This document provides details for a federal solicitation seeking mechanical, HVAC, and building management system construction services. The solicitation is identified as number 36C26120B0013 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21 for a project located at the VA Medical Center in Yankton, South Dakota. The solicitation is seeking offers for MV-HR BMS HVAC construction services related to project number 640-20-107. The closing date and any other details regarding proposal submission or contract award are not provided in this document.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TYPE lit
CATALOG # LIB24 115/277-19HDR-1,
VA PAH
LI Native BACnet Level Ipteriur (LI 8, LIB24, LIB4U)
Native level integration .
between lighting control .
panel and BAS via BACnet
Configure and control LI panel with any BACnet workstation
No proprietary configuration tools or software needed for commissioning
BACriet is a registered trademark of ASHFME
Industry standard ******* MS/TP communication
• • override time delays handled by
LI panel automatically
*Integral blink warnings and
Product Overview
Description
The Lighting Integrator Native BACnet panel (LIB) enables native level integration of lighting control between the LIB panel and any building automa-tion system that supports the ANSI/ASHRAE BACnet communication protocol. The LIB allows the BAS to schedule, monitor status, and override lighting freely without the need to support light-ing-specific functions (e.g., blink warning, local override switches, and delay timers).
Lighting Control Specific Functions
The LIB panel provides integral automation capa-bilities that enable lighting control compliant with state energy codes based on ASHRAE 90.1 and IECC. Its distributed processing also ensures operation of primary lighting control functions, such as wall switch overrides, blink warnings, and afterhours time out of overrides.
Applications
Operation
With the LIB panel system, panel relays and chan-nels are automatically exposed to the BAS as standard BACnet objects. Relays can be individu-ally commanded and monitored for their actualon/ off status, or be combined into channels and com-manded and monitored as a group. This permits a building to be conveniently divided into lighting control zones,greatly reducing the number of indi-vidual objects a BAS must administer. LIB panels perform all typical lighting control sequence of operations without continuous supervision by the
BAS.
In most applications, a BAS will set lighting zones to occupied/unoccupied status through a schedule or a workstation command. The LIB panel then coordinates local switch overrides, time delays and blink warnings based on this status.
Features • Integral automation enables BAS to easily provide code compliant lighting control
• Distributed processing ensures operation of primary lighting control functions
• Compatible with WattStopper occupancy sensors 2nd standard low voltage switch
• Supports Auto On, or energy saving Manual On function for lighting in areas scheduled as occu-pied
• Supports AS-100 Automatic Control Switch sweep off function
• Qualifies for use in ARRA-funded projects
WattStopper www.wattstopper.com 8 0 0 . 8 7 9 . 8 5 8 6
PI r I-a
I-
-i I-a a • .4 I.. a u
_`_,,-1 option card BACnet a I.
Lighting Integrator Panel Lighting integrator Panel
MS/TP network
AOrwpk.nd I Elksnrai www.wattstopper.com 1 8 0 0 . 8 7 9 . 8 5 8 5
) Specifications • MS/TP communications port with removable 120 ohm "end of line" termination jumper
• 9600/19200/38400/76800 baud rates, selectable
• MS/TP MAC address selectable, 0 - 127
• Device ID selectable, 0 - 999 or 86000 - 86999
• Compatible with direct wired low voltage switches for relay override; not compatible with HDLS series dataline switches
• Description property writable for all objects
• One year warranty
BACnet Objects
Supported
Native BACnet Card and System
Layout
• Binary Output, Instance range 01-48 (1per relay), monitor and control relays ON (1), OFF (NULL)
• Binary Value, Instance range 01-08 (1 per channel), command channels to occupied (1) or unoc-cupied (0) status
• Multi State Value, Instance range 01-08 (1 per channel), read channel relays' status as ALL ON, ALL OFF, BLINK, or MIXED state
• Binary Value, Instance range 101-108(1 per channel), sets channel relays to manual-ON (1) or auto-ON (0)
• Analog Value, Instance range 101-108 (1 per channel), sets blink warning time for channel relays as five minutes (5) or no blink (0), or AS-100 switch (250)
• Analog Value, Instance range 201-208 (1 per channel), sets time delay for each channel relay
(1-240 minutes) or no time delay (0)
• Analog Value, Instance range 01-48 (one per relay), sets relay to follow channel A-H (1-8)
LIB Panel Network
BACnet workstation
BAS ,11W'
General LI Description
Operation (coned.)
