Previous Report for Buildings 35 and 36.pdf
PDF 534 KB Posted
- Attached to
- H359--Electrical Equipment Testing - CI Period of Performance: 07/01/2023 - 06/30/2024 PO: 636C37117
- Solicitation number
- 36C26323Q0650
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S06. 36C26323Q0650 0002.pdf | ||
| 25051529-035 BOM.rtf | RTF text file | |
| 36C26323Q0650 0002_1.docx | DOCX document | |
| 25051529-031 and 036 BOM.rtf | RTF text file | |
| 25051529-035-COMBINED.pdf | ||
| 25051529-031-COMBINED.pdf | ||
| 25051529-033 BOM.rtf | RTF text file | |
| 25051529-036-COMBINED.pdf | ||
| 25051529-033-COMBINED.pdf | ||
| 36C26323Q0650 0001_1.docx | DOCX document | |
| Campus One-Line with Cottage Included.pdf | ||
| 20230524_132324.jpg | JPG image | |
| S06. 36C26323Q0650 0001.pdf | ||
| S02. 36C26323Q0650 Electrical Equipment Testing - CI.pdf | ||
| 36C26323Q0650_1.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MEDIUM-VOLTAGE
CIRCUIT BREAKE
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310 ADDRESS
; 3600 30th St ; Des Moines IA 503
CMMS # ̀
EQPT. LOCATION
DATE 05-Oct-2017 TEMPERATURE 72 °F HUMIDITY 86 % CIRCUIT ID MAIN BRKR 52-2 SUBSTATION 36th St Service TEST STATUS Pass
MANUFACTURER:
BREAKER TYPE:
Square D
VR
CATALOG:
SERIAL NO.:
V5D6133Y000
17 59666
AGE:
BIL LEVEL:
8 YEARS
INTERRUPTING TIME: 3 CYCLES AMPACITY: 1200 A OPERATING VOLTAGE: 13.2 kV
INTERRUPT CAPACITY:
OTHER:
25 kA MAX VOLTAGE: 15 kV
OPERATING MECHANISM:
Spring-charged
VISUAL & MECHANICAL INSPECTION Sat Unsat N/A Note No.: Sat Unsat N/A Note No.:
Compare nameplate data with drawings & specifications.**
Check cell fit and element alignment.
Inspect physical and mechanical condition.
Inspect puffer operation.
Verify**/Utilize** correct application of manufacturer's recommended lubricants.
Check racking mechanism.
Inspect anchorage, alignment, grounding, arc chutes. Inspect moving and stationary contacts for condition, wear and alignment.
Clean unit prior to testing unless as-found and as-left tests are required.***
Perform circuit breaker travel time test.
Verify that all maintenance devices are available for servicing and operating the breaker.
Inspect all bolted electrical connections for high resistance using one of the following methods:
Low Resistance Ohmmeter Torque Wrench hermographic Survey Perform all mechanical operator (inc. slow close) and contact alignment tests on both the breaker and its operating mechanism.
**Acceptance Testing Only ***Maintenance Testing Only
TEST RESULTS
RESISTANCE
MEASUREMENTS
POLE 1 POLE 2 POLE 3
OVERPOTENTIAL TEST (in microamps)
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
POLE 1 POLE 2 POLE 3 BOLTED CONNECTION
RESISTANCE
(Microhms)
Line - - - - - -
Load - - - - - - 1.1 1 1.2
CONTACT RESISTANCE
(Microhms) 34 34 41 41 37 37 Test kV 19 kV (VLF RMS) 27 kV MAX
COMMENTS:
DEFICIENCIES:
TESTED BY
INSULATION RESISTANCE in Megohm @ 5 kVdc
POLE 1 (P1-P2) POLE 2 (P2-P3) POLE 3 (P1-P3)
Pole to Pole 219,000 186,400 180,300
Pole to Frame 145,000 121,600 97,300
Line to Load 263,000 221,000 253,000
OPERATIONAL TESTS Performed/ Note Verified No.
Trip and close breaker with control switch.
Trip breaker by operating each protective device.
Verify trip-free and anitpump function.
Perform insulation resistance test on control wiring.
Verify operation of heaters.
