24-046.2 MGVAMC Summer 2024 AHERA 3-Year Reinspection Rpt_.pdf

PDF 3 MB Posted

Attached to
Y1DA--CON-NRM-668-24-102 Replace Windows Building 1
Solicitation number
36C26026R0011
Issued by

About this file

This document is a 3-Year AHERA (Asbestos Hazard Emergency Response Act) Asbestos Reinspection Report for Mann Grandstaff Veteran Affairs Medical Center in Spokane, Washington, dated May 31, 2024.

The inspection covers Buildings 1, 2, 3, 5, and 7 to assess the condition of known regulated asbestos-containing materials (ACMs). The facility contains multiple categories of ACM throughout these buildings, including thermal systems insulation (TSI) with piping insulation at 4-12% chrysotile and mudded fittings at 65-70% chrysotile, vinyl floor tiles (VFT) at 6-8% chrysotile, black mastic at 4-8% chrysotile, and exterior tar and felt roofing systems (assumed asbestos-containing). Building 6 contains potentially asbestos-containing loose-fill vermiculite insulation in wall cavities. Materials are located in basement, first, second, eighth, and ninth floors across various rooms including mechanical spaces, offices, laundry operations, and maintenance areas. The inspection identified most materials in intact to good condition with minimal visible damage. However, two areas of asbestos-contaminated ground soil in Building 1 basement rooms (A005 and C005 East Side) are exposed and present accidental exposure risks, with recommendations for either abatement or enclosure in the near future. Two floor areas in the basement with substrate expansion cracks and minor visible damage have been sealed with wax-sealer requiring continued maintenance. The next AHERA 3-Year Reinspection is scheduled for Summer 2027, with 6-month ACM surveillance required for Winter 2024/25. The inspection was conducted by certified AHERA Building Inspector Samuel W. Bailey Jr. under modified protocols of 40 CFR 763.85.

View the file

Other files

File Type Posted
Attachment 11- Cost Division Breakout Version 1.xlsx XLSX spreadsheet
36C26026R0011 0004.docx DOCX document
668-24-102 Technical Questions Consolidated Responses updated 4-3-2026.pdf PDF
36C26026R0011_1 Solicitation Page 27.pdf PDF
36C26026R0011 0003.docx DOCX document
36C26026R0011 - 668-24-102 - Questions with Consolidated Responses.pdf PDF
82-1000 VA Spokane Windows HazMat Survey Report _no dwgs.pdf PDF
668-24-102 Pre-Bid Walk-Through Sign In.pdf PDF
36C26026R0011 0002.docx DOCX document
Attachment 13 - 668-24-102 - Site Visit Area Map - Revised.pdf PDF
36C26026R0011 0001.docx DOCX document
36C26026R0011_1.docx DOCX document
Attachment 4 - 668-24-102 - PCRA_VHA PCRA.pdf PDF
Attachment 1 - 668-24-102 - CON SOW.pdf PDF
Attachment 3 - 668-24-102 - BID SET SPECIFICATIONS 2_18_26.pdf PDF
Attachment 10 - 668-24-102 - Past Performance Questionnaire.docx DOCX document
Attachment 7 - 668-24-102 - Hazardous Survey Report.pdf PDF
Attachment 8 - 668-24-102 - Limitations on Subcontracting-Construction.pdf PDF
Attachment 11 - 668-24-102 - Cost Division Breakout.xls XLS spreadsheet
Attachment 9 - 668-24-102 - Contractor Rules of Behavior.pdf PDF
Attachment 5 - 668-24-102 - LEVEL 2 Window project VHA ICRA.pdf PDF
Attachment 12 - 668-24-102 - Spokane Wage Determination 1_23_26.pdf PDF
Attachment 2 - 668-24-102 - BID SET DRAWINGS.pdf PDF
Attachment 13 - 668-24-102 - Site Visit Area Map.pdf PDF
Attachment 6 - 668-22-102 - LEVEL 3 Window project VHA ICRA.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Mann Grandstaff - Veteran Affairs Medical Center 3-Year AHERA Asbestos Reinspection: May 31, 2024 Buildings: 1, 2, 3, 5 & 7 (for known Regulated ACMs) Next AHERA 3-Year Reinspection: Summer 2027

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at Time of Visual Inspection Photographs

A001 Misc.

