This document contains a symbol list, general notes, and sheet index for a mechanical engineering project. It provides standard symbols and abbreviations for mechanical drawings as well as general notes covering coordination, access requirements, seismic anchorage, testing procedures, and other project requirements. The sheet index references 23 total drawings for mechanical, piping, schedules, details, and diagrams related to the HVAC system upgrade at the Mountain View Center for the VA Palo Alto Health Care System under solicitation number 36C26120B0013. This IFB is for HVAC construction services including installation of a new BMS and HVAC upgrades. The pre-solicitation originally published as RFP 36C26120R0012. Potential offerors are instructed not to contact individual VA medical centers for more information and to check beta.sam.gov for details.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FD FD
FSDFSD
X
X
CD-1
12x12
XX-X
LOCATION
X
S
ET
P
T
HWR
HWS
M
M
Abbreviations
NEW(N)
AIR CONDITION(ED)A/C
ACCESS DOORAD
ABOVE FINISHED FLOORAFF
AIR HANDLING UNITAHU
BOILERB
CEILING DIFFUSERCD
CONDENSATE DRAINCD
CUBIC FOOTCF
CUBIC FEET PER MINUTECFM
CENTERLINECL
CONTINUATIONCONT.
DRY BULBDB
DIAMETERDIA
ENTERING AIR TEMPERATUREEAT
ENERGY EFFICIENCY RATINGEER
EXHAUST FANEF
EFFICIENTEFF
ELEVATIONEL
ELECTRICALELECT
ENTERING WATER TEMPERATUREEWT
EXHAUSTEXH
FAHRENHEITF
FACE AREAFA
FLEXIBLE CONNECTORFC
FIRE DAMPERFD
FULL LOAD AMPSFLA
FLOW METERFM
FINS PER INCHFPI
FACE VELOCITYFVEL
GALLONSGAL
GALLONS PER HOURGPH
GALLONS PER MINUTEGPM
HEADHD
HORSEPOWERHP
HEATINGHTG
INCHESIN
KILOWATTKW
LEAVING AIR TEMPERATURELAT
POUNDSLBS.
LATENT HEATLH
LEAVING WATER TEMPERATURELWT
MIXED AIRMA
MAXIMUMMAX
THOUSAND BTU'S PER HOURMBH
MOTORIZED DAMPERMD
MINIMUMMIN
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
NOT IN CONTRACTNIC
NUMBERNO.
NOT TO SCALENTS
OUTSIDE AIROA
PUMPP
PRESSURE DROPPD
POUNDS PER SQUARE INCHPSI
QUANTITYQTY
RETURN AIRRA
REVOLUTIONS PER MINUTERPM
SUPPLY AIRSA
SEASONAL ENERGY EFFICIENCY RATINGSEER
SQUARE FEETSF
SENSIBLE HEATSH
STATIC PRESSURESP
VOLTV
VARIABLE AIR VOLUMEVAV
VOLUME DAMPER (HAND OPERATOR)VD
VELOCITYVEL
VARIABLE FREQUENCY DRIVEVFD
WATTW
WET BULBWB
WATER COLUMNWC
Dampers
FIRE DAMPER
FIRE/SMOKE DAMPER
VOLUME DAMPER
General
DETAIL BUBBLE
DIFFUSER OR GRILLE IDENTIFICATION
EQUIPMENT IDENTIFICATION
KEYED NOTE
OUTSIDE AIR
POINT OF CONNECTION
RETURN OR EXHAUST AIR
RETURN/EXHAUST AIR FLOW
SUPPLY AIR
SUPPLY AIR FLOW
Piping Fittings, Appurtenances and Equipment
AIR SEPARATOR
AUTOMATIC AIR VENT
EXPANSION TANK
FLEXIBLE CONNECTION
FLOW DIRECTION
MANUAL AIR VENT
PIPE DROP
PIPE GUIDE
PIPE RISE
PIPE TO DRAIN
PRESSURE GAUGE WITH COCK
PRESSURE RELIEF VALVE
PRESSURE SENSOR
PUMP
TEMPERATURE SENSOR
THERMOMETER
UNION
VENT TO ATMOSPHERE
Piping Systems
HEATING WATER RETURN
HEATING WATER SUPPLY
Piping Valves
BALANCING VALVE
CHECK VALVE
GATE VALVE
MOTORIZED, 2-WAY VALVE
MOTORIZED, 3-WAY VALVE
PRESSURE REDUCING VALVE
VALVE
VALVE, GENERAL
MECHANICAL SYMBOL LIST
NOTE: This is a standard symbol list and not all items listed may be used.