PICK-UP VOLTAGE TEST
VOLTAGE RANGE PICK-UP VOLTAGE
Shunt Trip N/A N/A N/A
Close Coil N/A N/A N/A
TIMING TEST POLE 1 POLE 2 POLE 3
Open Speed - - -
Close Speed - - -
COUNTER
READING
AS FOUND 118
AS LEFT 119
CONTACT MEASUREMENT (in inches)
POLE 1 POLE 2 POLE 3
Contact Gap Sat Sat Sat
Contact Erosion Sat Sat Sat
BLOWOUT COIL
RESISTANCE (Ohms)
POLE 1 POLE 2 POLE 3 N/A
VACUUM BOTTLE INTEGRITY POLE 1 POLE 2 POLE 3 N/A
Test kV 15 (rms) 0.4uA 0.5uA
MEDIUM-VOLTAGE
CIRCUIT BREAKE
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310 ADDRESS
USER 3600 30th St ; Des Moines IA 50310 CMMS #
EQPT. LOCATION
DATE 06-Oct-2017 TEMPERATURE 65 °F HUMIDITY 100 % CIRCUIT ID MAIN BRKR 52-1 SUBSTATION Douglas Service TEST STATUS Pass
MANUFACTURER:
BREAKER TYPE:
Square D
VR
CATALOG:
SERIAL NO.:
V5D6133Y000
17 59666
AGE:
BIL LEVEL:
8 YEARS
INTERRUPTING TIME: 3 CYCLES AMPACITY: 1200 A OPERATING VOLTAGE: 13.2 kV
INTERRUPT CAPACITY:
OTHER:
25 kA MAX VOLTAGE: 15 kV
OPERATING MECHANISM:
Spring-charged
VISUAL & MECHANICAL INSPECTION Sat Unsat N/A Note No.: Sat Unsat N/A Note No.:
Compare nameplate data with drawings &
Check cell fit and element alignment.
Inspect physical and mechanical condition.
Inspect puffer operation.
Verify**/Utilize** correct application of manufacturer's recommended lubricants.
Check racking mechanism.
Inspect anchorage, alignment, grounding, arc chutes. Inspect moving and stationary contacts for condition, wear and alignment.
Clean unit prior to testing unless as-found and as-left tests are required.***
Perform circuit breaker travel time test.
Verify that all maintenance devices are available for servicing and operating the breaker.
Inspect all bolted electrical connections for high resistance using one of the following methods:
Low Resistance Ohmmeter Torque Wrench hermographic Survey Perform all mechanical operator (inc. slow close) and contact alignment tests on both the breaker and its operating mechanism.
TEST RESULTS
MEASUREMENTS
POLE 1 POLE 2 POLE 3
OVERPOTENTIAL TEST (in microamps)
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
POLE 1 POLE 2 POLE 3 BOLTED CONNECTION
RESISTANCE
(Microhms)
Line - - - - - -
Load - - - - - - 7.3 7.0 7.7
CONTACT RESISTANCE
(Microhms) 22 22 26 26 27 27 Test kV 19 kV (VLF RMS) 27 kV MAX
TESTED BY:
INSULATION RESISTANCE in Megohm @ 5 kVdc
POLE 1 (P1-P2) POLE 2 (P2-P3) POLE 3 (P1-P3)
Pole to Pole 15900 8550 13700
Pole to Frame 5100 6450 6650
Line to Load 11600 12300 11700
OPERATIONAL TESTS Performed/ Note Verified No.
Trip and close breaker with control switch.
Trip breaker by operating each protective device.
Verify trip-free and anitpump function.
Verify operation of heaters.
PICK-UP VOLTAGE TEST
VOLTAGE RANGE PICK-UP VOLTAGE
Shunt Trip N/A N/A N/A
Close Coil N/A N/A N/A
TIMING TEST POLE 1 POLE 2 POLE 3
Open Speed - - -
Close Speed - - -
COUNTER
READING
AS FOUND
AS LEFT
CONTACT MEASUREMENT (in inches)
POLE 1 POLE 2 POLE 3
Contact Gap SAT SAT SAT
Contact Erosion SAT SAT SAT
BLOWOUT COIL
RESISTANCE (Ohms)
POLE 1 POLE 2 POLE 3 N/A
VACUUM BOTTLE INTEGRITY POLE 1 POLE 2 POLE 3 N/A
Test kV 15 AC 3.1 2.6 2.9
AIR SWITCH
CUSTOMER 4
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310 3600 30th St ; Des Moines IA 50310
ADDRESS
USER CMMS #
EQPT. LOCATION
COMMENTS:
DEFICIENCIES:
TEST EQUIPMENT USED: TEST
C.
