S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.SCHEDULE_MECH.MH5.01.pdf
PDF 141 KB Posted
- Attached to
- Y1DA--640-20-107 MV-HR BMS HVAC CONST
- Solicitation number
- 36C26120B0013
About this file
This document contains mechanical schedules and specifications for the Mountain View Center project located at 1776 Old Middlefield Road in Mountain View, California. The schedules provide details on various mechanical systems and components required for the project, including boilers, pumps, air handling units, fans, diffusers, and other HVAC equipment. Specified manufacturers, model numbers, performance requirements, and notes are included.
The related federal contract opportunity is a solicitation for project number 640-20-107 seeking a contractor to provide HVAC construction and building management system work for the Mountain View Center. Interested parties can find additional details by searching for solicitation number 36C26120B0013 on SAM.gov. The solicitation was originally published as RFP 36C26120R0012 but is now identified as IFB 36C26120B0013. The opportunity is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21. No further information is to be requested from individual VA medical centers.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AS-1 HEATING WATER BELL & GOSSETT RL-2 OR EQUAL 25 3 -- 100 7" X 16" 1
NOTES: 1: WITHOUT STRAINER
AIR SEPARATOR SCHEDULE
SYMBOL SERIVE BASIS OF DESIGN
MAX.
GPM
INLTET SIZE
(IN)
MAX. P.D. (FT.
H2O)
MAX. OPER.
WEIGHT (LBS)
SIZE DIA. X
HT.
REMARKS
B-1 414 450 0.83 42.0 - 150 180 PATTERSON KELLEY C-450 500 120V/60 12.4 -- --
NOTES:
1 CERTIFIEND LOW NOX PERFORMANCE; CSA CERTIFIED 92% TO 96% EFFIENCY
2 FULLY MODULATING BURNER WITH 5:1 TURDOWN.
3 OUTDOOR ROOF TOP INSTALLATION, COMBINATION PID TEMPERATURE CONTROL AND FLAME MANAGEMENT
4 MICRO PROCESSOR
5 ON-BOARD DIGITAL TOUCH-PAD USER INTERFACE
6 BOIL CONTROL, CAPACABLE TO COMMUNICATE WITH BMS
7 ON BOARD VARIABLE SPEED PUMP CONTROLLER.
BOILER SCHEDULE
SYMBOL
MAX.
GROSS
OUTPUT
(MBH)
MIN.
GROSS
INTPUT
(MBH)
MIN.
EFF.
(AFUE)
FLOW
RATE
(GPM)
FLUE
SIZE
(IN.)
ENTER
WATER
TEMP.
(°F)
LEAVING
WATER
TEMP. (°f)
BASIS OF DESIGN
MAX
WEIGHT
(LBS)
ELECTRICAL
REMARKS
VOLT/PH
BURNER
(HP)
MCA MOCP
ET-1 HEATING WATER WESSELS - NLA-50 13 BLADDER 14" x 25" 180
NOTES: 1: PRECHARGE 10 TO 15 JPSIG ABOVE SYSTEM PRESSURE
2: PROVIDE BASE RING
EXPANSION TANK SCHEDULE
SYMBOL SERIVE BASIS OF DESIGN
MIN. TANK
VOL.
GALLONS
TYPE SIZE
MAX. OPER.
WEIGHT (LBS)
REMARKS
VOLT/PH HP
EF-1 RESTROOMS CENTRIFUFGAL EXHAUST 1,100 0.60 1,150 58 GREENHECK GB-131-4 75 115/1 1/4 1
EF-2 ELEV. MACHINE ROOM INLINE CABINET FAN 300 0.30 1,000 42 GREENHECK CSP-A410 40 115/1 139 WATTS THERMOSTAT 1
EF-3 2ND FLOOR ELECTRICAL ROOM INLINE CABINET FAN 370 0.50 1,550 54 GREENHECK SQ-97-D 41 115/1 0.1 THERMOSTAT 1
EF-4 1ST FLOOR ELECTRICAL ROOM INLINE CABINET FAN 370 0.50 1,550 54 GREENHECK SQ-97-D 41 115/1 0.1 THERMOSTAT 1
NOTE:
1 PROVIDED WITH SPEED CONTROL
FAN SCHEDULE
SYMBOL AREA SERVED TYPE
AIR FLOW
(CFM)
T.S.P.
(IN.H20)
MAX.