Information WattStopper'sLighting Integrator (LI) is a low voltage, relay based lighting control panel. The LI interior is shipped as a separate assembly from the panel enclosure and cover to facilitate project rough-in requirements. Interiors are configured as 8, 24 or 48 relay capacity with the quantity of relays installed as called for on the order. The interior field mounts into an appropriate enclosure supplied separately.
Inputs can be wired to accommodate momentary three wire, momentary two wire (toggle) or maintained contact switches as well as occupancy sensors. The switch input circuits are auto sensing and will automatically configure appropriately when Watt Stopper occupancy sensors are connected.
Group Switching
Operation
LI relays are driven into a latched on or off state via a 24 volt DC pulse generated by the relay driver cards. A momentary pushbutton is provided for each relay driver circuit to manually force the relay to toggle its state with each button press.
An isolated set of contacts in the relays provides a positive status feedback to the relay driver circuits that are annunciated by an LED associated with each relay. Removable terminal blocks allow connection of direct wired low voltage devices for remote control of relays.
• Interior provides complete isolation between line and low voltage when used with a compatible LENC series enclosure
• Individual plug-in, latching style single pole relays with isolated pilot/status contacts
• Integral push button override, status LED, and pilot light output per relay
• Two slots available for optional automation, networking and integration control cards
Group switching provides the unique WattStopper Smartwired switching function. This simple button press interface allows any quantity of relays to be assigned quickly to each group switching channel for common on/off control or for pattern (scene) style control. Each of the eight channels is provided with an override pushbutton, LED status indicator and terminals for connection of wall switches and occupancy sensors. Eight and 24 size panels can be ordered with one group switch card (8 channels), 48 size panels can have two group switch cards for a total of 16 channels (8 controllable by scheduling, eight by switching only).
• Supports WattStopper occupancy sensor heads without need for separate sensor power packs
• Smartwire feature allows grouping of relays for common control
• DIN rail mounting provided within the Class 2 section for mounting of optional accessories
• Control multi-pole circuits with optional contactors and compatible LENC enclosure
• Optional configuration available for use on emergency lighting circuits
( C2)
WattStopper
8 0 0 . 8 7 9 . 8 5 8 5
24 relay interior capacity
14'
35.56 cm
48 relay Interior capacity
14"
35.56 cm
8 relay Interior capacity
13°
33.02 cm
Panel Interior Dimensions
10.5°
26.67 cm
23.37"
59.37 cm
35.75°
90.80 cm
General LI Specifications
• Interior capacity:
- 8 circuits, up to 8 SPST relays
- 24 circuits, up to 24 SPST relays
- 48 circuits, up to 48 SPST relays
• Input voltage options, 120/277V 60 Hz, 120/347V 60 Hz, 240V50 Hz
• Group switching, eight channels per installed group switching card. One card max per LI8 and LI24. Two cards max LI48.
• Low voltage switch inputs, removable terminal blocks with screw-less connection, configurable for three wire momentary, two wire momentary (toggle), and two wire maintained dry contact switches or WattStopper occupancy sensors.