Pole 1 (P1-P2) Pole 2 (P2-P3) Pole 3 (P3-P1)
Pole to Pole 38,700 27,200 41,900 Pole to Ground 15,600 21,000 17,100
Line to Load 44,400 49,700 58,900
OVERPOTENTIAL TEST (Microamps) @ 27 kV AC
Pole 1 Pole 2 Pole 3
450 520 520
DATE 05-Oct-2017 TEMPERATURE 72 °F HUMIDITY 86 % CIRCUIT ID Feeder #1 Switch
NAMEPLATE DATA FUSE DATA
Manufacturer: Square D Manufacturer: N/A
Type: Load Current Interruptor Switch Class: N/A
Serial No: N/A Catalog No: N/A
Voltage: 15 Amps: 600 Voltage: N/A Amps: N/A
Catalog No: N/A Interrupt Rating: N/A Holder:
N/A B.I.L. Rating: 95 Other: Refill Element Type: N/A
Momentary Fault Closing Amp: 40 kA T.C.C. No: N/A
VISUAL AND MECHANICAL INSPECTION
Sat Unsat N/A Note No.:
Compare nameplate data with drawings and
Compare switchblade clearances with industry standards.
Sat Unsat N/A Note No.:
Inspect physical and mechanical condition. Inspect all indicating and control devices for correct operation. Verify**/Utilize***correct application of manufacturer's recommended lubricants. Inspect insulating assemblies for evidence of physical damage or contaminated surfaces.*** Verify appropriate anchorage and required area clearances. Exercise all active components.***
Verify appropriate equipment grounding. Verify operation of heaters, if applicable.
Verify correct blade alignment, blade penetration, travel stops, and mechanical operation.
Clean unit prior to testing unless as-found and as-left tests are required.***
Verify that fuse sizes and types are in accordance with drawings, short-circuit and coordination studies. Inspect all bolted electrical connections for high resistance using one of the following methods:
Verify that expulsion-limiting devices are in place on all holders having expulsion-type elements.
Verify that each fuse holder has adequate mechanical support.
Low Resistance Torque Ohmmeter Wrench
Thermographic Survey
Verify correct phase-barrier materials and installation.** Test all interlocking systems for correct operation and sequencing.
ELECTRICAL TESTS
MEASUREMENTS
POLE 1 POLE 2 POLE 3
As Found As Left As Found As Left As Found As Left
Fuse Resistance (Microhms) N/A N/A N/A N/A N/A N/A Fuse Holder - Top/Bottom (Microhms) N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A
Contact Resistance (Microhms) 59 59 61 61 65 65
Counter Reading
As Found
As Left
CUSTOMER 5
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310 3600 30th St ; Des Moines IA 50310
ADDRESS
USER CMMS #
EQPT. LOCATION
COMMENTS:
DEFICIENCIES:
Pole to Pole 45,300 32,900 39,100
Line to Load 57,600 53,200 54,000
360 300 320
DATE 05-Oct-2017 TEMPERATURE 72 °F HUMIDITY 86 % CIRCUIT ID Feeder #2 Switch
Type: Load Current Interruptor Switch Class: N/A
Sat Unsat N/A Note No.:
Inspect physical and mechanical condition. Inspect all indicating and control devices for correct operation. Verify**/Utilize***correct application of manufacturer's recommended lubricants. Inspect insulating assemblies for evidence of physical damage or contaminated surfaces.*** Verify appropriate anchorage and required area clearances. Exercise all active components.***
Verify appropriate equipment grounding. Verify operation of heaters, if applicable.
Verify correct blade alignment, blade penetration, travel stops, and mechanical operation.
