VA SAN FRANCISCO
VA PROJECT# 662-18-001
Install Continuous Water Monitoring System
SECTION 22 11 00
FACILITY WATER DISTRIBUTION
PART 1 - GENERAL
1.1 DESCRIPTION
A. Domestic water systems, including piping, equipment and all necessary accessories as designated in this section.
1.2 RELATED WORK
A. Penetrations in rated enclosures: Section 07 84 00, FIRESTOPPING.
B. Preparation and finish painting and identification of piping systems: Section 09 91 00, PAINTING.
C. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.
1.3 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Manufacturer's Literature and Data:
1. Piping.
2. All items listed in Part 2 - Products.
1.4 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. Federal Specifications (Fed. Spec.):
A-A-1427C Sodium Hypochlorite Solution
A-A-59617 Unions, Brass or Bronze Threaded, Pipe Connections and Solder-Joint Tube Connections
C. American National Standards Institute (ANSI):
American Society of Mechanical Engineers (ASME): (Copyrighted Society)
A13.1-96 Scheme for Identification of Piping Systems
B16.11‑01 Forged Steel Fittings, Socket-Welding and Threaded ANSI/ASME
B16.15-85(R 1994) Cast Bronze Threaded Fittings ANSI/ASME
B16.18-01 Cast Copper Alloy Solder-Joint Pressure Fittings ANSI/ASME B16.22-01 Wrought Copper and Copper Alloy Solder Joint Pressure Fittings ANSI/ASME
Element ANSI/ASME
D. American Society for Testing and Materials (ASTM):
B32-03 Solder Metal
B61-02 Steam or Bronze Castings
B62-02 Composition Bronze or Ounce Metal Castings
B75-99(Rev A) Seamless Copper Tube
B88-03 Seamless Copper Water Tube
B584-00 Copper Alloy Sand Castings for General Applications Revision A
B687-99 Brass, Copper, and Chromium-Plated Pipe Nipples
E1120 Standard Specification For Liquid Chlorine
E1229 Standard Specification For Calcium Hypochlorite
E. American Water Works Association (AWWA):
C110-03/ A21.10-03……..
Ductile Iron and Gray Iron Fittings - 75 mm thru 1200 mm (3 inch thru 48 inches) for Water and other liquids AWWA/ ANSI
C151-00/ A21.51-02……..
Ductile-Iron Pipe, Centrifugally Cast in Metal Molds or Sand-Lined Molds, for Water or Other Liquids AWWA/ ANSI
C203‑02 Coal-Tar Protective Coatings and Linings for Steel Water Pipelines - Enamel and Tape - Hot Applied AWWA/ ANSI
C651‑99 Disinfecting Water Mains
F. American Welding Society (AWS):
A5.8-92 Filler Metals for Brazing
G. National Association of Plumbing - Heating - Cooling Contractors (PHCC):
National Standard Plumbing Code - 1996
H. International Association of Plumbing and Mechanical Officials (IAPMO):
Uniform Plumbing Code - 2000
IS6-93
Installation Standard
I. Manufacturers Standardization Society of the Valve and Fittings Industry, Inc. (MSS):
SP-72-99
Ball Valves With Flanged or Butt Welding For General Purpose
SP-110-96
Ball Valve Threaded, Socket Welding, Solder Joint, Grooved and Flared Ends
J. American Society of Sanitary Engineers (ASSE):
1001-02 Pipe Applied Atmospheric Type Vacuum Breakers
1018-01 Performance for trap seal primer valve-water supply fed
1020-04 Vacuum Breakers, Anti-Siphon, Pressure Type
PART 2 ‑ PRODUCTS
2.1 WATER SERVICE CONNECTIONS TO BUILDINGS
A. From inside face of exterior wall to approximately 1500 mm (5 feet) outside of building and underground inside building, material selected shall be the same for the size specified.
B. Seventy-five millimeters (3 inch) Diameter and Over: Ductile iron, AWWA C151, 850 kPa (125 pounds) water steam pressure (WSP), exterior bituminous coating, cement lined. Provide flanged and anchored connection to interior piping.
C. Under 75 mm (3 inch) Diameter: Copper tubing, ASTM B88, Type K, seamless, annealed. Fittings as specified under Article, INTERIOR DOMESTIC WATER PIPING. Use brazing alloys, AWS A5.8, Classification BCuP.
