Attachment 12 - Drawings 589-501 91-115.pdf
PDF 12 MB Posted
- Solicitation number
- 36C77624B0031
About this file
This document appears to be Attachment 12 - Drawings 589-501 91-115.pdf, which contains architectural drawings related to the federal contract opportunity for the 589-501 Construction Outpatient Mental Health Addition (VA-24-00072549).
The drawings provide detailed specifications and schematics for the construction of an outpatient mental health addition facility for the Department of Veterans Affairs Technology Acquisition Center Austin. The drawings cover various construction elements such as site plans, floor plans, elevations, sections, and details. This attachment would be provided to offerors to support the development of their proposals in response to the solicitation.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B
CR
M
M M
DH DH H
M H
E E
M MS SS
M
S S
E E
S
S
S
DEMOLITION PLAN NOTES:
1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE ELECTRICAL
DEMOLITION WORK. THE ELECTRICAL CONTRACTOR SHALL DISCONNECT
ELECTRICAL SERVICES TO ALL EQUIPMENT BEING REMOVED, SEE
MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION TO RETAIN
REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES, LIGHTS, PANELS,
ETC. NOT BEING USED IN THE FINISHED WORK. COORDINATE WITH OWNER
PRIOR TO STARTING DEMOLITION. PROPERLY AND LEGALLY DISPOSE OF
ALL EQUIPMENT AND MATERIALS BEING REMOVED.
2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND
CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING
CONDUIT IN WALL OR FLOOR WHERE CUT.
3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE SHELVING,
CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND MAY REQUIRE
REMOVAL.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING ALL
OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF EQUIPMENT,
RACEWAY SYSTEMS, OUTLET BOXES, ETC.
5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED, THE
CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT OF SUPPLY.
WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED TO MAINTAIN
CONTINUITY OF THE CIRCUIT OR OPERATION OF THE SYSTEM.
6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL BE
REMOVED, UNLESS NOTED OTHERWISE.
7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE BEING
REMOVED FROM FLUSH-MOUNTED OUTLET BOXES IN EXISTING WALLS TO
REMAIN.
8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
BEGINNING WORK.
9. EXISTING NURSE CALL DEVICES TO BE REUSED. REMOVE DEVICES AS
INDICATED ON PLAN. PRESERVE AND PROTECT DURING CONSTRUCTION AS
REQUIRED FOR REINSTALLATION. SEE SYSTEMS PLANS FOR FURTHER
INFORMATION.
50A
FAAP
EXISTING DATA RACK
& FIBER ENCLOSURE
TO REMAIN.
EXISTING
PHONE BACK
BOARD
L1C-2
L1C-1
D
D
DD
D
D
D D
D D D
DD
D
D
D D
D
DD
D D D D D D
D
D
D D
D D
D D
D D
D D
D D
D D
D D
D
FAN
FAN
D D
D
D
D D
D
D
D
D
D
D
D D DD
D
D D
D
D
D D
D
D
D
D
D
D
DD
D
D
D
D
D2
D3
/A ED111.1
/A ED112
D8
D9
REMOVE EXISTING
POWER-POLE AND
ASSOCIATED CABLING
BACK TO POINT OF
SUPPLY. TYPICAL OF 3.
K.3
L.3
16 17.2
30 32 33
N
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 pec1.com
Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
ISSUED FOR BID
/2
/2
:2
:0
P
M A u to d e s k D o c s
/1
.2
A tr ia x
T o p e k a
V A
M e n ta l H e a lt h C lin ic
(M o d
-0
E
L E
C R
.r v t
ED111
ELECTRICAL DEMOLITION - FIRST
FLOOR
Outpatient Mental Health Clinic
Colmery-O'Neil VAMC Topeka, KS
03/29/2024 DDC RWL
KEYED NOTES:
D2 EXISTING I.T. CLOSET AND ASSOCIATED EQUIPMENT TO REMAIN
OPERATIONAL DURING PROJECT. EXISTING TELECOMMUNICATIONS
BACKBONE CABLING SHALL REMAIN. PRESERVE AND PROTECT DURING
CONSTRUCTION AS REQUIRED. REMOVE EXISTING HORIZONTAL
CABLING BACK TO I.T. CLOSET FROM DEVICES REMOVED DURING
DEMOLITION AS REQUIRED. COORDINATE ROOM ACCESS WITH OWNER.
D3 EXISTING PANELBOARDS TO REMAIN FOR REUSE. REMOVE ALL
EXISTING BRANCH CIRCUIT WIRING AS REQUIRED.
D8 REMOVE EXISTING FIRE ALARM ANNUNCIATOR PANEL AND ALL
ASSOCIATED CABLING BACK TO FIRE ALARM CONTROL PANEL LOCATED
IN BASEMENT AS REQUIRED.
D9 EXISTING CARD READER AND ASSOCIATED POWER CONNECTION TO
EXISTING DOOR TO REMAIN. RECONNECT COMPONENTS TO NEW DOOR
AS REQUIRED. COORDINATE ALL REQUIREMENTS WITH DOOR
HARDWARE PROVIDER.
0 8' 16'4'1/8" = 1'-0"1
ELECTRICAL DEMOLITION PLAN - 1ST FLOOR - ADDITION
N
Revisions: Date:
03/27/2024
GROUND ROD. TYPICAL.
TEST WELL. TYPICAL.
12"H LIGHTNING AIR TERMINAL, TYPICAL.
PROVIDE (4) LIGHTNING AIR TERMINALS
ON SCREEN WALL. LOCATE IN CORNERS
AS INDICATED.
CONNECT TO BUILDING
EXISTING LIGHTNING
PROTECTION SYSTEM
AS REQUIRED.
L.5
M
P
P.5
O.5
N
O
L
K(E)
J(E)
M.9
L.9
M.3
A
B
K.3
L.3
2 2.8
3 4
5.8
8 10
1112 13
16 17.2 29.1
30 32 33
34 354.5
7 9 9.8 15 17
31 33.1
GROUNDING PLAN NOTES:
1. GROUND RODS FOR THIS PROJECT SHALL BE 3/4" x 10'-0"COPPER CLAD
STEEL UNLESS OTHERWISE NOTED.
2. MULTIPLE ROD GROUNDING SYSTEMS SHALL BE CONNECTED TOGETHER
WITH #4/0 AWG BARE STRANDED COPPER CABLE. ALL CONNECTIONS
SHALL BE EXOTHERMIC WELDED.
3. PROVIDE 1" PVC CONDUIT SLEEVES FOR GROUNDING CABLE
PENETRATIONS THROUGH CONCRETE FLOORS AND/OR WALLS.
4. CONNECTING SURFACES OF STEEL AND CABLES SHALL BE THOROUGHLY
CLEANED AND PREPARED PRIOR TO COMPLETING THE CONNECTION.
5. LOCATIONS OF GROUND RODS AND GROUNDING CABLE SHOWN ARE
APPROXIMATE, UNLESS LOCATED BY DIMENSIONS. FIELD VERIFY EXACT
LOCATIONS TO SUIT JOB SITE CONDITIONS AND TO AVOID OBSTRUCTIONS.
