S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.CONTROL_DIAGRAMS_MECH.MH8.02.pdf

PDF 138 KB Posted

Attached to
Y1DA--640-20-107 MV-HR BMS HVAC CONST
Solicitation number
36C26120B0013
Issued by

About this file

This document contains control diagrams and sequences of operation for a building automation system at a Department of Veterans Affairs medical facility. The diagrams specify control sequences for air handling units, variable air volume boxes, exhaust fans, pumps, boilers and other mechanical equipment. Sensors, controllers and other control components are shown along with their integration on the network. Points, alarms and interfaces are defined. This level of detail indicates the project involves retrofitting the existing HVAC and controls infrastructure with a new building management system to centralize monitoring and control of mechanical and electrical equipment.

View the file

Other files

File Type Posted
S02 - SF30 Solicitation Amend P00003 - 36C26120B0013 0003.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.REFLECTED_CEILING_PLAN_LEVEL2.AS6.02.pdf PDF
S02 - SF30 Solicitation Amend P00001 - 36C26120B0013 - MV - HR BMS HVAC CONST.pdf PDF
S02 - SF30 Solicitation Amend P00002 - 36C26120B0013 - MV - HR BMS HVAC CONST.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.REFLECTED_CEILING_PLAN_LEVEL1.AS6.01.pdf PDF
S02 - MV LIGHTING CONTROLS_1.pdf PDF
S02 - RFI Log - MV - HR HVAC BMS.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.DETAILS_MECH.MH6.05.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.LEVEL2_PLAN_MECH.MH2.02.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.ROOF_PLAN_MECH.MH2.03.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.SYMBOL_LIST_GEN_NOTES_SHEET_INDEX_MECH.MHO.01.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.CONTROL_DIAGRAMS_MECH.MH8.01.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.DETAILS_MECH.MH6.03.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.LEVEL1_PLAN_MECH_PIPING.MH3.01.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.LEVEL1_PLAN_MECH.MH2.01.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.PIPING_DIAGRAMS_MECH.MH7.01.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.DETAILS_MECH.MH6.04.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.SCHEDULE_MECH.MH5.01.pdf PDF
S04 - Site Visit Sign-in Sheet - MV - HR BMS_FILLED OUT.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.DETAILS_MECH.MH6.02.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.LEVEL_2_PLAN_MECH_PIPING.MH3.02.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.DETAILS_MECH.MH6.01.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.PIPING_DIAGRAMS_MECH.MH7.02.pdf PDF
S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.SCHEDULE_MECH.MH5.02.pdf PDF
36C26120B0013-001.docx DOCX document
36C26120B0013-008.pdf PDF
36C26120B0013-009.pdf PDF
36C26120B0013-007.pdf PDF
36C26120B0013-006.pdf PDF
36C26120B0013-010.pdf PDF
36C26120B0013-002.pdf PDF
36C26120B0013-011.pdf PDF
36C26120B0013-004.pdf PDF
36C26120B0013-003.pdf PDF
36C26120B0013-005.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M

M

BCU-1

TS

SEQUENCE OF OPERATIONS

THE UNIT SHALL MAINTAIN A COOLING SETPOINT OF 74°F (ADJ.)

ZONE ALARMS SHALL BE PROVIDED AS FOLLOWS:

HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS 5°F GREATER THAN THE COOLING SETPOINT.

LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS 5°F LESS THAN THE HEATING SETPOINT.

RUN CONDITIONS - SCHEDULED:

24 VAC

CONTROLLER

UNIT

PX

TEMP

SENSOR

ZONE TEMPERATURE

AO

SETPOINT

AI AI

T

VAV

AO

TRANSDUCER

PRESSURE

CFM VAV

DAMPER

ACTUATOR

T

AI

AIR

TEMP.

SUPPLY

FURNISHED BY CONTROLS CONTRACTOR,

INSTALLED BY VAV MFR.

AO

24 VAC

CONTROLLER

UNIT

PX

TEMP

SENSOR

ZONE TEMPERATURE

AO

SETPOINT

AI AI

T

VAV

HWS

AO

TRANSDUCER

PRESSURE

CFM VAV

DAMPER

ACTUATOR

HWR

T

AI

M

AIR

TEMP.

SUPPLY

C

H

FURNISHED BY CONTROLS CONTRACTOR,

INSTALLED BY VAV MFR.

ZONE

REHEAT

VALVE

(TWO OR

THREE

WAY AS

SHOWN

ON

PLANS)

SEQUENCE OF OPERATIONS

THE UNIT SHALL MAINTAIN A COOLING SETPOINT OF 74°F (ADJ.)

ZONE ALARMS SHALL BE PROVIDED AS FOLLOWS:

HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS 5°F GREATER THAN THE COOLING SETPOINT.

LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS 5°F LESS THAN THE HEATING SETPOINT.

RUN CONDITIONS - SCHEDULED:

THE GENERAL EXHAUST FAN SHALL RUN WHEN SCHEDULED. IF THE FAN IS COMMANDED

ON BUT STATUS DOES NOT SHOW PROOF OF FAN OPERATION, SEND AN ALARM TO THE

OPERATOR WORKSTATION.

EXHAUST FAN

MS

CS

FAN

STATUS DODI STOP

START/

FAN

(EF-1)

SEQUENCE OF OPERATIONS

COMM LINK

SECOND FLOOR

ROOF

24 VAC

24 VAC 24 VAC 120 VAC

MULTI-

PURPOSE

CONTROLLER

EXHAUST FAN

EF-1

MULTI-

PURPOSE

CONTROLLER

MULTI-

PURPOSE

CONTROLLER

AHU-1

VAV BOX

CONTROLLER

VAV BOX

CONTROL

WORKSTATION

LOCATION:

IT/DATA ROOM

BUILDING CONTROL UNIT

LOCATION: 2ND FLOOR ELECTRICAL ROOM

DEDICATED

120 VAC

24 VAC

VAV BOX

CONTROLLER

VAV BOX

CONTROL

REFERENCE DRAWINGS FOR

QUANTITY AND LOCATION OF VAV

BOXES

24 VAC

VAV BOX

CONTROLLER

VAV BOX

CONTROL

24 VAC

VAV BOX

CONTROLLER

VAV BOX

CONTROL

REFERENCE DRAWINGS FOR

QUANTITY AND LOCATION OF VAV

BOXES

1ST FLOOR

MORNING WARM UP:

VAV DAMPER SHALL BE AT FULLY OPEN WHILE REHEAT COIL CONTROL VALVE AT CLOSED

POSITIONS.

24 VAC

PUMP

CONTROLLER

1 VAV WITH REHEAT CONTROL DIAGRAM

NO SCALE

2 VAV WITH/OUT REHEAT CONTROL DIAGRAM

NO SCALE

3 EXHAUST FAN CONTROL DIAGRAM

NO SCALE

5 CONTROL ARCHITECTURE

NO SCALE

EXHAUST FAN

MS

CS

FAN

STATUS DODI STOP

START/

FAN

(EF-3 & 4)

6 ELECTRICAL ROOM EXHAUST FAN CONTROL DIAGRAM

NO SCALE

THERMOSTAT

24 VAC

LIGHTING

CONTROL

SECONDARY

PUMP

HWP-2

PRIMARY

PUMP

HWP-1

BOILER

EXHAUST FAN

WIRED SWITCH

(EF-2)

4 EXHAUST FAN CONTROL DIAGRAM

Office of Construction and Facilities Management

N

E N G I N E E R I N G

I N T E R F A C E

TEL

FAX

PROJECT:

CONTACT:

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

Date Signed: ----

EFORP

DERET

SI

GE

R

R E

E

NI

GN

E

LA

NOISS

CA L I FO

RN

I AS TA T E OF

Exp. 06-30-2012

No. M29691

M

E C H A N IC A L

G E

OR

GE

L . ARELLA

N O

C o p yr ig h t

S te in b e rg

A rc h it e c ts

A ll R ig h ts

R e s e rv e d

T h e s e

P la n s a n d o r S p e c if ic a ti o n s a re in te n d e d fo r th e s o le b e n e fi t o f S te in b e rg

A rc h it e c ts c lie n t a n d m a y n o t b e u s e d re u s e d ,c o p ie d ,o r re p ro d u c e d in a n y fo rm w it h o u t th e e x p re s s w ri tt e n c o n s e n t o f S te in b e rg

A rc h it e c ts

George Arellano

2010-0410

DATEREV ISSUE

ARCHITECT

PROJECT #:

DATE:

SCALE:

CLIENT

Steinberg Architects 98 Battery Street, Suite 300 San Francisco, CA 94111

02.09.2011 100% Schematic Design

03.16.2011 100% Design Development

05.02.2011 90% Construction Documents

05.31.2011 100% Construction Documents

/2 /2 :2 :5 A M

C R e v it L o c a l\ -0 V a P a lo A lt o \V A P a lo A lt o

J o n e s B ld g E B v .r v t

1776 OLD MIDDLEFIELD

ROAD, MOUNTAIN VIEW, CA

94043

MH8.02

VAPAHCS Mountain View Center - #640-381

CONTROL DIAGRAMS -

MECHANICAL

10037.00 5.31.2011

VA Palo Alto Health Care System 3801 Miranda Ave. Building 6, C360 Palo Alto, CA 94304

100%

CONSTRUCTION

DOCUMENTS