This document is a permit revision application for the addition of an emergency generator engine and other insignificant activities at the Lexington VA Health Care System-Leestown Road facility in Kentucky. The application includes the required DEP7007 forms, emission calculations, and manufacturer data for the new emergency generator. It analyzes the regulatory applicability, including 40 CFR 63 Subpart ZZZZ and 40 CFR 60 Subpart IIII requirements, and determines the installation of the new equipment does not require an advance permit revision. The insignificant activities include a diesel fuel tank, five small natural gas-fired boilers, and four small natural gas-fired water heaters associated with the construction of two new buildings and renovations to an existing building.

The related federal contract opportunity is for architect-engineer (A-E) services to develop construction documents, including working drawings, specifications, cost estimates, and construction period services, for a new radiation oncology building at the Lexington VA Medical Center. This is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB). The project has an estimated construction cost between $10-20 million and a 280-calendar-day design completion period. The A-E selection process involves evaluating Statement of Qualifications (SF 330) submissions based on primary criteria like specialized experience, professional qualifications, capacity, and past performance, as well as a secondary geographic location criterion.

View the file

Other files

File Type Posted
36C77624R0144_2.docx DOCX document
SF330 TQ Tracking Spreadsheet - Lex Rad Onc Design.pdf PDF
36C77624R0144_1.docx DOCX document
SOW Att. 01 - AE CPM Schedules.pdf PDF
SOW Att. 06 - LDP Process.pdf PDF
SOW Att. 08 - Additional Technical Requirements.pdf PDF
SOW Att. 03 - Campus Map.pdf PDF
SOW Att. 02 - PG-18-15 Volume C.pdf PDF
SOW Att. 07 - LFUCG Ordinance Reduction of Erosion Control.pdf PDF
SOW Att. 05 - KHC Cover Sheet 106 Review.pdf PDF
SOW_596-335.pdf PDF
36C77624R0144.docx DOCX document
PPQ.docx DOCX document
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

[TO BE PRINTED ON VA LETTERHEAD]

August 19, 2022

Mr. Zachary Bittner Division for Air Quality – Combustion Section Supervisor Kentucky Department for Environmental Protection 300 Sower Blvd., 2nd Floor Frankfort, KY 40601

RE: Permit Revision Application for State Origin Permit No. S-21-012 R1 Lexington VAHCS-Leestown Road (AI #1106)

Dear Mr. Bittner:

Lexington VA Health Care System-Leestown Road (VAHCS) is hereby filing a permit revision application for the addition of an emergency generator engine, in accordance with 401 KAR 52:040 Section 13 Actions that Do Not Require a Permit Revision in Advance. As part of this revision application, VAHCS has included notification of planned installation of insignificant activities, including the diesel fuel tank serving the generator, 5 small (< 1 MMBtu/hr) natural gas-fired boilers, and 4 small (< 1 MMBtu/hr) natural gas-fired water heaters. The new equipment will be associated with the construction of two (2) new buildings, Buildings 204 and 205 and, the renovations being done for building 39, at the Leestown Road campus.

The State Origin permit for the Leestown Road campus requires revisions to include a new engine in the existing Section B diesel-fired engine emission unit group, starting on page 12 of 24, as Emissions Unit 43.

This letter and its attachments contain all the required elements of a permit revision as specified in 401 KAR 52:040 Section 5, except pursuant to 401 KAR 52:040 Section 4(c), the application will provide only the information related to this change.

APPLICATION CONTENTS

This application letter provides a description of the new equipment being added and an analysis of the air permitting and regulatory requirements. A completed set of applicable DEP7007 series application forms (AI, EE, N, and V) are provided in Attachment 1 for the emergency generator engine being added and DEP7007 Form DD for insignificant activities. Emission calculations for the emergency generator engine can be found in Attachment 2. The engine’s Emission Data Sheet and Certificate of Conformity are provided in Attachment 3. A process flow diagram of the emergency generator engine is provided in Attachment 4.

REGULATORY APPLICABILITY AND AIR PERMITTING REQUIREMENTS

40 CFR 63 Subpart ZZZZ – Stationary Reciprocating Internal Combustion Engines (RICE) Pursuant to 40 CFR 63.6590(c)(1), a new stationary RICE located at an area source of hazardous air pollutant (HAP) emissions must meet 40 CFR 60 Subpart IIII requirements in order to meet the 40 CFR 63 Subpart ZZZZ requirements. VAHCS is an area source of HAP and; therefore, no further requirements apply for such engines under 40 CFR 63 Subpart ZZZZ.

Mr. Zachary Bittner - Page 2

40 CFR 60 Subpart IIII – Stationary Compression Ignition (CI) Internal Combustion Engines (ICE) Owners and operators that commenced construction after July 11, 2005, of a stationary CI ICE manufactured after April 1, 2006, and are not fire pump engines are subject to 40 CFR 60 Subpart IIII pursuant to 40 CFR 60.4200(a)(2)(i). Pursuant to 40 CFR 60.4205(b), the new emergency stationary CI ICE with a displacement less than 30 liters per cylinder that are not fire pump engines shall comply with the emission standards referenced in 40 CFR 60.4202(a)(2), which refers to the certification emission standards for new nonroad CI engines in 40 CFR 89.112 Table 1. According to the manufacturer emissions data sheet, provided in Attachment 1, the diesel generator engine is well within the required emission standards for Table 1 in 40 CFR 89.112 of 4.0 g/hp-hr for NMHC + NOX, 3.5 g/hp-hr for CO, and 0.20 g/hp-hr for PM.

40 CFR 63 Subpart JJJJJJ – Industrial, Commercial, and Institutional Boilers at Area Sources – Not Subject Pursuant to 40 CFR 63.1195(e) and (f), neither a gas-fired boiler nor a hot water heater is subject to this regulation. Therefore, this regulation does not apply to gas-fired boilers and water heaters to be installed per this permit revision application.

401 KAR 59:015 – New Indirect Heat Exchangers – Not Subject Pursuant to 401 KAR 59:015 Section 1, an affected facility is an indirect heat exchanger having a heat input capacity greater than one (1) million BTU per hour. None of the new natural gas-fired boilers nor hot water heaters have a capacity greater than 1 MMBtu/hr; therefore, this regulation does not apply to the equipment to be installed per this permit revision application.

40 KAR 59:050 – New Storage Vessels for Petroleum Liquids – Not Subject 401 KAR 59:050 applies to certain storage vessels which store “petroleum liquids”. Pursuant to 401 KAR 59:050 Section 2, a “petroleum liquid” does not mean Number 2 through Number 6 fuel oils, gas turbine fuel oil Number 2-GT through 4-GT, or diesel fuel oils Numbers 2-D and 4-D. The diesel fuel tank associated with the emergency generator engine stores only Number 2 fuel oil and, therefore, is not subject to this regulation.

