SOW Att. 04 - Sample Air Emissions Permit Application.pdf
PDF 875 KB Posted
- Solicitation number
- 36C77624R0144
About this file
This document is a permit revision application for the addition of an emergency generator engine and other insignificant activities at the Lexington VA Health Care System-Leestown Road facility in Kentucky. The application includes the required DEP7007 forms, emission calculations, and manufacturer data for the new emergency generator. It analyzes the regulatory applicability, including 40 CFR 63 Subpart ZZZZ and 40 CFR 60 Subpart IIII requirements, and determines the installation of the new equipment does not require an advance permit revision. The insignificant activities include a diesel fuel tank, five small natural gas-fired boilers, and four small natural gas-fired water heaters associated with the construction of two new buildings and renovations to an existing building.
The related federal contract opportunity is for architect-engineer (A-E) services to develop construction documents, including working drawings, specifications, cost estimates, and construction period services, for a new radiation oncology building at the Lexington VA Medical Center. This is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB). The project has an estimated construction cost between $10-20 million and a 280-calendar-day design completion period. The A-E selection process involves evaluating Statement of Qualifications (SF 330) submissions based on primary criteria like specialized experience, professional qualifications, capacity, and past performance, as well as a secondary geographic location criterion.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C77624R0144_2.docx | DOCX document | |
| SF330 TQ Tracking Spreadsheet - Lex Rad Onc Design.pdf | ||
| 36C77624R0144_1.docx | DOCX document | |
| SOW Att. 01 - AE CPM Schedules.pdf | ||
| SOW Att. 06 - LDP Process.pdf | ||
| SOW Att. 08 - Additional Technical Requirements.pdf | ||
| SOW Att. 03 - Campus Map.pdf | ||
| SOW Att. 02 - PG-18-15 Volume C.pdf | ||
| SOW Att. 07 - LFUCG Ordinance Reduction of Erosion Control.pdf | ||
| SOW Att. 05 - KHC Cover Sheet 106 Review.pdf | ||
| SOW_596-335.pdf | ||
| 36C77624R0144.docx | DOCX document | |
| PPQ.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
[TO BE PRINTED ON VA LETTERHEAD]
August 19, 2022
Mr. Zachary Bittner Division for Air Quality – Combustion Section Supervisor Kentucky Department for Environmental Protection 300 Sower Blvd., 2nd Floor Frankfort, KY 40601
RE: Permit Revision Application for State Origin Permit No. S-21-012 R1 Lexington VAHCS-Leestown Road (AI #1106)
Dear Mr. Bittner:
Lexington VA Health Care System-Leestown Road (VAHCS) is hereby filing a permit revision application for the addition of an emergency generator engine, in accordance with 401 KAR 52:040 Section 13 Actions that Do Not Require a Permit Revision in Advance. As part of this revision application, VAHCS has included notification of planned installation of insignificant activities, including the diesel fuel tank serving the generator, 5 small (< 1 MMBtu/hr) natural gas-fired boilers, and 4 small (< 1 MMBtu/hr) natural gas-fired water heaters. The new equipment will be associated with the construction of two (2) new buildings, Buildings 204 and 205 and, the renovations being done for building 39, at the Leestown Road campus.
The State Origin permit for the Leestown Road campus requires revisions to include a new engine in the existing Section B diesel-fired engine emission unit group, starting on page 12 of 24, as Emissions Unit 43.
This letter and its attachments contain all the required elements of a permit revision as specified in 401 KAR 52:040 Section 5, except pursuant to 401 KAR 52:040 Section 4(c), the application will provide only the information related to this change.
APPLICATION CONTENTS
This application letter provides a description of the new equipment being added and an analysis of the air permitting and regulatory requirements. A completed set of applicable DEP7007 series application forms (AI, EE, N, and V) are provided in Attachment 1 for the emergency generator engine being added and DEP7007 Form DD for insignificant activities. Emission calculations for the emergency generator engine can be found in Attachment 2. The engine’s Emission Data Sheet and Certificate of Conformity are provided in Attachment 3. A process flow diagram of the emergency generator engine is provided in Attachment 4.
REGULATORY APPLICABILITY AND AIR PERMITTING REQUIREMENTS
40 CFR 63 Subpart ZZZZ – Stationary Reciprocating Internal Combustion Engines (RICE) Pursuant to 40 CFR 63.6590(c)(1), a new stationary RICE located at an area source of hazardous air pollutant (HAP) emissions must meet 40 CFR 60 Subpart IIII requirements in order to meet the 40 CFR 63 Subpart ZZZZ requirements. VAHCS is an area source of HAP and; therefore, no further requirements apply for such engines under 40 CFR 63 Subpart ZZZZ.
Mr. Zachary Bittner - Page 2
40 CFR 60 Subpart IIII – Stationary Compression Ignition (CI) Internal Combustion Engines (ICE) Owners and operators that commenced construction after July 11, 2005, of a stationary CI ICE manufactured after April 1, 2006, and are not fire pump engines are subject to 40 CFR 60 Subpart IIII pursuant to 40 CFR 60.4200(a)(2)(i). Pursuant to 40 CFR 60.4205(b), the new emergency stationary CI ICE with a displacement less than 30 liters per cylinder that are not fire pump engines shall comply with the emission standards referenced in 40 CFR 60.4202(a)(2), which refers to the certification emission standards for new nonroad CI engines in 40 CFR 89.112 Table 1. According to the manufacturer emissions data sheet, provided in Attachment 1, the diesel generator engine is well within the required emission standards for Table 1 in 40 CFR 89.112 of 4.0 g/hp-hr for NMHC + NOX, 3.5 g/hp-hr for CO, and 0.20 g/hp-hr for PM.
40 CFR 63 Subpart JJJJJJ – Industrial, Commercial, and Institutional Boilers at Area Sources – Not Subject Pursuant to 40 CFR 63.1195(e) and (f), neither a gas-fired boiler nor a hot water heater is subject to this regulation. Therefore, this regulation does not apply to gas-fired boilers and water heaters to be installed per this permit revision application.
401 KAR 59:015 – New Indirect Heat Exchangers – Not Subject Pursuant to 401 KAR 59:015 Section 1, an affected facility is an indirect heat exchanger having a heat input capacity greater than one (1) million BTU per hour. None of the new natural gas-fired boilers nor hot water heaters have a capacity greater than 1 MMBtu/hr; therefore, this regulation does not apply to the equipment to be installed per this permit revision application.
40 KAR 59:050 – New Storage Vessels for Petroleum Liquids – Not Subject 401 KAR 59:050 applies to certain storage vessels which store “petroleum liquids”. Pursuant to 401 KAR 59:050 Section 2, a “petroleum liquid” does not mean Number 2 through Number 6 fuel oils, gas turbine fuel oil Number 2-GT through 4-GT, or diesel fuel oils Numbers 2-D and 4-D. The diesel fuel tank associated with the emergency generator engine stores only Number 2 fuel oil and, therefore, is not subject to this regulation.