• Accessory power available
- LI8: 1000 MA fa24VAC or 800 MA (a 24VDC
- LI24 and LI48: 1400 MA (a 24VAC or 800 MA (a
24VDC
• SCCR (short circuit current rating) 14,000 amps with HDR Heavy Duty Relay
• HDR relays:
- Coil voltage, 24 VDC, pulse ON and pulse OFF
- Mechanically Latched contacts
- 1/2" K,O, mounting, LV plug-connection, individually replaceable
- Contact ratings
30 amps ballast (a 277V
20 amps ballast ra 347V
20 amps tungsten fa 120V
30 amps resistive fa 347V
1.5 HP Cd 120V
- Endurance: 300,000 mechanical cycles
• Pilot light output, 24 V rectified or 24VAC, other voltages configurable with external power supply
• One year warranty
Ordering Information
05)
Pub. No. 19506 rev. 08/2009
Interior Capacity Installed Options Voltage Options Relay Count Group Switch Card Emergency Relays Coil Voltage
III LI88 0 115/277 19 HDR relays installed )max of interior capacity)
1 GS cards (max 1 in 8, 24, 2 in 48) ili 115
. LIB24 I 115/347 0 240
IIII LIB48 II 240 I 277
I 347 A Om* 10Ies et www.wattstopper.com I 8 0 0 . 8 7 9 . 8 5 8 5
16-gauge all steel tubs with galvineal finish
Screw on, powder coated cover permits temporary hanging via key hole screw slots
Surface or flush mounting with back mounting holes, screw cover
Do e
12"
DIN Rail Mounting Options
DMP1
DMP1EM
14" 4.375"
DMP3EM _L
4'
I/
22"
18"
DMP2
3.5"
_L 4.376"
0 0
14"
—r
21"
14'
TYPE 11-1.
CATALOG # LENC:
VA PAH
Lhhtiflg Intr: rator P Encloawas
- I
Lig))
Lockable door access to Class 2 panel section, meets NFPA 70
Studs provided for quick installation of panel interior section
UL and CUL listed;
one year warranty
Product Overview
WattStopper www.wattstopper.com 8 0 . 8 7 9 . 8 5 8 5
Description
Lighting Integrator panel enclosures are designed specifically to work with all configurations of LI panel interiors containing 8 to 48 relays. The enclosures are provided with integral mounting studs that are configured to accept the panel interior making the installation quick and easy.
Covers are secured to the tubs with screws and have keyhole style mounting. This allows the cover to be temporarily hung on the tub during the construction phase of the project. All covers have hinged doors that expose only the low voltage (Class 2) section of the panel and are equipped with key locks and two keys each. All Lighting Integrator enclosures are NEMA 1 rated. Consult factory for other NEMA rated applications.
Configurations
Enclosures rated for 24 or 48 relay capacity have space provided at the bottom for optional mounting plates (DMP) to accept DIN rail mounted accessories such as multi-pole contactors and ELCU-100 Emergency Lighting Control Units.
Standard LENC24 and LENC48 enclosures will accommodate up to six four pole contactors (requires DMP mounting plate) or four ELCU- 100 units (requires DMP-1EM mounting plate).
LENC8-24 and LENC24-48 enclosures have additional space provided and will accommodate up to twelve four pole contactors (requires DMP-2 mounting plate) or 12 ELCU-100 units (requires DMP-3EM mounting plate).
