Attachment 12 - Drawings 589-501 91-115.pdf

PDF 12 MB Posted

Attached to
589-501 Construction Outpatient Mental Health Addition (VA-24-00072549)
Solicitation number
36C77624B0031
Issued by

About this file

This document appears to be Attachment 12 - Drawings 589-501 91-115.pdf, which contains architectural drawings related to the federal contract opportunity for the 589-501 Construction Outpatient Mental Health Addition (VA-24-00072549).

The drawings provide detailed specifications and schematics for the construction of an outpatient mental health addition facility for the Department of Veterans Affairs Technology Acquisition Center Austin. The drawings cover various construction elements such as site plans, floor plans, elevations, sections, and details. This attachment would be provided to offerors to support the development of their proposals in response to the solicitation.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B

CR

M

M M

DH DH H

M H

E E

M MS SS

M

S S

E E

S

S

S

DEMOLITION PLAN NOTES:

1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE ELECTRICAL

DEMOLITION WORK. THE ELECTRICAL CONTRACTOR SHALL DISCONNECT

ELECTRICAL SERVICES TO ALL EQUIPMENT BEING REMOVED, SEE

MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION TO RETAIN

REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES, LIGHTS, PANELS,

ETC. NOT BEING USED IN THE FINISHED WORK. COORDINATE WITH OWNER

PRIOR TO STARTING DEMOLITION. PROPERLY AND LEGALLY DISPOSE OF

ALL EQUIPMENT AND MATERIALS BEING REMOVED.

2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND

CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING

CONDUIT IN WALL OR FLOOR WHERE CUT.

3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE SHELVING,

CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND MAY REQUIRE

REMOVAL.

4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING ALL

OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF EQUIPMENT,

RACEWAY SYSTEMS, OUTLET BOXES, ETC.

5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED, THE

CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT OF SUPPLY.

WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED TO MAINTAIN

CONTINUITY OF THE CIRCUIT OR OPERATION OF THE SYSTEM.

6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL BE

REMOVED, UNLESS NOTED OTHERWISE.

7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE BEING

REMOVED FROM FLUSH-MOUNTED OUTLET BOXES IN EXISTING WALLS TO

REMAIN.

8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO

BEGINNING WORK.

9. EXISTING NURSE CALL DEVICES TO BE REUSED. REMOVE DEVICES AS

INDICATED ON PLAN. PRESERVE AND PROTECT DURING CONSTRUCTION AS

REQUIRED FOR REINSTALLATION. SEE SYSTEMS PLANS FOR FURTHER

INFORMATION.

50A

FAAP

EXISTING DATA RACK

& FIBER ENCLOSURE

TO REMAIN.

EXISTING

PHONE BACK

BOARD

L1C-2

L1C-1

D

D

DD

D

D

D D

D D D

DD

D

D

D D

D

DD

D D D D D D

D

D

D D

D D

D D

D D

D D

D D

D D

D D

D

FAN

FAN

D D

D

D

D D

D

D

D

D

D

D

D D DD

D

D D

D

D

D D

D

D

D

D

D

D

DD

D

D

D

D

D2

D3

/A ED111.1

/A ED112

D8

D9

REMOVE EXISTING

POWER-POLE AND

ASSOCIATED CABLING

BACK TO POINT OF

SUPPLY. TYPICAL OF 3.

K.3

L.3

16 17.2

30 32 33

N

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 pec1.com

Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

KEYPLAN

ISSUED FOR BID

/2

/2

:2

:0

P

M A u to d e s k D o c s

/1

.2

A tr ia x

T o p e k a

V A

M e n ta l H e a lt h C lin ic

(M o d

-0

E

L E

C R

.r v t

ED111

ELECTRICAL DEMOLITION - FIRST

FLOOR

Outpatient Mental Health Clinic

Colmery-O'Neil VAMC Topeka, KS

03/29/2024 DDC RWL

KEYED NOTES:

D2 EXISTING I.T. CLOSET AND ASSOCIATED EQUIPMENT TO REMAIN

OPERATIONAL DURING PROJECT. EXISTING TELECOMMUNICATIONS

BACKBONE CABLING SHALL REMAIN. PRESERVE AND PROTECT DURING

CONSTRUCTION AS REQUIRED. REMOVE EXISTING HORIZONTAL

CABLING BACK TO I.T. CLOSET FROM DEVICES REMOVED DURING

DEMOLITION AS REQUIRED. COORDINATE ROOM ACCESS WITH OWNER.

D3 EXISTING PANELBOARDS TO REMAIN FOR REUSE. REMOVE ALL

EXISTING BRANCH CIRCUIT WIRING AS REQUIRED.

D8 REMOVE EXISTING FIRE ALARM ANNUNCIATOR PANEL AND ALL

ASSOCIATED CABLING BACK TO FIRE ALARM CONTROL PANEL LOCATED

IN BASEMENT AS REQUIRED.

D9 EXISTING CARD READER AND ASSOCIATED POWER CONNECTION TO

EXISTING DOOR TO REMAIN. RECONNECT COMPONENTS TO NEW DOOR

AS REQUIRED. COORDINATE ALL REQUIREMENTS WITH DOOR

HARDWARE PROVIDER.

0 8' 16'4'1/8" = 1'-0"1

ELECTRICAL DEMOLITION PLAN - 1ST FLOOR - ADDITION

N

Revisions: Date:

03/27/2024

GROUND ROD. TYPICAL.

TEST WELL. TYPICAL.

12"H LIGHTNING AIR TERMINAL, TYPICAL.

PROVIDE (4) LIGHTNING AIR TERMINALS

ON SCREEN WALL. LOCATE IN CORNERS

AS INDICATED.

CONNECT TO BUILDING

EXISTING LIGHTNING

PROTECTION SYSTEM

AS REQUIRED.

L.5

M

P

P.5

O.5

N

O

L

K(E)

J(E)

M.9

L.9

M.3

A

B

K.3

L.3

2 2.8

3 4

5.8

8 10

1112 13

16 17.2 29.1

30 32 33

34 354.5

7 9 9.8 15 17

31 33.1

GROUNDING PLAN NOTES:

1. GROUND RODS FOR THIS PROJECT SHALL BE 3/4" x 10'-0"COPPER CLAD

STEEL UNLESS OTHERWISE NOTED.

2. MULTIPLE ROD GROUNDING SYSTEMS SHALL BE CONNECTED TOGETHER

WITH #4/0 AWG BARE STRANDED COPPER CABLE. ALL CONNECTIONS

SHALL BE EXOTHERMIC WELDED.

3. PROVIDE 1" PVC CONDUIT SLEEVES FOR GROUNDING CABLE

PENETRATIONS THROUGH CONCRETE FLOORS AND/OR WALLS.

4. CONNECTING SURFACES OF STEEL AND CABLES SHALL BE THOROUGHLY

CLEANED AND PREPARED PRIOR TO COMPLETING THE CONNECTION.

5. LOCATIONS OF GROUND RODS AND GROUNDING CABLE SHOWN ARE

APPROXIMATE, UNLESS LOCATED BY DIMENSIONS. FIELD VERIFY EXACT

LOCATIONS TO SUIT JOB SITE CONDITIONS AND TO AVOID OBSTRUCTIONS.