QUALIFICATION FOR TREATMENT AS “ACTIONS THAT DO NOT
REQUIRE A PERMIT REVISION IN ADVANCE”
As a natural minor source subject to state-origin permitting requirements, Sections 12 and 13 of 401 KAR 52:040 establish two (2) categories of permit actions:
1. Actions that Require a Permit or Permit Revision in Advance. Per Section 12 of 401 KAR 52:040, for the modification of a source that will increase its potential to emit (PTE) by 2.5 tpy or more of a HAP, 7.5 tpy or more of combined HAPs, or 25 tpy or more of a nonhazardous regulated air pollutant, the permittee must obtain a permit or permit revision prior to commencing construction.
2. Actions that Do Not Require a Permit Revision in Advance. For all permit revisions except those covered by Section 12, the permittee must submit a complete application for the permit revision and may implement the change immediately upon submittal of the application.
Mr. Zachary Bittner - Page 3
Based on the minimal emissions increases from installation of the new emergency generator and insignificant activity boilers and water heaters, shown in Attachment 2, this action does not require an advance permit revision.
If you have any questions or comments about the information presented in this letter, please do not hesitate to call me at 859.233.4511 ext. 3354.
Sincerely, Richard J. Archer, MPH, CIH Lexington VA Health Care System – Safety Manager
Attachments cc: Ms. Margot Fosnaugh, Trinity Consultants, Inc.
ATTACHMENT 1
DEP 7007 Forms (AI, N, V, DD, EE)
11/2018 DEP7007AI
___ Section AI.1: Source Information
___ Section AI.2: Applicant Information ___ Section AI.3: Owner Information ___ Section AI.4: Type of Application
___ Section AI.5: Other Required Information ___ Section AI.6: Signature Block ___ Section AI.7: Notes, Comments, and Explanations
21-
Agency Interest (AI) ID:
County: Zip Code:
State: Zip Code:
Longitude: Latitude:
Primary (NAICS) Category: General Medical and Surgical Hospitals Primary NAICS #: 622110
Mailing Address:
Street or P.O. Box:
Same as Physical Address
City:
Standard Coordinates for Source Physical Location
-84.53747 (decimal degrees) 38.07479 (decimal degrees)
Section AI.1: Source Information Physical Location
Address:
Street: 2250 Leestown Road City: Lexington Fayette 40511
Date:
Frankfort, KY 40601
(502) 564-3999
Source Name: Lexington VAHCS
KY EIS (AFS) #: 067-00008
Permit #: S-21-012 R1
Aug-22
Division for Air Quality DEP7007AI Additional Documentation Administrative Information
300 Sower Boulevard ___ Additional Documentation attached
Rural Area Residential Area Yes
Urban Area Commercial Area No
Is this source portable? Yes No
NPDES/KPDES: Currently Hold Need N/A
Solid Waste: Currently Hold Need N/A
RCRA: Currently Hold Need N/A
UST: Currently Hold Need N/A
Mixed Waste Generator Generator Recycler Other: ______________
U.S. Importer of Hazardous Waste Transporter Treatment/Storage/Disposal Facility N/A
Type of Regulated Waste Activity:
Description of Area Surrounding Source:
Industrial Park Is any part of the source located on federal land?
Number of Employees:
Approximate distance to nearest residence or commercial property:
Property Area:883 ft ~150 acres
What other environmental permits or registrations does this source currently hold or need to obtain in Kentucky?
700-800 Industrial Area
Classification (SIC) Category: Medical Laboratories Primary SIC #: 8071
Briefly discuss the type of business conducted at this site:
The Franklin Sousley Campus located at 2250 Leestown Road offers inpatient Post-Traumatic Stress Disorder (PTSD) and substance abuse treatment, nursing home care, hospice and respite services, home based primary care, prosthetics and orthotics, geriatrics, optometry, mental health as well as primary care and women's health.
City: State: Zip Code:
City: State: Zip Code:
City: State: Zip Code:
Email: Richard.Archer2@va.gov
Phone: 859-233-4511 x3365
Title: Safety Manager
Mailing Address:
Street or P.O. Box: Same as above
Email: Richard.Archer2@va.gov
Phone: 859-233-4511 x3365
Air Permit Contact for Source
Name: Richard J. Archer, MPH, CIH
Title: Safety Manager
Street or P.O. Box: Same as above
Email: (if individual)
Phone:
Technical Contact
Name: Richard J. Archer, MPH, CIH
Mailing Address:
Street or P.O. Box: 2250 Leestown Road
Lexington KY 40511
Title: (if individual)
Section AI.2: Applicant Information
Applicant Name: Lexington VAHCS - Leestown Road
Street or P.O. Box:
State: Zip Code:
Name Position
List names of owners and officers of the company who have an interest in the company of 5% or more.
Email:
Phone:
Title:
City:
Section AI.3: Owner Information
Owner same as applicant Name:
Title V Conditional Major State-Origin General Permit Registration None
Name Change Initial Registration Significant Revision Administrative Permit Amendment
Renewal Permit Revised Registration Minor Revision Initial Source-wide OperatingPermit
502(b)(10)Change Extension Request Addition of New Facility Portable Plant Relocation Notice
Revision Off Permit Change Landfill Alternate Compliance Submittal Modification of Existing Facilities
Ownership Change Closure
Title V Conditional Major State-Origin PSD NSR Other:
Yes No
Requested Limit:
Single HAP
Combined HAPs
Carbon Dioxide
Greenhouse Gases (GHG)
Other
Yes No
For Modifications:
Proposed Start Date of Modification:
(MM/YYYY) Proposed Operation Start-Up Date: (MM/YYYY) na na
Applicant is seeking coverage under a permit shield.
Identify any non-applicable requirements for which permit shield is sought on a separate attachment to the application.
Proposed Start Date of Construction:
(MM/YYYY) Proposed Operation Start-Up Date: (MM/YYYY)
08/2022 08/2022
For New Construction:
Nitrogen Oxides
Sulfur Dioxide
Lead
Volatile Organic Compounds (VOC)
Carbon Monoxide Air Toxics (40 CFR 68, Subpart F)
Section AI.4: Type of Application
Current Status:
Requested Action:
(check all that apply)
Is the source requesting a limitation of potential emissions?
Requested Status: ____________
Particulate Matter
Pollutant: Pollutant: Requested Limit:
DEP7007A Indirect Heat Exchangers and Turbines DEP7007CC Compliance Certification DEP7007B Manufacturing or Processing Operations DEP7007DD Insignificant Activities DEP7007C Incinerators and Waste Burners DEP7007EE Internal Combustion Engines DEP7007F Episode Standby Plan DEP7007FF Secondary Aluminum Processing DEP7007J Volatile Liquid Storage DEP7007GG Control Equipment DEP7007K Surface Coating or Printing Operations DEP7007HH Haul Roads DEP7007L Mineral Processes Confidentiality Claim DEP7007M Metal Cleaning Degreasers Ownership Change Form DEP7007N Source Emissions Profile Secretary of State Certificate DEP7007P Perchloroethylene Dry Cleaning Systems Flowcharts or diagrams depicting process DEP7007R Emission Offset Credit Digital Line Graphs (DLG) files of buldings, roads, etc.
