S02 - 640-381.MVW.6.2011.2011.MOUNTAIN_VIEW_CENTER.DETAILS_MECH.MH6.03.pdf
PDF 145 KB Posted
- Attached to
- Y1DA--640-20-107 MV-HR BMS HVAC CONST
- Solicitation number
- 36C26120B0013
About this file
This document provides mechanical engineering details for the Mountain View Center project located at 1776 Old Middlefield Road in Mountain View, California. The details specify requirements for installing galvanized sheet metal pipe shields, supports, expansion tanks, pumps, boilers and associated mounting hardware. Requirements include using redwood sleepers, lag bolts, mastics, insulation, welding, brackets, seismic isolators and reinforced concrete pads. The project number is 10037.00 and the construction documents are dated May 31, 2011.
The related federal contract opportunity is a solicitation issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21. Solicitation number 36C26120B0013, formerly RFP 36C26120R0012, is for the MV-HR BMS HVAC construction project located at the VA Palo Alto Health Care System, 3801 Miranda Ave. Building 6, C360 in Palo Alto, California. The pre-solicitation was originally published on beta.sam.gov and the solicitation provides for HVAC and controls construction work.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROVIDE GALVANIZED SHEET
METAL PIPE SHIELD OVER
ALUMINUM JACKET AT SUPPORTS
BOLT PIPE CLAMP TO REDWOOD
SLEEPER USING 1/4"� LAG BOLTS
6"x4" REDWOOD SLEEPER SHAPED AS
REQUIRED FOR PITCH/SLOPE. SET
IN FULL COVERAGE MASTIC
PIPING WITH INSULATION
AS SPECIFIED
PROVIDE SUPPORTS 6'-0" MIN.
ON CENTERS AND AT CHANGE OF
DIRECTION
ROOF
1 EXPANSION TANK MOUNTING
2 PUMP MOUNTING
3 BOILER MOUNTING DETAIL
A
D
3-1/4" MIN.
EMBEDMENT (TYP)
(4) ANCHOR BOLT
CONCRETE PAD
AIR
SEPARATOR
5 DUCT SUPPORT ON ROOF
4 AIR SEPARATOR MOUNTING
NO SCALE
NO SCALE NO SCALE
NO SCALE
NO SCALE
NO SCALE
(TYPICAL)
JOINTS WELDED
ALL SUPPORT
INSULATION
WOOD SLEEPER
DUCT
VARIES
THRU BOLT
W/WASHER AND 3/8"x8"x8"
PLATE BELOW DECK
MINIMUM
GALVANIZED ANGLE IRON SIZE
PER SMACNA 1½x1½x1/8
LEVEL
AS NECESSARY
4"x 6"x 16 GA.BASE PLATE
SLEEPER W/ LAG BOLTS
SEISMIC BRACING
WELDED TO ANGLE & BOLTED TO
FLASHING PENETRATION
MASTIC IN HOLES AND AT
SLOPE FOR WATER RUN-OFF
PUMP
PUMP
SECTION
SUPERSTRUT OR
ANGLE SUPPORT
FRAME
SEISMIC ISOLATOR
1/2"x6"
(4 REQUIRED)
ANGLE 4"x4"x
SECTION A
ET-1 (14")
(4)-3/4"� ANCHOR
BOLT, 3-1/4" MIN
EMBEDMENT (TYPICAL)
CONCRETE PAD
PLATE 1/4"x4"
(TYP BOTH SIDES
SIDES OF ANGLE 4)
x6" (TYP BOTH
ANGLE 4"x4"x1/2"
CONCRETE PAD
PLATE & ANGLE 4
TYP. BETWEEN
PLATE & TANK
H
180 LB
WEIGHT
ET-1 14" 25"
D H
OF ANGLE 4)
3/16
3/16
TYP BETWEEN
BOILER - SECURE TO
PAD W/1/2"� EXPANSION
SHIELD & BOLT MIN. 3"
PROVIDE REINFORCEMENT BARS
CONCRETE PAD
EMBEDMENT (TYP. 3 PER SIDE)BOILER SUPPORT FRAME
SEE A-A
1/2"x 3" ANCHOR BOLT,
(2) PER ISOLATOR
SEISMIC ISOLATOR
MASON SSLFH
CONCRETE PAD
SUPERSTRUT OR
ANGLE SUPPORT
FRAME
A - A
ROOF STRUCTURE
SEE ARCHITECTURAL
DRAWING
ROOF STRUCTURE
SEE ARCHITECTURAL
DRAWING
CONCRETE PADCONCRETE PAD
FLASHING MEMBRANE
WELDED SPLICEROOF MEMBRANE
GSM COUNTERFLASHING
6 PIPE SUPPORT ON ROOF
Office of Construction and Facilities Management
N
E N G I N E E R I N G
I N T E R F A C E
TEL
FAX
PROJECT:
CONTACT:
www.interfaceengineering.com
717 Market Street
Suite 500
San Francisco, CA 94103
415.489.7240
415.489.7289
Date Signed: ----
EFORP
DERET
SI
GE
R
R E
E
NI
GN
E
LA
NOISS
CA L I FO
RN
I AS TA T E OF
Exp. 06-30-2012
No. M29691
M
E C H A N IC A L
G E
OR
GE
L . ARELLA
N O
C o p yr ig h t
S te in b e rg
A rc h it e c ts
A ll R ig h ts
R e s e rv e d
T h e s e
P la n s a n d o r S p e c if ic a ti o n s a re in te n d e d fo r th e s o le b e n e fi t o f S te in b e rg
A rc h it e c ts c lie n t a n d m a y n o t b e u s e d re u s e d ,c o p ie d ,o r re p ro d u c e d in a n y fo rm w it h o u t th e e x p re s s w ri tt e n c o n s e n t o f S te in b e rg
A rc h it e c ts
George Arellano
2010-0410
DATEREV ISSUE
ARCHITECT
PROJECT #:
DATE:
SCALE:
CLIENT
Steinberg Architects 98 Battery Street, Suite 300 San Francisco, CA 94111
02.09.2011 100% Schematic Design
03.16.2011 100% Design Development
05.02.2011 90% Construction Documents
05.31.2011 100% Construction Documents
/2 /2 :2 :1 A M
C R e v it L o c a l\ -0 V a P a lo A lt o \V A P a lo A lt o
J o n e s B ld g E B v .r v t
1776 OLD MIDDLEFIELD
ROAD, MOUNTAIN VIEW, CA
94043
MH6.03
VAPAHCS Mountain View Center - #640-381
DETAILS - MECHANICAL
10037.00 5.31.2011
VA Palo Alto Health Care System 3801 Miranda Ave. Building 6, C360 Palo Alto, CA 94304