Clean unit prior to testing unless as-found and as-left tests are required.***
Verify that fuse sizes and types are in accordance with drawings, short-circuit and coordination studies. Inspect all bolted electrical connections for
Low Resistance Torque Ohmmeter Wrench
Thermographic Survey
Verify correct phase-barrier materials and installation.**
MEASUREMENTS
POLE 1 POLE 2 POLE 3
As Found As Left As Found As Left As Found As Left
Fuse Resistance (Microhms) N/A N/A N/A N/A N/A N/A Fuse Holder - Top/Bottom (Microhms) N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A
Contact Resistance (Microhms) 63 63 69 69 65 65
As Found
CUSTOMER 6
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310 3600 30th St ; Des Moines IA 50310
ADDRESS
USER CMMS #
EQPT. LOCATION
COMMENTS:
DEFICIENCIES:
Pole to Pole 44,500 34,300 35,500
Line to Load 54,600 42,300 49,900
240 240 230
DATE 05-Oct-2017 TEMPERATURE 57 °F HUMIDITY 86 % CIRCUIT ID Feeder #3 Switch
Manufacturer: Square D Manufacturer: Square D
Type: Load Current Interruptor Switch Class: N/A
Serial No: N/A Catalog No: 175GDMSJD25E
Voltage: 15 Amps: 600 Voltage: 17.5 kV Amps: 25
Catalog No: N/A
Interrupt Rating: 65 kA Holder:
Clip B.I.L. Rating: 95 Other:
Refill Element Type: N/A
Sat Unsat N/A Note No.:
Inspect physical and mechanical condition. Inspect all indicating and control devices for correct operation. Verify**/Utilize***correct application of manufacturer's recommended lubricants. Inspect insulating assemblies for evidence of physical damage or contaminated surfaces.*** Verify appropriate anchorage and required area clearances. Exercise all active components.***
Verify appropriate equipment grounding. Verify operation of heaters, if applicable.
Verify correct blade alignment, blade penetration, travel stops, and mechanical operation.
Clean unit prior to testing unless as-found and as-left tests are required.***
Verify that fuse sizes and types are in accordance with drawings, short-circuit and coordination studies. Inspect all bolted electrical connections for
Low Resistance Torque Ohmmeter Wrench
Thermographic Survey
Verify correct phase-barrier materials and installation.**
MEASUREMENTS
POLE 1 POLE 2 POLE 3
As Found As Left As Found As Left As Found As Left
Fuse Resistance (Microhms) 51,000 51,000 51,000 51,000 51,000 51,000 Fuse Holder - Top/Bottom (Microhms) 51 / 49 51 / 49 55 / 57 55 / 57 61 / 54 61 / 54
Contact Resistance (Microhms) 60 60 66 66 66 66
As Found
CUSTOMER 7
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310 3600 30th St ; Des Moines IA 50310
ADDRESS
USER CMMS #
EQPT. LOCATION
COMMENTS:
DEFICIENCIES:
Pole to Pole 36,700 29,800 31,300
Line to Load 39,100 43,600 57,200
340 300 300
DATE 05-Oct-2017 TEMPERATURE 72 °F HUMIDITY 86 % CIRCUIT ID Main Switch
Type: Load Current Interruptor Switch Class: N/A
Sat Unsat N/A Note No.:
Inspect physical and mechanical condition. Inspect all indicating and control devices for correct operation. Verify**/Utilize***correct application of manufacturer's recommended lubricants. Inspect insulating assemblies for evidence of physical damage or contaminated surfaces.*** Verify appropriate anchorage and required area clearances. Exercise all active components.***
Verify appropriate equipment grounding. Verify operation of heaters, if applicable.
Verify correct blade alignment, blade penetration, travel stops, and mechanical operation.