DEP7007S Service Stations Site Map DEP7007T Metal Plating and Surface Treatment Operations Map or drawing depicting location of facility DEP7007V Applicable Requirements and Compliance Activities Safety Data Sheet (SDS) DEP7007Y Good Engineering Practice and Stack Height Determination Emergency Response Plan DEP7007AA Compliance Schedule for Non-complying Emission Units Other: ____Engine Certificate of Conformity DEP7007BB Certified Progress Report
Type or Printed Name of Signatory Title of Signatory
*Responsible official as defined by 401 KAR 52:001.
I, the undersigned, hereby certify under penalty of law, that I am a responsible official*, and that I have personally examined, and am familiar with, the information submitted in this document and all its attachments. Based on my inquiry of those individuals with primary responsibility for obtaining the information, I certify that the information is on knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false or incomplete information, including the possibility of fine or imprisonment.
Authorized Signature Date
Kerri Dauteuil Acting Chief, Engineering Svc
Section AI.6: Signature Block
Section AI.5 Other Required Information Indicate the documents attached as part of this application:
Section AI.7: Notes, Comments, and Explanations
11/2018 DEP7007DD
DEP7007DD
Insignificant Activities ___ Section DD.1: Table of Insignificant Activities ___ Section DD.2: Signature Block ___ Section DD.3: Notes, Comments, and Explanations
Source Name:
KY EIS (AFS) #: 21-
Permit #:
Agency Interest (AI) ID:
Date:
36.
One (1) 3,920 gallon diesel fuel oil tank
Two(2) <4,000 gallon diesel fuel oil tanks
N/A N/A < 5 tpy of all criteria pollutants < 1,000 lb/yr of HAP
37. NG Hot Water Boiler – 0.6 MMBTU/hr Campus Advantus model AV0600 N/A 0.216 tpy of CO as highest emitting criteria pollutant
38. NG Hot Water Boiler – 0.6 MMBTU/hr Campus Advantus model AV0600 N/A 0.216 tpy of CO as highest emitting criteria pollutant
39. NG Hot Water Boiler – 0.6 MMBTU/hr Campus Advantus model AV0600 N/A 0.216 tpy of CO as highest emitting criteria pollutant
40. NG Hot Water Heater – 0.5 MMBTU/hr
Power VTX 50 L 225A-PVX N/A 0.180 tpy of CO as highest emitting criteria pollutant
Lexington VAHCS
Division for Air Quality 300 Sower Boulevard Frankfort, KY 40601
(502) 564-3999
067-00008
S-21-012 R1
Aug-22
Section DD.1: Table of Insignificant Activities *Identify each activity with a unique Insignificant Activity number (IA #); for example: 1, 2, 3… etc.
Insignificant Activity #
Description of Activity including Rated
Capacity
Serial Number or Other Unique Identifier Applicable Regulation(s) Calculated Emissions
Insignificant Activity #
Description of Activity including Rated
Capacity
Serial Number or Other Unique Identifier Applicable Regulation(s) Calculated Emissions
41. NG Hot Water Heater – 0.5 MMBTU/hr
Power VTX 50 L 225A-PVX N/A 0.180 tpy of CO as highest emitting criteria pollutant
42. NG Hot Water Heater – 0.5 MMBTU/hr
Power VTX 50 L 225A-PVX N/A 0.180 tpy of CO as highest emitting criteria pollutant
43. NG Hot Water Boiler – 0.75 MMBTU/hr Benchmark 750-6000 N/A 0.271 tpy of CO as highest emitting criteria pollutant
44. NG Hot Water Boiler – 0.75 MMBTU/hr Benchmark 750-6000 N/A 0.271 tpy of CO as highest emitting criteria pollutant
45. NG Hot Water Heater – 0.15 MMBTU/hr Bradford and White EF-100T-150E-3N(A) N/A 0.054 tpy of CO as highest emitting criteria pollutant
Insignificant Activity #
Description of Activity including Rated
Capacity
Serial Number or Other Unique Identifier Applicable Regulation(s) Calculated Emissions
Authorized Signature Date
Kerri Dauteuil Acting Chief, Engineering Svc
Type/Print Name of Siguatory Title of Siguatory
Section DD.2: Signature Block I, THE UNDERSIGNED, HEREBY CERTIFY UNDER PENALTY OF LAW, THAT I AM A RESPONSIBLE OFFICIAL, AND THAT I HAVE PERSONALLY
EXAMINED, AND AM FAMILIAR WITH, THE INFORMATION SUBMITTED IN THIS DOCUMENT AND ALL ITS ATTACHMENTS. BASED ON MY INQUIRY OF THOSE INDIVIDUALS WITH PRIMARY RESPONSIBILITY FOR OBTAINING THE INFORMATION, I CERTIFY THAT THE INFORMATION IS ON
KNOWLEDGE AND BELIEF, TRUE, ACCURATE, AND COMPLETE. I AM AWARE THAT THERE ARE SIGNIFICANT PENALTIES FOR SUBMITTING FALSE
OR INCOMPLETE INFORMATION, INCLUDING THE POSSIBILITY OF FINE OR IMPRISONMENT.