BRANCH GROUNDING CABLE CONNECTION TO MAIN GROUNDING CABLE

SHALL BE TEE TAP. INSTALL UNDERGROUND GROUNDING CABLE 18"

MINIMUM BELOW GRADE.

6. SIZE MAIN GROUNDING CABLE AS INDICATED. USE #4/0 AWG STRANDED

COPPER CABLE FOR ALL GROUND CONDUCTORS UNLESS OTHERWISE

NOTED. LOCATE EXPOSED GROUNDING CABLE TO AVOID MECHANICAL

DAMAGE, ADEQUATELY SUPPORTED WITH NONFERROUS CABLE CLAMPS

ON MINIMUM 4'-0" CENTERS. NO CHANGES SHALL BE MADE WITHOUT PRIOR

WRITTEN APPROVAL OF THE ENGINEER.

N

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 pec1.com

Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

KEYPLAN

ISSUED FOR BID

/2

/2

:2

:0

P

M A u to d e s k D o c s

/1

.2

A tr ia x

T o p e k a

V A

M e n ta l H e a lt h C lin ic

(M o d

-0

E

L E

C R

.r v t

EG301

LIGHTNING PROTECTION ROOF PLAN Outpatient Mental Health Clinic

Colmery-O'Neil VAMC Topeka, KS

03/29/2024 DDC RWL 133 170

0 16' 32'8'1/16" = 1'-0"A

LIGHTNING PROTECTION PLAN - ROOF

N

12. METAL BODIES OF INDUCTANCE LOCATED ABOUT THE ROOF,

SUCH AS: METAL FLASHING, GRAVEL STOPS, ROOF DRAINS,

SOIL POPE VENTS, INSULATION VENTS, LOUVERS AND DOOR

FRAME SITUATED WITHIN 6'-0" OF A LIGHTNING CONDUCTOR

OR BONDED METAL BODY SHALL BE INTERCONNECTED TO

THE LIGHTNING CONDUCTOR SYSTEM.

13. CONDUCTORS SHALL INTERCONNECT ALL AIR TERMINALS

AND SHALL FORM A TWO-WAY PATH FROM EACH AIR

TERMINAL HORIZONTALLY OR DOWNWARD TO CONNECTIONS

WITH GROUND TERMINALS.

14. BARE COPPER LIGHTNING PROTECTION MATERIALS SHALL

NOT BE INSTALLED ON ALUMINUM ROOF OR SIDING OR

OTHER ALUMINUM ROOF OR SIDING OR INSTALLED ON

COPPER ROOFING OR COPPER SIDING OR OTHER COPPER

SURFACES.

15. THE LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED

IN A NEAT AND INCONSPICUOUS MANNER SO THAT ALL

COMPONENTS WILL BLEND IN WITH THE APPEARANCE OF

THE BUILDING. DOWNLEADS SHALL BE RUN INTERNALLY

WHERE POSSIBLE. ROUTING PATHS MUST MEET APPROVAL

OF ENGINEER AND OWNER PRIOR TO ROUGH-IN.

16. THE DESIGN LAYOUT AND INSTALLATION DETAILS SHOWN

HEREON SHALL MEET THE REQUIREMENTS OF

UNDERWRITERS' LABORATORIES STANDARD 96A FOR

MASTER LABELED LIGHTNING PROTECTION SYSTEMS, THE

ACTUAL MASTER LABEL WILL BE DELIVERED UPON

COMPLETION OF INSTALLATION.

17. THE LIGHTNING PROTECTION INSTALLATION SHALL COMPLY

IN ALL RESPECTS TO LIGHTNING PROTECTION INSTITUTE

STANDARD 175. THE INSTALLATION SHALL BE MADE BY OR

UNDER THE SUPERVISION OF AN L.P.I. CERTIFIED MASTER

INSTALLER. THE COMPLETED INSTALLATION WILL RECEIVE

SYSTEM CERTIFICATION SUBMITTAL FORM LPI 176.

18. FIELD VERIFY EXISTING LIGHTNING PROTECTION SYSTEM

INSTALLATION AND LOCATIONS OF CONDUCTORS, AIR

TERMINALS, AND GROUND RODS.

1. LOCATE AIR TERMINALS AS SHOWN. TAKE CARE TO INSURE

THAT ALL POINTS ARE WITHIN 2'-0" OF OUTSIDE BUILDING

EDGE, OUTSIDE CORNERS, AND RIDGE ENDS, AND THAT

MAXIMUM SPACING DOES NOT EXCEED 20'-0", AND THAT

MINIMUM PROJECTION ABOVE OBJECT PROTECTED IS 10"

(POINTS PROJECTION 24" MAY BE SPACED AT 25" MAXIMUM).

2. MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN

CONDUCTOR.

3. ALL CONDUCTOR BENDS SHALL HAVE AT LEAST AN 8" RADIUS

AND SHALL FORM A FINAL INCLUDED ANGLE OF NOT LESS THAN

90 DEGREES.

4. ATTACH ALL EXPOSED ROOF, DOWN LEAD AND BONDING

CABLES AT 3'-0" ON CENTER MAXIMUM. VERIFY COMPATABILITY

OR ADHESIVE ON MEMBRANE ROOF APPLICATIONS PRIOR TO

INSTALLATION.

5. GROUND ELECTRODES SHALL BE INSTALLED AS SHOWN, BUT IN

NO INSTANCE SHALL THEY BE LESS THAN 1'-0" BELOW GRADE

AND 2'-0" FROM FOUNDATION WALL. DRIVEN GROUND RODS

SHALL PENETRATE THE EARTH AT LEAST 10'-0".

6. BOND TO WATER SERVICE AND OTHER PIPING SYSTEMS AS

SHOWN AND AS REQUIRED BY CODES.

7. INTERCONNECT LIGHTNING PROTECTION GROUND TO

ELECTRIC,TELEPHONE, AND OTHER BUILDING GROUND

SYSTEMS AS SHOWN OR AS REQUIRED BY CODE.

8. SYSTEM SHALL BE INSTALLED AS SHOWN TO INSURE PROPER

CODE COMPLIANCE AND SYSTEM CERTIFICATION.ANY MAJOR

VARIANCE SHALL REQUIRE RESUBMITTAL AND NEW

APPROVAL.

9. AS-BUILT DRAWINGS SHALL BE SUBMITTED IN ACCORDANCE

WITH CERTIFICATION PROCEDURES.

10. ALL MATERIALS SHALL BE UNDERWRITERS LABORATORIES

APPROVED WITH LABELS OM CONDUCTORS AT 10'-0"

INTERVALS AND LABELS ON ALL AIR TERMINALS.

11. All MATERIALS SHOWN SHALL BE EQUAL TO THOSE AS

MANUFACTURED BY THOMPSON LIGHTNING PROTECTION INC.

LIGHTNING PROTECTION GENERAL NOTES

COPPER CABLE

COPPER SECONDARY

BONDING WIRE.

CAST BRONZE PARALLEL

COMBINATION CABLE SPLICER

CAST BRONZE PARALLEL

COMBINATION CABLE SPLICER.