Clean unit prior to testing unless as-found and as-left tests are required.***
Verify that fuse sizes and types are in accordance with drawings, short-circuit and coordination studies. Inspect all bolted electrical connections for
Low Resistance Torque Ohmmeter Wrench
Thermographic Survey
Verify correct phase-barrier materials and installation.**
MEASUREMENTS
POLE 1 POLE 2 POLE 3
As Found As Left As Found As Left As Found As Left
Fuse Resistance (Microhms) 51,000 51,000 51,000 51,000 51,000 51,000 Fuse Holder - Top/Bottom (Microhms) 55 / 54 55 / 54 49 / 53 49 / 53 57 / 61 57 / 61
Contact Resistance (Microhms) 61 61 66 66 64 64
As Found
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310 ; 3600 30th St ; Des Moines IA 50310
ADDRESS
USER CMMS #
COMMENTS:
DEFICIENCIES:
TEST EQUIPMENT TESTED BY:
Pole to Pole 14500 14300 14600 Pole to Ground 5100 5220 5400
Line to Load 9850 11800 8750
339 332 374
EQPT. LOCATION Douglas Station DATE 06-Oct-2017 TEMPERATURE 72 °F HUMIDITY 100 % CIRCUIT ID Feeder #1 Switch
Type: Load Current Interruptor Switch Class: N/A
Catalog No: 44036-0325-0 Interrupt Rating: N/A Holder:
B.I.L. Rating: 95 Other: N/A Refill Element Type: N/A
Sat Unsat N/A Note No.:
Inspect physical and mechanical condition. Inspect all indicating and control devices for correct operation. Verify**/Utilize***correct application of manufacturer's recommended lubricants. Inspect insulating assemblies for evidence of physical damage or contaminated surfaces.*** Verify appropriate anchorage and required area clearances. Exercise all active components.***
Verify appropriate equipment grounding. Verify operation of heaters, if applicable.
Verify correct blade alignment, blade penetration, travel stops, and mechanical operation.
Clean unit prior to testing unless as-found and as-left tests are required.***
Verify that fuse sizes and types are in accordance with drawings, short-circuit and coordination studies. Inspect all bolted electrical connections for
Low Resistance Torque Ohmmeter Wrench
Thermographic Survey
Verify correct phase-barrier materials and installation.**
MEASUREMENTS
POLE 1 POLE 2 POLE 3
As Found As Left As Found As Left As Found As Left
Fuse Resistance (Microhms) N/A N/A N/A N/A N/A N/A Fuse Holder - Top/Bottom (Microhms) N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A
Contact Resistance (Microhms) 51 47 61 53 48 45
As Found
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310
3600 30th St ; Des Moines IA 50310
ADDRESS
USER CMMS #
EQPT. LOCATION
COMMENTS:
TEST EQUIPMENT US
Pole to Pole 14500 14300 14600 Pole to Ground 5100 5220 5400
Line to Load 9400 12200 13500
244 235 235
DATE 06-Oct-2017 TEMPERATURE 72 °F HUMIDITY 86 % CIRCUIT ID Feeder #2 Switch
Type: Load Current Interruptor Switch Class: N/A
Sat Unsat N/A Note No.:
Inspect physical and mechanical condition. Inspect all indicating and control devices for correct operation. Verify**/Utilize***correct application of manufacturer's recommended lubricants. Inspect insulating assemblies for evidence of physical damage or contaminated surfaces.*** Verify appropriate anchorage and required area clearances. Exercise all active components.***
Verify appropriate equipment grounding. Verify operation of heaters, if applicable.
Verify correct blade alignment, blade penetration, travel stops, and mechanical operation.
Clean unit prior to testing unless as-found and as-left tests are required.***
Verify that fuse sizes and types are in accordance with drawings, short-circuit and coordination studies. Inspect all bolted electrical connections for
Low Resistance Torque Ohmmeter Wrench
Thermographic Survey
Verify correct phase-barrier materials and installation.**
MEASUREMENTS
POLE 1 POLE 2 POLE 3
As Found As Left As Found As Left As Found As Left
Fuse Resistance (Microhms) NA NA NA NA NA NA Fuse Holder - Top/Bottom (Microhms) NA / NA NA / NA NA / NA NA / NA NA / NA NA / NA
Contact Resistance (Microhms) 52 49 54 48 54 52
As Found
CUSTOMER 10
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310 3600 30th St ; Des Moines IA 50310
ADDRESS
USER CMMS #
TES
Pole to Pole 10500 11700 10700 Pole to Ground 4340 5050 4640
Line to Load 4840 6250 5500
74 61 88
DATE 06-Oct-2017 TEMPERATURE 72 °F HUMIDITY 86 % CIRCUIT ID Main Switch
Type: Load Current Interruptor Switch Class: N/A
Catalog No: 44036-325-50 Interrupt Rating: N/A Holder:
B.I.L. Rating: 95 Other: N/A Refill Element Type: N/A
Sat Unsat N/A Note No.:
Inspect physical and mechanical condition. Inspect all indicating and control devices for correct operation. Verify**/Utilize***correct application of manufacturer's recommended lubricants. Inspect insulating assemblies for evidence of physical damage or contaminated surfaces.*** Verify appropriate anchorage and required area clearances. Exercise all active components.***
Verify appropriate equipment grounding. Verify operation of heaters, if applicable.