By:
Section DD.3: Notes, Comments, and Explanations
11/2018 DEP7007EE
Source Name:
KY EIS (AFS) #: 21-
Permit #:
Agency Interest (AI) ID:
Date:
43 Emergency Engine - Kohler 400REOZJC na S1 KOHLER 400REOZJC 2021 1/1/2021 na
40 CFR 63
Subpart ZZZZ, 40 CFR 60 Subpart
IIII
Aug-22
Section EE.1: General Information
Division for Air Quality DEP7007EE Additional Documentation
Internal Combustion Engines __ Complete DEP7007AI, DEP7007N, DEP7007V, and DEP7007GG300 Sower Boulevard ___ Section EE.1: General Information
Frankfort, KY 40601 ___ Section EE.2: Operating Information __ Attach EPA certification of the engine
(502) 564-3999 ___ Section EE.3: Design Information ___ Section EE.4: Fuel Information ___ Section EE.5: Emission Factor Information ___ Section EE.6: Notes, Comments, and Explanations
Lexington VAHCS 067-00008 S-21-012 R1
Emission Unit # Emission Unit Name Control Device ID Stack ID Manufacturer Model Number Model Year Date of
Manufacture
Proposed/Actual Date of
Construction Commencement
(MM/YYYY)
Date Reconstructed/
Modified
List Applicable Regulations
08/2022
43 Emergency 500 No na
Section EE.2: Operating Information
Emission Unit #
Engine Purpose (Identify if Non-Emergency, Emergency,Fire/Water Pump, Black-start engine for combustion turbine, Engine
Testing)
Hours Operated
Is this engine a rental? (Yes/No)
Rental Time Period
(hrs)
Alternate Operating Scenarios (Describe any operating scenarios in which the engine may be used in a different configuration)
43 Stationary Compression Ignition 4-Stroke 617 1,800 13.5 6
Section EE.3: Design Information
Emission Unit # Engine Type
(Identify all that apply: Commercial, Institutional, Stationary, Non-Road)
Ignition Type (Identify if either
Compression or Spark Ignition)
Engine Family (Identify all that apply: 2-stroke, 4-stroke, Rich Burn, Lean Burn)
Maximum Engine Power
(bhp)
Maximum Engine Speed (rpm)
Total Displacement
(L)
Number of Cylinders
43 Primary Diesel na 100 0.0306 Mgal/hr 137 MMBtu/Mgal 0.0015 20200102 Mgal Diesel
Burned
SCC Units
Section EE.4: Fuel Information
Emission Unit # Identify if Primary, Secondary, or Tertiary Fuel
Fuel Type (Identify if Diesel, Gasoline, Natural Gas, Liquefied Petroleum Gas (LPG), Landfill/Digester Gas, or Other)
Fuel Grade Percent
Time Used
Maximum Fuel Consumption
Heat Content
Sulfur Content
SCC Code
43 Primary PM/PM10/PM2.5 3.31 lb/Mgal Diesel Burned Manufacturer Emissions Data Sheet
43 Primary NOx 109.70 lb/Mgal Diesel Burned Manufacturer Emissions Data Sheet
43 Primary SO2 0.21 lb/Mgal Diesel Burned AP-42 Table 3.4-1 (S is sulfur content in %)
43 Primary VOC 3.65 lb/Mgal Diesel Burned Manufacturer Emissions Data Sheet
43 Primary CO 19.88 lb/Mgal Diesel Burned Manufacturer Emissions Data Sheet
43 Primary CO2 22,338 lb/Mgal Diesel Burned 40 CFR 98, Subpart C, Table C-1
43 Primary N2O 0.18 lb/Mgal Diesel Burned 40 CFR 98, Subpart C, Table C-2
43 Primary CH4 0.91 lb/Mgal Diesel Burned 40 CFR 98, Subpart C, Table C-2
43 Primary Benzene 0.106 lb/Mgal Diesel Burned AP-42 Table 3.4-4
43 Primary Toluene 0.038 lb/Mgal Diesel Burned AP-42 Table 3.4-4
43 Primary Xylene 0.026 lb/Mgal Diesel Burned AP-42 Table 3.4-4
Section EE.5: Emission Factor Information Emission factors expressed here are based on the potential to emit.
Emission Unit # Fuel Pollutant Emission Factor Emission Factor Units Source of Emission Factor
Section EE.6: Notes, Comments, and Explanations
11/2018 DEP7007N
21-
Agency Interest (AI) ID:
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 PM/PM10/PM2.5 3.31 Manufacturer
Emissions Data Sheet na na 0.101 na 0.025 na
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 NOx 109.70 Manufacturer
Emissions Data Sheet na na 3.36 na 0.84 na
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 SO2 0.21 AP-42 Table 3.4-1 (S is sulfur content in %) na na 6.35E-03 na 1.59E-03 na
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 VOC 3.65 Manufacturer
Emissions Data Sheet na na 0.112 na 0.028 na
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 CO 19.88 Manufacturer
Emissions Data Sheet na na 0.61 na 0.15 na
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 CO2 22338.35 40 CFR 98, Subpart C, Table C-1 na na 683.55 na 170.89 na
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 N2O 0.18 40 CFR 98, Subpart C, Table C-2 na na 5.55E-03 na 1.39E-03 na
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 CH4 0.91 40 CFR 98, Subpart C, Table C-2 na na 0.028 na 6.93E-03 na
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 Benzene 0.11 AP-42 Table 3.4-4 na na 3.25E-03 na 8.13E-04 na
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 Toluene 0.04 AP-42 Table 3.4-4 na na 1.18E-03 na 2.95E-04 na
43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 Xylene 0.03 AP-42 Table 3.4-4 na na 8.09E-04 na 2.02E-04 na
Division for Air Quality
DEP7007N
Source Emissions Profile Additional Documentation
300 Sower Boulevard __ Section N.1: Emission Summary
Permit #:
Frankfort, KY 40601 __ Section N.2: Stack Information __ Complete DEP7007AI
(502) 564-3999 __ Section N.3: Fugitive Information
__ Section N.4: Notes, Comments, and Explanations Source Name:
KY EIS (AFS) #:
Lexington VAHCS 067-00008 S-21-012 R1
Date:
N.1: Emission Summary
Emission Unit # Emission Unit Name Process
ID Process Name Control Device Name
Control Device
ID
Stack
ID
Maximum Design
Capacity
(SCC
Units/hour)
Pollutant
Uncontrolled Emission
Factor (lb/SCC Units)
Emission Factor Source (e.g. AP-42, Stack Test, Mass Balance)
Aug-22
Capture Efficiency
Control Efficiency
Hourly Emissions Annual Emissions
Uncontrolled Potential
(lb/hr)
Controlled Potential
(lb/hr)
Uncontrolled Potential
(tons/yr)
Controlled Potential
(tons/yr)
UTM Zone:
S1 43 0.30 7.3 944 4,216,977 716,000 2860.488004 879.8 696.22
Easting (m)
Flowrate (acfm)
Temperature ( ° F)
Exit Velocity (ft/sec)
Section N.2: Stack Information
Stack ID
Identify all Emission Units (with Process ID) and Control Devices that Feed to Stack
Stack Physical Data Stack UTM Coordinates Stack Gas Stream Data
Equivalent Diameter
(ft)
Height (ft)
Base Elevation
(ft)
Northing (m)
UTM Zone:
Not Applicable for this Application
Easting (m)
Release Temperature
( °F)
Release Height
(ft)
Section N.3: Fugitive Information
Emission Unit # Emission Unit Name Process ID
Area Physical Data Area UTM Coordinates Area Release Data
Length of the X Side (ft)
Length of the Y Side (ft)
Northing (m)
Section N.4: Notes, Comments, and Explanations
11/2018 DEP7007V
21-
Agency Interest (AI) ID:
43 na na
43 NMHC +
NOX
From 60.4202 referenced in 60.4205, NMHC + NOX shall not exceed 4.0 g/kW-hr according to Table 1 of 40 CFR 89.112 over the entire life of the engine (60.4206).
067-00008
Division for Air Quality DEP7007V Additional Documentation
Applicable Requirements and Compliance Activities __ Complete DEP7007AI
300 Sower Boulevard ___ Section V.1: Emission and Operating Limitation(s)
Permit #:
Frankfort, KY 40601 ___ Section V.2: Monitoring Requirements
(502) 564-3999 ___ Section V.3: Recordkeeping Requirements
___ Section V.4: Reporting Requirements ___ Section V.5: Testing Requirements ___ Section V.6: Notes, Comments, and Explanations
Source Name:
KY EIS (AFS) #:
Lexington VAHCS
S-21-012 R1
Date:
Section V.1: Emission and Operating Limitation(s)
Emission Unit # Emission Unit Description
Applicable Regulation or Requirement
Pollutant Emission Limit (if applicable)
Voluntary Emission Limit or
Exemption (if applicable)
Operating Requirement or Limitation
(if applicable)
Method of Determining Compliance with the
Emission and Operating Requirement(s)
Aug-22
Emergency Engine - Kohler
400REOZJC
NESHAP ZZZZ: 40
CFR 63.6590(c) na Meet the requirements of NESHAP
ZZZZ by complying with NSPS IIII. Comply with NSPS IIII.