LENC8S
LENC8F
16.5'
Tub Dimensions
15.08" Low voltage section 13.58"
LENC24S
LENC24F
23.88'
14.5' Note:
Tub depth 4.50" Cover thickness .075"
23.38" 31.38 Low voltage section uo rp as a th
M O
A a n
15.0'
31.38"
26°
16'
LENC8-24S
LENC8-24F
23.88'
Low voltage section
Overall Dimensions Overall Weight Including Cover (HxWxD)
Catalog No. Description
Qualifies for use in ARRA-funded projects. A enar, Itaaal I D lostra,X www.wattstopper.com I 8 0 0 . 8 7 9 . 8 5 8 5
4.94-
14.0' 4.94=
23 3r
2051w
Low voltage section
43 88'
40.5' a 6'
LENC48S
LENC48F
23.88" 14.0' 4.94"
43 8"
40.5
Low voltage section o• if-
35.8'
8.08'
16°
LENC24-48S
LENC24-48F
23.88'
. LENC8S 8 relay capacity, surface mount 15.75" x 16.62" x 4.575" 18 lbs
III LENC8F 8 relay capacity, flush mount 17.10" x 18.48" x 4.575" 20 lbs
0 LENC8-24S 8 relay capacity with 24 size tub, surface mount 32.00" x 24.00" x 4.575" 45 lbs
D LENC8-24F 8 relay capacity with 24 size tub, flush mount 33.35" x 25.85" x 4.575" 50 lbs
• LENC24S 24 relay capacity, surface mount 32.00" x 24.00" x 4.575" 45 lbs •
• LENC24F 24 relay capacity, flush mount 33.35" x 25,85" x 4.575" 50 lbs
• LENC24-48S 24 relay capacity with 48 size tub, surface mount 44.50" x 24.00" x 4.575" 62 lbs
0 LENC24-48F 24 relay capacity with 48 size tub, flush mount 45.85" x 25.85" x 4.575" 66 lbs
0 LENC48S 48 relay capacity, surface mount 44.50" x24.00" x 4.575" 62 lbs
D LENC48F 48 relay capacity, flush mount 45.85" x 25.85" x 4.575" 66 lbs
• DMP mounting plate, one DIN rail for up to 6 contactors 8" x 12" x 4.625" 1.86 lbs
0 DMP-2 mounting plate, two DIN rail for up to 12 contactors 21"x 14" x 4.625" 5.30 tbs.
0 DMP-1EM mounting plate, one DIN rail with barrier for up to 4
ELCU-100s
10" x 14" x 4.37" 3.64 lbs.
0 DMP-3EM mounting plate, three DIN rail with barrier for up to
12 ELCU-100s
22" x 14" x 4.37" 7.60 lbs.
Ordering Information
Pub, No. 10808 rev. 11/2011
4.94-
8.0"
4.82 -0*---11.68",--.-
.2
Product Overview
Features
TYPE 2H,
CATALOG # LIB24 115/277-19HDR-1
VA PAH
LI t'Lifc.. net Levet IntLviul (LUO, LI 4., LILJ4.L)
Native level integration . • between lighting control panel and BAS via BACnet
Configure and control LI panel with any BACnet workstation
Industry standard ******* MS/TP communication
. 'Integral blink warnings and
. • • override time delays handled by LI panel automatically
No proprietary configuration tools or software needed for commissioning
BACnet tea registered trademark at ASHRAE
Description
The Lighting Integrator Native BACnet panel (LIB) enables native level integration of lighting control between the LIB panel and any building automa-tion system that supports the ANSI/ASHRAE BACnet communication protocol. The LIB allows the BAS to schedule, monitor status, and override lighting freely without the need to support light-ing-specific functions (e.g., blink warning, local override switches, and delay timers).
Operation
With the LIB panel system, panel relays and chan-nels are automatically exposed to the BAS as standard BACnet objects. Relays can be individu-ally commanded and monitored for their actualon/ off status, or be combined into channels and com-manded and monitored as a group. This permits a building to be conveniently divided into lighting control zones, greatly reducing the number of indi-vidual objects a BAS must administer. LIB panels perform all typical lighting control sequence of operations without continuous supervision by the
BAS.
• Integral automation enables BAS to easily provide code compliant lighting control
• Distributed processing ensures operation of primary lighting control functions
• Compatible with WattStopper occupancy sensors 2nd standard tow voltage switch
Lighting Control Specific Functions
The LIB panel provides integral automation capa-bilities that enable lighting control compliant with state energy codes based on ASHRAE 90.1 and IECC. Its distributed processing also ensures operation of primary lighting control functions, such as wall switch overrides, blink warnings, and afterhours time out of overrides.