BRANCH GROUNDING CABLE CONNECTION TO MAIN GROUNDING CABLE
SHALL BE TEE TAP. INSTALL UNDERGROUND GROUNDING CABLE 18"
MINIMUM BELOW GRADE.
6. SIZE MAIN GROUNDING CABLE AS INDICATED. USE #4/0 AWG STRANDED
COPPER CABLE FOR ALL GROUND CONDUCTORS UNLESS OTHERWISE
NOTED. LOCATE EXPOSED GROUNDING CABLE TO AVOID MECHANICAL
DAMAGE, ADEQUATELY SUPPORTED WITH NONFERROUS CABLE CLAMPS
ON MINIMUM 4'-0" CENTERS. NO CHANGES SHALL BE MADE WITHOUT PRIOR
WRITTEN APPROVAL OF THE ENGINEER.
N
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 pec1.com
Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
ISSUED FOR BID
/2
/2
:2
:0
P
M A u to d e s k D o c s
/1
.2
A tr ia x
T o p e k a
V A
M e n ta l H e a lt h C lin ic
(M o d
-0
E
L E
C R
.r v t
EG301
LIGHTNING PROTECTION ROOF PLAN Outpatient Mental Health Clinic
Colmery-O'Neil VAMC Topeka, KS
03/29/2024 DDC RWL 133 170
0 16' 32'8'1/16" = 1'-0"A
LIGHTNING PROTECTION PLAN - ROOF
N
12. METAL BODIES OF INDUCTANCE LOCATED ABOUT THE ROOF,
SUCH AS: METAL FLASHING, GRAVEL STOPS, ROOF DRAINS,
SOIL POPE VENTS, INSULATION VENTS, LOUVERS AND DOOR
FRAME SITUATED WITHIN 6'-0" OF A LIGHTNING CONDUCTOR
OR BONDED METAL BODY SHALL BE INTERCONNECTED TO
THE LIGHTNING CONDUCTOR SYSTEM.
13. CONDUCTORS SHALL INTERCONNECT ALL AIR TERMINALS
AND SHALL FORM A TWO-WAY PATH FROM EACH AIR
TERMINAL HORIZONTALLY OR DOWNWARD TO CONNECTIONS
WITH GROUND TERMINALS.
14. BARE COPPER LIGHTNING PROTECTION MATERIALS SHALL
NOT BE INSTALLED ON ALUMINUM ROOF OR SIDING OR
OTHER ALUMINUM ROOF OR SIDING OR INSTALLED ON
COPPER ROOFING OR COPPER SIDING OR OTHER COPPER
SURFACES.
15. THE LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED
IN A NEAT AND INCONSPICUOUS MANNER SO THAT ALL
COMPONENTS WILL BLEND IN WITH THE APPEARANCE OF
THE BUILDING. DOWNLEADS SHALL BE RUN INTERNALLY
WHERE POSSIBLE. ROUTING PATHS MUST MEET APPROVAL
OF ENGINEER AND OWNER PRIOR TO ROUGH-IN.
16. THE DESIGN LAYOUT AND INSTALLATION DETAILS SHOWN
HEREON SHALL MEET THE REQUIREMENTS OF
UNDERWRITERS' LABORATORIES STANDARD 96A FOR
MASTER LABELED LIGHTNING PROTECTION SYSTEMS, THE
ACTUAL MASTER LABEL WILL BE DELIVERED UPON
COMPLETION OF INSTALLATION.
17. THE LIGHTNING PROTECTION INSTALLATION SHALL COMPLY
IN ALL RESPECTS TO LIGHTNING PROTECTION INSTITUTE
STANDARD 175. THE INSTALLATION SHALL BE MADE BY OR
UNDER THE SUPERVISION OF AN L.P.I. CERTIFIED MASTER
INSTALLER. THE COMPLETED INSTALLATION WILL RECEIVE
SYSTEM CERTIFICATION SUBMITTAL FORM LPI 176.
18. FIELD VERIFY EXISTING LIGHTNING PROTECTION SYSTEM
INSTALLATION AND LOCATIONS OF CONDUCTORS, AIR
TERMINALS, AND GROUND RODS.
1. LOCATE AIR TERMINALS AS SHOWN. TAKE CARE TO INSURE
THAT ALL POINTS ARE WITHIN 2'-0" OF OUTSIDE BUILDING
EDGE, OUTSIDE CORNERS, AND RIDGE ENDS, AND THAT
MAXIMUM SPACING DOES NOT EXCEED 20'-0", AND THAT
MINIMUM PROJECTION ABOVE OBJECT PROTECTED IS 10"
(POINTS PROJECTION 24" MAY BE SPACED AT 25" MAXIMUM).
2. MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN
CONDUCTOR.
3. ALL CONDUCTOR BENDS SHALL HAVE AT LEAST AN 8" RADIUS
AND SHALL FORM A FINAL INCLUDED ANGLE OF NOT LESS THAN
90 DEGREES.
4. ATTACH ALL EXPOSED ROOF, DOWN LEAD AND BONDING
CABLES AT 3'-0" ON CENTER MAXIMUM. VERIFY COMPATABILITY
OR ADHESIVE ON MEMBRANE ROOF APPLICATIONS PRIOR TO
INSTALLATION.
5. GROUND ELECTRODES SHALL BE INSTALLED AS SHOWN, BUT IN
NO INSTANCE SHALL THEY BE LESS THAN 1'-0" BELOW GRADE
AND 2'-0" FROM FOUNDATION WALL. DRIVEN GROUND RODS
SHALL PENETRATE THE EARTH AT LEAST 10'-0".
6. BOND TO WATER SERVICE AND OTHER PIPING SYSTEMS AS
SHOWN AND AS REQUIRED BY CODES.
7. INTERCONNECT LIGHTNING PROTECTION GROUND TO
ELECTRIC,TELEPHONE, AND OTHER BUILDING GROUND
SYSTEMS AS SHOWN OR AS REQUIRED BY CODE.
8. SYSTEM SHALL BE INSTALLED AS SHOWN TO INSURE PROPER
CODE COMPLIANCE AND SYSTEM CERTIFICATION.ANY MAJOR
VARIANCE SHALL REQUIRE RESUBMITTAL AND NEW
APPROVAL.
9. AS-BUILT DRAWINGS SHALL BE SUBMITTED IN ACCORDANCE
WITH CERTIFICATION PROCEDURES.
10. ALL MATERIALS SHALL BE UNDERWRITERS LABORATORIES
APPROVED WITH LABELS OM CONDUCTORS AT 10'-0"
INTERVALS AND LABELS ON ALL AIR TERMINALS.
11. All MATERIALS SHOWN SHALL BE EQUAL TO THOSE AS
MANUFACTURED BY THOMPSON LIGHTNING PROTECTION INC.
LIGHTNING PROTECTION GENERAL NOTES
COPPER CABLE
COPPER SECONDARY
BONDING WIRE.