COPPER DOWNLEAD CABLE. COURSE CABLE

EXPOSED DOWN EXTERIOR WALL CONSTRUCTION

TO BELOW GRADE.

COPPER LOOP TYPE MASONRY CABLE ANCHOR.

FURNISHED WITH 1/4" X 1-1/4" MASONARY DRIVE

ANCHOR. FASTEN CABLE 3'-0" MAX.

COPPER LOOP TYPE CABLE FASTENER.

SECURE WITH #1 X 1" STAINLESS STEEL

SCREW. FASTEN CABLE 3'-0" MAX.

COPPER CABLE. COURSE CABLE TO THE

NEAREST MAIN CONDUCTOR AND CLOSE

CIRCUIT WHERE REQUIRED WITH SPLICER.

3/8" CAST BRONZE ADHESIVE TYPE POINT BASE.

SECURE IN PLACE WITH RUBBER ADHESIVE

COMPOUND.

COPPER CABLE. COURSE CABLE AS THE

MAIN CONDUCTOR AND CLOSE CIRCUIT

WHERE REQUIRED WITH SPLICER.

COPPER ADHESIVE TYPE CABLE HOLDER.

SECURE IN PLACE WITH RUBBER ADHESIVE

COMPOUND. FASTEN CABLE 3'-0" O.C. MAX.

3/8" x 10" BARE COPPER POINT.

REFER TO GENERAL NOTES FOR LOCATION.

COPPER LOOP TYPE CABLE FASTENER.

SECURE WITH #10 X 1" STAINLESS STEEL

TEK SCREW. FASTEN CABLE 3'-0" O.C. MAX.

3/8" CAST BRONZE POINT BASE.

SECURE WITH (2) #10 X 5/8"

STAINLESS STEEL TEK SCREWS.

COPPER CABLE. COURSE CABLE AS THE

MAIN CONDUCTOR AND CLOSE CIRCUIT

WHERE REQUIRED WITH SPLICER.

3/8" x 12" BARE COPPER POINT TO EXTEND

A MINIMUM OF 10" ABOVE PARAPET.

REFER TO GENERAL NOTES FOR LOCATION.

3/8" STRAP TYPE TINNED COPPER POINT BASE.

SECURE WITH FOUR #10 x 1" STAINLESS STEEL

SCREWS.

3/8" x 24" LEADED COPPER POINT

TO EXTEND A MINIMUM OF 10"

ABOVE TOP OF EQUIPMENT.

REFER TO GENERAL NOTES FOR LOCATION.

3/4" PVC CONDUIT. COURSE CONDUIT CONCEALED

WITHIN COLUMN/WALL CONSTRUCTION.

SEAL END PERMANENTLY WATER TIGHT WITH DUCT SEAL.

EXIT WITHIN CEILING OR AT EAVE.

CAST BRONZE CABLE TO

GROUND ROD CLAMP.

COPPER CLAD STEEL GROUND ROD

REFER GENERAL NOTES FOR

LOCATION

APPROX.

FINISHED

GRADE

CAST BRONZE REBAR BONDING CLAMP

INSTALLING CONTRACTOR TO FIELD

ADJUSTAND INSURE A SECURE BOND.

COPPER CABLE. COURSE CABLE CONCEALED WITHIN

CONDUIT UP TO EAVE OR TO CEILING SPACE.

COPPER CABLE. COURSE CABLE BELOW GRADE

TO GROUND ROD CONNECTION. REFER TO

GENERAL NOTES FOR LOCATION.

CAST BRONZE PARALLEL

COMBINATION CABLE

SPLICER.

COPPER CABLE. COURSE CABLE TO THE

NEAREST MAIN CONDUCTOR AND CLOSE

CIRCUIT WHERE REQUIRED WITH SPLICER.

CAST BRONZE CABLE TO

STEEL BONDING CLAMP.

COPPER TO COPPER THRU-ROOF CABLE CONNECTING

ASSEMBLY. FURNISHED WITH 1/2"∅ x 12" ALLTHREAD

ROD.

SEAL PENETRATION PERMANENTLY WATER TIGHT WITH

NEOPRENE WASHER FURNISHED WITH ASSEMBLY.

COPPER DOWNLEAD CABLE. COURSE CABLE IN CONDUIT,

CONCEALED WITHIN COLUMN AND/OR WALL CONSTRUCTION;

EXIT AT LOWER ROOF OR EXIT BELOW GRADE.

3/4"PVC CONDUIT. FURNISHED AND INSTALLED BY THE

ELECTRICAL CONTRACTOR. COURSE CONDUIT CONCEALED

WITHIN COLUMN AND/OR WALL CONSTRUCTION.

SEAL ENDS OF CONDUIT PERMANENTLY WATER TIGHT

WITH DUCT SEAL. EXIT AT LOWER ROOF OR EXIT BELOW

GRADE.

LESS THAN 90°

REFER TO GENERAL NOTE "4"

NOT ACCEPTABLE

ACCEPTABLE

SHEET ___

NOT ACCEPTABLE

LESS THAN 8" RADIUS

90° MIN.

LESS THAN

8" RADIUS

8" RADIUS (MIN.)

90°

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 pec1.com

Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

ISSUED FOR BID

/2

/2

:2

:0

P

M A u to d e s k D o c s

/1

.2

A tr ia x

T o p e k a

V A

M e n ta l H e a lt h C lin ic

(M o d

-0

E

L E

C R

.r v t

EG501

LIGHTNING PROTECTION DETAILS Outpatient Mental Health Clinic

Colmery-O'Neil VAMC Topeka, KS

03/29/2024 DDC RWL 134 170

N0 SCALE

TYPICAL CABLE SPLICERS

N0 SCALE

EXPOSED DOWNLEAD AT SCREENWALL

N0 SCALE

ADHESIVE AIR TERMINAL

N0 SCALE

PARAPET AIR TERMINAL

N0 SCALE

EQUIP. AIR TERMINAL

N0 SCALE

CONCEALED DOWNLEAD TO GROUNDING CONN.

N0 SCALE

THRU-ROOF CABLE CONN. AT STANDING SEAM METAL ROOF

N0 SCALE

TYPICAL CABLE BEND REQUIREMENTS

DN

M

M M

M M

M

M

M

M M M

M

M M M M M M

M M

M M

M

M M

M

M

M M

M M M MM M M M M

M M

M M

M M

M

1D1D1D

1D1D1D1D1D

1D 1D 1D

1D1D1D

1D 1D 1D 1D 1D

1D

1D

1D1D1D

1D 1D

D

1DM

M

M

D 1D 1D MM

M

M

M

M M

M

D

D

M

D

D

D

D

D

J

D

M

D

M

M

M

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS

AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.

ASSEMBLY NUMBERS.

4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH

THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND

SPECIFICATIONS.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE

FIRE BARRIER.

8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT

FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR

TO ROUGH-IN.

