500
ORLANDO, FL. 32809
407-917-2430
04/07/2025
595-22-700
ECWACA
EHRM INFRASTRUCTURE UPGRADES
LEBANON, PA.
100% BID DOCUMENT SUBMISSION
BUILDING 01 - TECHNOLOGY
ENLARGED PLANS
01-TN400
-2
-7
-T
N
/2
/2
.p d f
1/4" = 1'-0"
EQUIPMENT ENLARGEMENT ROOM TR-#6A
G15
1/4" = 1'-0"
PATHWAY ENLARGEMENT ROOM TR-#6A
G10 1" = 1'-0"
RACK ELEVATION TR-#6A
G5
1/4" = 1'-0"
EQUIPMENT ENLARGEMENT ROOM TR-#27A
B15 1/4" = 1'-0"
PATHWAY ENLARGEMENT ROOM TR-#27A
B10 1" = 1'-0"
RACK ELEVATION TR-#27A
B5
N
BUILDING
NORTH
NOTES:
1. REFER TO PATHWAY ENLARGEMENT PLANS FOR CABLE TRAY LAYOUT.
2. REFER TO 00-TN602 FOR TECHNOLOGY EQUIPMENT SCHEDULE.
3. REFER TO ELECTRICAL DRAWING FOR ELECTRICAL PANEL BONDING LOCATION.
KEYNOTES:
1. PROVIDE CAT6A CABLE FROM NEW EQUIPMENT RACK TO EACH EXISTING ACCESS CONTROL PANEL THAT SERVES THIS FLOOR. COORDINATE EXACT LOCATION OF ACCESS CONTROL PANELS WITH SIEMENS.
2. RELOCATE EXISTING VIDEO SURVEILLANCE NETWORK SWITCHES TO NEW EQUIPMENT RACKS IN NEW OR RE-USED TELECOM ROOMS. COORDINATE EXACT LOCATION AND QUANTITY OF NETWORK SWITCHES
WITH SIEMENS.
3. PROVIDE NEW 6-STRAND, OM4, OPTICAL FIBER CABLE IN INNERDUCT FROM FIBER DISTRIBUTION IN NEW TELECOM RACK TO EXISTING TELECOM ROOM. TERMINATE FIBER WITH LC CONNECTORS AT BOTH ENDS.
COORDINATE EXACT TERMINATION LOCATION IN EXISTING TELECOM ROOM WITH SIEMENS.
4. VERIFY EXISTING CAMERA QUANTITIES/LOCATIONS WITH SIEMENS AND PROVIDE NEW CAT6A CABLES TO
MATCH QUANTITIES. CONNECT CAMERA'S NEW CABLES TO SAME PATCH PANELS.
NOTES:
1. REFER TO PATHWAY ENLARGEMENT PLANS FOR CABLE TRAY LAYOUT.
2. REFER TO 00-TN602 FOR TECHNOLOGY EQUIPMENT SCHEDULE.
3. REFER TO…
This is the start of the file's text. The full file is on GovTribe.