CAST BRONZE PARALLEL
COMBINATION CABLE SPLICER
CAST BRONZE PARALLEL
COMBINATION CABLE SPLICER.
COPPER DOWNLEAD CABLE. COURSE CABLE
EXPOSED DOWN EXTERIOR WALL CONSTRUCTION
TO BELOW GRADE.
COPPER LOOP TYPE MASONRY CABLE ANCHOR.
FURNISHED WITH 1/4" X 1-1/4" MASONARY DRIVE
ANCHOR. FASTEN CABLE 3'-0" MAX.
COPPER LOOP TYPE CABLE FASTENER.
SECURE WITH #1 X 1" STAINLESS STEEL
SCREW. FASTEN CABLE 3'-0" MAX.
COPPER CABLE. COURSE CABLE TO THE
NEAREST MAIN CONDUCTOR AND CLOSE
CIRCUIT WHERE REQUIRED WITH SPLICER.
3/8" CAST BRONZE ADHESIVE TYPE POINT BASE.
SECURE IN PLACE WITH RUBBER ADHESIVE
COMPOUND.
COPPER CABLE. COURSE CABLE AS THE
MAIN CONDUCTOR AND CLOSE CIRCUIT
WHERE REQUIRED WITH SPLICER.
COPPER ADHESIVE TYPE CABLE HOLDER.
SECURE IN PLACE WITH RUBBER ADHESIVE
COMPOUND. FASTEN CABLE 3'-0" O.C. MAX.
3/8" x 10" BARE COPPER POINT.
REFER TO GENERAL NOTES FOR LOCATION.
COPPER LOOP TYPE CABLE FASTENER.
SECURE WITH #10 X 1" STAINLESS STEEL
TEK SCREW. FASTEN CABLE 3'-0" O.C. MAX.
3/8" CAST BRONZE POINT BASE.
SECURE WITH (2) #10 X 5/8"
STAINLESS STEEL TEK SCREWS.
COPPER CABLE. COURSE CABLE AS THE
MAIN CONDUCTOR AND CLOSE CIRCUIT
WHERE REQUIRED WITH SPLICER.
3/8" x 12" BARE COPPER POINT TO EXTEND
A MINIMUM OF 10" ABOVE PARAPET.
REFER TO GENERAL NOTES FOR LOCATION.
3/8" STRAP TYPE TINNED COPPER POINT BASE.
SECURE WITH FOUR #10 x 1" STAINLESS STEEL
SCREWS.
3/8" x 24" LEADED COPPER POINT
TO EXTEND A MINIMUM OF 10"
ABOVE TOP OF EQUIPMENT.
REFER TO GENERAL NOTES FOR LOCATION.
3/4" PVC CONDUIT. COURSE CONDUIT CONCEALED
WITHIN COLUMN/WALL CONSTRUCTION.
SEAL END PERMANENTLY WATER TIGHT WITH DUCT SEAL.
EXIT WITHIN CEILING OR AT EAVE.
CAST BRONZE CABLE TO
GROUND ROD CLAMP.
COPPER CLAD STEEL GROUND ROD
REFER GENERAL NOTES FOR
LOCATION
APPROX.
FINISHED
GRADE
CAST BRONZE REBAR BONDING CLAMP
INSTALLING CONTRACTOR TO FIELD
ADJUSTAND INSURE A SECURE BOND.
COPPER CABLE. COURSE CABLE CONCEALED WITHIN
CONDUIT UP TO EAVE OR TO CEILING SPACE.
COPPER CABLE. COURSE CABLE BELOW GRADE
TO GROUND ROD CONNECTION. REFER TO
GENERAL NOTES FOR LOCATION.
CAST BRONZE PARALLEL
COMBINATION CABLE
SPLICER.
COPPER CABLE. COURSE CABLE TO THE
NEAREST MAIN CONDUCTOR AND CLOSE
CIRCUIT WHERE REQUIRED WITH SPLICER.
CAST BRONZE CABLE TO
STEEL BONDING CLAMP.
COPPER TO COPPER THRU-ROOF CABLE CONNECTING
ASSEMBLY. FURNISHED WITH 1/2"∅ x 12" ALLTHREAD
ROD.
SEAL PENETRATION PERMANENTLY WATER TIGHT WITH
NEOPRENE WASHER FURNISHED WITH ASSEMBLY.
COPPER DOWNLEAD CABLE. COURSE CABLE IN CONDUIT,
CONCEALED WITHIN COLUMN AND/OR WALL CONSTRUCTION;
EXIT AT LOWER ROOF OR EXIT BELOW GRADE.
3/4"PVC CONDUIT. FURNISHED AND INSTALLED BY THE
ELECTRICAL CONTRACTOR. COURSE CONDUIT CONCEALED
WITHIN COLUMN AND/OR WALL CONSTRUCTION.
SEAL ENDS OF CONDUIT PERMANENTLY WATER TIGHT
WITH DUCT SEAL. EXIT AT LOWER ROOF OR EXIT BELOW
GRADE.
LESS THAN 90°
REFER TO GENERAL NOTE "4"
NOT ACCEPTABLE
ACCEPTABLE
SHEET ___
NOT ACCEPTABLE
LESS THAN 8" RADIUS
90° MIN.
LESS THAN
8" RADIUS
8" RADIUS (MIN.)
90°
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 pec1.com
Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
ISSUED FOR BID
/2
/2
:2
:0
P
M A u to d e s k D o c s
/1
.2
A tr ia x
T o p e k a
V A
M e n ta l H e a lt h C lin ic
(M o d
-0
E
L E
C R
.r v t
EG501
LIGHTNING PROTECTION DETAILS Outpatient Mental Health Clinic
Colmery-O'Neil VAMC Topeka, KS
03/29/2024 DDC RWL 134 170
N0 SCALE
TYPICAL CABLE SPLICERS
N0 SCALE
EXPOSED DOWNLEAD AT SCREENWALL
N0 SCALE
ADHESIVE AIR TERMINAL
N0 SCALE
PARAPET AIR TERMINAL
N0 SCALE
EQUIP. AIR TERMINAL
N0 SCALE
CONCEALED DOWNLEAD TO GROUNDING CONN.
N0 SCALE
THRU-ROOF CABLE CONN. AT STANDING SEAM METAL ROOF
N0 SCALE
TYPICAL CABLE BEND REQUIREMENTS
DN
M
M M
M M
M
M
M
M M M
M
M M M M M M
M M
M M
M
M M
M
M
M M
M M M MM M M M M
M M
M M
M M
M
1D1D1D
1D1D1D1D1D
1D 1D 1D
1D1D1D
1D 1D 1D 1D 1D
1D
1D
1D1D1D
1D 1D
D
1DM
M
M
D 1D 1D MM
M
M
M
M M
M
D
D
M
D
D
D
D
D
J
D
M
D
M
M
M
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS
AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.
ASSEMBLY NUMBERS.
4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH
THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE
FIRE BARRIER.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT
FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR
TO ROUGH-IN.
