RFI FORM
Contractor Name: Phigenics, LLC Address: 3S701 West Ave, Ste 100, Warrenville, IL 60555 Phone/email: 937-305-3318/cwyrick@phigenics.com Send to: karen.smith 3@va.gov
RFI
(REQUEST FOR INFORMATION)
PROJECT NO.:
| 662-18-001 |
| RFI NO.: |
| 3 |
PROJECT NAME:
| Install Continuous Monitoring System Device |
| DATE REQUESTED: |
| 8/15/18 |
SOLICITATION NO.:
| 36C-261-18-B-0471 |
| REFERENCE: |
| SOW |
DRAWING:
SPECIFICATION
SECTION:
DESCRIPTION OF PROBLEM OR INFORMATION BEING REQUESTED
Please be specific as possible:
VHA 1061 Requires that representative outlets (in addition to the incoming building water supply) be monitored for Oxidant Residual. The SOW lists 10 buildings that need to be monitored, but there is no indication of how many oxidant residual monitors are required for locations (other than incoming water supply) throughout each building. Can you please provide the quantity of oxidant residual monitors required for each building (not including the incoming building water supply)?
Per the directive: Monitoring the oxidant residual in water supplied to representative outlets (e.g., loop or branch, hydraulic remoteness, flow) is to be continual.
PROJECT MANAGER’S RESPONSE
Please refer to Appendix A, VHA Directive 1061.
| TRACKING NO.: |
| AMENDMENT NO.: 0002 |
| VA PROJECT ENGINEER/MANAGER: William Fotter |
| DATE: 8-21-2018 |