22.7

25.4

32.5 33.3

33.8

L.5

M

P

P.5

O.5

N.5

N

O

22.2

L

J.8

J

L (E)

K(E)

J(E)

K.8

M.9

L.9

M.3

21.1

A

B

K.3

L.3

2 2.8

3 4

5.8

8 10

1112 13

16 17.2 29.1 34 354.5

7 9 9.8 15 17 31 33.1

EL110

EL110

EL110

EL110

R

E1D:11 L5

R

X1 L6 A

E1D:11

L5

L6 X1

R

A

L6

X2 E1D:11

R

A

E1D:11

L5

L6

X1

R

N

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 pec1.com

Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

KEYPLAN

ISSUED FOR BID

/2

/2

:2

:1

P

M A u to d e s k D o c s

/1

.2

A tr ia x

T o p e k a

V A

M e n ta l H e a lt h C lin ic

(M o d

-0

E

L E

C R

.r v t

EL110

LIGHTING PLAN - FIRST FLOOR

OVERALL

Outpatient Mental Health Clinic

Colmery-O'Neil VAMC Topeka, KS

03/29/2024 DDC RWL

KEYED NOTES:

L5 ROUTE CIRCUIT VIA PHOTOCELL.

L6 CONNECT EXIT LIGHT TO EXISTING CORRIDOR EMERGENCY LIGHTING

CIRCUIT.

0 16' 32'8'1/16" = 1'-0"1

LIGHTING PLAN - 1ST FLOOR OVERALL

0 4' 8'2'1/4" = 1'-0"2 LIGHTING PLAN - Callout 1

0 4' 8'2'1/4" = 1'-0"3 LIGHTING PLAN - Callout 2

0 4' 8'2'1/4" = 1'-0"4 LIGHTING PLAN - Callout 3

0 4' 8'2'1/4" = 1'-0"5 LIGHTING PLAN - Callout 4

N

M M M

1D1D1D

1D1D1D1D1D

1D 1D 1D

1D1D1D

1D 1D 1D 1D 1D

1D

1D

1D1D1D

1D 1D

D

1DM

M

M

D 1D 1D MM

M

M

M

M M

M

D

D

M

D

D

D

D

D

J

D

M

D

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS

AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.

ASSEMBLY NUMBERS.

4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH

THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND

SPECIFICATIONS.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE

FIRE BARRIER.

8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT

FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR

TO ROUGH-IN.

D

E E

L1C-1L1C-2

G2 G2

HA

HA

HA

G2

HA

G2

F4

G2

HA

X1

KB

X1

KB KB

M4

M4 M4

M4

K3

K3

K3

K3

K3

K3

K3

K3 F4

F4 F4

F4

K3K3

G2

HA

G2

HA

F4

F4 KB

K3

K3

KB

KB

KB X2KBKBKBKBKB KB KB X2

K3 K3

K3K3

K3 K3

K3K3

K3K3

K3 K3

KB

KB

KB

K3

K3

K3

K3

K3

K3

K3

K3K3

K3

K3

K3

K3

K3K3

K3

KB

X1

KBKBKB

KB

KBK3

K3K3

K3

K3 K3

K3K3

K3

K3

K3

K3

KB

KB

KB

KBX1 KB KB

K3

K3

K3

K3

K3

K3

K3

K3

K3

K3

K3

K3

K3

K3

X14

X14

R

R

R

C1C1C1

C1 C1 C1

L4

L4

L4

L4

L4

L4

L4

L4

L4

L4

L4

S4S4S4

L4 L4

L4

L4

L4

X1

X1 R a a a a b b b b a a aa b b bb

3a

3b

3b

3a

3a3b

KB

HA

HA

HA

G2G2

HA

HAHA

K3

K3

K3

K3 K3

K3 K3

K3

K3

K3

R

KB

KB

X1

KB

K2

K2 K2

K2

K2K2

K2

KB

F4

KB

KB

KB KB KB

X1 a aa a b c d b a c d

KB

KB

K3 K3

K3K3

IT-D107

L1D-2

L1D-1

R

F4

KB

K2 K2

L1D-2:24

L1D-2:26

IT-D107:18

L3

L3 L3

L3

L3

L3

L3

L3

L3

L3

NL

NL

NL

NL

NL

NL NL NL

NL

NL

NL

NL

NL

X1

L1D-2:28

X1

NL

E1D:10

L4

E1D:11

NL

ab a a a ab b

E1D:12

E1D:12

L4

L4

L6

L4L4

L4

L4L4

L6

L4

L4

NL

NL

NL

NL

KB NL

X1

E1D:9

L4

L1C-2:41

L3

L3

L3

L3

P3

NL

S4 e e

X1

22.7

25.4

32.5 33.3

33.8

L.5

M

P

P.5

29.1

O.5

N.5

N

O

27 30.928.5

22.2

L

J.8

J

L (E)

K(E)

J(E)

K.8

M.9

L.9

M.3

21.1

K.3

L.3

16 17.2

30 32 33

E1D:13L1C-2:42

KB NL

L1C-2:43

SUD GROUP THERAPY

C136

P. TLT.

A128

P. TLT.

A129

P. TLT.

A105

MSA

A103

ALCOVE

A106

VESTIBULE

A100

VESTIBULE

A102

COURTYARD

D135

SUD OFFICE

C134

SUD OFFICE

C133

P. TLT.

C126

P. TLT.

C125

STOR.

C127

CAROTAS

C128

STAFF LOUNGE

C129

S. TLT.

C131

S. TLT.

C130

VESTIBULE

D109

CWT OFFICE

D108

IT

D107

P. TLT.

D110 BHIP OFFICE

D112

ELEC

D137

STAFF WORK

D113

CONF / CLASS

D114CORRIDOR

1CDR10

CORRIDOR

1CDR10 P. TLT.

D111

HSK

D138

CORRIDOR

1CDR10

BHIP OFFICE

D106

BHIP OFFICE

D105

BHIP OFFICE

D104

BHIP OFFICE

D103

CONSULT

D102

HOLD

D101

CORRIDOR

1CDR10

BHIP OFFICE

D120

BHIP OFFICE

D119

BHIP OFFICE

D118

BHIP OFFICE

D121

BHIP OFFICE

D122

BHIP OFFICE

D123

BHIP OFFICE

D117

BHIP OFFICE

D116

BHIP OFFICE

D115

BHIP OFFICE

D124

BHIP OFFICE

D125

BHIP OFFICE

D126

BHIP OFFICE

D127

BHIP OFFICE

D128

BHIP OFFICE

D129

BHIP OFFICE

D130CONF

D131

BHIP OFFICE

D132

BHIP OFFICE

D133

BHIP OFFICE

D134

STOR.

C132

HALL

A131

LOBBY

A101

CHILDREN'S WAITING

A104

DRINKING FOUNTAIN

A130

CORRIDOR

1CDR7

CORRIDOR

1CDR11

E1D

N

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 pec1.com

Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

KEYPLAN

ISSUED FOR BID

/2

/2

:2

:1

P

M A u to d e s k D o c s

/1

.2

A tr ia x

T o p e k a

V A

M e n ta l H e a lt h C lin ic

(M o d

-0

E

L E

C R

.r v t

EL111

LIGHTING PLAN - FIRST FLOOR

ADDITION

Outpatient Mental Health Clinic

Colmery-O'Neil VAMC Topeka, KS

03/29/2024 DDC RWL

KEYED NOTES:

L3 INTERLOCK LOCAL OCCUPANCY SENSORS PER MANUFACTURER

REQUIREMENTS.