22.7
25.4
32.5 33.3
33.8
L.5
M
P
P.5
O.5
N.5
N
O
22.2
L
J.8
J
L (E)
K(E)
J(E)
K.8
M.9
L.9
M.3
21.1
A
B
K.3
L.3
2 2.8
3 4
5.8
8 10
1112 13
16 17.2 29.1 34 354.5
7 9 9.8 15 17 31 33.1
EL110
EL110
EL110
EL110
R
E1D:11 L5
R
X1 L6 A
E1D:11
L5
L6 X1
R
A
L6
X2 E1D:11
R
A
E1D:11
L5
L6
X1
R
N
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 pec1.com
Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
ISSUED FOR BID
/2
/2
:2
:1
P
M A u to d e s k D o c s
/1
.2
A tr ia x
T o p e k a
V A
M e n ta l H e a lt h C lin ic
(M o d
-0
E
L E
C R
.r v t
EL110
LIGHTING PLAN - FIRST FLOOR
OVERALL
Outpatient Mental Health Clinic
Colmery-O'Neil VAMC Topeka, KS
03/29/2024 DDC RWL
KEYED NOTES:
L5 ROUTE CIRCUIT VIA PHOTOCELL.
L6 CONNECT EXIT LIGHT TO EXISTING CORRIDOR EMERGENCY LIGHTING
CIRCUIT.
0 16' 32'8'1/16" = 1'-0"1
LIGHTING PLAN - 1ST FLOOR OVERALL
0 4' 8'2'1/4" = 1'-0"2 LIGHTING PLAN - Callout 1
0 4' 8'2'1/4" = 1'-0"3 LIGHTING PLAN - Callout 2
0 4' 8'2'1/4" = 1'-0"4 LIGHTING PLAN - Callout 3
0 4' 8'2'1/4" = 1'-0"5 LIGHTING PLAN - Callout 4
N
M M M
1D1D1D
1D1D1D1D1D
1D 1D 1D
1D1D1D
1D 1D 1D 1D 1D
1D
1D
1D1D1D
1D 1D
D
1DM
M
M
D 1D 1D MM
M
M
M
M M
M
D
D
M
D
D
D
D
D
J
D
M
D
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS
AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.
ASSEMBLY NUMBERS.
4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH
THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE
FIRE BARRIER.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT
FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR
TO ROUGH-IN.
D
E E
L1C-1L1C-2
G2 G2
HA
HA
HA
G2
HA
G2
F4
G2
HA
X1
KB
X1
KB KB
M4
M4 M4
M4
K3
K3
K3
K3
K3
K3
K3
K3 F4
F4 F4
F4
K3K3
G2
HA
G2
HA
F4
F4 KB
K3
K3
KB
KB
KB X2KBKBKBKBKB KB KB X2
K3 K3
K3K3
K3 K3
K3K3
K3K3
K3 K3
KB
KB
KB
K3
K3
K3
K3
K3
K3
K3
K3K3
K3
K3
K3
K3
K3K3
K3
KB
X1
KBKBKB
KB
KBK3
K3K3
K3
K3 K3
K3K3
K3
K3
K3
K3
KB
KB
KB
KBX1 KB KB
K3
K3
K3
K3
K3
K3
K3
K3
K3
K3
K3
K3
K3
K3
X14
X14
R
R
R
C1C1C1
C1 C1 C1
L4
L4
L4
L4
L4
L4
L4
L4
L4
L4
L4
S4S4S4
L4 L4
L4
L4
L4
X1
X1 R a a a a b b b b a a aa b b bb
3a
3b
3b
3a
3a3b
KB
HA
HA
HA
G2G2
HA
HAHA
K3
K3
K3
K3 K3
K3 K3
K3
K3
K3
R
KB
KB
X1
KB
K2
K2 K2
K2
K2K2
K2
KB
F4
KB
KB
KB KB KB
X1 a aa a b c d b a c d
KB
KB
K3 K3
K3K3
IT-D107
L1D-2
L1D-1
R
F4
KB
K2 K2
L1D-2:24
L1D-2:26
IT-D107:18
L3
L3 L3
L3
L3
L3
L3
L3
L3
L3
NL
NL
NL
NL
NL
NL NL NL
NL
NL
NL
NL
NL
X1
L1D-2:28
X1
NL
E1D:10
L4
E1D:11
NL
ab a a a ab b
E1D:12
E1D:12
L4
L4
L6
L4L4
L4
L4L4
L6
L4
L4
NL
NL
NL
NL
KB NL
X1
E1D:9
L4
L1C-2:41
L3
L3
L3
L3
P3
NL
S4 e e
X1
22.7
25.4
32.5 33.3
33.8
L.5
M
P
P.5
29.1
O.5
N.5
N
O
27 30.928.5
22.2
L
J.8
J
L (E)
K(E)
J(E)
K.8
M.9
L.9
M.3
21.1
K.3
L.3
16 17.2
30 32 33
E1D:13L1C-2:42
KB NL
L1C-2:43
SUD GROUP THERAPY
C136
P. TLT.
A128
P. TLT.
A129
P. TLT.
A105
MSA
A103
ALCOVE
A106
VESTIBULE
A100
VESTIBULE
A102
COURTYARD
D135
SUD OFFICE
C134
SUD OFFICE
C133
P. TLT.
C126
P. TLT.
C125
STOR.
C127
CAROTAS
C128
STAFF LOUNGE
C129
S. TLT.
C131
S. TLT.
C130
VESTIBULE
D109
CWT OFFICE
D108
IT
D107
P. TLT.
D110 BHIP OFFICE
D112
ELEC
D137
STAFF WORK
D113
CONF / CLASS
D114CORRIDOR
1CDR10
CORRIDOR
1CDR10 P. TLT.
D111
HSK
D138
CORRIDOR
1CDR10
BHIP OFFICE
D106
BHIP OFFICE
D105
BHIP OFFICE
D104
BHIP OFFICE
D103
CONSULT
D102
HOLD
D101
CORRIDOR
1CDR10
BHIP OFFICE
D120
BHIP OFFICE
D119
BHIP OFFICE
D118
BHIP OFFICE
D121
BHIP OFFICE
D122
BHIP OFFICE
D123
BHIP OFFICE
D117
BHIP OFFICE
D116
BHIP OFFICE
D115
BHIP OFFICE
D124
BHIP OFFICE
D125
BHIP OFFICE
D126
BHIP OFFICE
D127
BHIP OFFICE
D128
BHIP OFFICE
D129
BHIP OFFICE
D130CONF
D131
BHIP OFFICE
D132
BHIP OFFICE
D133
BHIP OFFICE
D134
STOR.
C132
HALL
A131
LOBBY
A101
CHILDREN'S WAITING
A104
DRINKING FOUNTAIN
A130
CORRIDOR
1CDR7
CORRIDOR
1CDR11
E1D
N
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 pec1.com
Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
ISSUED FOR BID
/2
/2
:2
:1
P
M A u to d e s k D o c s
/1
.2
A tr ia x
T o p e k a
V A
M e n ta l H e a lt h C lin ic
(M o d
-0
E
L E
C R
.r v t
EL111
LIGHTING PLAN - FIRST FLOOR
ADDITION
Outpatient Mental Health Clinic
Colmery-O'Neil VAMC Topeka, KS
03/29/2024 DDC RWL
KEYED NOTES:
L3 INTERLOCK LOCAL OCCUPANCY SENSORS PER MANUFACTURER
REQUIREMENTS.