Emergency Engine - Kohler
400REOZJC
NSPS IIII: 40 CFR
60.4205(b) na na
Purchase engine certified to the emission standards and install and configure according to the manufacturer specifications (60.4211(c)).
Emission Unit # Emission Unit Description
Applicable Regulation or Requirement
Pollutant Emission Limit (if applicable)
Voluntary Emission Limit or
Exemption (if applicable)
Operating Requirement or Limitation
(if applicable)
Method of Determining Compliance with the
Emission and Operating Requirement(s)
43 CO
From 60.4202 referenced in 60.4205, CO shall not exceed 3.5 g/kW-hr according to Table 1 of 40 CFR 89.112 over the entire life of the engine (60.4206).
43 PM
From 60.4202 referenced in 60.4205, PM shall not exceed 0.20 g/kW-hr according to Table 1 of 40 CFR 89.112 over the entire life of the engine (60.4206).
43 na na
43 na na
43 na na
Emergency Engine - Kohler
400REOZJC
NSPS IIII: 40 CFR
60.4205(b) na na
Purchase engine certified to the emission standards and install and configure according to the manufacturer specifications (60.4211(c)).
Use diesel fuel that meets requirements of 40 CFR 80.510(b) for nonroad diesel fuel.
Purchase only compliant diesel fuel.
Emergency Engine - Kohler
400REOZJC
NSPS IIII: 40 CFR
60.4211(f) na
Operate according to the requirements in (f)(1) through (3) to be considered an emergency stationary ICE.
Monitor hours of operation in emergency and non-emergency service and the reason the engine was in operation during that time.
Emergency Engine - Kohler
400REOZJC
NSPS IIII: 40 CFR
60.4211(a) na
Operate and maintain the stationary CI internal combustion engine and control device according to the manufacturer's emission-related written instructions.
Change only those emission-related settings that are permitted by the manufacturer. Meet the requirements of 40 CFR parts 89, 94, and/or 1068, as they apply to you.
Maintain records of maintenance conducted on the engine consistent with the operating requirements of 40 CFR 60.4211(a).
Emergency Engine - Kohler
400REOZJC
NSPS IIII: 40 CFR
60.4205(b) na na
Purchase engine certified to the emission standards and install and configure according to the manufacturer specifications (60.4211(c)).
Emergency Engine - Kohler
400REOZJC
NSPS IIII: 40 CFR
60.4207(b) na
43 Emergency Engine - Kohler 400REOZJC na NSPS IIII: 40 CFR 60.4209(a) Operating Hours Install a non-resettable hour meter prior to startup of the engine.
Section V.2: Monitoring Requirements
Emission Unit #
Emission Unit Description Pollutant Applicable Regulation or Requirement Parameter Monitored Description of Monitoring
43 Emergency Engine - Kohler 400REOZJC na NSPS IIII: 40 CFR 60.4211(a) Maintenance Records Maintain records of maintenance conducted on the engine consistent with the operating requirements of 40 CFR 60.4211(a).
43 Emergency Engine - Kohler 400REOZJC na NSPS IIII: 40 CFR 60.4214(b) Operating Hours
Maintain records of the operation of the engine in emergency and non-emergency service that are recorded through the non-resettable hour meter. The owner must record the time of operation of the engine and the reason the engine was in operation during that time.
Section V.3: Recordkeeping Requirements
Emission Unit #
Emission Unit Description Pollutant Applicable Regulation or
Requirement Parameter Recorded Description of Recordkeeping
Kohler 400REOZJC na na na na
Section V.4: Reporting Requirements
Emission Unit #
Emission Unit Description Pollutant Applicable Regulation or
Requirement Parameter Reported Description of Reporting
Kohler 400REOZJC na na na na
Section V.5: Testing Requirements
Emission Unit #
Emission Unit Description Pollutant Applicable Regulation or
Requirement Parameter Tested Description of Testing
Section V.6: Notes, Comments, and Explanations
ATTACHMENT 2
Calculations for the Emergency Generator Engine and the Natural Gas-Fired Boilers/Hot Water Heaters
Lexington VAMC-Leestown Road Air Emissions Calculations
2.1.1 Source Classification Code
SCC: 20200102
SCC Description:
SCC Units:
2.1.2 Engine Power and Fuel Consumption Data
Mechanical Power in bhp (100% load, standby): 617 bhp 460 bkW Generator Output in kW (100% load, standby): 400 kW Specific Fuel Consumption Rate in Mgal/hr: 0.031 Mgal/hr 31 gph Maximum Presumptive Annual Operating Hours: 500 hrs Typical Heat Content of Diesel Fuel (HHV): 137 MMBtu/Mgal
2.1.3 Emission Calculation Methodology and Emission Factors
2.1.3.1 NOX
Emission factor for NOX: 3.310 g/kW-hr Manufacturer Emissions Data Sheet NOX emission factor in terms of SCC units: 109.70 lb/Mgal
2.1.3.2 VOC
Emission factor for VOC: 0.110 g/kW-hr Manufacturer Emissions Data Sheet VOC emission factor in terms of SCC units: 3.65 lb/Mgal
2.1.3.3 CO
Emission factor for CO: 0.600 g/kW-hr Manufacturer Emissions Data Sheet CO emission factor in terms of SCC units: 19.88 lb/Mgal
2.1.3.4 PM/PM10/PM2.5
Emission factor for PM/PM10/PM2.5: 0.100 g/kW-hr Manufacturer Emissions Data Sheet PM/PM10/PM2.5 emission factor in terms of SCC units: 3.31 lb/Mgal
Internal Combustion Engines, Industrial (2-02), Distillate Oil (Diesel) (2-02-001), Reciprocating (2-02-001-02)
= 3.310 g/kW-hr * 460 bkW / 0.0306 Mgal/hr * 0.0022046 lb/g
= 0.110 g/kW-hr * 460 bkW / 0.0306 Mgal/hr * 0.0022046 lb/g
One (1) diesel-fired emergency generator engine will be installed to support Buildings 204 & 205.
= 0.600 g/kW-hr * 460 bkW / 0.0306 Mgal/hr * 0.0022046 lb/g
= 0.100 g/kW-hr * 460 bkW / 0.0306 Mgal/hr * 0.0022046 lb/g
2.1. Generator Engine
Pertinent data on engine power and fuel usage pulled from the technical data sheet for the Kohler 600REOZVB generator engine. Typical heating value of diesel fuel was taken from Appendix A in AP-42.