GENERAL MECHANICAL NOTES
A. COORDINATE EXACT LOCATION OF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES WITH LIGHTING
LAYOUT, CEILING TILE PATTERN AND WITH ARCHITECTURAL REFLECTED CEILING PLANS.
B. PROVIDE MANUAL VOLUME DAMPERS TO FACILITATE PROPER BALANCE OF THE AIR DISTRIBUTION
SYSTEM. VOLUME DAMPER AT DIFFUSERS AND REGISTERS SHALL NOT BE USED FOR AIR
BALANCING.
C. SEAL ALL OPENINGS AROUND PIPING AND DUCTWORK PENETRATING FIRE RESISTIVE RATED WALLS
AND FLOORS TO MAINTAIN RATING INTEGRITY.
D. COORDINATE EXACT LOCATION OF CEILING, WALL OR FLOOR ACCESS PANELS FOR FIRE, SMOKE OR
COMBINATION FIRE SMOKE DAMPERS AND VOLUME DAMPERS WITH ARCHITECT.
E. FLEXIBLE SUPPLY DUCT LENGTH SHALL BE MAXIMUM 5'-0".
MINIMUM RADIUS SHALL BE 1.5 TIMES DIAMETER OF DUCT.
F. PROVIDE MANUAL VOLUME DAMPER REMOTE REGULATOR AT INACCESSIBLE CEILING. SIMILAR TO
YOUNG REGULATOR.
G. COORDINATE EXACT LOCATION OF CORE DRILLING, CUTTING OF FLOOR SLAB, OR WALLS OF THE
BUILDING WITH THE ARCHITECTURAL AND STRUCTURAL DRAWINGS.
H. PROVIDE ACCESS DOOR FOR ALL EQUIPMENT, VALVES AND CLEANOUTS WHICH REQUIRE ACCESS
FOR ADJUSTMENT OR SERVICING, AND WHICH ARE LOCATED IN OTHERWISE INACCESSIBLE
LOCATIONS. OPENINGS SHALL BE LARGE ENOUGH TO PERMIT MAINTENANCE AND ADJUSTMENT OF
THE DEVICE.
I. PITCH PIPELINES AS REQUIRED FOR PROPER DRAINAGE AND ELIMINATION OF AIR.
J. PROVIDE CONDENSATE DRAIN PIPING WITH DRAINAGE FITTINGS FOR ALL COOLING COILS AND
ROUTE TO A NEAREST APPROVED RECEPTOR. SEE PLUMBING DRAWINGS.
K. MANUFACTURERS NAMES FOR PRODUCTS LISTED ON DRAWINGS ARE BASIS OF DESIGN. SEE
SPECIFICATIONS FOR EQUIVALENT MANUFACTURERS.
L. THE PROJECT DESIGN SHOWN ON THE DRAWINGS AND SPECIFIC ITEMS REFERENCED IN THE
SPECIFICATIONS IS IN COMPLIANCE WITH THE CODES AND ORDINANCES LISTED IN DIVISION 23
SPECIFICATIONS.
M. PROVIDE SEISMIC ANCHORAGE AND BRACING FOR MECHANICAL EQUIPMENT, PIPING AND
DUCTWORK. SEE "GENERAL SEISMIC NOTES" FOR DETAIL REQUIREMENTS.
N. INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER
RECOMMENDATIONS UNLESS SPECIFICALLY INDICATED OTHERWISE OR WHERE THE LOCAL CODES
OR REGULATIONS TAKE PRECEDENCE.
O. PREPARE SHOP DRAWINGS FOR INSTALLATION OF ALL NEW WORK BEFORE INSTALLATION TO VERIFY
COORDINATION BETWEEN TRADES.
P. PROVIDE OFFSETS, ELBOWS AND TRANSITIONS IN DUCTWORK AND PIPING AS REQUIRED AT NO
ADDITIONAL COST TO THE OWNER.
Q. VERIFY ALL CONNECTIONS WITH MANUFACTURER'S CERTIFIED DRAWINGS. PROVIDE TRANSITIONS
FOR FINAL CONNECTION TO EQUIPMENT. FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OF
WORK.
R. VERIFY DIFFUSERS, GRILLS, AND REGISTER MOUNTING FRAME TYPES WITH CEILING TYPE AND
CONFIGURATION.
S. FIRE-SAFE PIPE AND DUCTWORK PENETRATIONS OF ALL FIRE RATED AND SMOKE RESISTIVE
CONSTRUCTION. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION AND DETAILS OF ALL
PENETRATION AND FIRE-SAFING REQUIREMENTS.