L4 PROVIDE PHOTOCELL ON ROOF FACING NORTH FOR CONTROL OF
CANOPY AND EXTERIOR LIGHT FIXTURES.
P3 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN EXISTING PANELBOARD AS
INDICATED. MATCH EXISTING BREAKER TYPE AND AIC RATING AS
REQUIRED. UPDATE PANEL DIRECTORY.
0 8' 16'4'1/8" = 1'-0"1
LIGHTING PLAN - 1ST FLOOR ADDITION
N
LAY-IN
LIGHT FIXTURE
SECURE FIXTURE
TO GRID (TYPICAL
OF 4 LOCATIONS)
J-BOX
EMT CONDUIT FOR
BRANCH CIRCUITING
CEILING GRID INSTALLED PER GRID
MANUFACTURER (TYPICAL). CEILING
INSTALLER SHALL PROVIDE
ADDITIONAL
GRID SUPPORT AT LIGHT FIXTURE
LOCATIONS AS RRQUIRED.
≤ 3'
≤ 3'
FLEX CONNECTION SIZE
AS REQUIRED - 3/8" MIN.
LENGTH SHALL ALLOW FIXTURE
TO BE RELOCATED 4'-0" IN
ANY DIRECTION.
ALL THREAD
J-BOX SUPPORT
CONDUIT SUPPORT (3'-0"
MAD. FROM J-BOX)
SUPPORT FLEX A MINIMUM OF
6" ABOVE CEILING GRID.
ALL THREAD OR SUPPORT WIRING TO
BUILDING STRUCTURE (TYPICAL).
SUPPORT WIRES SHALL BE SECURED TO
CEILING GRID AND SHALL NOT DEFORM
CEILING GRID INSTALLATION IN ANY
WAY. SUPPORT WIRES SHALL BE
MARKED TO IDENTIFY THEM AS
ELECTRICAL SUPPORT WIRES AND NOT
CEILING GRID SUPPORT WIRES
PER NEC SECTION 300.11.
NOTES:
1. ADDITIONAL LIGHT FIXTURE SUPPORT MAY BE REQUIRED
DUE TO POTENTIAL SEISMIC CONDITIONS, BUILDING
OCCUPANCY, AND FIXTURE TYPE. REFER TO THE
SPECIFICATIONS.
2. MOUNTING AND CONNECTION OF RECESSED CAN LIGHTS
SHALL UTILIZE BAR HANGERS SECURED TO GRID.
ALL THREAD OR SUPPORT WIRE
TO BUILDING STRUCTURE
(TYPICAL OF 4 CORNERS; FOR
ROUND LUMINAIRES, SPACE
SUPPORTS APPROXIMATELY
EQUIDISTANT AROUND).
3 TWIST MINIMUM (TYP)
CEILING MAIN BEAM
GYPSUM BOARD (TYP)
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERS. ATTACH
WITH SHEET METAL SCREW
CEILING CROSS BEAM
GYPSUM BOARD
CEILING CROSS BEAM
LUMINAIRE.
REFER TO
SCHEDULE
DRYWALL BORDER
LUMINAIRE
SUSPENSION WIRES (#
10 MIN) ATTACHED TO
STRUCTURE (TYP EA.
CORNER)
FIXTURE WHIP FROM
JUNCTION BOX (6FT.
LONG MAX.)
LUMINAIRE.
REFER TO
SCHEDULE
SEAL JOINT BETWEEN
CEILING AND LIGHTING
FIXTURE
1. GENERAL CONTRACTOR SHALL PROVIDE FIREPROOFING AROUND RECESSED FIXTURES INSTALLED IN FIRE RATED CEILING PER U.L. REQUIREMENTS. ELECTRICAL CONTRACTOR WILL
COORDINATE.
2. MANUFACTURERS LISTED IN THIS SCHEDULE OR APPROVED BY WRITTEN ADDENDUM WILL BE THE ONLY APPROVED MANUFACTURERS TO BID THE LIGHTING FIXTURES FOR THIS PROJECT.
CONTRACTORS AND SUPPLIERS USING PRICING FROM MANUFACTURERS NOT LISTED ON SCHEDULE OR BY ADDENDUM DO SO AT THEIR OWN RISK.
3. LIGHT FIXTURE SELECTIONS ARE BASED ON THE MANUFACTURER IN THE LEFT MOST COLUMN AS LISTED IN THE SCHEDULE. FIXTURES APPROVED AS EQUALS IN THIS SCHEDULE OR BY ADDENDUM SHALL BE EQUAL TO THE UNIT SPECIFIED IN THE LEFT MOST COLUMN, IE: SPRING LOADED LATCHES, POST PAINTED FINISH, AND PHOTOMETRICS.
4. ALL LIGHT FIXTURES SHALL BE SECURED TO THE CEILING FRAMING SYSTEM BY MECHANICAL MEANS (SUCH AS BOLTS, SCREWS, OR RIVETS) OR BY CLIPS IDENTIFIED FOR USE WITH THE TYPE
OF CEILING FRAMING MEMBER AND LIGHT FIXTURE.
5. LIGHT FIXTURES SHALL BE PROVIDED WITH 0-10V DIMMING DRIVERS. DRIVERS SHALL BE CAPABLE OF DIMMING TO A MINIMUM OF 10% OF TOTAL LIGHT OUTPUT. LED DRIVERS SHALL HAVE A DISCONNECTING MEANS MEETING THE REQUIREMENTS OF NEC SECTION 410.130(G), EXCEPT FOR THOSE INSTALLED IN CORD-AND-PLUG CONNECTED FIXTURES. WHERE APPLICABLE, WHEN DIMMING SWITCHES ARE NOT PROVIDED AS PART OF THE DESIGN, CONTRACTOR SHALL CAP OFF 0-10V DIMMING WIRES FOR FUTURE EXTENSION BY OWNER.
6. PROVIDE ARROWS AND FACES AS INDICATED ON THE DRAWINGS.
LIGHTING FIXTURE SCHEDULE NOTES
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 pec1.com
Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
ISSUED FOR BID
/2
/2
:2
:1
P
M A u to d e s k D o c s
/1
.2
A tr ia x
T o p e k a
V A
M e n ta l H e a lt h C lin ic
(M o d
-0
E
L E
C R
.r v t
EL501
LIGHTING DETAILS Outpatient Mental Health Clinic
Colmery-O'Neil VAMC Topeka, KS
03/29/2024 DDC RWL 139 170
N0 SCALE
TYPICAL LAY-IN FIXTURE INSTALLATION
N0 SCALE
TYPICAL GYP FIXTURE INSTALLATION
LIGHTING FIXTURE SCHEDULE
MARK DESCRIPTION
MANUFACTURER 1
CATALOG NUMBER
MANUFACTURER 2
CATALOG NUMBER
LIGHT SOURCE
LENS/LOUVER/FINISH
DIMENSIONS REF.