L4 PROVIDE PHOTOCELL ON ROOF FACING NORTH FOR CONTROL OF

CANOPY AND EXTERIOR LIGHT FIXTURES.

P3 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN EXISTING PANELBOARD AS

INDICATED. MATCH EXISTING BREAKER TYPE AND AIC RATING AS

REQUIRED. UPDATE PANEL DIRECTORY.

0 8' 16'4'1/8" = 1'-0"1

LIGHTING PLAN - 1ST FLOOR ADDITION

N

LAY-IN

LIGHT FIXTURE

SECURE FIXTURE

TO GRID (TYPICAL

OF 4 LOCATIONS)

J-BOX

EMT CONDUIT FOR

BRANCH CIRCUITING

CEILING GRID INSTALLED PER GRID

MANUFACTURER (TYPICAL). CEILING

INSTALLER SHALL PROVIDE

ADDITIONAL

GRID SUPPORT AT LIGHT FIXTURE

LOCATIONS AS RRQUIRED.

≤ 3'

≤ 3'

FLEX CONNECTION SIZE

AS REQUIRED - 3/8" MIN.

LENGTH SHALL ALLOW FIXTURE

TO BE RELOCATED 4'-0" IN

ANY DIRECTION.

ALL THREAD

J-BOX SUPPORT

CONDUIT SUPPORT (3'-0"

MAD. FROM J-BOX)

SUPPORT FLEX A MINIMUM OF

6" ABOVE CEILING GRID.

ALL THREAD OR SUPPORT WIRING TO

BUILDING STRUCTURE (TYPICAL).

SUPPORT WIRES SHALL BE SECURED TO

CEILING GRID AND SHALL NOT DEFORM

CEILING GRID INSTALLATION IN ANY

WAY. SUPPORT WIRES SHALL BE

MARKED TO IDENTIFY THEM AS

ELECTRICAL SUPPORT WIRES AND NOT

CEILING GRID SUPPORT WIRES

PER NEC SECTION 300.11.

NOTES:

1. ADDITIONAL LIGHT FIXTURE SUPPORT MAY BE REQUIRED

DUE TO POTENTIAL SEISMIC CONDITIONS, BUILDING

OCCUPANCY, AND FIXTURE TYPE. REFER TO THE

SPECIFICATIONS.

2. MOUNTING AND CONNECTION OF RECESSED CAN LIGHTS

SHALL UTILIZE BAR HANGERS SECURED TO GRID.

ALL THREAD OR SUPPORT WIRE

TO BUILDING STRUCTURE

(TYPICAL OF 4 CORNERS; FOR

ROUND LUMINAIRES, SPACE

SUPPORTS APPROXIMATELY

EQUIDISTANT AROUND).

3 TWIST MINIMUM (TYP)

CEILING MAIN BEAM

GYPSUM BOARD (TYP)

LUMINAIRE MANUFACTURER'S

EARTHQUAKE CLIP, (4) PER

FIXTURE AT CORNERS. ATTACH

WITH SHEET METAL SCREW

CEILING CROSS BEAM

GYPSUM BOARD

CEILING CROSS BEAM

LUMINAIRE.

REFER TO

SCHEDULE

DRYWALL BORDER

LUMINAIRE

SUSPENSION WIRES (#

10 MIN) ATTACHED TO

STRUCTURE (TYP EA.

CORNER)

FIXTURE WHIP FROM

JUNCTION BOX (6FT.

LONG MAX.)

LUMINAIRE.

REFER TO

SCHEDULE

SEAL JOINT BETWEEN

CEILING AND LIGHTING

FIXTURE

1. GENERAL CONTRACTOR SHALL PROVIDE FIREPROOFING AROUND RECESSED FIXTURES INSTALLED IN FIRE RATED CEILING PER U.L. REQUIREMENTS. ELECTRICAL CONTRACTOR WILL

COORDINATE.

2. MANUFACTURERS LISTED IN THIS SCHEDULE OR APPROVED BY WRITTEN ADDENDUM WILL BE THE ONLY APPROVED MANUFACTURERS TO BID THE LIGHTING FIXTURES FOR THIS PROJECT.

CONTRACTORS AND SUPPLIERS USING PRICING FROM MANUFACTURERS NOT LISTED ON SCHEDULE OR BY ADDENDUM DO SO AT THEIR OWN RISK.

3. LIGHT FIXTURE SELECTIONS ARE BASED ON THE MANUFACTURER IN THE LEFT MOST COLUMN AS LISTED IN THE SCHEDULE. FIXTURES APPROVED AS EQUALS IN THIS SCHEDULE OR BY ADDENDUM SHALL BE EQUAL TO THE UNIT SPECIFIED IN THE LEFT MOST COLUMN, IE: SPRING LOADED LATCHES, POST PAINTED FINISH, AND PHOTOMETRICS.

4. ALL LIGHT FIXTURES SHALL BE SECURED TO THE CEILING FRAMING SYSTEM BY MECHANICAL MEANS (SUCH AS BOLTS, SCREWS, OR RIVETS) OR BY CLIPS IDENTIFIED FOR USE WITH THE TYPE

OF CEILING FRAMING MEMBER AND LIGHT FIXTURE.

5. LIGHT FIXTURES SHALL BE PROVIDED WITH 0-10V DIMMING DRIVERS. DRIVERS SHALL BE CAPABLE OF DIMMING TO A MINIMUM OF 10% OF TOTAL LIGHT OUTPUT. LED DRIVERS SHALL HAVE A DISCONNECTING MEANS MEETING THE REQUIREMENTS OF NEC SECTION 410.130(G), EXCEPT FOR THOSE INSTALLED IN CORD-AND-PLUG CONNECTED FIXTURES. WHERE APPLICABLE, WHEN DIMMING SWITCHES ARE NOT PROVIDED AS PART OF THE DESIGN, CONTRACTOR SHALL CAP OFF 0-10V DIMMING WIRES FOR FUTURE EXTENSION BY OWNER.

6. PROVIDE ARROWS AND FACES AS INDICATED ON THE DRAWINGS.

LIGHTING FIXTURE SCHEDULE NOTES

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 pec1.com

Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

ISSUED FOR BID

/2

/2

:2

:1

P

M A u to d e s k D o c s

/1

.2

A tr ia x

T o p e k a

V A

M e n ta l H e a lt h C lin ic

(M o d

-0

E

L E

C R

.r v t

EL501

LIGHTING DETAILS Outpatient Mental Health Clinic

Colmery-O'Neil VAMC Topeka, KS

03/29/2024 DDC RWL 139 170

N0 SCALE

TYPICAL LAY-IN FIXTURE INSTALLATION

N0 SCALE

TYPICAL GYP FIXTURE INSTALLATION

LIGHTING FIXTURE SCHEDULE

MARK DESCRIPTION

MANUFACTURER 1

CATALOG NUMBER

MANUFACTURER 2

CATALOG NUMBER

LIGHT SOURCE

LENS/LOUVER/FINISH

DIMENSIONS REF.