Emissions for this engine are tied to the SCC code for diesel fueled engines listed below.
1000 Gallons Distillate
Emission factors for NOX, HC, CO, and PM are based on the manufacturer emissions data sheet. Conservatively over-estimating VOC emissions by assuming HC is equal to VOC and over-estimating PM by assuming PM is equal to PM10/PM2.5. The emission factor for SO2 is based on sulfur content of the fuel and the equation found in Table 3.4-1 in AP-42 Chapter 3.4 for Large Stationary Diesel Engines.
2.1.3.5 SO2
AP42 Factor for SO2 based on sulfur content: 1.01 S lb/MMBtu
Sulfur Content: 0.0015 %
SO2 emission factor (lb/MMBtu): 1.52E-03 lb/MMBtu = 1.01 EF x 0.0015%, sulfur SO2 emission factor in terms of SCC units: 0.2076 lb/Mgal
2.1.3.6 HAP Emission Estimates
Pollutant CAS # HAP?
Emission Factor
(lb/MMBtu)
Emission Factor
(lb/hp-hr)
Emission Factor
(lb/Mgal) Emission Factor Basis Benzene 71-43-2 Y 7.76E-04 5.27E-06 0.11 AP-42 Table 3.4-4 Toluene 108-88-3 Y 2.81E-04 1.91E-06 0.038 AP-42 Table 3.4-4 Xylene 1330-20-7 Y 1.93E-04 1.31E-06 0.026 AP-42 Table 3.4-4
2.1.3.7 GHG Emission Factors
Global Warming Potentials of GHGs per 40 CFR 98 Subpart A, Table A-1.
CO2 1
CH4 25
N2O 298
Pollutant
Emission Factor
(kg/MMBtu)
Equivalent Factor
(lb/Mgal) CO2e 73.96 22,338 40 CFR 98, Subpart C, Table C-1 CH4 3.00E-03 0.91 40 CFR 98, Subpart C, Table C-2 N2O 6.00E-04 0.18 40 CFR 98, Subpart C, Table C-2 CO2e 74.21 22,415
To take into account the lower sulfur content of the diesel fuel burned, for purposes of representing SO2 emissions from the engine, the factor in AP42 Table 3.4-1 (Large Stationary Diesel Engines, 10/1996 edition) is used as shown below. This factor expresses SO2 as a function of sulfur content. As required under NSPS Subpart IIII, the ultra low sulfur diesel (ULSD) must be used in the new emergency generator engine.
Based on maximum sulfur content in ULSD of 15 ppm
AP-42 Table 3.4-1 (S is sulfur content in %)
Emission factors for organic HAP compounds expected to be emitted are based on emission factors in AP-42 Table 3.4- 3 (10/96 Edition). Emission factors are converted from lb/MMBtu as provided in AP-42 to lb/Mgal as applicable to the SCC designation.
CO2, CH4 and N2O emissions for diesel fuel combustion are estimated using the Distillate Fuel Oil No. 2 emission factors published in 40 CFR 98, Subpart C, Table C-1 & 2. CO2e emissions for diesel fuel combustion are estimated using the global warming potentials published in 40 CFR 98, Subpart A, Table A-1.
= 1.52E-03 lb/MMBtu * 137 MMBtu/Mgal
2.1.4 Summary of Engine Potential Emissions
Pollutant
Emission Factor
(lb/Mgal) Basis
Hourly Emissions
(lb/hr)
Annual Emissions
(tpy) NOX 109.70 Manufacturer Emissions Data Sheet 3.36 0.84 CO 19.88 Manufacturer Emissions Data Sheet 0.61 0.15 VOC 3.65 Manufacturer Emissions Data Sheet 0.11 0.028 PM/PM10/PM2.5 3.31 Manufacturer Emissions Data Sheet 0.10 0.025 SO2 0.21 AP-42 Table 3.4-1 (S is sulfur content in %) 6.35E-03 1.59E-03 Benzene 0.11 AP-42 Table 3.4-4 3.25E-03 8.13E-04 Toluene 0.038 AP-42 Table 3.4-4 1.18E-03 2.95E-04 Xylene 0.026 AP-42 Table 3.4-4 8.09E-04 2.02E-04
CO2 22,338 40 CFR 98, Subpart C, Table C-1 683.55 170.89 CH4 0.91 40 CFR 98, Subpart C, Table C-2 2.77E-02 6.93E-03 N2O 0.18 40 CFR 98, Subpart C, Table C-2 5.55E-03 1.39E-03 CO2e 22,415 40 CFR 98, Subpart C 685.90 171.47
2.2.1 Source Classification Code
SCC: 10200603
SCC Description:
SCC Units:
2.2.2 Indirect Heat Exchanger Process Rate
Heat Content of Natural Gas (HHV): 1,020 Btu/scf AP-42 Appendix A
Capacity: 0.60 MMBtu/hr 5.88E-04 MMscf/hr
2.2.3 Emission Calculation Methodology and Emission Factors
2.2.3.1 NOx
Pollutant Value Units Emission Factor Basis NOx 9 ppmv Manufacturer specification at 3% O2 NO2 Molecular Weight 46 lb/lbmol Consistent with Method 19, assuming all NOx is NO2 Molar Volume Conversion 386 scf/lbmol Ideal gas law at 68 deg. F and 1 atm NOx Exhaust Concentration 1.07E-06 lb NOx/dscf
F-Factor 8,710 dscf/MMBtu
O2 Conc. For EF Correction 3 % Manufacturer specification, SCAQMD regulation NOx Heat Input Rate-Based
EF
0.011 lb/MMBtu
Calculated NOx Natural Gas Usage Rate-Based EF
11.13 lb/MMscf = 0.011 lb NO2/MMBtu x 1,020 MMBtu/MMscf
Remaining emission factors are based on emission factors in AP-42 Section 1.4 (07/98 Edition). Emission factors are in lb/MMscf as provided in AP-42 which corresponds to the applicable SCC designation.
The calculated NOx emission factor is based on emissions estimates provided in the manufacturer specifications converted
= 9 lbmol NOx/lbmol gas x 46 lb NO2/1 lbmol NO2 x 1 lbmol gas/386 scf gas
EPA Method 19 Table 19-2 F-Factor for Various Fuels dry F-factor for natural gas
= 1.07E-06 lb NO2/dscf x 8,710 dscf/MMBtu x 20.9% / (20.9% - 3%)
2.2. Natural Gas-fired Indirect Heat Exchangers
Three (3) natural gas-fired boilers will be installed 2 support Buildings 204 & 205.
Emissions for this indirect heat exchanger are tied to the SCC code for external combustion boilers listed below.
External Combustion Boilers, Industrial (1-02), Natural Gas (1-02-006), < 10 Million Btu/hr (1-02-006-03) Million Cubic Feet Natural
2.2.1 Summary of Potential Emissions
Pollutant1
Emission Factor
(lb/SCC)
Hourly Emissions
(lb/hr)
Annual Emissions
(tpy) Emission Factor Basis NOx 11.13 6.54E-03 0.029 F-15-047 Section D.3.