QUALIFICATION FOR TREATMENT AS “ACTIONS THAT DO NOT

REQUIRE A PERMIT REVISION IN ADVANCE”

As a natural minor source subject to state-origin permitting requirements, Sections 12 and 13 of 401 KAR 52:040 establish two (2) categories of permit actions:

1. Actions that Require a Permit or Permit Revision in Advance. Per Section 12 of 401 KAR 52:040, for the modification of a source that will increase its potential to emit (PTE) by 2.5 tpy or more of a HAP, 7.5 tpy or more of combined HAPs, or 25 tpy or more of a nonhazardous regulated air pollutant, the permittee must obtain a permit or permit revision prior to commencing construction.

2. Actions that Do Not Require a Permit Revision in Advance. For all permit revisions except those covered by Section 12, the permittee must submit a complete application for the permit revision and may implement the change immediately upon submittal of the application.

Mr. Zachary Bittner - Page 3

Based on the minimal emissions increases from installation of the new emergency generator and insignificant activity boilers and water heaters, shown in Attachment 2, this action does not require an advance permit revision.

If you have any questions or comments about the information presented in this letter, please do not hesitate to call me at 859.233.4511 ext. 3354.

Sincerely, Richard J. Archer, MPH, CIH Lexington VA Health Care System – Safety Manager

Attachments cc: Ms. Margot Fosnaugh, Trinity Consultants, Inc.

ATTACHMENT 1

DEP 7007 Forms (AI, N, V, DD, EE)

11/2018 DEP7007AI

___ Section AI.1: Source Information

___ Section AI.2: Applicant Information ___ Section AI.3: Owner Information ___ Section AI.4: Type of Application

___ Section AI.5: Other Required Information ___ Section AI.6: Signature Block ___ Section AI.7: Notes, Comments, and Explanations

21-

Agency Interest (AI) ID:

County: Zip Code:

State: Zip Code:

Longitude: Latitude:

Primary (NAICS) Category: General Medical and Surgical Hospitals Primary NAICS #: 622110

Mailing Address:

Street or P.O. Box:

Same as Physical Address

City:

Standard Coordinates for Source Physical Location

-84.53747 (decimal degrees) 38.07479 (decimal degrees)

Section AI.1: Source Information Physical Location

Address:

Street: 2250 Leestown Road City: Lexington Fayette 40511

Date:

Frankfort, KY 40601

(502) 564-3999

Source Name: Lexington VAHCS

KY EIS (AFS) #: 067-00008

Permit #: S-21-012 R1

Aug-22

Division for Air Quality DEP7007AI Additional Documentation Administrative Information

300 Sower Boulevard ___ Additional Documentation attached

Rural Area Residential Area Yes

Urban Area Commercial Area No

Is this source portable? Yes No

NPDES/KPDES: Currently Hold Need N/A

Solid Waste: Currently Hold Need N/A

RCRA: Currently Hold Need N/A

UST: Currently Hold Need N/A

Mixed Waste Generator Generator Recycler Other: ______________

U.S. Importer of Hazardous Waste Transporter Treatment/Storage/Disposal Facility N/A

Type of Regulated Waste Activity:

Description of Area Surrounding Source:

Industrial Park Is any part of the source located on federal land?

Number of Employees:

Approximate distance to nearest residence or commercial property:

Property Area:883 ft ~150 acres

What other environmental permits or registrations does this source currently hold or need to obtain in Kentucky?

700-800 Industrial Area

Classification (SIC) Category: Medical Laboratories Primary SIC #: 8071

Briefly discuss the type of business conducted at this site:

The Franklin Sousley Campus located at 2250 Leestown Road offers inpatient Post-Traumatic Stress Disorder (PTSD) and substance abuse treatment, nursing home care, hospice and respite services, home based primary care, prosthetics and orthotics, geriatrics, optometry, mental health as well as primary care and women's health.

City: State: Zip Code:

City: State: Zip Code:

City: State: Zip Code:

Email: Richard.Archer2@va.gov

Phone: 859-233-4511 x3365

Title: Safety Manager

Mailing Address:

Street or P.O. Box: Same as above

Email: Richard.Archer2@va.gov

Phone: 859-233-4511 x3365

Air Permit Contact for Source

Name: Richard J. Archer, MPH, CIH

Title: Safety Manager

Street or P.O. Box: Same as above

Email: (if individual)

Phone:

Technical Contact

Name: Richard J. Archer, MPH, CIH

Mailing Address:

Street or P.O. Box: 2250 Leestown Road

Lexington KY 40511

Title: (if individual)

Section AI.2: Applicant Information

Applicant Name: Lexington VAHCS - Leestown Road

Street or P.O. Box:

State: Zip Code:

Name Position

List names of owners and officers of the company who have an interest in the company of 5% or more.

Email:

Phone:

Title:

City:

Section AI.3: Owner Information

Owner same as applicant Name:

Title V Conditional Major State-Origin General Permit Registration None

Name Change Initial Registration Significant Revision Administrative Permit Amendment

Renewal Permit Revised Registration Minor Revision Initial Source-wide OperatingPermit

502(b)(10)Change Extension Request Addition of New Facility Portable Plant Relocation Notice

Revision Off Permit Change Landfill Alternate Compliance Submittal Modification of Existing Facilities

Ownership Change Closure

Title V Conditional Major State-Origin PSD NSR Other:

Yes No

Requested Limit:

Single HAP

Combined HAPs

Carbon Dioxide

Greenhouse Gases (GHG)

Other

Yes No

For Modifications:

Proposed Start Date of Modification:

(MM/YYYY) Proposed Operation Start-Up Date: (MM/YYYY) na na

Applicant is seeking coverage under a permit shield.

Identify any non-applicable requirements for which permit shield is sought on a separate attachment to the application.

Proposed Start Date of Construction:

(MM/YYYY) Proposed Operation Start-Up Date: (MM/YYYY)

08/2022 08/2022

For New Construction:

Nitrogen Oxides

Sulfur Dioxide

Lead

Volatile Organic Compounds (VOC)

Carbon Monoxide Air Toxics (40 CFR 68, Subpart F)

Section AI.4: Type of Application

Current Status:

Requested Action:

(check all that apply)

Is the source requesting a limitation of potential emissions?

Requested Status: ____________

Particulate Matter

Pollutant: Pollutant: Requested Limit:

DEP7007A Indirect Heat Exchangers and Turbines DEP7007CC Compliance Certification DEP7007B Manufacturing or Processing Operations DEP7007DD Insignificant Activities DEP7007C Incinerators and Waste Burners DEP7007EE Internal Combustion Engines DEP7007F Episode Standby Plan DEP7007FF Secondary Aluminum Processing DEP7007J Volatile Liquid Storage DEP7007GG Control Equipment DEP7007K Surface Coating or Printing Operations DEP7007HH Haul Roads DEP7007L Mineral Processes Confidentiality Claim DEP7007M Metal Cleaning Degreasers Ownership Change Form DEP7007N Source Emissions Profile Secretary of State Certificate DEP7007P Perchloroethylene Dry Cleaning Systems Flowcharts or diagrams depicting process DEP7007R Emission Offset Credit Digital Line Graphs (DLG) files of buldings, roads, etc.