NOTE

REMARKS

# TYPE WATTS VOLTS W L D

C1 4" RECESSED

LINEAR

A LIGHT D54-LH-35-HE-XP-B-D-E-Q AXIS LIGHTING EX4R-1000-80-35-BW-4-WDF 1 LED 28 UNV ACRYLIC .5 4.0 0.33 5 3048LM; 3500K; 80CRI, DAMP LOCATION

RATED

D EXISTING

FIXTURE TO BE

REMOVED

1 0

E EXISTING

FIXTURE TO

REMAIN

1 LED 5 7

F4 4' STRIP COLUMBIA MPS-35HL-CW-EU LITHONIA

ZL1N-L48-5000LM-FST-MVOLT-35K-80CRI

1 LED 34 UNV ACRYLIC 0.23 4.0 0.17 5 5000LM; 3500K; 80CRI

G2 2' WALL

MOUNTED

LIGHTWAY VTEV24-LED-02B-3-T4-WSA-DIM OXYGEN 3-524-24 1 LED 15 UNV WHITE SMOOTH

ACRYLIC

0.88 2.0 0.42 5 2000LM; 3500K; 80CRI; MOUNT 6" ABOVE

VANITY MIRROR

HA 4" RECESSED

DOWNLIGHT

W/LENS

PRESCOLITE

LTR-4RD-H-SL15L-DM1-LTR-4RD-T-SL35K8MD-SS

GOTHAM EVO4-35K/25-AR-MD-LSS-GZ1 1 LED 19 UNV SEMI-CLEAR 1.17 1.32 0.55 5 1500LM; 3500K; 80CRI

K2 2X4 LAY-IN COLUMBIA LCAT24-35XWG-ED LITHONIA 2BLT4-30L-ADP-EZ1-LP835 1 LED 19 UNV ACRYLIC 2.0 4.0 0.33 5 2383LM; 3500K; 80CRI

K3 2X4 LAY-IN COLUMBIA LCAT24-35MWG-ED LITHONIA 2BLT4-40L-ADP-EZ1-LP835 1 LED 30 UNV ACRYLIC 2.0 4.0 0.33 5 3424LM; 3500K; 80CRI

KB 2X2 LAY-IN COLUMBIA LCAT22-35MLG-EDU LITHONIA 2BLT2-33L-ADP-EZ1-LP835 1 LED 29 UNV ACRYLIC 2.0 2.0 0.33 5 3000LM; 3500K; 80CRI

L4 4" WIDE LAY-IN LITECONTROL 4L-LGD4-04SOFC135K-D065-D01-1C MARK ARCH LIGHTING

SL4L-LOP-4FT-FLP-TG-80CRI-35K-350LMF MINI

120ZT

1 LED 23 UNV SOFT DIFFUSE

ACRYLIC

1.0 4.0 0.33 5 2600LM; 3500K; 80CRI

L6 4" WIDE LAY-IN LITECONTROL 4L-LGD4-06SOFC135K-D065-D01-1C MARK ARCH LIGHTING

SL4L-LOP-6FT-FLP-TG-80CRI-35K-350LMF MINI

120ZT

1 LED 34 UNV SOFT DIFFUSE

ACRYLIC

1.0 6.0 0.33 5 3900LM; 3500K; 80CRI

M4 2X4 RECESSED -

VANDAL

KURTZON VLR3-2X4-2/LEDR/835-2/6 LUMINAIRE LED

RMP-R24-FH16CRSP-D16SSB-PRD-7300LM-35K-AL

S-2ES-WHT

1 LED 68 UNV ACRYLIC 2.0 4.0 0.33 5 7230LM; 3500K; 80CRI

R EXTERIOR WALL

PACK

KIM LIGHTING WDSD-24L-40-4K7-3 LITHONIA

ASW1-LED-42C-350-40K-SR2-MVOLT-DDBXD

1 LED 40 UNV DARK BRONZE 1.15 1.25 0.77 4000LM; 4000K; 70CRI, MOUNT 10'-0"

ABOVE GRADE

S4 2" SUSPENDED

LINEAR

LITECONTROL 2LPD04-SOF35K-D050-D011C-FA1 MARK ARCHITECTURAL LIGHTING

S2PD-LLP-4FT-MSL4-600LMF

1 LED 21 UNV SOFT DIFFUSE

ACRYLIC

1.0 4.0 0.33 5 2000LM; 3500K; 80CRI

X1 1 FACE/EM.

BATT.

MULE MD-A-U-R-BA ACUITY LESR 1 LED 5 UNV CAST ALUMINUM 0.71 1.06 0.17 6 RED W/ EMERGENCY BATTERY

X2 2 FACE/EM.

BATT.

MULE MD-A-U-R-BA ACUITY LESR 1 LED 5 UNV CAST ALUMINUM 0.74 1.06 0.17 6 RED W/ EMERGENCY BATTERY

X14 1 FACE/EM.

BATT.

MULE N4X-AX-1-R ACUITY LVSR 1 LED 5 UNV NEMA-4X 0.98 0.98 0.42 6 RED W/ EMERGENCY BATTERY

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY NUMBERS.

5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE

WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS

AND SPECIFICATIONS.

6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE

MOLDABLE FIRE BARRIER.

9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

LBA

SBA

B2

CT FANCWP

ESM.T.S.

FACP

MSB

ES2

RECONNECT TO EXISTING

EMERGENCY POWER CIRCUIT

SERVING FACP AS REQUIRED.

N

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 pec1.com

Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

KEYPLAN

ISSUED FOR BID

/2

/2

:2

:1

P

M A u to d e s k D o c s

/1

.2

A tr ia x

T o p e k a

V A

M e n ta l H e a lt h C lin ic

(M o d

-0

E

L E

C R

.r v t

EP101

POWER PLAN - BASEMENT Outpatient Mental Health Clinic

Colmery-O'Neil VAMC Topeka, KS

03/29/2024 DDC RWL

0 4' 8'2'1

POWER PLAN - BASEMENT

N

H

H

H

J JJ

H

H

HH

J

J

J JJ

HH

H

H

H

H

H

H

J

J

J J

J

J J

JJ

J

J

J

J

J

J

J

JJ

J

J

H

H

J

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY NUMBERS.

5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE

WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS

AND SPECIFICATIONS.

6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE

MOLDABLE FIRE BARRIER.

9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

22.7

25.4

33.8

L.5

M

P

P.5

O.5

N.5

N

O

22.2

L

J.8

J

L (E)

K(E)

J(E)

K.8

M.9

L.9

M.3

21.1

EP110

EP110

EP110

EP110

E1D:7

P12

CORRIDOR

A261

#10

E1D:7

P12

WAITING AREA

A255

#10

EXISTING DOOR

CONTROLS TO REMAIN.

CORRIDOR

A274

E1D:8

P12

CORRIDOR

A325

#10

N

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 pec1.com

Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

KEYPLAN

ISSUED FOR BID

/2

/2

:2

:1

P

M A u to d e s k D o c s

/1

.2

A tr ia x

T o p e k a

V A

M e n ta l H e a lt h C lin ic

(M o d

-0

E

L E

C R

.r v t

EP110

POWER PLAN - FIRST FLOOR

OVERALL

Outpatient Mental Health Clinic

Colmery-O'Neil VAMC Topeka, KS

03/29/2024 DDC RWL

KEYED NOTES:

P12 PROVIDE 120V. CONNECTION TO ACCESS CONTROL DOOR CONTROLLER.