NOTE
REMARKS
# TYPE WATTS VOLTS W L D
C1 4" RECESSED
LINEAR
A LIGHT D54-LH-35-HE-XP-B-D-E-Q AXIS LIGHTING EX4R-1000-80-35-BW-4-WDF 1 LED 28 UNV ACRYLIC .5 4.0 0.33 5 3048LM; 3500K; 80CRI, DAMP LOCATION
RATED
D EXISTING
FIXTURE TO BE
REMOVED
1 0
E EXISTING
FIXTURE TO
REMAIN
1 LED 5 7
F4 4' STRIP COLUMBIA MPS-35HL-CW-EU LITHONIA
ZL1N-L48-5000LM-FST-MVOLT-35K-80CRI
1 LED 34 UNV ACRYLIC 0.23 4.0 0.17 5 5000LM; 3500K; 80CRI
G2 2' WALL
MOUNTED
LIGHTWAY VTEV24-LED-02B-3-T4-WSA-DIM OXYGEN 3-524-24 1 LED 15 UNV WHITE SMOOTH
ACRYLIC
0.88 2.0 0.42 5 2000LM; 3500K; 80CRI; MOUNT 6" ABOVE
VANITY MIRROR
HA 4" RECESSED
DOWNLIGHT
W/LENS
PRESCOLITE
LTR-4RD-H-SL15L-DM1-LTR-4RD-T-SL35K8MD-SS
GOTHAM EVO4-35K/25-AR-MD-LSS-GZ1 1 LED 19 UNV SEMI-CLEAR 1.17 1.32 0.55 5 1500LM; 3500K; 80CRI
K2 2X4 LAY-IN COLUMBIA LCAT24-35XWG-ED LITHONIA 2BLT4-30L-ADP-EZ1-LP835 1 LED 19 UNV ACRYLIC 2.0 4.0 0.33 5 2383LM; 3500K; 80CRI
K3 2X4 LAY-IN COLUMBIA LCAT24-35MWG-ED LITHONIA 2BLT4-40L-ADP-EZ1-LP835 1 LED 30 UNV ACRYLIC 2.0 4.0 0.33 5 3424LM; 3500K; 80CRI
KB 2X2 LAY-IN COLUMBIA LCAT22-35MLG-EDU LITHONIA 2BLT2-33L-ADP-EZ1-LP835 1 LED 29 UNV ACRYLIC 2.0 2.0 0.33 5 3000LM; 3500K; 80CRI
L4 4" WIDE LAY-IN LITECONTROL 4L-LGD4-04SOFC135K-D065-D01-1C MARK ARCH LIGHTING
SL4L-LOP-4FT-FLP-TG-80CRI-35K-350LMF MINI
120ZT
1 LED 23 UNV SOFT DIFFUSE
ACRYLIC
1.0 4.0 0.33 5 2600LM; 3500K; 80CRI
L6 4" WIDE LAY-IN LITECONTROL 4L-LGD4-06SOFC135K-D065-D01-1C MARK ARCH LIGHTING
SL4L-LOP-6FT-FLP-TG-80CRI-35K-350LMF MINI
120ZT
1 LED 34 UNV SOFT DIFFUSE
ACRYLIC
1.0 6.0 0.33 5 3900LM; 3500K; 80CRI
M4 2X4 RECESSED -
VANDAL
KURTZON VLR3-2X4-2/LEDR/835-2/6 LUMINAIRE LED
RMP-R24-FH16CRSP-D16SSB-PRD-7300LM-35K-AL
S-2ES-WHT
1 LED 68 UNV ACRYLIC 2.0 4.0 0.33 5 7230LM; 3500K; 80CRI
R EXTERIOR WALL
PACK
KIM LIGHTING WDSD-24L-40-4K7-3 LITHONIA
ASW1-LED-42C-350-40K-SR2-MVOLT-DDBXD
1 LED 40 UNV DARK BRONZE 1.15 1.25 0.77 4000LM; 4000K; 70CRI, MOUNT 10'-0"
ABOVE GRADE
S4 2" SUSPENDED
LINEAR
LITECONTROL 2LPD04-SOF35K-D050-D011C-FA1 MARK ARCHITECTURAL LIGHTING
S2PD-LLP-4FT-MSL4-600LMF
1 LED 21 UNV SOFT DIFFUSE
ACRYLIC
1.0 4.0 0.33 5 2000LM; 3500K; 80CRI
X1 1 FACE/EM.
BATT.
MULE MD-A-U-R-BA ACUITY LESR 1 LED 5 UNV CAST ALUMINUM 0.71 1.06 0.17 6 RED W/ EMERGENCY BATTERY
X2 2 FACE/EM.
BATT.
MULE MD-A-U-R-BA ACUITY LESR 1 LED 5 UNV CAST ALUMINUM 0.74 1.06 0.17 6 RED W/ EMERGENCY BATTERY
X14 1 FACE/EM.
BATT.
MULE N4X-AX-1-R ACUITY LVSR 1 LED 5 UNV NEMA-4X 0.98 0.98 0.42 6 RED W/ EMERGENCY BATTERY
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.
5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE
WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE
MOLDABLE FIRE BARRIER.
9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE
THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.
LBA
SBA
B2
CT FANCWP
ESM.T.S.
FACP
MSB
ES2
RECONNECT TO EXISTING
EMERGENCY POWER CIRCUIT
SERVING FACP AS REQUIRED.
N
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 pec1.com
Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
ISSUED FOR BID
/2
/2
:2
:1
P
M A u to d e s k D o c s
/1
.2
A tr ia x
T o p e k a
V A
M e n ta l H e a lt h C lin ic
(M o d
-0
E
L E
C R
.r v t
EP101
POWER PLAN - BASEMENT Outpatient Mental Health Clinic
Colmery-O'Neil VAMC Topeka, KS
03/29/2024 DDC RWL
0 4' 8'2'1
POWER PLAN - BASEMENT
N
H
H
H
J JJ
H
H
HH
J
J
J JJ
HH
H
H
H
H
H
H
J
J
J J
J
J J
JJ
J
J
J
J
J
J
J
JJ
J
J
H
H
J
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.
5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE
WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE
MOLDABLE FIRE BARRIER.
9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE
THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.
22.7
25.4
33.8
L.5
M
P
P.5
O.5
N.5
N
O
22.2
L
J.8
J
L (E)
K(E)
J(E)
K.8
M.9
L.9
M.3
21.1
EP110
EP110
EP110
EP110
E1D:7
P12
CORRIDOR
A261
#10
E1D:7
P12
WAITING AREA
A255
#10
EXISTING DOOR
CONTROLS TO REMAIN.