DEP7007S Service Stations Site Map DEP7007T Metal Plating and Surface Treatment Operations Map or drawing depicting location of facility DEP7007V Applicable Requirements and Compliance Activities Safety Data Sheet (SDS) DEP7007Y Good Engineering Practice and Stack Height Determination Emergency Response Plan DEP7007AA Compliance Schedule for Non-complying Emission Units Other: ____Engine Certificate of Conformity DEP7007BB Certified Progress Report

Type or Printed Name of Signatory Title of Signatory

*Responsible official as defined by 401 KAR 52:001.

I, the undersigned, hereby certify under penalty of law, that I am a responsible official*, and that I have personally examined, and am familiar with, the information submitted in this document and all its attachments. Based on my inquiry of those individuals with primary responsibility for obtaining the information, I certify that the information is on knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false or incomplete information, including the possibility of fine or imprisonment.

Authorized Signature Date

Kerri Dauteuil Acting Chief, Engineering Svc

Section AI.6: Signature Block

Section AI.5 Other Required Information Indicate the documents attached as part of this application:

Section AI.7: Notes, Comments, and Explanations

11/2018 DEP7007DD

DEP7007DD

Insignificant Activities ___ Section DD.1: Table of Insignificant Activities ___ Section DD.2: Signature Block ___ Section DD.3: Notes, Comments, and Explanations

Source Name:

KY EIS (AFS) #: 21-

Permit #:

Agency Interest (AI) ID:

Date:

36.

One (1) 3,920 gallon diesel fuel oil tank

Two(2) <4,000 gallon diesel fuel oil tanks

N/A N/A < 5 tpy of all criteria pollutants < 1,000 lb/yr of HAP

37. NG Hot Water Boiler – 0.6 MMBTU/hr Campus Advantus model AV0600 N/A 0.216 tpy of CO as highest emitting criteria pollutant

38. NG Hot Water Boiler – 0.6 MMBTU/hr Campus Advantus model AV0600 N/A 0.216 tpy of CO as highest emitting criteria pollutant

39. NG Hot Water Boiler – 0.6 MMBTU/hr Campus Advantus model AV0600 N/A 0.216 tpy of CO as highest emitting criteria pollutant

40. NG Hot Water Heater – 0.5 MMBTU/hr

Power VTX 50 L 225A-PVX N/A 0.180 tpy of CO as highest emitting criteria pollutant

Lexington VAHCS

Division for Air Quality 300 Sower Boulevard Frankfort, KY 40601

(502) 564-3999

067-00008

S-21-012 R1

Aug-22

Section DD.1: Table of Insignificant Activities *Identify each activity with a unique Insignificant Activity number (IA #); for example: 1, 2, 3… etc.

Insignificant Activity #

Description of Activity including Rated

Capacity

Serial Number or Other Unique Identifier Applicable Regulation(s) Calculated Emissions

Insignificant Activity #

Description of Activity including Rated

Capacity

Serial Number or Other Unique Identifier Applicable Regulation(s) Calculated Emissions

41. NG Hot Water Heater – 0.5 MMBTU/hr

Power VTX 50 L 225A-PVX N/A 0.180 tpy of CO as highest emitting criteria pollutant

42. NG Hot Water Heater – 0.5 MMBTU/hr

Power VTX 50 L 225A-PVX N/A 0.180 tpy of CO as highest emitting criteria pollutant

43. NG Hot Water Boiler – 0.75 MMBTU/hr Benchmark 750-6000 N/A 0.271 tpy of CO as highest emitting criteria pollutant

44. NG Hot Water Boiler – 0.75 MMBTU/hr Benchmark 750-6000 N/A 0.271 tpy of CO as highest emitting criteria pollutant

45. NG Hot Water Heater – 0.15 MMBTU/hr Bradford and White EF-100T-150E-3N(A) N/A 0.054 tpy of CO as highest emitting criteria pollutant

Insignificant Activity #

Description of Activity including Rated

Capacity

Serial Number or Other Unique Identifier Applicable Regulation(s) Calculated Emissions

Authorized Signature Date

Kerri Dauteuil Acting Chief, Engineering Svc

Type/Print Name of Siguatory Title of Siguatory

Section DD.2: Signature Block I, THE UNDERSIGNED, HEREBY CERTIFY UNDER PENALTY OF LAW, THAT I AM A RESPONSIBLE OFFICIAL, AND THAT I HAVE PERSONALLY

EXAMINED, AND AM FAMILIAR WITH, THE INFORMATION SUBMITTED IN THIS DOCUMENT AND ALL ITS ATTACHMENTS. BASED ON MY INQUIRY OF THOSE INDIVIDUALS WITH PRIMARY RESPONSIBILITY FOR OBTAINING THE INFORMATION, I CERTIFY THAT THE INFORMATION IS ON

KNOWLEDGE AND BELIEF, TRUE, ACCURATE, AND COMPLETE. I AM AWARE THAT THERE ARE SIGNIFICANT PENALTIES FOR SUBMITTING FALSE

OR INCOMPLETE INFORMATION, INCLUDING THE POSSIBILITY OF FINE OR IMPRISONMENT.

By:

Section DD.3: Notes, Comments, and Explanations

11/2018 DEP7007EE

Source Name:

KY EIS (AFS) #: 21-

Permit #:

Agency Interest (AI) ID:

Date:

43 Emergency Engine - Kohler 400REOZJC na S1 KOHLER 400REOZJC 2021 1/1/2021 na

40 CFR 63

Subpart ZZZZ, 40 CFR 60 Subpart

IIII

Aug-22

Section EE.1: General Information

Division for Air Quality DEP7007EE Additional Documentation

Internal Combustion Engines __ Complete DEP7007AI, DEP7007N, DEP7007V, and DEP7007GG300 Sower Boulevard ___ Section EE.1: General Information

Frankfort, KY 40601 ___ Section EE.2: Operating Information __ Attach EPA certification of the engine

(502) 564-3999 ___ Section EE.3: Design Information ___ Section EE.4: Fuel Information ___ Section EE.5: Emission Factor Information ___ Section EE.6: Notes, Comments, and Explanations

Lexington VAHCS 067-00008 S-21-012 R1

Emission Unit # Emission Unit Name Control Device ID Stack ID Manufacturer Model Number Model Year Date of

Manufacture

Proposed/Actual Date of

Construction Commencement

(MM/YYYY)

Date Reconstructed/

Modified

List Applicable Regulations

08/2022

43 Emergency 500 No na

Section EE.2: Operating Information

Emission Unit #

Engine Purpose (Identify if Non-Emergency, Emergency,Fire/Water Pump, Black-start engine for combustion turbine, Engine

Testing)

Hours Operated

Is this engine a rental? (Yes/No)

Rental Time Period

(hrs)

Alternate Operating Scenarios (Describe any operating scenarios in which the engine may be used in a different configuration)