CO 84.00 0.049 0.216 AP-42 Table 1.4-1 CO2 120,000 70.59 309.18 AP-42 Table 1.4-2 Lead 0.0005 2.94E-07 1.29E-06 AP-42 Table 1.4-2 N2O 2.2 1.29E-03 5.67E-03 AP-42 Table 1.4-2 PM 7.6 4.47E-03 1.96E-02 AP-42 Table 1.4-2 PM10 7.6 4.47E-03 1.96E-02 AP-42 Table 1.4-2 PM2.5 7.6 4.47E-03 1.96E-02 AP-42 Table 1.4-2 SO2 0.6 3.53E-04 1.55E-03 AP-42 Table 1.4-2 Methane 2.3 1.35E-03 5.93E-03 AP-42 Table 1.4-2 VOC 5.5 3.24E-03 1.42E-02 AP-42 Table 1.4-2 Formaldehyde 0.075 4.41E-05 1.93E-04 AP-42 Table 1.4-3
1 Factors for PM10 and PM2.5 are conservatively assumed as the factor for PM.
2.3.1 Source Classification Code
SCC: 10200603
SCC Description:
SCC Units:
2.3.2 Indirect Heat Exchanger Process Rate
Heat Content of Natural Gas (HHV): 1,020 Btu/scf AP-42 Appendix A
Capacity: 0.50 MMBtu/hr 4.90E-04 MMscf/hr
2.3.3 Emission Calculation Methodology and Emission Factors
2.3.3.1 NOx
Pollutant Value Units Emission Factor Basis NOx 20 ppmv Manufacturer specification at 3% O2 NO2 Molecular Weight 46 lb/lbmol Consistent with Method 19, assuming all NOx is NO2 Molar Volume Conversion 386 scf/lbmol Ideal gas law at 68 deg. F and 1 atm NOx Exhaust Concentration 2.38E-06 lb NOx/dscf
F-Factor 8,710 dscf/MMBtu
O2 Conc. For EF Correction 3 % Manufacturer specification, SCAQMD regulation NOx Heat Input Rate-Based
EF
0.024 lb/MMBtu
NOx Natural Gas Usage Rate- Based EF
24.7 lb/MMscf = 0.024 lb NO2/MMBtu x 1,020 MMBtu/MMscf
2.3. Natural Gas-fired Hot Water Heaters
Three (3) natural gas-fired hot water heater will be installed to support Buildings 204 & 205 currently under construction.
Emissions for this indirect heat exchanger are tied to the SCC code for external combustion boilers listed below.
External Combustion Boilers, Industrial (1-02), Natural Gas (1-02-006), < 10 Million Btu/hr (1-02-006-03) Million Cubic Feet Natural
Remaining emission factors are based on emission factors in AP-42 Section 1.4 (07/98 Edition). Emission factors are in lb/MMscf as provided in AP-42 which corresponds to the applicable SCC designation.
= 20 lbmol NOx/lbmol gas x 46 lb NO2/1 lbmol NO2 x 1 lbmol gas/386 scf gas
EPA Method 19 Table 19-2 F-Factor for Various Fuels dry F-factor for natural gas
= 2.38E-06 lb NO2/dscf x 8,710 dscf/MMBtu x 20.9% / (20.9% - 3%)
The calculated NOx emission factor is based on emissions estimates provided in the manufacturer specifications converted to lb/MMscf, which corresponds to the applicable SCC designation.
2.3.1 Summary of Potential Emissions
Pollutant1
Emission Factor
(lb/SCC)
Hourly Emissions
(lb/hr)
Annual Emissions
(tpy) Emission Factor Basis NOX 24.7 1.21E-02 0.053 F-15-047 Section D.3.
CO 84.0 0.041 0.180 AP-42 Table 1.4-1 CO2 120,000 58.82 257.65 AP-42 Table 1.4-2 Lead 0.0005 2.45E-07 1.07E-06 AP-42 Table 1.4-2 N2O 2.2 1.08E-03 4.72E-03 AP-42 Table 1.4-2 PM 7.6 3.73E-03 1.63E-02 AP-42 Table 1.4-2 PM10 7.6 3.73E-03 1.63E-02 AP-42 Table 1.4-2 PM2.5 7.6 3.73E-03 1.63E-02 AP-42 Table 1.4-2 SO2 0.6 2.94E-04 1.29E-03 AP-42 Table 1.4-2 Methane 2.3 1.13E-03 4.94E-03 AP-42 Table 1.4-2 VOC 5.5 2.70E-03 1.18E-02 AP-42 Table 1.4-2 Formaldehyde 0.075 3.68E-05 1.61E-04 AP-42 Table 1.4-3
2.4.1 Source Classification Code
SCC: 10200603
SCC Description:
SCC Units:
2.4.2 Indirect Heat Exchanger Process Rate
Heat Content of Natural Gas (HHV): 1,020 Btu/scf AP-42 Appendix A
Capacity: 0.75 MMBtu/hr 7.35E-04 MMscf/hr
2.4.3 Emission Calculation Methodology and Emission Factors
2.4.3.1 NOx
Pollutant Value Units Emission Factor Basis NOx 9 ppmv Manufacturer specification at 3% O2 NO2 Molecular Weight 46 lb/lbmol Consistent with Method 19, assuming all NOx is NO2 Molar Volume Conversion 386 scf/lbmol Ideal gas law at 68 deg. F and 1 atm NOx Exhaust Concentration 1.07E-06 lb NOx/dscf
F-Factor 8,710 dscf/MMBtu
O2 Conc. For EF Correction 3 % Manufacturer specification NOx Heat Input Rate-Based
EF
0.011 lb/MMBtu
Calculated NOx Natural Gas Usage Rate-Based EF
11.13 lb/MMscf = 0.011 lb NO2/MMBtu x 1,020 MMBtu/MMscf
2.4. Natural Gas-fired Indirect Heat Exchangers
Two (2) natural gas-fired boilers will be installed to support the Building 39 Renovation.
Emissions for this indirect heat exchanger are tied to the SCC code for external combustion boilers listed below.
External Combustion Boilers, Industrial (1-02), Natural Gas (1-02-006), < 10 Million Btu/hr (1-02-006-03) Million Cubic Feet Natural
Remaining emission factors are based on emission factors in AP-42 Section 1.4 (07/98 Edition). Emission factors are in lb/MMscf as provided in AP-42 which corresponds to the applicable SCC designation.
= 9 lbmol NOx/lbmol gas x 46 lb NO2/1 lbmol NO2 x 1 lbmol gas/386 scf gas
EPA Method 19 Table 19-2 F-Factor for Various Fuels dry F-factor for natural gas
= 1.07E-06 lb NO2/dscf x 8,710 dscf/MMBtu x 20.9% / (20.9% - 3%)
The calculated NOx emission factor is based on emissions estimates provided in the manufacturer specifications converted to lb/MMscf, which corresponds to the applicable SCC designation.