Non-Friable

9”x 9” VFT 6-8% Chrysotile;

Black Mastic

4-8% Chrysotile

AHERA 5,

PLD 4

Intact Condition – No Visible Damage

A001 TSI

Friable

Piping Runs Insulation

4-12% Chrysotile

Mudded Fittings 65-70% Chrysotile

Enclosed Hidden Above Suspended Ceiling Tile System

Assumed to be in Good Condition No Photograph

Available

A002, A002A & A002B

TSI

Damage

Suspended Ceiling Tile System

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

A003 TSI

Assumed to be in Good Condition

A005 Misc.

12”x 12” VFT

A005 TSI

AHERA 1,

PLD 3

Intact to Fair Conditions – Minor Visible Damage

Enclosed Hidden Above Suspended Ceiling Tile System & Exposed in Vertical Chase Behind Laundry Chute

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

A005 TSI

Asbestos Contaminated Ground Soil

PLD 2

Exposed Soil, Not Safe Accidental Exposure Possible.

Recommend an AHERA Response Action of Either Abatement or Enclosure, in the near future.

A006 & A006C

Misc.

Intact Good Condition - No Visible Damage;

Room A006 is Exposed & Room A006C is Enclosed Under Carpeting.

A006 & A006C

Damage

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at Time of Visual Inspection Photographs

A007, A007A, A007B, A007C

Damage

Mostly Enclosed Hidden Above

CB-A1 Misc.

Damage

Past Noted Minor Damage Has Been O&M Repaired

CB-A1 TSI

Damage

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

B001 Misc.

Enclosed Under Carpeting – No Visible Damage

B002 Misc.

Access to Room was not Obtainable During Inspection;

Not Sure if Flooring Materials are Present in Room?

No Photograph Available

B002 TSI

Access to Room was not Obtainable During Inspection;

Not Sure if Overhead Piping Insulation Materials are Present in Room?

No Photograph

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

B004 TSI

Damage

B005, B005A, B005B, B005E & B005F

Damage with Exposed Materials

Some Areas are Enclosed under Carpeting.

B006 Misc.

Enclosed Under Carpeting – No Visible Damage No Photograph

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

B006 TSI

Damage

B007 Misc.

CB-B2

Central Outside Access to Rooms:

B008, B010 & B012

AHERA 4,

Affected Area has been Sealed with a Wax-Sealer; Substrate Expansion Crack is Present and VFT Material is showing Visible Minor Damaged.

Continue to Maintain the Encapsulant Sealer. Until future repairs can be conducted.

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

B011 Misc.

B016A Misc.

B016 & B016A

Damage

Suspended Ceiling System

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at Time of Visual Inspection Photographs

B018 & B018A

Damage

Suspended Ceiling System

CB-B2 Misc.

CB-B2

North

End Area by

Loading Dock

AHERA 4,

Affected Area has been Sealed with a Wax-Sealer; Substrate Expansion Crack is Still Present, but VFT Material is only Visible Minor Damaged.

Continue to Maintain the Encapsulant Sealer. Until future repairs can be conducted.

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

CB-B2 TSI

Damage

C002, C002A, C002B & C002C

Damage

C003 & C003A

Damage

Mostly Enclosed Hidden Above Suspended Ceiling Tile System;

Partially Exposed in A003A.

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at Time of Visual Inspection Photographs

C004 & C004A

Damage

Suspended Ceiling Tile System.

C005, C005A, C005B, C005C & Area W.