43 Stationary Compression Ignition 4-Stroke 617 1,800 13.5 6

Section EE.3: Design Information

Emission Unit # Engine Type

(Identify all that apply: Commercial, Institutional, Stationary, Non-Road)

Ignition Type (Identify if either

Compression or Spark Ignition)

Engine Family (Identify all that apply: 2-stroke, 4-stroke, Rich Burn, Lean Burn)

Maximum Engine Power

(bhp)

Maximum Engine Speed (rpm)

Total Displacement

(L)

Number of Cylinders

43 Primary Diesel na 100 0.0306 Mgal/hr 137 MMBtu/Mgal 0.0015 20200102 Mgal Diesel

Burned

SCC Units

Section EE.4: Fuel Information

Emission Unit # Identify if Primary, Secondary, or Tertiary Fuel

Fuel Type (Identify if Diesel, Gasoline, Natural Gas, Liquefied Petroleum Gas (LPG), Landfill/Digester Gas, or Other)

Fuel Grade Percent

Time Used

Maximum Fuel Consumption

Heat Content

Sulfur Content

SCC Code

43 Primary PM/PM10/PM2.5 3.31 lb/Mgal Diesel Burned Manufacturer Emissions Data Sheet

43 Primary NOx 109.70 lb/Mgal Diesel Burned Manufacturer Emissions Data Sheet

43 Primary SO2 0.21 lb/Mgal Diesel Burned AP-42 Table 3.4-1 (S is sulfur content in %)

43 Primary VOC 3.65 lb/Mgal Diesel Burned Manufacturer Emissions Data Sheet

43 Primary CO 19.88 lb/Mgal Diesel Burned Manufacturer Emissions Data Sheet

43 Primary CO2 22,338 lb/Mgal Diesel Burned 40 CFR 98, Subpart C, Table C-1

43 Primary N2O 0.18 lb/Mgal Diesel Burned 40 CFR 98, Subpart C, Table C-2

43 Primary CH4 0.91 lb/Mgal Diesel Burned 40 CFR 98, Subpart C, Table C-2

43 Primary Benzene 0.106 lb/Mgal Diesel Burned AP-42 Table 3.4-4

43 Primary Toluene 0.038 lb/Mgal Diesel Burned AP-42 Table 3.4-4

43 Primary Xylene 0.026 lb/Mgal Diesel Burned AP-42 Table 3.4-4

Section EE.5: Emission Factor Information Emission factors expressed here are based on the potential to emit.

Emission Unit # Fuel Pollutant Emission Factor Emission Factor Units Source of Emission Factor

Section EE.6: Notes, Comments, and Explanations

11/2018 DEP7007N

21-

Agency Interest (AI) ID:

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 PM/PM10/PM2.5 3.31 Manufacturer

Emissions Data Sheet na na 0.101 na 0.025 na

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 NOx 109.70 Manufacturer

Emissions Data Sheet na na 3.36 na 0.84 na

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 SO2 0.21 AP-42 Table 3.4-1 (S is sulfur content in %) na na 6.35E-03 na 1.59E-03 na

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 VOC 3.65 Manufacturer

Emissions Data Sheet na na 0.112 na 0.028 na

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 CO 19.88 Manufacturer

Emissions Data Sheet na na 0.61 na 0.15 na

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 CO2 22338.35 40 CFR 98, Subpart C, Table C-1 na na 683.55 na 170.89 na

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 N2O 0.18 40 CFR 98, Subpart C, Table C-2 na na 5.55E-03 na 1.39E-03 na

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 CH4 0.91 40 CFR 98, Subpart C, Table C-2 na na 0.028 na 6.93E-03 na

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 Benzene 0.11 AP-42 Table 3.4-4 na na 3.25E-03 na 8.13E-04 na

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 Toluene 0.04 AP-42 Table 3.4-4 na na 1.18E-03 na 2.95E-04 na

43 Emergency Engine - Kohler 400REOZJC 1 Diesel Combustion na na S1 0.0306 Xylene 0.03 AP-42 Table 3.4-4 na na 8.09E-04 na 2.02E-04 na

Division for Air Quality

DEP7007N

Source Emissions Profile Additional Documentation

300 Sower Boulevard __ Section N.1: Emission Summary

Permit #:

Frankfort, KY 40601 __ Section N.2: Stack Information __ Complete DEP7007AI

(502) 564-3999 __ Section N.3: Fugitive Information

__ Section N.4: Notes, Comments, and Explanations Source Name:

KY EIS (AFS) #:

Lexington VAHCS 067-00008 S-21-012 R1

Date:

N.1: Emission Summary

Emission Unit # Emission Unit Name Process

ID Process Name Control Device Name

Control Device

ID

Stack

ID

Maximum Design

Capacity

(SCC

Units/hour)

Pollutant

Uncontrolled Emission

Factor (lb/SCC Units)

Emission Factor Source (e.g. AP-42, Stack Test, Mass Balance)

Aug-22

Capture Efficiency

Control Efficiency

Hourly Emissions Annual Emissions

Uncontrolled Potential

(lb/hr)

Controlled Potential

(lb/hr)

Uncontrolled Potential

(tons/yr)

Controlled Potential

(tons/yr)

UTM Zone:

S1 43 0.30 7.3 944 4,216,977 716,000 2860.488004 879.8 696.22

Easting (m)

Flowrate (acfm)

Temperature ( ° F)

Exit Velocity (ft/sec)

Section N.2: Stack Information

Stack ID

Identify all Emission Units (with Process ID) and Control Devices that Feed to Stack

Stack Physical Data Stack UTM Coordinates Stack Gas Stream Data

Equivalent Diameter

(ft)

Height (ft)

Base Elevation

(ft)

Northing (m)

UTM Zone:

Not Applicable for this Application

Easting (m)

Release Temperature

( °F)

Release Height

(ft)

Section N.3: Fugitive Information

Emission Unit # Emission Unit Name Process ID

Area Physical Data Area UTM Coordinates Area Release Data

Length of the X Side (ft)

Length of the Y Side (ft)

Northing (m)

Section N.4: Notes, Comments, and Explanations

11/2018 DEP7007V

21-

Agency Interest (AI) ID:

43 na na

43 NMHC +

NOX

From 60.4202 referenced in 60.4205, NMHC + NOX shall not exceed 4.0 g/kW-hr according to Table 1 of 40 CFR 89.112 over the entire life of the engine (60.4206).

067-00008

Division for Air Quality DEP7007V Additional Documentation

Applicable Requirements and Compliance Activities __ Complete DEP7007AI

300 Sower Boulevard ___ Section V.1: Emission and Operating Limitation(s)

Permit #:

Frankfort, KY 40601 ___ Section V.2: Monitoring Requirements

(502) 564-3999 ___ Section V.3: Recordkeeping Requirements

___ Section V.4: Reporting Requirements ___ Section V.5: Testing Requirements ___ Section V.6: Notes, Comments, and Explanations

Source Name:

KY EIS (AFS) #:

Lexington VAHCS

S-21-012 R1

Date:

Section V.1: Emission and Operating Limitation(s)

Emission Unit # Emission Unit Description

Applicable Regulation or Requirement

Pollutant Emission Limit (if applicable)

Voluntary Emission Limit or

Exemption (if applicable)

Operating Requirement or Limitation

(if applicable)

Method of Determining Compliance with the

Emission and Operating Requirement(s)

Aug-22

Emergency Engine - Kohler

400REOZJC

NESHAP ZZZZ: 40

CFR 63.6590(c) na Meet the requirements of NESHAP

ZZZZ by complying with NSPS IIII. Comply with NSPS IIII.