CORRIDOR
A274
E1D:8
P12
CORRIDOR
A325
#10
N
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 pec1.com
Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
ISSUED FOR BID
/2
/2
:2
:1
P
M A u to d e s k D o c s
/1
.2
A tr ia x
T o p e k a
V A
M e n ta l H e a lt h C lin ic
(M o d
-0
E
L E
C R
.r v t
EP110
POWER PLAN - FIRST FLOOR
OVERALL
Outpatient Mental Health Clinic
Colmery-O'Neil VAMC Topeka, KS
03/29/2024 DDC RWL
KEYED NOTES:
P12 PROVIDE 120V. CONNECTION TO ACCESS CONTROL DOOR CONTROLLER.
VERIFY ALL REQUIREMENTS WITH SYSTEM MANUFACTURER AS REQUIRED.
0 16' 32'8'1/16" = 1'-0"1
POWER PLAN - 1ST FLOOR OVERALL
0 4' 8'2'1/4" = 1'-0"2 POWER PLAN - Callout 1
0 4' 8'2'1/4" = 1'-0"3 POWER PLAN - Callout 2
0 4' 8'2'1/4" = 1'-0"4 POWER PLAN - Callout 3
0 4' 8'2'1/4" = 1'-0"5 POWER PLAN - Callout 4
N
H
H
J
J
J J
JJ
J
J
J
J
J
J
J
J
J
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.
5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE
WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE
MOLDABLE FIRE BARRIER.
9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE
THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.
CT
CT CT
CT
CT
CT
CT CT CT REF.
CT
CT
WP
FB FB
FB
FB
P1
P1
P1P1
L1C-2
L1C-1
FB
P1
P1
L1D-1
L1D-2
88" 88" 88" 88"
88"
88" 88" 88" 88"
88" 88"
88"
CT88"
88"
88" 88"CT 88" 88"
L1D-1:1
EP111
IT-D107
L1D-1:3
L1D-1:5L1D-1:7L1D-1:9L1D-1:11L1D-1:13
L1D-1:15
COPIER
COUNTERTOP
PRINTER
L1D-1:17
L1D-1:19
L1D-1:21
L1D-1:25
L1D-1:23
L1D-1:27
L1D-1:29
L1D-1:4
L1D-1:2
L1D-1:6
L1D-1:8
L1D-1:10
L1D-1:16 L1D-1:14
L1D-1:12
L1D-1:18
L1D-1:20L1D-1:22L1D-1:24
L1D-1:30 L1D-1:28 L1D-1:26
88"88"
88" 88"
88"
88"
L1D-2:11L1D-2:5L1D-2:7
L1D-2:9 L1D-2:3 L1D-2:1
E1D:4
P2
WP
L1D-2:13
WP
L1D-2:15
E1D:2 P2
L1D-2:17
L1D-2:19
L1D-2:25 L1D-2:23
L1D-2:21
E1D:6
P1 P1P2
L1C-2:29
L1C-2:31
88"88"
L1C-2:30
L1C-2:35
L1C-2:32 L1C-2:33
46"
ICE MACHINE
L1C-2:34
L1C-2:36 L1C-2:40
L1C-2:39
L1C-2:37
COPIER
L1D-2:22
L1D-2:20
P
WTV
L1D-1:31
P
WTV
L1D-1:33
60"
L1C-2:38
WTV
88"
E1D:1
P12
IT-D107:20
CT
DF
L1C-2:28
P12
P12
P12
P12
P12
#10 #10
#10
#10
#10 #10
#10
P12
P12 E1D:3
PHARMACY
KIOSK
E1D:15
NAC
PANEL
P12
P12
22.7
25.4
32.5 33.3
33.8
L.5
M
P
P.5
O.5
N.5
N
O
L
J.8
J
L (E)
K(E)
J(E)
K.8
M.9
L.9
M.3
21.1
L1C-2:27
SUD GROUP THERAPY
C136
P. TLT.
A128
P. TLT.
A129
P. TLT.
A105
MSA
A103
ALCOVE
A106
VESTIBULE
A100
VESTIBULE
A102
COURTYARD
D135
SUD OFFICE
C134
SUD OFFICE
C133
P. TLT.
C126
P. TLT.
C125
STOR.
C127
CAROTAS
C128
STAFF LOUNGE
C129
S. TLT.
C131
S. TLT.
C130
VESTIBULE
D109
CWT OFFICE
D108
IT
D107
P. TLT.
D110 BHIP OFFICE
D112
ELEC
D137
STAFF WORK
D113
CONF / CLASS
D114
CORRIDOR
1CDR10
CORRIDOR
1CDR10
P. TLT.
D111
HSK
D138
CORRIDOR
1CDR10
BHIP OFFICE
D106
BHIP OFFICE
D105
BHIP OFFICE
D104
BHIP OFFICE
D103
CONSULT
D102HOLD
D101
CORRIDOR
1CDR10
BHIP OFFICE
D120
BHIP OFFICE
D119
BHIP OFFICE
D118
BHIP OFFICE
D121
BHIP OFFICE
D122
BHIP OFFICE
D123
BHIP OFFICE
D117
BHIP OFFICE
D116
BHIP OFFICE
D115
BHIP OFFICE
D124
BHIP OFFICE
D125
BHIP OFFICE
D126
BHIP OFFICE
D127
BHIP OFFICE
D128
BHIP OFFICE
D129
BHIP OFFICE
D130CONF
D131
BHIP OFFICE
D132
BHIP OFFICE
D133
BHIP OFFICE
D134
STOR.
C132
E1D
HALL
A131
LOBBY
A101
CHILDREN'S WAITING
A104
E1D:5
DRINKING FOUNTAIN
A130
CORRIDOR
1CDR7
IT-D107
IT-D107:1
IT-D107:3
R
R
R
IT-D107:5,7,9
IT-D107:11
#10
#10
P4P4
IT2
IT2
IT2
IT-D107:13,15,17
IT-D107:19
P4P4
IT-D107:16
#10
IT-D107:10,12,14
P4P4
TGB-D107
N.E.C. REQUIRED
WORKING CLEARANCE
M
28.5
N
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 pec1.com
Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
ISSUED FOR BID
/2
/2
:2
:2
P
M A u to d e s k D o c s
/1
.2
A tr ia x
T o p e k a
V A
M e n ta l H e a lt h C lin ic
(M o d
-0
E
L E
C R
.r v t
EP111
POWER PLAN - FIRST FLOOR
ADDITION
Outpatient Mental Health Clinic
Colmery-O'Neil VAMC Topeka, KS
03/29/2024 DDC RWL
KEYED NOTES:
P1 PROVIDE 120V. CONNECTION TO MOTORIZED DOOR OPERATOR. VERIFY
ALL REQUIREMENTS WITH DOOR HARDWARE SUPPLIER.
P2 PROVIDE 120V. 20A. 1P. CONNECTION TO EXISTING SPARE BREAKER IN
PANELBOARD AS INDICATED. UPDATE PANEL DIRECTORY
P4 PROVIDE DEDICATED DOUBLE DUPLEX RECEPTACLE AND SPECIAL OUTLET
‘IT2’ ON BOTTOM OF DATA RACK. COORDINATE OVERHEAD CONDUIT
ROUTING WITH CABLE TRAY, LIGHTS, ETC. AS REQUIRED PRIOR TO
ROUGH-IN.