Applications
In most applications, a BAS will set lighting zones to occupied/unoccupied status through a schedule or a workstation command. The LIB panel then coordinates local switch overrides, time delays and blink warnings based on this status.
• Supports Auto On, or energy saving Manual On function for lighting in areas scheduled as occu-pied
• Supports AS-100 Automatic Control Switch sweep off function
• Qualifies for use in ARRA-funded projects
WattStopper'
8 0 0 . 8 7 9 . 8 5 8 5
) Specifications • MS/TP communications port with removable 120 ohm "end of line" termination jumper
• 9600/19200/38400/76800 baud rates, selectable
• MS/TP MAC address selectable, 0 - 127
• Device ID selectable, 0 - 999 or 86000 - 86999
• Compatible with direct wired low voltage switches for relay override; not compatible with HDLS series dataline switches
• Description property writable for all objects
• One year warranty
BACnet Objects
Supported
Native BACnet Card and System
Layout
• Binary Output, Instance range 01-48 (lper relay), monitor and control relays ON (1), OFF (NULL)
• Binary Value, Instance range 01-08 (1 per channel), command channels to occupied (1) or unoc-cupied (0) status
• Multi State Value, Instance range 01-08 (1 per channel), read channel relays' status as ALL ON, ALL OFF, BLINK, or MIXED state
• Binary Value, Instance range 101-108(1 per channel), sets channel relays to manual-ON (1) or auto-ON (0)
• Analog Value, Instance range 101 -1 08 (1 per channel), sets blink warning time for channel relays as five minutes (5) or no blink (0), or AS-100 switch (250)
• Analog Value, Instance range 201-208 (1 per channel), sets time delay for each channel relay
(1-240 minutes) or no time delay (0)
• Analog Value, Instance range 01-48 (one per relay), sets relay to follow channel A-H (1-8)
LIB Panel. Network
BACnet workstation
• t-
BACnet i.. r i-
A A
. 1
BAS
Panel
Light ng Integrator Panel Lighting Integrator
MS/TP network
AOmplond la lesrend www.wattstopper.com IS 0 0 . 8 7 9 .8 5 8 5
General LI Description
Operation (cont'd.)
Information WattStopper'sLighting Integrator (LI) is a low voltage, relay based lighting control panel. The LI interior is shipped as a separate assembly from the panel enclosure and cover to facilitate project rough-in requirements. Interiors are configured as 8, 24 or 48 relay capacity with the quantity of relays installed as called for on the order. The interior field mounts into an appropriate enclosure supplied separately.
Inputs can be wired to accommodate momentary three wire, momentary two wire (toggle) or maintained contact switches as well as occupancy sensors. The switch input circuits are auto sensing and will automatically configure appropriately when Watt Stopper occupancy sensors are connected.
Group Switching
Operation
LI relays are driven into a latched on or off state via a 24 volt DC pulse generated by the relay driver cards. A momentary pushbutton is provided for each relay driver circuit to manually force the relay to toggle its state with each button press.
An isolated set of contacts in the relays provides a positive status feedback to the relay driver circuits that are annunciated by an LED associated with each relay. Removable terminal blocks allow connection of direct wired low voltage devices for remote control of relays.
• Interior provides complete isolation between line and low voltage when used with a compatible LENC series enclosure
• Individual plug-in, latching style single pole relays with isolated pilot/status contacts
• Integral push button override, status LED, and pilot tight output per relay
• Two slots available for optional automation, networking and integration control cards
Group switching provides the unique WattStopper Smartwired switching function. This simple button press interface allows any quantity of relays to be assigned quickly to each group switching channel for common on/off control or for pattern (scene) style control. Each of the eight channels is provided with an override pushbutton, LED status indicator and terminals for connection of wall switches and occupancy sensors. Eight and 24 size panels can be ordered with one group switch card (8 channels), 48 size panels can have two group switch cards for a total of 16 channels (8 controllable by scheduling, eight by switching only).