RPM
SOUND
(Dba)
BASIS OF DESIGN
MAX. WT.
(LBS)
ELECTRICAL
CONTROL REMARKS
SYMBOL TYPE FACE SIZE BORDER FACE FINISH BASIS OF DESIGN REMARKS
CD-1 CEILING DIFFUSER 24x24 SURFACE/LAY-IN LOUVERED WHITE TITUS TDC 1, 2, 3, 4 , 5
CD-2 CEILING DIFFUSER 24x24 SURFACE/LAY-IN LOUVERED WHITE TITUS TDC 1, 2, 3, 4 , 5
CRG-1 CEILING RETURN GRILLE 24x24 SURFACE/LAY-IN LOUVERED WHITE TITUS TDC 1, 2, 3, 4 , 5
CEG-1 CEILING EXHAUST GRILLE 24x24 SURFACE/LAY-IN LOUVERED WHITE TITUS PAR 1, 2, 3, 4 , 5
SD-1 LINEAR SLOT DIFFUSER 3/4" SLOT LINEAR SLOT SLOT WHITE TITUS FL-25JT 1, 2, 3, 4 , 5
SD-2 LINEAR SLOT DIFFUSER 3/4" SLOT LINEAR SLOT SLOT WHITE TITUS FL-25JT 1, 2, 3, 4 , 5
TG-1 TRANSFER GRILLE SEE PLANS SURFACE LOUVERED WHITE TITUS 350RL; 350RS 1, 2, 3, 4 , 5
NOTES:
1 PROVIDE SIZES AND LOCATION AS INDICATED IN DRAWINGS
2 REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPE TO DETERMINE REQUIRED FRAME TYPE.
3 PROVIDE REMOTE CONTROL RODS FOR DAMPER WHEN REQUIRED.
4 PROVIDE SQUARE TO ROUND ADPATER AS REQUIRED.
5 COORDINATE CUSTOM COLORS WITH ARCHITECT.
DIFFUSER, REGISTER AND GRILLE SCHEDULE
AHU-1 ENERGY INC - ELPF ROOF 85 10,000 24,000 (2)4.25 2.00 (2)11.21 (2)11.75 1,546 22,000 2.00 12.20 15.00 481.00 539.0 536.3 76/61 55/54 0.3 388.0 27.6 1 150/180 52 68 .1 2 8 1.25 85% 500.0 0.7 1.0 1.0 3.0 4.0 SCROLL 54.8 1 1.5
66.4 80.0
460 3 60.0 NO 12.3 24,000 1,2,3,4,5,6,7,8
1. DISCONNECT/ VARIABLE FREQUENCY DRIVES 5. MINIMUM OUTSIDE AIR (CODE REQUIREMENT) DAMPER POSITION & 100% ECONOMIZER CAPABILITY
2. PROVIDE FANS WITH INTERNAL VIRATION ISOLATORS, MINIMUM 2" DEFLECTION. 6. PROVIDE AC AND COMPONENT CONFIGURATION AND OPTIONS AS SHOWN ON DWGS AND SPECS
3. INTEGRAL BACNET DDC CONTROL - BASIS OF DESIGN = "RELIABLE CONTROL" 7. SMOKE DETECTORS PROVIDED & INSTALLED BY MECHANICAL, WIRED BY ELECTRICAL
4. STAINLESS STEEL DRAIN PANS. 8. PROVIDE FIELD INSTALLED 120V FOR LIGHTS AND CONTROLS
EMERGENCY
POWER (Y/N)
AMBIENT
TEMP (°F
WB)
HZPHASEVOLTMOCPMCA
HP
(EA)
QTYRLATYPEQTYHP (EA)QTY
FINAL
P.D.
IN.WG.
INITIAL
P.D.
IN.WG.
FACE
(FPM)
ASHRAE
EFF.
BRANCH
PIPE SIZE
(IN)
FIN/INROW
AIR P.D.
(IN.WG)
AIR
LAT °F
AIR
MAT °F
EWT/LWT
°F
WATER
P.D. FT.
FLOW
GPM
TOTAL
HEATING
MBH
AIR P.D. (IN.
WG)
SAT
LAT(DB/WB)
°F
MAT
EAT(DB/WB)
°F
SENSIBLE
MBH
TOTAL
MBH
FACE
VEL.
(FPM)
HPBHP
T.S.P. (IN.