2.4.1 Summary of Potential Emissions
Pollutant1
Emission Factor
(lb/SCC)
Hourly Emissions
(lb/hr)
Annual Emissions
(tpy) Emission Factor Basis NOx 11.13 8.18E-03 0.036 AP-42 Table 1.4-1 CO 84.00 0.062 0.271 AP-42 Table 1.4-1 CO2 120,000 88.24 386.47 AP-42 Table 1.4-2 Lead 0.0005 3.68E-07 1.61E-06 AP-42 Table 1.4-2 N2O 2.2 1.62E-03 7.09E-03 AP-42 Table 1.4-2 PM 7.6 5.59E-03 2.45E-02 AP-42 Table 1.4-2 PM10 7.6 5.59E-03 2.45E-02 AP-42 Table 1.4-2 PM2.5 7.6 5.59E-03 2.45E-02 AP-42 Table 1.4-2 SO2 0.6 4.41E-04 1.93E-03 AP-42 Table 1.4-2 Methane 2.3 1.69E-03 7.41E-03 AP-42 Table 1.4-2 VOC 5.5 4.04E-03 1.77E-02 AP-42 Table 1.4-2 Formaldehyde 0.075 5.51E-05 2.42E-04 AP-42 Table 1.4-3
2.5.1 Source Classification Code
SCC: 10200603
SCC Description:
SCC Units:
2.5.2 Indirect Heat Exchanger Process Rate
Heat Content of Natural Gas (HHV): 1,020 Btu/scf AP-42 Appendix A
Capacity: 0.15 MMBtu/hr 1.47E-04 MMscf/hr
2.5.3 Emission Calculation Methodology and Emission Factors
2.5.3.1 NOx
Pollutant Value Units Emission Factor Basis NOx 20 ppmv Manufacturer specification at 3% O2 NO2 Molecular Weight 46 lb/lbmol Consistent with Method 19, assuming all NOx is NO2 Molar Volume Conversion 386 scf/lbmol Ideal gas law at 68 deg. F and 1 atm NOx Exhaust Concentration 2.38E-06 lb NOx/dscf
F-Factor 8,710 dscf/MMBtu
O2 Conc. For EF Correction 3 % Manufacturer specification NOx Heat Input Rate-Based
EF
0.024 lb/MMBtu
NOx Natural Gas Usage Rate- Based EF
24.72 lb/MMscf = 0.024 lb NO2/MMBtu x 1,020 MMBtu/MMscf
Remaining emission factors are based on emission factors in AP-42 Section 1.4 (07/98 Edition). Emission factors are in lb/MMscf as provided in AP-42 which corresponds to the applicable SCC designation.
= 20 lbmol NOx/lbmol gas x 46 lb NO2/1 lbmol NO2 x 1 lbmol gas/386 scf gas
EPA Method 19 Table 19-2 F-Factor for Various Fuels dry F-factor for natural gas
= 2.38E-06 lb NO2/dscf x 8,710 dscf/MMBtu x 20.9% / (20.9% - 3%)
The calculated NOx emission factor is based on emissions estimates provided in the manufacturer specifications converted to lb/MMscf, which corresponds to the applicable SCC designation.
2.5. Natural Gas-fired Hot Water Heaters
One (1) natural gas-fired hot water heater will be installed to support the Building 39 Renovation.
Emissions for this indirect heat exchanger are tied to the SCC code for external combustion boilers listed below.
External Combustion Boilers, Industrial (1-02), Natural Gas (1-02-006), < 10 Million Btu/hr (1-02-006-03) Million Cubic Feet Natural
2.5.1 Summary of Potential Emissions
Pollutant1
Emission Factor
(lb/SCC)
Hourly Emissions
(lb/hr)
Annual Emissions
(tpy) Emission Factor Basis NOX 24.72 3.64E-03 0.016 AP-42 Table 1.4-1 CO 84.00 0.012 0.054 AP-42 Table 1.4-1 CO2 120,000 17.65 77.29 AP-42 Table 1.4-2 Lead 0.0005 7.35E-08 3.22E-07 AP-42 Table 1.4-2 N2O 2.2 3.24E-04 1.42E-03 AP-42 Table 1.4-2 PM 7.6 1.12E-03 4.90E-03 AP-42 Table 1.4-2 PM10 7.6 1.12E-03 4.90E-03 AP-42 Table 1.4-2 PM2.5 7.6 1.12E-03 4.90E-03 AP-42 Table 1.4-2 SO2 0.6 8.82E-05 3.86E-04 AP-42 Table 1.4-2 Methane 2.3 3.38E-04 1.48E-03 AP-42 Table 1.4-2 VOC 5.5 8.09E-04 3.54E-03 AP-42 Table 1.4-2 Formaldehyde 0.075 1.10E-05 4.83E-05 AP-42 Table 1.4-3
ATTACHMENT 3
Emission Data Sheet and Certificate of Conformity
Model: John Deere, 6135HF485S Bore: 132mm (5.2 in.)
Nameplate BHP @ 1800 RPM: 617 Stroke: 165mm (6.5 in.)
Type: 4-Cycle, 6 Cylinder, Inline Displacement: 13.5 L (824 cu. in.)
Aspiration: Turbocharged, Charge Air-Cooled
Compression Ratio 16.0:1 EPA Family: MJDXL13.5103
EPA Certificate: MJDXL13.5103-007
PERFORMANCE DATA:
1/4
Standby 1/2
Standby 3/4
Standby Full
Standby Engine bkW @ Stated Load 115 230 345 460
Fuel Consumption (g/kWh) 237 212 206 209
Exhaust Gas Flow (m3/min) 81
Exhaust Temperature (°C) 471
EXHAUST EMISSION DATA:
HC (Total Unburned Hydrocarbons)
NOx (Oxides of Nitrogen as NO2)
CO (Carbon Monoxide)
PM (Particulate Matter)
Data and specifications subject to change without notice.
TEST METHODS AND CONDITIONS
The emission data listed is measured from a laboratory test engine according to the test procedures of 40 CFR 89 or 40 CFR 1039, as applicable. The test engine is intended to represent nominal production hardware, and there is no guarantee that every production engine will have identical test results. The family parent data represents multiple ratings and this data may have been collected at a different engine speed and load. Emission results may vary due to engine manufacturing tolerances, engine operating conditions, fuels used, alternate test methods, or other conditions.
EPA D2 Cycle 5-mode weighted
0.11
3.31
0.6
0.10
Values are in g/kWh unless otherwise noted
Table 2
400REOZJC
60 HZ. DIESEL INDUSTRIAL GENERATOR SET
EMISSION DATA SHEET
ENGINE INFORMATION
Table 1
ATTACHMENT 4
Process Flow Diagram for Emergency Generator Engine
Figure 1
1717 Dixie Hwy, Ste. 900 Covington, KY 41011
Figure 1
Legend
Emissions Flow Raw Material Flow
Diesel Fuel 400 kW Emergency Generator with 617 bHP stationary engine
Fuel Combustion