VERIFY ALL REQUIREMENTS WITH SYSTEM MANUFACTURER AS REQUIRED.

0 16' 32'8'1/16" = 1'-0"1

POWER PLAN - 1ST FLOOR OVERALL

0 4' 8'2'1/4" = 1'-0"2 POWER PLAN - Callout 1

0 4' 8'2'1/4" = 1'-0"3 POWER PLAN - Callout 2

0 4' 8'2'1/4" = 1'-0"4 POWER PLAN - Callout 3

0 4' 8'2'1/4" = 1'-0"5 POWER PLAN - Callout 4

N

H

H

J

J

J J

JJ

J

J

J

J

J

J

J

J

J

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY NUMBERS.

5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE

WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS

AND SPECIFICATIONS.

6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE

MOLDABLE FIRE BARRIER.

9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

CT

CT CT

CT

CT

CT

CT CT CT REF.

CT

CT

WP

FB FB

FB

FB

P1

P1

P1P1

L1C-2

L1C-1

FB

P1

P1

L1D-1

L1D-2

88" 88" 88" 88"

88"

88" 88" 88" 88"

88" 88"

88"

CT88"

88"

88" 88"CT 88" 88"

L1D-1:1

EP111

IT-D107

L1D-1:3

L1D-1:5L1D-1:7L1D-1:9L1D-1:11L1D-1:13

L1D-1:15

COPIER

COUNTERTOP

PRINTER

L1D-1:17

L1D-1:19

L1D-1:21

L1D-1:25

L1D-1:23

L1D-1:27

L1D-1:29

L1D-1:4

L1D-1:2

L1D-1:6

L1D-1:8

L1D-1:10

L1D-1:16 L1D-1:14

L1D-1:12

L1D-1:18

L1D-1:20L1D-1:22L1D-1:24

L1D-1:30 L1D-1:28 L1D-1:26

88"88"

88" 88"

88"

88"

L1D-2:11L1D-2:5L1D-2:7

L1D-2:9 L1D-2:3 L1D-2:1

E1D:4

P2

WP

L1D-2:13

WP

L1D-2:15

E1D:2 P2

L1D-2:17

L1D-2:19

L1D-2:25 L1D-2:23

L1D-2:21

E1D:6

P1 P1P2

L1C-2:29

L1C-2:31

88"88"

L1C-2:30

L1C-2:35

L1C-2:32 L1C-2:33

46"

ICE MACHINE

L1C-2:34

L1C-2:36 L1C-2:40

L1C-2:39

L1C-2:37

COPIER

L1D-2:22

L1D-2:20

P

WTV

L1D-1:31

P

WTV

L1D-1:33

60"

L1C-2:38

WTV

88"

E1D:1

P12

IT-D107:20

CT

DF

L1C-2:28

P12

P12

P12

P12

P12

#10 #10

#10

#10

#10 #10

#10

P12

P12 E1D:3

PHARMACY

KIOSK

E1D:15

NAC

PANEL

P12

P12

22.7

25.4

32.5 33.3

33.8

L.5

M

P

P.5

O.5

N.5

N

O

L

J.8

J

L (E)

K(E)

J(E)

K.8

M.9

L.9

M.3

21.1

L1C-2:27

SUD GROUP THERAPY

C136

P. TLT.

A128

P. TLT.

A129

P. TLT.

A105

MSA

A103

ALCOVE

A106

VESTIBULE

A100

VESTIBULE

A102

COURTYARD

D135

SUD OFFICE

C134

SUD OFFICE

C133

P. TLT.

C126

P. TLT.

C125

STOR.

C127

CAROTAS

C128

STAFF LOUNGE

C129

S. TLT.

C131

S. TLT.

C130

VESTIBULE

D109

CWT OFFICE

D108

IT

D107

P. TLT.

D110 BHIP OFFICE

D112

ELEC

D137

STAFF WORK

D113

CONF / CLASS

D114

CORRIDOR

1CDR10

CORRIDOR

1CDR10

P. TLT.

D111

HSK

D138

CORRIDOR

1CDR10

BHIP OFFICE

D106

BHIP OFFICE

D105

BHIP OFFICE

D104

BHIP OFFICE

D103

CONSULT

D102HOLD

D101

CORRIDOR

1CDR10

BHIP OFFICE

D120

BHIP OFFICE

D119

BHIP OFFICE

D118

BHIP OFFICE

D121

BHIP OFFICE

D122

BHIP OFFICE

D123

BHIP OFFICE

D117

BHIP OFFICE

D116

BHIP OFFICE

D115

BHIP OFFICE

D124

BHIP OFFICE

D125

BHIP OFFICE

D126

BHIP OFFICE

D127

BHIP OFFICE

D128

BHIP OFFICE

D129

BHIP OFFICE

D130CONF

D131

BHIP OFFICE

D132

BHIP OFFICE

D133

BHIP OFFICE

D134

STOR.

C132

E1D

HALL

A131

LOBBY

A101

CHILDREN'S WAITING

A104

E1D:5

DRINKING FOUNTAIN

A130

CORRIDOR

1CDR7

IT-D107

IT-D107:1

IT-D107:3

R

R

R

IT-D107:5,7,9

IT-D107:11

#10

#10

P4P4

IT2

IT2

IT2

IT-D107:13,15,17

IT-D107:19

P4P4

IT-D107:16

#10

IT-D107:10,12,14

P4P4

TGB-D107

N.E.C. REQUIRED

WORKING CLEARANCE

M

28.5

N

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 pec1.com

Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

KEYPLAN

ISSUED FOR BID

/2

/2

:2

:2

P

M A u to d e s k D o c s

/1

.2

A tr ia x

T o p e k a

V A

M e n ta l H e a lt h C lin ic

(M o d

-0

E

L E

C R

.r v t

EP111

POWER PLAN - FIRST FLOOR

ADDITION

Outpatient Mental Health Clinic

Colmery-O'Neil VAMC Topeka, KS

03/29/2024 DDC RWL

KEYED NOTES:

P1 PROVIDE 120V. CONNECTION TO MOTORIZED DOOR OPERATOR. VERIFY

ALL REQUIREMENTS WITH DOOR HARDWARE SUPPLIER.

P2 PROVIDE 120V. 20A. 1P. CONNECTION TO EXISTING SPARE BREAKER IN

PANELBOARD AS INDICATED. UPDATE PANEL DIRECTORY

P4 PROVIDE DEDICATED DOUBLE DUPLEX RECEPTACLE AND SPECIAL OUTLET

‘IT2’ ON BOTTOM OF DATA RACK. COORDINATE OVERHEAD CONDUIT

ROUTING WITH CABLE TRAY, LIGHTS, ETC. AS REQUIRED PRIOR TO

ROUGH-IN.

P12 PROVIDE 120V. CONNECTION TO ACCESS CONTROL DOOR CONTROLLER.