• Supports WattStopper occupancy sensor heads without need for separate sensor power packs
• Smartwire feature allows grouping of relays for common control
• DIN rail mounting provided within the Class 2 section for mounting of optional accessories
• Control multi-pole circuits with optional contactors and compatible LENC enclosure
• Optional configuration available for use on emergency lighting circuits
WattStopper
0 0 . 8 7 9 . 8 5 8 5
35.75'
90.80 cm
23.37'
59.37 cm
General LI Specifications
• Interior capacity:
- 8 circuits, up to 8 SPST relays
- 24 circuits, up to 24 SPST relays
- 48 circuits, up to 48 SPST relays
• Input voltage options, 120/277V 60 Hz, 120/347V 60 Hz, 240V 50 Hz
• Group switching, eight channels per installed group switching card. One card max per LI8 and LI24. Two cards max LI48.
• Low voltage switch inputs, removable terminal blocks with screw-less connection, configurable for three wire momentary, two wire momentary (toggle), and two wire maintained dry contact switches or WattStopper occupancy sensors.
• Accessory power available
- LI8: 1000 MA (24VAC or 800 MA 0 24VDC
- LI24 and LI48: 1400 MA ra 24VAC or 800 MA Ira
24VDC
• SCCR (short circuit current rating) 14,000 amps with HDR Heavy Duty Relay
• HDR relays:
- Coil voltage, 24 VDC, pulse ON and pulse OFF
- Mechanically latched contacts
- 1/2" K,O, mounting, LV plug-connection, individually replaceable
- Contact ratings 30 amps ballast ra 277V 20 amps ballast la 347V 20 amps tungsten Id 120V 30 amps resistive fa 347V
1.5 HP 0 120V
- Endurance: 300,000 mechanical cycles
• Pilot light output, 24 V rectified or 24VAC, other voltages configurable with external power supply
• One year warranty
Panel Interior Dimensions
8 relay Interior capacity
13' 1 33.02 cm
24 relay interior capacity
14"
35.66 cm
48 relay interior capacity
14" •
35.56 cm
Ordering Information
Pub. No. 19506 rev. 08/2009
Interior Capacity
Installed Options
Voltage Options Relay Count Group Switch Card Emergency Relays Coil Voltage
II L188 0 115/277 19 NCR relays installed (max of interior capacity)
1 GS cards (max
1 in 8.24, 2 in 481
II 115
I L1824 M 115/347 ii 240
II LI848 • 240 0 277
I 347
A 6ravi br*.1 teSzargi www.wattstopper.com 18 0 0 . 8 7 9 . 8 5 8 5
16-gauge all steel tubs with galvineal finish
S.
S.
Screw on, powder coated cover permits temporary hanging via key hole screw slots
Surface or flush mounting with back mounting holes, screw cover iisson•-• —
00 •
0 0
2"
14'
WattStopper° www.wattstopper.com
800. 8 7 9 . 8 5 86
3.5' irm 6.5" 2.5"
4,375"
DMP2
4.375" I--- 14 •-•-=11•.-
DMP3EM _L
4"
22" 18" 0 0
14"
DMP1EM
10"
TYPE 2111
CATALOG # LENC2
VA PAH
L" tin Intirrator Pane!, ralcIttures
Lockable door access to Class 2 panel section, meets NFPA 70
Studs provided for quick installation of panel interior section
UL and CUL listed;
one year warranty
Product Overview
Description
Lighting Integrator panel enclosures are designed specifically to work with all configurations of LI panel interiors containing 8 to 48 relays. The enclosures are provided with integral mounting studs that are configured to accept the panel interior making the installation quick and easy.
Covers are secured to the tubs with screws and have keyhole style mounting. This allows the cover to be temporarily hung on the tub during the construction phase of the project. All covers have hinged doors that expose only the low voltage (Class 2) section of the panel and are equipped with key locks and two keys each. All Lighting Integrator enclosures are NEMA 1 rated. Consult factory for other NEMA rated applications.