Emergency Engine - Kohler

400REOZJC

NSPS IIII: 40 CFR

60.4205(b) na na

Purchase engine certified to the emission standards and install and configure according to the manufacturer specifications (60.4211(c)).

Emission Unit # Emission Unit Description

Applicable Regulation or Requirement

Pollutant Emission Limit (if applicable)

Voluntary Emission Limit or

Exemption (if applicable)

Operating Requirement or Limitation

(if applicable)

Method of Determining Compliance with the

Emission and Operating Requirement(s)

43 CO

From 60.4202 referenced in 60.4205, CO shall not exceed 3.5 g/kW-hr according to Table 1 of 40 CFR 89.112 over the entire life of the engine (60.4206).

43 PM

From 60.4202 referenced in 60.4205, PM shall not exceed 0.20 g/kW-hr according to Table 1 of 40 CFR 89.112 over the entire life of the engine (60.4206).

43 na na

43 na na

43 na na

Emergency Engine - Kohler

400REOZJC

NSPS IIII: 40 CFR

60.4205(b) na na

Purchase engine certified to the emission standards and install and configure according to the manufacturer specifications (60.4211(c)).

Use diesel fuel that meets requirements of 40 CFR 80.510(b) for nonroad diesel fuel.

Purchase only compliant diesel fuel.

Emergency Engine - Kohler

400REOZJC

NSPS IIII: 40 CFR

60.4211(f) na

Operate according to the requirements in (f)(1) through (3) to be considered an emergency stationary ICE.

Monitor hours of operation in emergency and non-emergency service and the reason the engine was in operation during that time.

Emergency Engine - Kohler

400REOZJC

NSPS IIII: 40 CFR

60.4211(a) na

Operate and maintain the stationary CI internal combustion engine and control device according to the manufacturer's emission-related written instructions.

Change only those emission-related settings that are permitted by the manufacturer. Meet the requirements of 40 CFR parts 89, 94, and/or 1068, as they apply to you.

Maintain records of maintenance conducted on the engine consistent with the operating requirements of 40 CFR 60.4211(a).

Emergency Engine - Kohler

400REOZJC

NSPS IIII: 40 CFR

60.4205(b) na na

Purchase engine certified to the emission standards and install and configure according to the manufacturer specifications (60.4211(c)).

Emergency Engine - Kohler

400REOZJC

NSPS IIII: 40 CFR

60.4207(b) na

43 Emergency Engine - Kohler 400REOZJC na NSPS IIII: 40 CFR 60.4209(a) Operating Hours Install a non-resettable hour meter prior to startup of the engine.

Section V.2: Monitoring Requirements

Emission Unit #

Emission Unit Description Pollutant Applicable Regulation or Requirement Parameter Monitored Description of Monitoring

43 Emergency Engine - Kohler 400REOZJC na NSPS IIII: 40 CFR 60.4211(a) Maintenance Records Maintain records of maintenance conducted on the engine consistent with the operating requirements of 40 CFR 60.4211(a).

43 Emergency Engine - Kohler 400REOZJC na NSPS IIII: 40 CFR 60.4214(b) Operating Hours

Maintain records of the operation of the engine in emergency and non-emergency service that are recorded through the non-resettable hour meter. The owner must record the time of operation of the engine and the reason the engine was in operation during that time.

Section V.3: Recordkeeping Requirements

Emission Unit #

Emission Unit Description Pollutant Applicable Regulation or

Requirement Parameter Recorded Description of Recordkeeping

Kohler 400REOZJC na na na na

Section V.4: Reporting Requirements

Emission Unit #

Emission Unit Description Pollutant Applicable Regulation or

Requirement Parameter Reported Description of Reporting

Kohler 400REOZJC na na na na

Section V.5: Testing Requirements

Emission Unit #

Emission Unit Description Pollutant Applicable Regulation or

Requirement Parameter Tested Description of Testing

Section V.6: Notes, Comments, and Explanations

ATTACHMENT 2

Calculations for the Emergency Generator Engine and the Natural Gas-Fired Boilers/Hot Water Heaters

Lexington VAMC-Leestown Road Air Emissions Calculations

2.1.1 Source Classification Code

SCC: 20200102

SCC Description:

SCC Units:

2.1.2 Engine Power and Fuel Consumption Data

Mechanical Power in bhp (100% load, standby): 617 bhp 460 bkW Generator Output in kW (100% load, standby): 400 kW Specific Fuel Consumption Rate in Mgal/hr: 0.031 Mgal/hr 31 gph Maximum Presumptive Annual Operating Hours: 500 hrs Typical Heat Content of Diesel Fuel (HHV): 137 MMBtu/Mgal

2.1.3 Emission Calculation Methodology and Emission Factors

2.1.3.1 NOX

Emission factor for NOX: 3.310 g/kW-hr Manufacturer Emissions Data Sheet NOX emission factor in terms of SCC units: 109.70 lb/Mgal

2.1.3.2 VOC

Emission factor for VOC: 0.110 g/kW-hr Manufacturer Emissions Data Sheet VOC emission factor in terms of SCC units: 3.65 lb/Mgal

2.1.3.3 CO

Emission factor for CO: 0.600 g/kW-hr Manufacturer Emissions Data Sheet CO emission factor in terms of SCC units: 19.88 lb/Mgal

2.1.3.4 PM/PM10/PM2.5

Emission factor for PM/PM10/PM2.5: 0.100 g/kW-hr Manufacturer Emissions Data Sheet PM/PM10/PM2.5 emission factor in terms of SCC units: 3.31 lb/Mgal

Internal Combustion Engines, Industrial (2-02), Distillate Oil (Diesel) (2-02-001), Reciprocating (2-02-001-02)

= 3.310 g/kW-hr * 460 bkW / 0.0306 Mgal/hr * 0.0022046 lb/g

= 0.110 g/kW-hr * 460 bkW / 0.0306 Mgal/hr * 0.0022046 lb/g

One (1) diesel-fired emergency generator engine will be installed to support Buildings 204 & 205.

= 0.600 g/kW-hr * 460 bkW / 0.0306 Mgal/hr * 0.0022046 lb/g

= 0.100 g/kW-hr * 460 bkW / 0.0306 Mgal/hr * 0.0022046 lb/g

2.1. Generator Engine

Pertinent data on engine power and fuel usage pulled from the technical data sheet for the Kohler 600REOZVB generator engine. Typical heating value of diesel fuel was taken from Appendix A in AP-42.

