Q2C Number: 25051529 Quote Number: 2 Revision Number: 0

Project Name: VA PHASE 4B Project Sub-Name:

Project Location: DES MOINES, IA

Q2C Number: 25051529 Quote Number: 2 Revision Number: 0 Project Name: VA PHASE 4B Quote Name:

Item No.

Qty.

Catalog Number / Details

035-00

Designation: Douglas Ave.

Fully-Assembled MV MetalClad Swgr Metal Clad Switchgear > 1000 Volts

- - Consult Factory for Delivery - -

5 Section Line-up MASTERCLAD Switchgear Assembly Consisting of the following:

Network Communications Only RS485 Modbus Comms Wired Out Label Requirements: UL, for California Outdoor, Walk-in Single Aisle (Type 3R) With Front and Rear Access Rear Door Type 3R with Padlock Provisions

If Customer Witness Testing Required, must add in separately from this Bill of Material and price in at Standard Square D daily rate.

General Equipment Ratings Frequency: 60 Hertz Impulse Withstand Voltage (BIL): 95kV Maximum Bus Continuous Current: 1200A Maximum Short Circuit Current: 23kA (RMS Symmetrical) Maximum Voltage: 15kV Nominal System Voltage: 13.2kV, 3 Phase, 3 Wire, Ungrounded Delta One-Minute Withstand Voltage: 36kV RMS

General Structure Information 1200A Silver Plated Copper Main Bus Auxilary Control Power: Square D 120VAC Breaker Close Control Power: Square D Supplied 125VDC Breaker Trip Control Power: Square D Supplied 125VDC Bus Bracing: 23kA (RMS Symmetrical) Bus Supports: Epoxy (Std) Control Wiring: #12 AWG type SIS wire Current Circuit Wiring: #10 AWG type SIS wire Exterior Paint Color: ANSI #61, Light Gray (Std) Ground Bus: Copper, Unplated (Std) Lug Type: Supplied by Customer Screw Terminal Blocks, Insulated Square D LED Type lamps, (2) per cell 1 - 5th Wheel for Breaker 1 - Aisle Heater, up to 5kw 1 - Ammeter and Circuit Breaker for Strip Heater Circuit 1 - Fluorescent Battery Backed Emergency Lighting 1 - Humidistat for Space Heaters 1 - Mimic bus - painted device symbols (per cell) 1 - Padlock Hasps per Front Door 1 - Test Cabinet, 8 ft. cable 1 - Test Jumper, 14 ft. cable only 1 - Vent & Fan LV Panels Painted White

Dimensions:

Width of Lineup: 180.00" 4572mm Height @ Highest Point: 114.50" 2908mm Depth @ Base: 169.50 4305 mm Depth @ Roof: 178.50" 4534 mm Approximate Weight: 25104 lb 11411 kg

Special Features or TAG Items (per line-up) If Special Features are included in this Bill of Material, they will NOT appear on the Front-Elev or One-line Drawing and may alter the final layout and dimensions.

04 - Rear Door Assembly 05 - Special Creme Paint per email

Detailed Bill of Material

- - Consult Factory for Delivery - - This Metal Clad Switchgear shall be depicted in the attached drawing and shall including the following:

SECTION # 1, WORKSPACE -

1 - 72" Wide Blank Extension to Walk-in (Type 3R) w/Front Aisle 1 - Install HVL & UTILITY

SECTION # 2, UPPER, AUX. -

1 - VT Drawer with (3) VTs, (1) Primary Fuse per VT 1 - 15kVA, Single Phase CPT 1 - Insulating rear barrier over door-mounted components, (CA code/NEC)

SECTION # 2, LOWER, MAIN -

1 - 15kV Max. Voltage, 500MVA, 1200A, Vacuum Breaker Type: VR-15050-12 3 - Single Ratio 600:5 CT - Standard Accuracy - Model 780 - Set#4 1 - Breaker Control Switch 1t,1c (Std) 1 - Insulating rear barrier over door-mounted components, (CA code/NEC) 1 - Key Interlock (per key) Manufacturer :

Schneider 1 - MOC Switch Supplying 13 Additional Contacts (6a, 7b) 1 - TOC Switch Supplying 13 Additional Contacts (6a, 7b) 1 - Lockout Relay - 86-5 Deck 1 - Relay, 11, SEL, 351-7

SECTION # 3

1 - Special ATS

SECTION # 3, UPPER, AUX. -

1 - Blank Auxilary Cell (Upper) 1 - AC Control Power Transfer Scheme between two CPTs 1 - Insulating rear barrier over door-mounted components, (CA code/NEC)

SECTION # 3, LOWER, AUX. -

1 - VT Drawer with (3) VTs, (1) Primary Fuse per VT 1 - 15kVA, Single Phase CPT 1 - Insulating rear barrier over door-mounted components, (CA code/NEC)

SECTION # 4, WORKSPACE -

1 - 72" Wide Blank Extension to Walk-in (Type 3R) w/Front Aisle 2 - Install HVL

SECTION # 5, WORKSPACE -

1 - 72" Wide Blank Extension to Walk-in (Type 3R) w/Front Aisle 1 - DC Disconnect For Battery System 1 - Workspace Heater 1 - AC Loadcenter 1 - DC Loadcenter 1 - Eyewash System (Std w/ 72" Workspace & Provisions for Battery System) 1 - Change to 48" wide

Other files

File Type Posted
S06. 36C26323Q0650 0002.pdf PDF
36C26323Q0650 0002_1.docx DOCX document
25051529-031 and 036 BOM.rtf RTF text file
25051529-035-COMBINED.pdf PDF
25051529-031-COMBINED.pdf PDF
25051529-033 BOM.rtf RTF text file
25051529-036-COMBINED.pdf PDF
25051529-033-COMBINED.pdf PDF
36C26323Q0650 0001_1.docx DOCX document
Campus One-Line with Cottage Included.pdf PDF
Previous Report for Buildings 35 and 36.pdf PDF
20230524_132324.jpg JPG image
S06. 36C26323Q0650 0001.pdf PDF
S02. 36C26323Q0650 Electrical Equipment Testing - CI.pdf PDF
36C26323Q0650_1.docx DOCX document