Verify correct blade alignment, blade penetration, travel stops, and mechanical operation.
Clean unit prior to testing unless as-found and as-left tests are required.***
Verify that fuse sizes and types are in accordance with drawings, short-circuit and coordination studies. Inspect all bolted electrical connections for
Low Resistance Torque Ohmmeter Wrench
Thermographic Survey
Verify correct phase-barrier materials and installation.**
MEASUREMENTS
POLE 1 POLE 2 POLE 3
As Found As Left As Found As Left As Found As Left
Fuse Resistance (Microhms) NA NA NA NA NA NA Fuse Holder - Top/Bottom (Microhms) NA / NA NA / NA NA / NA NA / NA NA / NA NA / NA
Contact Resistance (Microhms) 48 46 44 40 47 42
Sat Unsat N/A Note No.:
Perform insulation resistance test on control wiring.
C2. HEATER HAS BEEN OFF FOR THE MORNING AND IT IS RAINING POSSIBLY CAUSING LOW READINGS.
C1. INSULATION RESISTANCE PHASE TO PHASE, PHASE TO GROUND PERFORMED WITH SWITCH OPEN ON LINE SIDE OF MAIN.
As Found
SLOPE METHOD
CUSTO 11
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 503103600 30th St ; Des Moines IA 50310 ADDRESS
USER CMMS #
www.powerdb.com
DATE 05-Oct-2017 TEMPERATURE 72 °F HUMIDITY 86 % CIRCUIT ID Fall of Potential
TYPE OF GROUND ROD Copper NUMBER OF GROUND RODS 1
DIAMETER OF GROUND ROD
SOIL TYPE Diry
1/2 INCHES LENGTH OF GROUND RODS
SOIL CONDITION: DRY
Unknown
DAMP WET
FEET
GROUND TESTER SERIAL NUMBER 158807NEDV LAST CALIBRATION DATE Jan-2017
PROBE PLACEMENT DIRECTION NORTH
280 DISTANCE FROM GROUND ELECTRODE TO C IN FEET
Interpolate Result
Measure Result
SLOPE CHANGE RESISTANCE/DISTANCE CURVE 1.50
PT / C
PT / (ft)
RESULT (ohms):
0.388
108.6
0.48
TEST EQUIPMENT USED: TESTED B
"P" PROBE
POSITION
PERCENT OF
OVERALL DISTANCE
DISTANCE IN
FEET
(GROUND ELECTRODE TO P)
RESISTANCE
READING
(OHMS)
R1 20.00 %C 56.0 0.46
R2 40.00 %C 112.0 0.48
R3 60.00 %C 168.0 0.51
CONNECTING CONDUCTOR SIZE 18(?) AWG CONNECTING CONDUCTOR BARE INSULATED
DIAGONAL MEASUREMENT OF GROUND GRID N/A FEET GROUND TESTER MAKE/MODEL AEMC MODEL 6472 http://www.powerdb.com/
SLOPE METHOD
CUSTO 12
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 503103600 30th St ; Des Moines IA 50310 ADDRESS
USER CMMS #
www.powerdb.com