WG)
CFMFRPMHPBHP
E.S.P
(IN.WG)
T.S.P. (IN.
WG)
TOTAL
CFM
REMARKS
OPER. WT.
(LBS)
MIN.
EER
ELECTRICALSPRAY PUMPCOMPRESSOR
CONDENSER
FAN
FILTERHEATING WATER COIL (MAX FV = 500 FPM)EVAPORATIVE COIL - DX (MAX FV = 400 FPM)RETURN FANSUPPLY FAN
MIN. OSA
CFM
LOCATIONBASIS OF DESIGNSYMBOL
PACKAGED EVAPORATIVE CONDENSER AIR CONDITIONING UNIT SCHEDULE
HWP-1 PRIMARY BOILER PUMP INLINE SERIES 60 1-1/4 X 1-1/4 X 5-1/4 5" 42 14.5 1,750 208/3 0.28 .33 56.27 55 BELL & GOSSETT 1, 2, 4, 5
HWP-2 SECONDARY DISTRIBUTION PUMP INLINE SERIES 90 2AA 5" 42 25 1,725 208/3 0.72 .75 56.11 70 BELL & GOSSETT 1, 2, 3, 4, 5, 6, 7
NOTE: 1. PROVIDE PREMIUM EFFICIENCY MOTOR
2. OPEN DRIP PROOF MOTOR WITH COVER 5. PROVIDE NEMA3 ENCLOSURE FOR HOUSING TCP CONTROLLER.
3. PROVIDE VFD TO PUMP WITH DIFFERENTIAL PRESSURE SENSOR. 6. PROVIDE PUMP FLEX CONNECTOR, ISOLATION VALVES, INLET/OUTLET GAUGE.
4. INLINE PUMP SERIES 90 7. WIRE PUMP CONTROLLER TO BMS BY DIVISION 26.
HPBHPVOLT/PHRPM
REMARKSBASIS OF DESIGN
OPERATING
WEIGHT
(LBS)
EFFICIENCY
ELECTRICAL
HEAD
(FT.H2O)
FLOW
RATE
(GPM)
IMPELLER
SIZE
PUMP SIZETYPESERVINGSYMBOL
HEATING WATER PUMP SCHEDULE
63.2
FLA
(* TWO POINT DISCONNECT)
32.8 50.027.5
Office of Construction and Facilities Management
N
E N G I N E E R I N G
I N T E R F A C E
TEL
FAX
PROJECT:
CONTACT:
www.interfaceengineering.com
717 Market Street
Suite 500
San Francisco, CA 94103
415.489.7240
415.489.7289
Date Signed: ----
EFORP
DERET
SI
GE
R
R E
E
NI
GN
E
LA
NOISS
CA L I FO
RN
I AS TA T E OF
Exp. 06-30-2012
No. M29691
M
E C H A N IC A L
G E
OR
GE
L . ARELLA
N O
C o p yr ig h t
S te in b e rg
A rc h it e c ts
A ll R ig h ts
R e s e rv e d
T h e s e
P la n s a n d o r S p e c if ic a ti o n s a re in te n d e d fo r th e s o le b e n e fi t o f S te in b e rg
A rc h it e c ts c lie n t a n d m a y n o t b e u s e d re u s e d ,c o p ie d ,o r re p ro d u c e d in a n y fo rm w it h o u t th e e x p re s s w ri tt e n c o n s e n t o f S te in b e rg
A rc h it e c ts
George Arellano
2010-0410
DATEREV ISSUE
ARCHITECT
PROJECT #:
DATE:
SCALE:
CLIENT
Steinberg Architects 98 Battery Street, Suite 300 San Francisco, CA 94111
02.09.2011 100% Schematic Design
03.16.2011 100% Design Development
05.02.2011 90% Construction Documents
05.31.2011 100% Construction Documents
/2 /2 :2 :3 A M
C R e v it L o c a l\ -0 V a P a lo A lt o \V A P a lo A lt o
J o n e s B ld g E B v .r v t
1776 OLD MIDDLEFIELD
ROAD, MOUNTAIN VIEW, CA
94043
MH5.01
VAPAHCS Mountain View Center - #640-381
SCHEDULES - MECHANICAL
10037.00 5.31.2011
VA Palo Alto Health Care System 3801 Miranda Ave. Building 6, C360 Palo Alto, CA 94304
100%
CONSTRUCTION
DOCUMENTS
File details come from the government source that posted it. Updated .