Mech Room

Mostly Intact Condition – Minor Visible Damage

Partially Exposed, Mostly Enclosed Hidden Above Suspended Ceiling Tile System; Mixed with Fiberglass Piping Insulations.

C005 East Side

Adjacent Large Mech.

Contaminated Ground Soil

Exposed Soil; Not Safe Accidental Exposure Possible.

Recommend an AHERA Response Action of Either Abatement or Enclosure.

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

CB-C1 Misc.

CB-C1 TSI

Damage

BUILDING 1 - 1ST FLOOR INTERIOR

Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at Time of Visual Inspection Photographs

A102, A102C & A102D

Assumed

ACM, VFT &

Mastic

Intact Condition – No Visible Damage

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - 1ST FLOOR INTERIOR

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at Time of Visual Inspection Photographs

A102, A102B, A102C & A102D

ACM, TSI

Piping

Enclosed Hidden Above Suspended Ceiling Tile System

A102E Misc.

ACM, VFT &

Area & Materials Not Accessible During Inspection. No Photo

A102E TSI

ACM, TSI

Piping

Inspection. No Photo

A119A TSI

ACM, TSI

Piping

Enclosed Hidden Under Newer Carpeting System

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - 1ST FLOOR INTERIOR

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

A122 Misc.

ACM, VFT &

122A Misc.

ACM, VFT &

Enclosed Hidden Under Carpeting

– No Visible Damage

A125 TSI

ACM, TSI

Piping

Materials Not Accessible During Inspection.

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - 1ST FLOOR INTERIOR

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at Time of Visual Inspection Photographs

B101, B101A & B101B

ACM, VFT &

Inspection; Past Inspect Indicated Present Under Carpeting.

B101, B101A & B101B

ACM, TSI

Piping

Inspection. No Photo

Available

B103 & B103A

ACM, VFT &

B116A TSI

ACM, TSI

Piping

Enclosed Hidden Under Newer Flooring System – No Visible Damage

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - 1ST FLOOR INTERIOR

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

B126 Misc.

ACM, VFT &

B128 Misc.

ACM, VFT &

C1-A1, C1-B1 & C1-C1

ACM, VFT &

Materials Enclosed Under Newer Vinyl Flooring System – No Visible Damage

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 - 1ST FLOOR INTERIOR

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at Time of Visual Inspection Photographs

C1-A1, C1-B1 & C1-C1

ACM, TSI

Piping

Materials Not Accessible During Inspection – Hidden Above Suspended Ceiling Tile System.

BUILDING 1 - 2ND FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

A203

1-2%

Chrysotile, 2-4%

Chrysotile

All but 16 ft² of Material has been Properly Abated by IRS Env. in April-May of 2021; Remaining Materials are Present Under IT Floor Mounted Racks - in Intact Good Condition

Next 6-Month ACM Surveillance: Winter 2024/25

Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

A800 TSI

ACM, TSI

Piping

8th Floor Access was Limited During Inspection, No Access Above Interior Suspended Ceilings was Allowed.

No Photo

A800A TSI

ACM, TSI

Piping

Inspection, No Access Above Interior Suspended Ceilings was Allowed.

No Photo

A800B TSI

ACM, TSI

Piping

Inspection, No Access Above Interior Suspended Ceilings was Allowed.

No Photo

A800C TSI

ACM, TSI

Piping

Inspection, No Access Above Interior Suspended Ceilings was Allowed.

No Photo

A800D TSI

ACM, TSI

Piping

Inspection, No Access Above Interior Suspended Ceilings was Allowed.

Next 6-Month ACM Surveillance: Winter 2024/25

Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

B800 TSI

ACM, TSI

Piping

B800 Misc.

ACM, VFT &

Recent Asbestos Testing in IT Closet A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.

Not tested in this area; but should reflect recent survey findings. In Good Condition.

B800A Misc.

ACM, VFT &

A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.

Not Accessible During Inspection; Past Inspect Indicated Present Under Carpeting.