DATE 10/8/2017 TEMPERATURE 80 °F HUMIDITY 38 % CIRCUIT ID Fall of Potential
TYPE OF GROUND ROD Copper NUMBER OF GROUND RODS 1
DIAMETER OF GROUND ROD
SOIL TYPE Dry
1/2 INCHES LENGTH OF GROUND RODS
SOIL CONDITION: DRY
Unknown
DAMP WET
FEET
GROUND TESTER SERIAL NUMBER 158807NEDV LAST CALIBRATION DATE Jan-2017
PROBE PLACEMENT DIRECTION NORTH
200 DISTANCE FROM GROUND ELECTRODE TO C IN FEET
Interpolate Result
Measure Result
SLOPE CHANGE RESISTANCE/DISTANCE CURVE 0.71
PT / C
PT / (ft)
RESULT (ohms):
0.595
119.0
0.53
TEST EQUIPMENT TESTED BY:
"P" PROBE
POSITION
PERCENT OF
OVERALL DISTANCE
DISTANCE IN
FEET
(GROUND ELECTRODE TO P)
RESISTANCE
READING
(OHMS)
R1 20.00 %C 40.0 0.41
R2 40.00 %C 80.0 0.48
R3 60.00 %C 120.0 0.53
CONNECTING CONDUCTOR SIZE 18(?) AWG CONNECTING CONDUCTOR BARE INSULATED
DIAGONAL MEASUREMENT OF GROUND GRID N/A FEET GROUND TESTER MAKE/MODEL AEMC MODEL 6472 http://www.powerdb.com/
DISTRIBUTION SWITCHGEAR
DATASHEET
CUSTOMER 13
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310 3600 30th St ; Des Moines IA 50310
ADDRESS
USER CMMS #
EQPT. LOCATION
Sat Unsat N/A Note No.: Visual and Mechanical Inspection Sat Unsat N/A Note No.:
COMPARE NAMEPLATE DATA WITH
DRAWINGS AND SPECIFICATIONS
INSPECT PHYSICAL AND MECHANICAL CONDITION
INSPECT ANCHORAGE, ALIGNMENT,
GROUNDING AND CLEARANCES
UNIT IS CLEAN. NO LOOSE PARTS. SHIPPING
BRACES AND DOCUMENTATION REMOVED
VERIFY FUSE AND BREAKER SIZES CORRESPOND
TO DRAWINGS AND COORDINATION STUDY
VERIFY CURRENT AND VOLTAGE TRANSFORMER
RATIOS CORRESPOND TO DRAWINGS
INSPECT BOLTED CONNECTIONS BY DLRO,
TORQUE WRENCH OR INFRARED SURVEY
CONFIRM OPERATION AND SEQUENCE OF
ELECTRICAL AND MECHANICAL INTERLOCKS
Visual and Mechanical Inspection
VERIFY APPROPRIATE LUBRICATION OF
CURRENT-CARRYING AND MECHANICAL PARTS
INSPECT INSULATORS FOR PHYSICAL DAMAGE
AND CONTAMINATION
VERIFY BARRIER AND SHUTTER
INSTALLATION AND OPERATION
EXERCISE ALL ACTIVE COMPONENTS
INSPECT MECHANICAL INDICATING DEVICES
FOR PROPER OPERATION
VERIFY THAT FILTERS ARE IN PLACE
AND VENTS ARE CLEAR
VISUAL AND MECHANICAL INSPECTION
OF INSTRUMENT TRANSFORMERS
INSPECT CONTROL POWER TRANSFORMERS
DATE 05-Oct-2017 TEMPERATURE 72 °F HUMIDITY 86 % CIRCUIT ID 36th St Service Bus
GENERAL INFORMATION
MANUFACTURER
VOLTAGE CLASS
Square D
15kV
SERIAL NO.