T. INSTALL ALL EQUIPMENT LEVEL AND PLUMB. PROVIDE BLOCKING AND HARDWARE AS REQUIRED.
U. PROVIDE HANGER, SUPPORT AND SWAY BRACES FOR ALL DUCTWORK, PIPING AND EQUIPMENT AS
REQUIRED BY THE LATEST EDITION OF THE SMACNA GUIDELINES.
V. DUCT SYSTEMS SHALL BE BALANCED TO CFM ON DRAWINGS. FANS SHALL BE FIELD TESTED TO
PROVED COMPLIANCE WITH SCHEDULED FAN PERFORMANCE, AIR FLOW AT DESIGN STATIC
PRESSURE.
W. ALL WORK AND MATERIALS SHALL BE IN COMPLIANCE WITH THE SPECIFICATIONS IN THE EVENT OF A
CONFLICT BETWEEN THE CONTRACT DRAWINGS AND THE SPECIFICATIONS, THE MOST STRINGENT
SHALL GOVERN.
X. INSTALL ALL PIPING AND DUCTWORK TO BEST SUIT FIELD CONDITIONS AND COORDINATE WITH
OTHER TRADES. THE DRAWINGS ARE DIAGRAMMATIC, AND SHALL NOT BE SCALED TO DETERMINE
THE EXACT LOCATIONS OF THE PIPING OR DUCTWORK.
Y. PROVIDE 1-IN AIR GAP AT ALL DRAIN CONNECTIONS.
Office of Construction and Facilities Management
N
E N G I N E E R I N G
I N T E R F A C E
TEL
FAX
PROJECT:
CONTACT:
www.interfaceengineering.com
717 Market Street
Suite 500
San Francisco, CA 94103
415.489.7240
415.489.7289
Date Signed: ----
EFORP
DERET
SI
GE
R
R E
E
NI
GN
E
LA
NOISS
CA L I FO
RN
I AS TA T E OF
Exp. 06-30-2012
No. M29691
M
E C H A N IC A L
G E
OR
GE
L . ARELLA
N O
C o p yr ig h t
S te in b e rg
A rc h it e c ts
A ll R ig h ts
R e s e rv e d
T h e s e
P la n s a n d o r S p e c if ic a ti o n s a re in te n d e d fo r th e s o le b e n e fi t o f S te in b e rg
A rc h it e c ts c lie n t a n d m a y n o t b e u s e d re u s e d ,c o p ie d ,o r re p ro d u c e d in a n y fo rm w it h o u t th e e x p re s s w ri tt e n c o n s e n t o f S te in b e rg
A rc h it e c ts
George Arellano
2010-0410
DATEREV ISSUE
ARCHITECT
PROJECT #:
DATE:
SCALE:
CLIENT
Steinberg Architects 98 Battery Street, Suite 300 San Francisco, CA 94111
02.09.2011 100% Schematic Design
03.16.2011 100% Design Development
05.02.2011 90% Construction Documents
05.31.2011 100% Construction Documents
/2 /2 :1 :1 A M
C R e v it L o c a l\ -0 V a P a lo A lt o \V A P a lo A lt o
J o n e s B ld g E B v .r v t
12" = 1'-0"
1776 OLD MIDDLEFIELD
ROAD, MOUNTAIN VIEW, CA
94043
MH0.01
VAPAHCS Mountain View Center - #640-381
SYMBOL LIST, GENERAL
NOTES AND SHEET INDEX -
MECHANICAL
10037.00 5.31.2011
VA Palo Alto Health Care System 3801 Miranda Ave. Building 6, C360 Palo Alto, CA 94304
100%
CONSTRUCTION
DOCUMENTS
MH0.01 SYMBOL LIST, GENERAL NOTES AND SHEET INDEX - MECHANICAL
MH2.01 LEVEL 1 PLAN - MECHANICAL
MH2.02 LEVEL 2 PLAN - MECHANICAL
MH2.03 ROOF PLAN - MECHANICAL
MH3.01 LEVEL 1 PLAN - MECHANICAL PIPING
MH3.02 LEVEL 2 PLAN - MECHANICAL PIPING
MH5.01 SCHEDULES - MECHANICAL
MH5.02 SCHEDULES - MECHANICAL
MH6.01 DETAILS - MECHANICAL
MH6.02 DETAILS - MECHANICAL
MH6.03 DETAILS - MECHANICAL
MH6.04 DETAILS - MECHANICAL
MH6.05 DETAILS - MECHANICAL
MH7.01 PIPING DIAGRAMS - MECHANICAL
MH7.02 PIPING DIAGRAMS - MECHANICAL
MH8.01 CONTROL DIAGRAMS - MECHANICAL
MH8.02 CONTROL DIAGRAMS - MECHANICAL
SHEET INDEX