No Photo

Next 6-Month ACM Surveillance: Winter 2024/25

Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

B802 Misc.

ACM, VFT &

A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.

Not Accessible During Inspection; Past Inspect Indicated Present Under Carpeting.

No Photo

B804 Misc.

ACM, VFT &

A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.

Not Accessible During Inspection; Past Inspect Indicated Present Exposed in Good Condition.

B804 TSI

ACM, TSI

Piping

Next 6-Month ACM Surveillance: Winter 2024/25

Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

B807 TSI

ACM, TSI

Piping

B808 TSI

ACM, TSI

Piping

Inspection, No Access Above Interior Suspended Ceilings was Allowed.

No Photo

B812 Misc.

ACM, VFT &

A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.

Our Inspection Identifies ACM Flooring Present Under Carpeting. In Good

B814 Misc.

ACM, VFT &

A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.

Our Inspection Identifies ACM Flooring Present Under Carpeting. In Good

Next 6-Month ACM Surveillance: Winter 2024/25

Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

B816 Misc.

ACM, VFT &

A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.

Our Inspection Identifies ACM Flooring Present Under Carpeting. In Good

B818 Misc.

ACM, VFT &

A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.

Our Inspection Identifies Suspect ACM Flooring Present Exposed. In Good

C8-A1

ACM, TSI

Piping

Next 6-Month ACM Surveillance: Winter 2024/25

Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT

Room Material

Category & Friability

Asbestos Content

AHERA

Assessment Categories

Material Condition at

C8-A1 Misc.

ACM, VFT &

A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.

Our Inspection Identifies Suspect ACM Flooring Present Exposed. In Good

C8-B1 Misc.

ACM, VFT &

A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.

Our Inspection Identifies Suspect ACM Flooring Present Exposed. In Good

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 1 – 9TH FLOOR MECHANICAL ROOM, REGULATED ASBESTOS MATERIAL PRESENT

Room or Area

Material Category &

Friability Asbestos Content

AHERA

Assessment Categories

Material Condition at

A900 TSI

ACM, TSI Piping

9th Floor South Vertical Mechanical Chase Access; Piping Running Down to the Basement Laundry Chute Room A005 Area.

Intact Fair Condition – No Visible Damage, Other Than Peeling Paint.

Limited Access Material.

BUILDING 2 – N. HALF LAUNDRY OPERATIONS, REGULATED ASBESTOS MATERIAL PRESENT

Room or Area

Material Category &

Friability Asbestos Content

AHERA

Assessment Categories

Material Condition at

Exterior Misc.

Tannish-Gray Non-Pliable

Caulking Sealant

4-6% Chrysotile

Present with remaining original ext.

window-frame & door-frame to concrete wall joints (approx. 300 lf present w/17 windows & 3 doors)

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 2 – N. HALF LAUNDRY OPERATIONS, REGULATED ASBESTOS MATERIAL PRESENT

Room or Area

Material Category &

Friability Asbestos Content

AHERA

Assessment Categories

Material Condition at

Tar & Felts Built-up Roofing

System

ASSUMED

Containing

Enclosed Hidden Under White Membrane Roofing System (approx. 6,100 ft² present)

No Visible Damage

BUILDING 3 – EMS & MAINTENANCE SHOPS, REGULATED ASBESTOS MATERIAL PRESENT

Area

Material Category &

Friability Asbestos Content

AHERA

Assessment Categories

Material Condition at Time of Visual Inspection Photographs

SE Office Rooms through

Black Flooring

3-5% Chrysotile

Remaining Material is Present -in Intact Good Condition Enclosed Hidden Under Carpeting & ACM-Free White 12” VFT (approx. 1,320 ft² is still present)

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 3 – EMS & MAINTENANCE SHOPS, REGULATED ASBESTOS MATERIAL PRESENT

Room or Area

Material Category &

Friability Asbestos Content

AHERA

Assessment Categories

Material Condition at

Membrane Roofing System (approx. 8,200 ft² present)