Emissions for this engine are tied to the SCC code for diesel fueled engines listed below.

1000 Gallons Distillate

Emission factors for NOX, HC, CO, and PM are based on the manufacturer emissions data sheet. Conservatively over-estimating VOC emissions by assuming HC is equal to VOC and over-estimating PM by assuming PM is equal to PM10/PM2.5. The emission factor for SO2 is based on sulfur content of the fuel and the equation found in Table 3.4-1 in AP-42 Chapter 3.4 for Large Stationary Diesel Engines.

2.1.3.5 SO2

AP42 Factor for SO2 based on sulfur content: 1.01 S lb/MMBtu

Sulfur Content: 0.0015 %

SO2 emission factor (lb/MMBtu): 1.52E-03 lb/MMBtu = 1.01 EF x 0.0015%, sulfur SO2 emission factor in terms of SCC units: 0.2076 lb/Mgal

2.1.3.6 HAP Emission Estimates

Pollutant CAS # HAP?

Emission Factor

(lb/MMBtu)

Emission Factor

(lb/hp-hr)

Emission Factor

(lb/Mgal) Emission Factor Basis Benzene 71-43-2 Y 7.76E-04 5.27E-06 0.11 AP-42 Table 3.4-4 Toluene 108-88-3 Y 2.81E-04 1.91E-06 0.038 AP-42 Table 3.4-4 Xylene 1330-20-7 Y 1.93E-04 1.31E-06 0.026 AP-42 Table 3.4-4

2.1.3.7 GHG Emission Factors

Global Warming Potentials of GHGs per 40 CFR 98 Subpart A, Table A-1.

CO2 1

CH4 25

N2O 298

Pollutant

Emission Factor

(kg/MMBtu)

Equivalent Factor

(lb/Mgal) CO2e 73.96 22,338 40 CFR 98, Subpart C, Table C-1 CH4 3.00E-03 0.91 40 CFR 98, Subpart C, Table C-2 N2O 6.00E-04 0.18 40 CFR 98, Subpart C, Table C-2 CO2e 74.21 22,415

To take into account the lower sulfur content of the diesel fuel burned, for purposes of representing SO2 emissions from the engine, the factor in AP42 Table 3.4-1 (Large Stationary Diesel Engines, 10/1996 edition) is used as shown below. This factor expresses SO2 as a function of sulfur content. As required under NSPS Subpart IIII, the ultra low sulfur diesel (ULSD) must be used in the new emergency generator engine.

Based on maximum sulfur content in ULSD of 15 ppm

AP-42 Table 3.4-1 (S is sulfur content in %)

Emission factors for organic HAP compounds expected to be emitted are based on emission factors in AP-42 Table 3.4- 3 (10/96 Edition). Emission factors are converted from lb/MMBtu as provided in AP-42 to lb/Mgal as applicable to the SCC designation.

CO2, CH4 and N2O emissions for diesel fuel combustion are estimated using the Distillate Fuel Oil No. 2 emission factors published in 40 CFR 98, Subpart C, Table C-1 & 2. CO2e emissions for diesel fuel combustion are estimated using the global warming potentials published in 40 CFR 98, Subpart A, Table A-1.

= 1.52E-03 lb/MMBtu * 137 MMBtu/Mgal

2.1.4 Summary of Engine Potential Emissions

Pollutant

Emission Factor

(lb/Mgal) Basis

Hourly Emissions

(lb/hr)

Annual Emissions

(tpy) NOX 109.70 Manufacturer Emissions Data Sheet 3.36 0.84 CO 19.88 Manufacturer Emissions Data Sheet 0.61 0.15 VOC 3.65 Manufacturer Emissions Data Sheet 0.11 0.028 PM/PM10/PM2.5 3.31 Manufacturer Emissions Data Sheet 0.10 0.025 SO2 0.21 AP-42 Table 3.4-1 (S is sulfur content in %) 6.35E-03 1.59E-03 Benzene 0.11 AP-42 Table 3.4-4 3.25E-03 8.13E-04 Toluene 0.038 AP-42 Table 3.4-4 1.18E-03 2.95E-04 Xylene 0.026 AP-42 Table 3.4-4 8.09E-04 2.02E-04

CO2 22,338 40 CFR 98, Subpart C, Table C-1 683.55 170.89 CH4 0.91 40 CFR 98, Subpart C, Table C-2 2.77E-02 6.93E-03 N2O 0.18 40 CFR 98, Subpart C, Table C-2 5.55E-03 1.39E-03 CO2e 22,415 40 CFR 98, Subpart C 685.90 171.47

2.2.1 Source Classification Code

SCC: 10200603

SCC Description:

SCC Units:

2.2.2 Indirect Heat Exchanger Process Rate

Heat Content of Natural Gas (HHV): 1,020 Btu/scf AP-42 Appendix A

Capacity: 0.60 MMBtu/hr 5.88E-04 MMscf/hr

2.2.3 Emission Calculation Methodology and Emission Factors

2.2.3.1 NOx

Pollutant Value Units Emission Factor Basis NOx 9 ppmv Manufacturer specification at 3% O2 NO2 Molecular Weight 46 lb/lbmol Consistent with Method 19, assuming all NOx is NO2 Molar Volume Conversion 386 scf/lbmol Ideal gas law at 68 deg. F and 1 atm NOx Exhaust Concentration 1.07E-06 lb NOx/dscf

F-Factor 8,710 dscf/MMBtu

O2 Conc. For EF Correction 3 % Manufacturer specification, SCAQMD regulation NOx Heat Input Rate-Based

EF

0.011 lb/MMBtu

Calculated NOx Natural Gas Usage Rate-Based EF

11.13 lb/MMscf = 0.011 lb NO2/MMBtu x 1,020 MMBtu/MMscf

Remaining emission factors are based on emission factors in AP-42 Section 1.4 (07/98 Edition). Emission factors are in lb/MMscf as provided in AP-42 which corresponds to the applicable SCC designation.

The calculated NOx emission factor is based on emissions estimates provided in the manufacturer specifications converted

= 9 lbmol NOx/lbmol gas x 46 lb NO2/1 lbmol NO2 x 1 lbmol gas/386 scf gas

EPA Method 19 Table 19-2 F-Factor for Various Fuels dry F-factor for natural gas

= 1.07E-06 lb NO2/dscf x 8,710 dscf/MMBtu x 20.9% / (20.9% - 3%)

2.2. Natural Gas-fired Indirect Heat Exchangers

Three (3) natural gas-fired boilers will be installed 2 support Buildings 204 & 205.

Emissions for this indirect heat exchanger are tied to the SCC code for external combustion boilers listed below.

External Combustion Boilers, Industrial (1-02), Natural Gas (1-02-006), < 10 Million Btu/hr (1-02-006-03) Million Cubic Feet Natural

2.2.1 Summary of Potential Emissions

Pollutant1

Emission Factor

(lb/SCC)

Hourly Emissions

(lb/hr)

Annual Emissions

(tpy) Emission Factor Basis NOx 11.13 6.54E-03 0.029 F-15-047 Section D.3.

