Updated responses to technical questions.docx

DOCX document 16 KB Posted

Attached to
Z2DA--675-22-706A EHRM Infrastructure Upgrades Construction Viera VA Clinic
Solicitation number
36C77625B0004
Issued by

About this file

This file contains updated technical questions and responses for a VA infrastructure upgrade project at the Viera VA Clinic. The document reveals conflicting guidance regarding conduit specifications, with initial responses indicating flex conduit was acceptable in walls, but a later update on 4/14/2025 stipulates that all conduits shall be rigid EMT (Electrical Metallic Tubing), not flexible. The solicitation (36C77625B0004) is for EHRM Infrastructure Upgrades Construction, managed by the Department of Veterans Affairs Technology Acquisition Center Austin, focusing on communication cabling infrastructure improvements at the Viera VA Clinic location.

View the file

Other files

File Type Posted
Updated responses to technical questions Amendment 0011.docx DOCX document
36C77625B0004 Amendment 0011.docx DOCX document
Wage Rates - Brevard County 3.21.25 - Viera.pdf PDF
36C77625B0004 0010.docx DOCX document
AutoCAD - 7.zip ZIP file
DEVIATION FEB 2025.docx DOCX document
CAD - 3.zip ZIP file
CAD - 4.zip ZIP file
852.222-71 COMPLIANCE WITH EXECUTIVE ORDER 13899.docx DOCX document
52.204-8 ANNUAL REPS AND CERTS DEV FEB 2025.docx DOCX document
CAD - 2.zip ZIP file
CAD - 1.zip ZIP file
CAD - 6.zip ZIP file
CAD - 5.zip ZIP file
CAD - 7.zip ZIP file
36C77625B0004 Amendment 0009.docx DOCX document
36C77625B0004 Amendment 0008.docx DOCX document
36C77625B0004 Amendment 0007.docx DOCX document
Wage Rates - Brevard County 3.14.25 - Viera.pdf PDF
36C77625B0004 0006.docx DOCX document
Original CAD 2.zip ZIP file
Original CAD 7.zip ZIP file
Original CAD 1.zip ZIP file
Original CAD 4.zip ZIP file
OVAHCS Physical Security Systems Technical Specifications 02-04-2025.pdf PDF
Orlando - VHA PCRA-1.2 - Oct 1 2024.docx DOCX document
Tech Questions Tracker - Viera 3.10.25 Final.docx DOCX document
Viera Life Safety March 2021.pdf PDF
VIERA Asbestos Report 2016.pdf PDF
Original CAD 5.zip ZIP file
Original CAD 3.zip ZIP file
Original CAD 6.zip ZIP file
Wage Rates - Brevard County 1.31.25 - Viera.pdf PDF
36C77625B0004 0005.docx DOCX document
36C77625B0004 0004.docx DOCX document
Viera EHRM - Offeror Site Visit Sign In Sheet 01-11-2025.pdf PDF
Wage Rates - Brevard County 1.3.25 - Viera.pdf PDF
36C77625B0004 0003.docx DOCX document
36C77625B0004 0002.docx DOCX document
36C77625B0004 0001.docx DOCX document
Viera EHRM - 675-22-706A Construction SOW.pdf PDF
36C77625B0004_1.docx DOCX document
Attachment 5 - Brand Name Justifcation - EHRM Viera.pdf PDF
Attachment 1 - REV1 675-22-706_Viera Final_Specs.pdf PDF
Attachment 7 - Site Visit Instructions.docx DOCX document
Attachment 4 - Wage Determination - Brevard County - 11.1.24.pdf PDF
Attachment 2 - 675-22-706A_Viera Final_Drawings.pdf PDF
Attachment 3 - Viera EHRM - PCRA-ILSM- ICRA- 675-22-706.pdf PDF
Attachment 6 - Limitations on Subcontracting - Construction.docx DOCX document
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1/21/25

Can the VA clarify if the use of flex conduit can be used for the new data drop locations? This would also reduce unnecessary damage to existing walls.
Flex conduit is acceptable in walls.
78
1/21/25
Can the VA clarify whether 1-1/4" Flex Conduit can be used in existing walls for communication cabling?
Flex conduit is acceptable in walls.

Original responses from Technical Questions:

Corrected responses are below:

73
1/21/25
Can the VA clarify if the use of flex conduit can be used for the new data drop locations? This would also reduce unnecessary damage to existing walls.
Flex conduit is acceptable in walls.
78
1/21/25
Can the VA clarify whether 1-1/4" Flex Conduit can be used in existing walls for communication cabling?
Flex conduit is acceptable in walls.
73
1/21/25
Can the VA clarify if the use of flex conduit can be used for the new data drop locations? This would also reduce unnecessary damage to existing walls.
Flex conduit is acceptable in walls.
78
1/21/25
Can the VA clarify whether 1-1/4" Flex Conduit can be used in existing walls for communication cabling?
Flex conduit is acceptable in walls.
73
1/21/25
Updated: 4/14/2025
Can the VA clarify if the use of flex conduit can be used for the new data drop locations? This would also reduce unnecessary damage to existing walls.
All conduits shall be rigid EMT, not flexible. Flex conduit is acceptable in walls.
78
1/21/25
Updated: 4/14/2025
Can the VA clarify whether 1-1/4" Flex Conduit can be used in existing walls for communication cabling?
All conduits shall be rigid EMT, not flexible. Flex conduit is acceptable in walls