VERIFY ALL REQUIREMENTS WITH SYSTEM MANUFACTURER AS REQUIRED.

0 8' 16'4'1/8" = 1'-0"1

POWER PLAN - 1ST FLOOR ADDITION

0 4' 8'2'1/4" = 1'-0"2

ENLARGED POWER PLAN - IT D107

N

J

J

J

J J

J J

F F

J

JF

J

F F

J

J

J

J

J J

JJ

J J

J J

F F

F F

J

JJJJ

L1D-2:27

P7

P7

P7

L1A-2:1

L1D-2:29

L1D-2:2

P6

P6 P5P5

P5P5

L1A-2:3

P2

P2

P6

P5P5

P8

L1D-2:4

L1C-1:24

P6 P6

P5 P5

P5 P5

L1C-1:26

L1C-1:28

P2

P6

P6P5P5

P5P5

P2 P2

P6 P6

P5P5 P5P5

L1C-1:30

P8

P2

P10P10P10

P9P9P9 L1A-2:5

P10

P9

22.7

25.4

32.5 33.3

33.8

L.5

M

P

P.5

O.5

N.5

N

O

L

J.8

J

L (E)

K(E)

J(E)

K.8

M.9

L.9

M.3

K.3

L.3

16 17.2 34

SUD GROUP THERAPY

C136

P. TLT.

A128

P. TLT.

A129

P. TLT.

A105

MSA

A103

ALCOVE

A106

VESTIBULE

A100

VESTIBULE

A102

COURTYARD

D135

SUD OFFICE

C134

SUD OFFICE

C133

P. TLT.

C126

P. TLT.

C125

STOR.

C127

CAROTAS

C128

STAFF LOUNGE

C129

S. TLT.

C131

S. TLT.

C130

VESTIBULE

D109

CWT OFFICE

D108

IT

D107

P. TLT.

D110

BHIP OFFICE

D112

ELEC

D137

STAFF WORK

D113

CONF / CLASS

D114

CORRIDOR

1CDR10

CORRIDOR

1CDR10

P. TLT.

D111

HSK

D138

CORRIDOR

1CDR10

BHIP OFFICE

D106

BHIP OFFICE

D105

BHIP OFFICE

D104

BHIP OFFICE

D103

CONSULT

D102HOLD

D101

CORRIDOR

1CDR10

BHIP OFFICE

D120

BHIP OFFICE

D119

BHIP OFFICE

D118

BHIP OFFICE

D121

BHIP OFFICE

D122

BHIP OFFICE

D123

BHIP OFFICE

D117

BHIP OFFICE

D116

BHIP OFFICE

D115

BHIP OFFICE

D124

BHIP OFFICE

D125

BHIP OFFICE

D126

BHIP OFFICE

D127

BHIP OFFICE

D128

BHIP OFFICE

D129

BHIP OFFICE

D130CONF

D131

BHIP OFFICE

D132

BHIP OFFICE

D133

BHIP OFFICE

D134

STOR.

C132

HALL

A131

LOBBY

A101

CHILDREN'S WAITING

A104

DRINKING FOUNTAIN

A130

CORRIDOR

1CDR7

2-TU-2.09

2-TU-2.06

2-TU-2.10

2-TU-2.05

2-TU-2.03

2-TU-2.02

2-TU-2.01

2-MS-IU-02

2-MS-IU-01

2-TU-2.14

2-TU-2.07

2-TU-2.08

2-TU-2.11

2-TU-2.12

2-TU-2.13

2-TU-2.15

2-TU-2.16

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY NUMBERS.

5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN

ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE

STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING

CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE

WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS

AND SPECIFICATIONS.

6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE

SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL

DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY

THE SPECIFIC U.L. ASSEMBLY.

8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED

WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON

OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET

BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE

MOLDABLE FIRE BARRIER.

9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE

THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.

N

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 pec1.com

Atriax, pllc 703 Main Avenue SW, Hickory, NC 28062 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

KEYPLAN

ISSUED FOR BID

/2

/2

:2

:2

P

M A u to d e s k D o c s

/1

.2

A tr ia x

T o p e k a

V A

M e n ta l H e a lt h C lin ic

(M o d

-0

E

L E

C R

.r v t

EP211

EQUIPMENT PLAN - FIRST FLOOR

ADDITION

Outpatient Mental Health Clinic

Colmery-O'Neil VAMC Topeka, KS

03/29/2024 DDC RWL

0 8' 16'4'1/8" = 1'-0"1

EQUIPMENT PLAN - 1ST FLOOR ADDITION

KEYED NOTES:

P2 PROVIDE 120V. 20A. 1P. CONNECTION TO EXISTING SPARE BREAKER IN

PANELBOARD AS INDICATED. UPDATE PANEL DIRECTORY

P5 PROVIDE 120V. CONNECTION TO PLUMBING FIXTURE SENSOR.

COORDINATE EXACT LOCATION WITH MECHANICAL PRIOR TO ROUGH-IN.

P6 PROVIDE FUSTAT ABOVE ACCESSIBLE CEILING FOR DISCONNECTING

MEANS TO ALL PLUMBING SENSORS LOCATED IN ROOM.

P7 PROVIDE 120V. 20A. CONNECTION TO HEAT TRACE LOCATED AT ROOF

DRAINS AS REQUIRED. VERIFY EXACT LOCATION AND ALL REQUIREMENTS

WITH MECHANICAL PRIOR TO ROUGH-IN. PROVIDE TOGGLE SWITCH IN

LOCATION DETERMINED BY OWNER FOR CONTROL OF HEAT TRACE

SYSTEM AS REQUIRED. LABEL SWITCH FACEPLATE.

P8 PROVIDE 120V. 20A. FUSTAT FOR CONNECTION TO LOW-VOLTAGE

TRANSFORMER SERVING TERMINAL UNITS AS REQUIRED. COORDINATE

EXACT LOCATION AND ALL REQUIREMENTS WITH MECHANICAL PRIOR TO

ROUGH-IN.

P9 PROVIDE 120V. 20A. CONNECTION TO MOTORIZED COILING GATE AT

RECEPTION DESK AS REQUIRED. COORDINATE EXACT LOCATION WITH

ARCHITECT PRIOR TO ROUGH-IN.

P10 PROVIDE UP/DOWN CONTROL SWITCH FOR MOTORIZED GATE AS

REQUIRED. VERIFY SWITCH LOCATION WITH OWNER PRIOR TO ROUGH-IN.

N

R

R

S

S

WP

WP

WP

L1B-2:9

OUTLET ON ROOF

AT EQUIPMENT.

TYPICAL.

L1C-2:1

P2

P2

WP

L1D-2:6

FAN

FAN

R

S

R S

2-AHU-2A/2B

2-AHU-1A/1B

L.5

M

P

P.5

O.5

N

O

L

K(E)

J(E)

M.9

L.9

M.3

A

B

K.3

L.3

2 2.8

3 4

5.8

8 10

1112 13

16 17.2 29.1 34 354.5

7 9 9.8 15 17 31 33.1

EQUIPMENT PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED

TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE

SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL

CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR

LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED

U.L. ASSEMBLY NUMBERS.

5. FOR…