CO 84.00 0.049 0.216 AP-42 Table 1.4-1 CO2 120,000 70.59 309.18 AP-42 Table 1.4-2 Lead 0.0005 2.94E-07 1.29E-06 AP-42 Table 1.4-2 N2O 2.2 1.29E-03 5.67E-03 AP-42 Table 1.4-2 PM 7.6 4.47E-03 1.96E-02 AP-42 Table 1.4-2 PM10 7.6 4.47E-03 1.96E-02 AP-42 Table 1.4-2 PM2.5 7.6 4.47E-03 1.96E-02 AP-42 Table 1.4-2 SO2 0.6 3.53E-04 1.55E-03 AP-42 Table 1.4-2 Methane 2.3 1.35E-03 5.93E-03 AP-42 Table 1.4-2 VOC 5.5 3.24E-03 1.42E-02 AP-42 Table 1.4-2 Formaldehyde 0.075 4.41E-05 1.93E-04 AP-42 Table 1.4-3

1 Factors for PM10 and PM2.5 are conservatively assumed as the factor for PM.

2.3.1 Source Classification Code

SCC: 10200603

SCC Description:

SCC Units:

2.3.2 Indirect Heat Exchanger Process Rate

Heat Content of Natural Gas (HHV): 1,020 Btu/scf AP-42 Appendix A

Capacity: 0.50 MMBtu/hr 4.90E-04 MMscf/hr

2.3.3 Emission Calculation Methodology and Emission Factors

2.3.3.1 NOx

Pollutant Value Units Emission Factor Basis NOx 20 ppmv Manufacturer specification at 3% O2 NO2 Molecular Weight 46 lb/lbmol Consistent with Method 19, assuming all NOx is NO2 Molar Volume Conversion 386 scf/lbmol Ideal gas law at 68 deg. F and 1 atm NOx Exhaust Concentration 2.38E-06 lb NOx/dscf

F-Factor 8,710 dscf/MMBtu

O2 Conc. For EF Correction 3 % Manufacturer specification, SCAQMD regulation NOx Heat Input Rate-Based

EF

0.024 lb/MMBtu

NOx Natural Gas Usage Rate- Based EF

24.7 lb/MMscf = 0.024 lb NO2/MMBtu x 1,020 MMBtu/MMscf

2.3. Natural Gas-fired Hot Water Heaters

Three (3) natural gas-fired hot water heater will be installed to support Buildings 204 & 205 currently under construction.

Emissions for this indirect heat exchanger are tied to the SCC code for external combustion boilers listed below.

External Combustion Boilers, Industrial (1-02), Natural Gas (1-02-006), < 10 Million Btu/hr (1-02-006-03) Million Cubic Feet Natural

Remaining emission factors are based on emission factors in AP-42 Section 1.4 (07/98 Edition). Emission factors are in lb/MMscf as provided in AP-42 which corresponds to the applicable SCC designation.

= 20 lbmol NOx/lbmol gas x 46 lb NO2/1 lbmol NO2 x 1 lbmol gas/386 scf gas

EPA Method 19 Table 19-2 F-Factor for Various Fuels dry F-factor for natural gas

= 2.38E-06 lb NO2/dscf x 8,710 dscf/MMBtu x 20.9% / (20.9% - 3%)

The calculated NOx emission factor is based on emissions estimates provided in the manufacturer specifications converted to lb/MMscf, which corresponds to the applicable SCC designation.

2.3.1 Summary of Potential Emissions

Pollutant1

Emission Factor

(lb/SCC)

Hourly Emissions

(lb/hr)

Annual Emissions

(tpy) Emission Factor Basis NOX 24.7 1.21E-02 0.053 F-15-047 Section D.3.

CO 84.0 0.041 0.180 AP-42 Table 1.4-1 CO2 120,000 58.82 257.65 AP-42 Table 1.4-2 Lead 0.0005 2.45E-07 1.07E-06 AP-42 Table 1.4-2 N2O 2.2 1.08E-03 4.72E-03 AP-42 Table 1.4-2 PM 7.6 3.73E-03 1.63E-02 AP-42 Table 1.4-2 PM10 7.6 3.73E-03 1.63E-02 AP-42 Table 1.4-2 PM2.5 7.6 3.73E-03 1.63E-02 AP-42 Table 1.4-2 SO2 0.6 2.94E-04 1.29E-03 AP-42 Table 1.4-2 Methane 2.3 1.13E-03 4.94E-03 AP-42 Table 1.4-2 VOC 5.5 2.70E-03 1.18E-02 AP-42 Table 1.4-2 Formaldehyde 0.075 3.68E-05 1.61E-04 AP-42 Table 1.4-3

2.4.1 Source Classification Code

SCC: 10200603

SCC Description:

SCC Units:

2.4.2 Indirect Heat Exchanger Process Rate

Heat Content of Natural Gas (HHV): 1,020 Btu/scf AP-42 Appendix A

Capacity: 0.75 MMBtu/hr 7.35E-04 MMscf/hr

2.4.3 Emission Calculation Methodology and Emission Factors

2.4.3.1 NOx

Pollutant Value Units Emission Factor Basis NOx 9 ppmv Manufacturer specification at 3% O2 NO2 Molecular Weight 46 lb/lbmol Consistent with Method 19, assuming all NOx is NO2 Molar Volume Conversion 386 scf/lbmol Ideal gas law at 68 deg. F and 1 atm NOx Exhaust Concentration 1.07E-06 lb NOx/dscf

F-Factor 8,710 dscf/MMBtu

O2 Conc. For EF Correction 3 % Manufacturer specification NOx Heat Input Rate-Based

EF

0.011 lb/MMBtu

Calculated NOx Natural Gas Usage Rate-Based EF

11.13 lb/MMscf = 0.011 lb NO2/MMBtu x 1,020 MMBtu/MMscf

2.4. Natural Gas-fired Indirect Heat Exchangers

Two (2) natural gas-fired boilers will be installed to support the Building 39 Renovation.

Emissions for this indirect heat exchanger are tied to the SCC code for external combustion boilers listed below.

External Combustion Boilers, Industrial (1-02), Natural Gas (1-02-006), < 10 Million Btu/hr (1-02-006-03) Million Cubic Feet Natural

Remaining emission factors are based on emission factors in AP-42 Section 1.4 (07/98 Edition). Emission factors are in lb/MMscf as provided in AP-42 which corresponds to the applicable SCC designation.

= 9 lbmol NOx/lbmol gas x 46 lb NO2/1 lbmol NO2 x 1 lbmol gas/386 scf gas

EPA Method 19 Table 19-2 F-Factor for Various Fuels dry F-factor for natural gas

= 1.07E-06 lb NO2/dscf x 8,710 dscf/MMBtu x 20.9% / (20.9% - 3%)

The calculated NOx emission factor is based on emissions estimates provided in the manufacturer specifications converted to lb/MMscf, which corresponds to the applicable SCC designation.