TYPE
N/A
Metal Clad Switchger
DWGS. NA
CONSISTING OF: 1 TOTAL BREAKERS 2 TOTAL INSTRUMENTS 1 TOTAL RELAYS
INSULATION RESISTANCE
BUS SECTION RESISTANCE IN MEGOHMS @ 5 KVDC
A-B B-C C-A A-NEU. B-NEU. C-NEU. A-GND B-GND C-GND N-GND
Enitre Load Side of Breaker 16000 184000 138000 - - - 5700 7850 7410 -
OVERPOTENTIAL TEST
BUS SECTION READINGS IN MICROAMPS @ 27 KVAC
COMMON BUS 700 650 650 - - - 700 650 650 -
BUS CONNECTIONS
BUS SECTION RESISTANCE IN MICRO-OHMS
FROM TO A B C N G
Main Breaker Feeder 1 219 212 190 - -
Main Breaker Feeder 2 245 239 278 - -
Main Breaker Feeder 3 274 289 299 - -
DISTRIBUTION SWITCHGEAR
DATASHEET
CUSTOMER 14
91000604
PAGE
JOB # 3600 30th St ; Des Moines IA 50310 3600 30th St ; Des Moines IA 50310
ADDRESS
USER CMMS #
EQPT. LOCATION
TESTED BY:
Sat Unsat N/A Note No.: Visual and Mechanical Inspection Sat Unsat N/A Note No.:
COMPARE NAMEPLATE DATA WITH
DRAWINGS AND SPECIFICATIONS
INSPECT PHYSICAL AND MECHANICAL CONDITION
INSPECT ANCHORAGE, ALIGNMENT,
GROUNDING AND CLEARANCES
UNIT IS CLEAN. NO LOOSE PARTS. SHIPPING
BRACES AND DOCUMENTATION REMOVED
VERIFY FUSE AND BREAKER SIZES CORRESPOND
TO DRAWINGS AND COORDINATION STUDY
VERIFY CURRENT AND VOLTAGE TRANSFORMER
RATIOS CORRESPOND TO DRAWINGS
INSPECT BOLTED CONNECTIONS BY DLRO,
TORQUE WRENCH OR INFRARED SURVEY
CONFIRM OPERATION AND SEQUENCE OF
ELECTRICAL AND MECHANICAL INTERLOCKS
Visual and Mechanical Inspection
VERIFY APPROPRIATE LUBRICATION OF
CURRENT-CARRYING AND MECHANICAL PARTS
INSPECT INSULATORS FOR PHYSICAL DAMAGE
AND CONTAMINATION
VERIFY BARRIER AND SHUTTER
INSTALLATION AND OPERATION
EXERCISE ALL ACTIVE COMPONENTS
INSPECT MECHANICAL INDICATING DEVICES
FOR PROPER OPERATION
VERIFY THAT FILTERS ARE IN PLACE
AND VENTS ARE CLEAR
VISUAL AND MECHANICAL INSPECTION
OF INSTRUMENT TRANSFORMERS
INSPECT CONTROL POWER TRANSFORMERS
DATE 10/6/2017 TEMPERATURE 65 °F HUMIDITY 100 % CIRCUIT ID Douglas Ave Bus
GENERAL INFORMATION
MANUFACTURER
VOLTAGE CLASS
Square D
15kV
SERIAL NO.
TYPE
17-25051529-035
Metal Clad Switchger
DWGS. NA
CONSISTING OF: 1 TOTAL BREAKERS 2 TOTAL INSTRUMENTS 1 TOTAL RELAYS
INSULATION RESISTANCE
BUS SECTION RESISTANCE IN MEGOHMS @ 5 KVDC
PANEL 14500 14300 14600 - - - 5100 5220 5400 -
OVERPOTENTIAL TEST
BUS SECTION READINGS IN MICROAMPS @ 27 KVAC
COMMON BUS 550 600 600 - - - 550 600 600 -
BUS CONNECTIONS
BUS SECTION RESISTANCE IN MICRO-OHMS
FROM TO A B C N G
Feeder 1 Feeder 2 75 79 80 - -
Feeder 1 Main Breaker 180 195 200 - -
| - |
| MAIN BRKR 52-2 |
| COMMENTS: DEFICIENCIES: |
| MAIN BRKR 52-1 |
| COMMENTS: DEFICIENCIES: |
| Feeder #1 Switch |
| Feeder #2 Switch |
| Feeder #3 Switch |
| Main Switch |
| Feeder #1 Switch |
| Feeder #2 Switch |
| Main Switch |
| COMMENTS: DEFICIENCIES: |
| Fall of Potential |
| COMMENTS: DEFICIENCIES: |
| Fall of Potential |
| COMMENTS: DEFICIENCIES: |
| 36th St Service Bus |
| GENERAL INFORMATION |
| Douglas Ave Bus |
| GENERAL INFORMATION |
| COMMENTS: |