Configurations
Enclosures rated for 24 or 48 relay capacity have space provided at the bottom for optional mounting plates (DMP) to accept DIN rail mounted accessories such as multi-pole contactors and ELCU-100 Emergency Lighting Control Units.
Standard LENC24 and LENC48 enclosures will accommodate up to six four pole contactors (requires DMP mounting plate) or four ELCU- 100 units (requires DM P-1EM mounting plate).
LENC8-24 and LENC24-48 enclosures have additional space provided and will accommodate up to twelve four pole contactors (requires DMP-2 mounting plate) or 12 ELCU-100 units (requires DMP-3EM mounting plate).
DIN Rail Mounting Options
DMP1
-4.94" 4 94,-
13.58'
23.38"
Low voltage section
14.5'
LENC24S
LENC24F
23.88' 14.0'
Low voltage section
Note:
Tub depth 4.50" Cover thickness .075"
31.38"
C.
cv
$.1g
15,0'
31.38'
Low voltage section
15.08"
LENC8S
LENC8F
16.5'
- 4.82'
8.0"
16"
LENC8-24S
LENC8-24F
23.88"
26'
43 88'
40.5" la ' 35.8'
Low voltage section
16"
LENC24-48S
LENC24-48F
23.88" 14.0'
8.8"
-4.94
Low voltage section 2337'
4388'
40.5"
CO
LENC48S
LENC48F
23.88" 14.0' .
• a
20.51'
16.38'
Pub, No. 10808 rev. 11/2011
16 16"
Catalog No. Description Overall Dimensions Overall Weight Including Cover 11-IxWx13)
0 LENC8S 8 relay capacity, surface mount 15.75" x 16.62" x 4.575" 18 lbs
0 LENC8F 8 relay capacity, flush mount 17.10" x 18.48" x 4,575" 20 lbs ll LENC8-24S 8 relay capacity with 24 size tub, surface mount 32,00" x 24.00" x 4.575" 45 lbs
0 LENC8-24F 8 relay capacity with 24 size tub, Rush mount 33.35" x 25.85" x 4.575" 50 tbs
E LENC24S 24 relay capacity, surface mount 32.00" x 24.00" x 4.575" 45 lbs ii LENC24F 24 relay capacity, flush mount 33.35" x 25.85" x 4.575" 50 lbs
0 LENC24-48S 24 relay capacity with 48 size tub, surface mount 44.50" x 24.00" x 4.575" 62 lbs
. LENC24-48F 24 relay capacity with 48 size tub, flush mount 45.85" x 25.85" x 4.575" 66 lbs
III LENC48S 48 relay capacity, surface mount 44.50" x 24.00" x 4.575" 62 lbs
I LENC48F 48 relay capacity, flush mount 45.85" x 25.85" x 4.575" 66 lbs
El DMP mounting plate, one DIN rail for up to 6 contactors 8" x 12" x 4.625" 1.86 lbs . DMP-2 mounting plate, two DIN rail for up to 12 contactors 21"x 14" x 4,625" 5.30 tbs.
EI OMP-1EM mounting plate, one DIN rail with barrier for up to 4
ELCU-100s
10" x 14" x 4.37" 3.64 tbs.
I DMP-3EM mounting plate, three DIN rail with barrier for up to
12 ELCU-100s
22"x 14" x 4.37" 7.60 lbs.
Qualifies for use in ARRA-funded projects.
www.wattstopper.com I 8 0 0 . 8 7 9 • 8 5 8 5
Tub Dimensions
Ordering Information
| Page 1 |
| Page 2 |
| Page 3 |
| Page 4 |
| Page 5 |
| Page 6 |
| Page 7 |
| Page 8 |
| Page 9 |
| Page 10 |
| Page 11 |
| Page 12 |
File details come from the government source that posted it. Updated .