BUILDING 6 – HUMAN RECOURSES, REGULATED ASBESTOS MATERIAL POTENTIALLY PRESENT

Area

Material Category &

Friability Asbestos Content

AHERA

Assessment Categories

Material Condition at Time of Visual Inspection Photographs

Interior Thermal Systems

(TSI)

Loose-Fill Vermiculite

AHERA 6,

Potentially Present, Hidden Within Exterior Inner-Wall Cavities (approx. 3,500 ft² present)

Next 6-Month ACM Surveillance: Winter 2024/25

BUILDING 7 – SUBSTANCE ABUSE TREATMENT CENTER, REGULATED ASBESTOS MATERIAL PRESENT

Room or Area

Material Category &

Friability Asbestos Content

AHERA

Assessment Categories

Material Condition at

Membrane Roofing System (approx. 8,400 ft² potentially present)

During this AHERA 3-Year Reinspection, prior identified Regulated ACMs were assessed for existing condition & newly uncovered suspect ACMs were inspected and added to ongoing documentation. An assessment of each ACM was attempted or carried out and recorded in this report.

Seven (7) categories are required for assessing RACM as mandated by 40 CFR Section 763.88, Assessment.

Defined as follows:

(1) Damaged or significantly damaged TSI-ACM.

(2) Damaged friable Surfacing-ACM.

(3) Significantly damaged friable Surfacing-ACM.

(4) Damaged or significantly damaged Friable Miscellaneous-ACM.

(5) ACM with potential for damage.

(6) ACM with potential for significant damage.

(7) Any remaining Friable ACM or Friable suspected ACM.

Next 6-Month ACM Surveillance: Winter 2024/25

After field assessments, a Priority Level Determination (PLD) is made and assigned for each asbestos containing material (ACM).

The PLD is a judgment, based on our experience and expertise in asbestos evaluations, which provides a framework for assessing material condition and exposure potential.

The PLD ranking prioritizes the nature and immediacy of any corrective actions for repair/removal activities that may be required.

Mountain Consulting utilizes several techniques to approach the PLD. All materials were rated on the PLD scale, which describes the relative comparable risk of material location, condition and potential for occupant’s exposure to asbestos.

The PLD scale is numerical and is prioritized as follows:

1 = Damage extensive or severe; exposure potential high.

2 = Localized damage (Contact, age, repair, vibration); exposure potential intermediate.

3 = Minimal or slight damage (age deterioration); exposure potential low.

4 = No visible damage, or non-friable in good condition; minimal exposure potential for undisturbed materials.

Mountain Consulting Services, LLC hereby certifies that the AHERA Based Asbestos 3-Year Reinspection conducted for the known regulated asbestos-containing building materials present throughout the interior of Buildings 1, 2, 3, 5 & 7 located on the Mann Grandstaff Veteran Affairs Medical Center at 4815 North Assembly Street in Spokane, Washington was conducted under modified protocols of 40 CFR 763.85.

All statements contained herein are certified true and correct to the best of Mountain Consulting Services ability, using "State-of-the- Art" practices.

Inspector: __________________________________ Date: June 12th of 2024

Samuel W. Bailey Jr.

AHERA Building Inspector Certification: BIR20230907-05 Expiration: September 9, 2024

Certifications attached.

Certificate of Completion

Samuel Bailey, Jr has successfully completed

4-Hr AHERA Certified Building Inspector Refresher Training

In compliance with TSCA Title II AHERA 40 CFR Part 763 as approved by the State of Missouri

Kyron Environmental Accreditation #MO-129 Date of Training & Exam: September 7, 2023, in Spokane, WA

Certificate # BIR20230907-05

Tim Lee, Instructor

Expires: 9/07/2024

24-046.2 MGVAMC; Summer 2024, AHERA 3-Year Reinspection Rpt.