P12 PROVIDE 120V. CONNECTION TO ACCESS CONTROL DOOR CONTROLLER.
VERIFY ALL REQUIREMENTS WITH SYSTEM MANUFACTURER AS REQUIRED.
0 8' 16'4'1/8" = 1'-0"1
POWER PLAN - 1ST FLOOR ADDITION
0 4' 8'2'1/4" = 1'-0"2
ENLARGED POWER PLAN - IT D107
N
J
J
J
J J
J J
F F
J
JF
J
F F
J
J
J
J
J J
JJ
J J
J J
F F
F F
J
JJJJ
L1D-2:27
P7
P7
P7
L1A-2:1
L1D-2:29
L1D-2:2
P6
P6 P5P5
P5P5
L1A-2:3
P2
P2
P6
P5P5
P8
L1D-2:4
L1C-1:24
P6 P6
P5 P5
P5 P5
L1C-1:26
L1C-1:28
P2
P6
P6P5P5
P5P5
P2 P2
P6 P6
P5P5 P5P5
L1C-1:30
P8
P2
P10P10P10
P9P9P9 L1A-2:5
P10
P9
22.7
25.4
32.5 33.3
33.8
L.5
M
P
P.5
O.5
N.5
N
O
L
J.8
J
L (E)
K(E)
J(E)
K.8
M.9
L.9
M.3
K.3
L.3
16 17.2 34
SUD GROUP THERAPY
C136
P. TLT.
A128
P. TLT.
A129
P. TLT.
A105
MSA
A103
ALCOVE
A106
VESTIBULE
A100
VESTIBULE
A102
COURTYARD
D135
SUD OFFICE
C134
SUD OFFICE
C133
P. TLT.
C126
P. TLT.
C125
STOR.
C127
CAROTAS
C128
STAFF LOUNGE
C129
S. TLT.
C131
S. TLT.
C130
VESTIBULE
D109
CWT OFFICE
D108
IT
D107
P. TLT.
D110
BHIP OFFICE
D112
ELEC
D137
STAFF WORK
D113
CONF / CLASS
D114
CORRIDOR
1CDR10
CORRIDOR
1CDR10
P. TLT.
D111
HSK
D138
CORRIDOR
1CDR10
BHIP OFFICE
D106
BHIP OFFICE
D105
BHIP OFFICE
D104
BHIP OFFICE
D103
CONSULT
D102HOLD
D101
CORRIDOR
1CDR10
BHIP OFFICE
D120
BHIP OFFICE
D119
BHIP OFFICE
D118
BHIP OFFICE
D121
BHIP OFFICE
D122
BHIP OFFICE
D123
BHIP OFFICE
D117
BHIP OFFICE
D116
BHIP OFFICE
D115
BHIP OFFICE
D124
BHIP OFFICE
D125
BHIP OFFICE
D126
BHIP OFFICE
D127
BHIP OFFICE
D128
BHIP OFFICE
D129
BHIP OFFICE
D130CONF
D131
BHIP OFFICE
D132
BHIP OFFICE
D133
BHIP OFFICE
D134
STOR.
C132
HALL
A131
LOBBY
A101
CHILDREN'S WAITING
A104
DRINKING FOUNTAIN
A130
CORRIDOR
1CDR7
2-TU-2.09
2-TU-2.06
2-TU-2.10
2-TU-2.05
2-TU-2.03
2-TU-2.02
2-TU-2.01
2-MS-IU-02
2-MS-IU-01
2-TU-2.14
2-TU-2.07
2-TU-2.08
2-TU-2.11
2-TU-2.12
2-TU-2.13
2-TU-2.15
2-TU-2.16
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.
5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE
WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE
MOLDABLE FIRE BARRIER.
9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE
THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.
N
Drawing Title
Approved: Associate Director
Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration Approved: Chief of Staff
Approved: Infection Control
Approved: Chief Engineer
Approved: Safety Officer
Approved: Chief, Police & Security
GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 pec1.com
Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
ISSUED FOR BID
/2
/2
:2
:2
P
M A u to d e s k D o c s
/1
.2
A tr ia x
T o p e k a
V A
M e n ta l H e a lt h C lin ic
(M o d
-0
E
L E
C R
.r v t
EP211
EQUIPMENT PLAN - FIRST FLOOR
ADDITION
Outpatient Mental Health Clinic
Colmery-O'Neil VAMC Topeka, KS
03/29/2024 DDC RWL
0 8' 16'4'1/8" = 1'-0"1
EQUIPMENT PLAN - 1ST FLOOR ADDITION
KEYED NOTES:
P2 PROVIDE 120V. 20A. 1P. CONNECTION TO EXISTING SPARE BREAKER IN
PANELBOARD AS INDICATED. UPDATE PANEL DIRECTORY
P5 PROVIDE 120V. CONNECTION TO PLUMBING FIXTURE SENSOR.
COORDINATE EXACT LOCATION WITH MECHANICAL PRIOR TO ROUGH-IN.
P6 PROVIDE FUSTAT ABOVE ACCESSIBLE CEILING FOR DISCONNECTING
MEANS TO ALL PLUMBING SENSORS LOCATED IN ROOM.
P7 PROVIDE 120V. 20A. CONNECTION TO HEAT TRACE LOCATED AT ROOF
DRAINS AS REQUIRED. VERIFY EXACT LOCATION AND ALL REQUIREMENTS
WITH MECHANICAL PRIOR TO ROUGH-IN. PROVIDE TOGGLE SWITCH IN
LOCATION DETERMINED BY OWNER FOR CONTROL OF HEAT TRACE
SYSTEM AS REQUIRED. LABEL SWITCH FACEPLATE.
P8 PROVIDE 120V. 20A. FUSTAT FOR CONNECTION TO LOW-VOLTAGE
TRANSFORMER SERVING TERMINAL UNITS AS REQUIRED. COORDINATE
EXACT LOCATION AND ALL REQUIREMENTS WITH MECHANICAL PRIOR TO
ROUGH-IN.
P9 PROVIDE 120V. 20A. CONNECTION TO MOTORIZED COILING GATE AT
RECEPTION DESK AS REQUIRED. COORDINATE EXACT LOCATION WITH
ARCHITECT PRIOR TO ROUGH-IN.
P10 PROVIDE UP/DOWN CONTROL SWITCH FOR MOTORIZED GATE AS
REQUIRED. VERIFY SWITCH LOCATION WITH OWNER PRIOR TO ROUGH-IN.
N
R
R
S
S
WP
WP
WP
L1B-2:9
OUTLET ON ROOF
AT EQUIPMENT.
TYPICAL.
L1C-2:1
P2
P2
WP
L1D-2:6
FAN
FAN
R
S
R S
2-AHU-2A/2B
2-AHU-1A/1B
L.5
M
P
P.5
O.5
N
O
L
K(E)
J(E)
M.9
L.9
M.3
A
B
K.3
L.3
2 2.8
3 4
5.8
8 10
1112 13
16 17.2 29.1 34 354.5
7 9 9.8 15 17 31 33.1
EQUIPMENT PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.