2.2 INTERIOR DOMESTIC WATER PIPING
A. Pipe: Copper tube, ASTM B88, Type K or L, drawn.
B. Fittings for Copper Tube:
1. Wrought copper or bronze castings conforming to ANSI B16.18 and B16.22. Unions shall be bronze, MSS SP72 & SP 110, Solder or braze joints.
C. Adapters: Provide adapters for joining screwed pipe to copper tubing.
D. Solder: ASTM B32 Composition Sb5 HA or HB. Provide non‑corrosive flux.
E. Brazing alloy: AWS A5.8, Classification BCuP.
2.3 EXPOSED WATER PIPING
A. Inside Generator Building: Chrome‑plated brass piping is not required. Paint piping systems as specified in Section 09 91 00, PAINTING.
2.4 WATERPROOFING
A. Provide at points where pipes pass through membrane waterproofed floors or walls in contact with earth.
B. Floors: Provide cast iron stack sleeve with flashing device and a underdeck clamp. After stack is passed through sleeve, provide a waterproofed caulked joint at top hub.
C. Walls: See detail shown on drawings.
2.5 DIELECTRIC FITTINGS
A. Provide dielectric couplings or unions between ferrous and non‑ferrous pipe.
2.6 STERILIZATION CHEMICALS
1. Liquid Chlorine: ASTM E1120.
2. Hypochlorite: ASTM E1229, or Fed. Spec. AA-1427C, grade B.
PART 3 ‑ EXECUTION
3.1 INSTALLATION
A. General: Comply with the PHCC National Standard Plumbing Code and the following:
1. Install branch piping for water from the piping system and connect to all fixtures, valves, hose bibbs, including those furnished by the Government or specified in other sections.
2. Pipe shall be round and straight. Cutting shall be done with proper tools. Pipe, shall be reamed to full size after cutting.
3. All pipe runs shall be laid out to avoid interference with other work.
4. Pipe Hangers, Supports and Accessories:
a. All piping shall be supported per of the National Standard Plumbing Code, Chapter No. 8.
b. Shop Painting and Plating: Hangers, supports, rods, inserts and accessories used for Pipe supports shall be shop coated with red lead or zinc Chromate primer paint. Electroplated copper hanger rods, hangers and accessories may be used with copper tubing.
c. Floor, Wall and Ceiling Plates, Supports, Hangers:
1) Solid or split unplated cast iron.
2) All plates shall be provided with set screws.
3) Pipe Hangers: Height adjustable clevis type.
4) Adjustable Floor Rests and Base Flanges: Steel.
5) Hanger Rods: Mild, low carbon steel, fully threaded or Threaded at each end with two removable nuts at each end for positioning rod and hanger and locking each in place.
6) Self-drilling type expansion shields shall be "Phillips" type, with case hardened steel expander plugs.
5. Install cast escutcheon with set screw at each wall, floor and ceiling penetration in exposed finished locations and within cabinets and millwork.
6. Penetrations:
a. Fire Stopping: Where pipes pass through fire partitions, fire walls, smoke partitions, or floors, install a fire stop that provides an effective barrier against the spread of fire, smoke and gases as specified in Section 07 84 00, FIRESTOPPING. Completely fill and seal clearances between raceways and openings with the fire stopping materials.
b. Waterproofing: At floor penetrations, completely seal clearances around the pipe and make watertight with sealant as specified in Section 07 92 00, JOINT SEALANTS.
B. Piping shall conform to the following:
1. Domestic Water:
a. Where possible, grade all lines to facilitate drainage. Provide drain valves at bottom of risers. All unnecessary traps in circulating lines shall be avoided.
b. Connect branch lines at bottom of main serving fixtures below and pitch down so that main may be drained through fixture. Connect branch lines to top of main serving only fixtures located on floor above.
3.2 TESTS
A. General: Test system either in its entirety or in sections.
B. Potable Water System: Test after installation of piping, but before piping is concealed, before covering is applied, and before plumbing fixtures are connected. Fill systems with water and maintain hydrostatic pressure of 690 kPa (100 psi) gage for two hours. No decrease in pressure is allowed. Provide a pressure gage with a shutoff and bleeder valve at the highest point of the piping being tested.
3.3 STERILIZATION
A. After tests have been successfully completed, thoroughly flush and sterilize the interior domestic water distribution system in accordance with AWWA C651.
B. Use either liquid chlorine or hypochlorite for sterilization.
END OF SECTION 22 11 00