2.4.1 Summary of Potential Emissions

Pollutant1

Emission Factor

(lb/SCC)

Hourly Emissions

(lb/hr)

Annual Emissions

(tpy) Emission Factor Basis NOx 11.13 8.18E-03 0.036 AP-42 Table 1.4-1 CO 84.00 0.062 0.271 AP-42 Table 1.4-1 CO2 120,000 88.24 386.47 AP-42 Table 1.4-2 Lead 0.0005 3.68E-07 1.61E-06 AP-42 Table 1.4-2 N2O 2.2 1.62E-03 7.09E-03 AP-42 Table 1.4-2 PM 7.6 5.59E-03 2.45E-02 AP-42 Table 1.4-2 PM10 7.6 5.59E-03 2.45E-02 AP-42 Table 1.4-2 PM2.5 7.6 5.59E-03 2.45E-02 AP-42 Table 1.4-2 SO2 0.6 4.41E-04 1.93E-03 AP-42 Table 1.4-2 Methane 2.3 1.69E-03 7.41E-03 AP-42 Table 1.4-2 VOC 5.5 4.04E-03 1.77E-02 AP-42 Table 1.4-2 Formaldehyde 0.075 5.51E-05 2.42E-04 AP-42 Table 1.4-3

2.5.1 Source Classification Code

SCC: 10200603

SCC Description:

SCC Units:

2.5.2 Indirect Heat Exchanger Process Rate

Heat Content of Natural Gas (HHV): 1,020 Btu/scf AP-42 Appendix A

Capacity: 0.15 MMBtu/hr 1.47E-04 MMscf/hr

2.5.3 Emission Calculation Methodology and Emission Factors

2.5.3.1 NOx

Pollutant Value Units Emission Factor Basis NOx 20 ppmv Manufacturer specification at 3% O2 NO2 Molecular Weight 46 lb/lbmol Consistent with Method 19, assuming all NOx is NO2 Molar Volume Conversion 386 scf/lbmol Ideal gas law at 68 deg. F and 1 atm NOx Exhaust Concentration 2.38E-06 lb NOx/dscf

F-Factor 8,710 dscf/MMBtu

O2 Conc. For EF Correction 3 % Manufacturer specification NOx Heat Input Rate-Based

EF

0.024 lb/MMBtu

NOx Natural Gas Usage Rate- Based EF

24.72 lb/MMscf = 0.024 lb NO2/MMBtu x 1,020 MMBtu/MMscf

Remaining emission factors are based on emission factors in AP-42 Section 1.4 (07/98 Edition). Emission factors are in lb/MMscf as provided in AP-42 which corresponds to the applicable SCC designation.

= 20 lbmol NOx/lbmol gas x 46 lb NO2/1 lbmol NO2 x 1 lbmol gas/386 scf gas

EPA Method 19 Table 19-2 F-Factor for Various Fuels dry F-factor for natural gas

= 2.38E-06 lb NO2/dscf x 8,710 dscf/MMBtu x 20.9% / (20.9% - 3%)

The calculated NOx emission factor is based on emissions estimates provided in the manufacturer specifications converted to lb/MMscf, which corresponds to the applicable SCC designation.

2.5. Natural Gas-fired Hot Water Heaters

One (1) natural gas-fired hot water heater will be installed to support the Building 39 Renovation.

Emissions for this indirect heat exchanger are tied to the SCC code for external combustion boilers listed below.

External Combustion Boilers, Industrial (1-02), Natural Gas (1-02-006), < 10 Million Btu/hr (1-02-006-03) Million Cubic Feet Natural

2.5.1 Summary of Potential Emissions

Pollutant1

Emission Factor

(lb/SCC)

Hourly Emissions

(lb/hr)

Annual Emissions

(tpy) Emission Factor Basis NOX 24.72 3.64E-03 0.016 AP-42 Table 1.4-1 CO 84.00 0.012 0.054 AP-42 Table 1.4-1 CO2 120,000 17.65 77.29 AP-42 Table 1.4-2 Lead 0.0005 7.35E-08 3.22E-07 AP-42 Table 1.4-2 N2O 2.2 3.24E-04 1.42E-03 AP-42 Table 1.4-2 PM 7.6 1.12E-03 4.90E-03 AP-42 Table 1.4-2 PM10 7.6 1.12E-03 4.90E-03 AP-42 Table 1.4-2 PM2.5 7.6 1.12E-03 4.90E-03 AP-42 Table 1.4-2 SO2 0.6 8.82E-05 3.86E-04 AP-42 Table 1.4-2 Methane 2.3 3.38E-04 1.48E-03 AP-42 Table 1.4-2 VOC 5.5 8.09E-04 3.54E-03 AP-42 Table 1.4-2 Formaldehyde 0.075 1.10E-05 4.83E-05 AP-42 Table 1.4-3

ATTACHMENT 3

Emission Data Sheet and Certificate of Conformity

Model: John Deere, 6135HF485S Bore: 132mm (5.2 in.)

Nameplate BHP @ 1800 RPM: 617 Stroke: 165mm (6.5 in.)

Type: 4-Cycle, 6 Cylinder, Inline Displacement: 13.5 L (824 cu. in.)

Aspiration: Turbocharged, Charge Air-Cooled

Compression Ratio 16.0:1 EPA Family: MJDXL13.5103

EPA Certificate: MJDXL13.5103-007

PERFORMANCE DATA:

1/4

Standby 1/2

Standby 3/4

Standby Full

Standby Engine bkW @ Stated Load 115 230 345 460

Fuel Consumption (g/kWh) 237 212 206 209

Exhaust Gas Flow (m3/min) 81

Exhaust Temperature (°C) 471

EXHAUST EMISSION DATA:

HC (Total Unburned Hydrocarbons)

NOx (Oxides of Nitrogen as NO2)

CO (Carbon Monoxide)

PM (Particulate Matter)

Data and specifications subject to change without notice.

TEST METHODS AND CONDITIONS

The emission data listed is measured from a laboratory test engine according to the test procedures of 40 CFR 89 or 40 CFR 1039, as applicable. The test engine is intended to represent nominal production hardware, and there is no guarantee that every production engine will have identical test results. The family parent data represents multiple ratings and this data may have been collected at a different engine speed and load. Emission results may vary due to engine manufacturing tolerances, engine operating conditions, fuels used, alternate test methods, or other conditions.

EPA D2 Cycle 5-mode weighted

0.11

3.31

0.6

0.10

Values are in g/kWh unless otherwise noted

Table 2

400REOZJC

60 HZ. DIESEL INDUSTRIAL GENERATOR SET

EMISSION DATA SHEET

ENGINE INFORMATION

Table 1

ATTACHMENT 4

Process Flow Diagram for Emergency Generator Engine

Figure 1

1717 Dixie Hwy, Ste. 900 Covington, KY 41011

Figure 1

Legend

Emissions Flow Raw Material Flow

Diesel Fuel 400 kW Emergency Generator with 617 bHP stationary engine

Fuel Combustion