24-046.2 MGVAMC Summer 2024 AHERA 3-Year Reinspection Rpt_.pdf
PDF 3 MB Posted
- Solicitation number
- 36C26026R0011
About this file
This document is a 3-Year AHERA (Asbestos Hazard Emergency Response Act) Asbestos Reinspection Report for Mann Grandstaff Veteran Affairs Medical Center in Spokane, Washington, dated May 31, 2024.
The inspection covers Buildings 1, 2, 3, 5, and 7 to assess the condition of known regulated asbestos-containing materials (ACMs). The facility contains multiple categories of ACM throughout these buildings, including thermal systems insulation (TSI) with piping insulation at 4-12% chrysotile and mudded fittings at 65-70% chrysotile, vinyl floor tiles (VFT) at 6-8% chrysotile, black mastic at 4-8% chrysotile, and exterior tar and felt roofing systems (assumed asbestos-containing). Building 6 contains potentially asbestos-containing loose-fill vermiculite insulation in wall cavities. Materials are located in basement, first, second, eighth, and ninth floors across various rooms including mechanical spaces, offices, laundry operations, and maintenance areas. The inspection identified most materials in intact to good condition with minimal visible damage. However, two areas of asbestos-contaminated ground soil in Building 1 basement rooms (A005 and C005 East Side) are exposed and present accidental exposure risks, with recommendations for either abatement or enclosure in the near future. Two floor areas in the basement with substrate expansion cracks and minor visible damage have been sealed with wax-sealer requiring continued maintenance. The next AHERA 3-Year Reinspection is scheduled for Summer 2027, with 6-month ACM surveillance required for Winter 2024/25. The inspection was conducted by certified AHERA Building Inspector Samuel W. Bailey Jr. under modified protocols of 40 CFR 763.85.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Mann Grandstaff - Veteran Affairs Medical Center 3-Year AHERA Asbestos Reinspection: May 31, 2024 Buildings: 1, 2, 3, 5 & 7 (for known Regulated ACMs) Next AHERA 3-Year Reinspection: Summer 2027
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at Time of Visual Inspection Photographs
A001 Misc.
Non-Friable
9”x 9” VFT 6-8% Chrysotile;
Black Mastic
4-8% Chrysotile
AHERA 5,
PLD 4
Intact Condition – No Visible Damage
A001 TSI
Friable
Piping Runs Insulation
4-12% Chrysotile
Mudded Fittings 65-70% Chrysotile
Enclosed Hidden Above Suspended Ceiling Tile System
Assumed to be in Good Condition No Photograph
Available
A002, A002A & A002B
TSI
Damage
Suspended Ceiling Tile System
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
A003 TSI
Assumed to be in Good Condition
A005 Misc.
12”x 12” VFT
A005 TSI
AHERA 1,
PLD 3
Intact to Fair Conditions – Minor Visible Damage
Enclosed Hidden Above Suspended Ceiling Tile System & Exposed in Vertical Chase Behind Laundry Chute
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
A005 TSI
Asbestos Contaminated Ground Soil
PLD 2
Exposed Soil, Not Safe Accidental Exposure Possible.
Recommend an AHERA Response Action of Either Abatement or Enclosure, in the near future.
A006 & A006C
Misc.
Intact Good Condition - No Visible Damage;
Room A006 is Exposed & Room A006C is Enclosed Under Carpeting.
A006 & A006C
Damage
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at Time of Visual Inspection Photographs
A007, A007A, A007B, A007C
Damage
Mostly Enclosed Hidden Above
CB-A1 Misc.
Damage
Past Noted Minor Damage Has Been O&M Repaired
CB-A1 TSI
Damage
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
B001 Misc.
Enclosed Under Carpeting – No Visible Damage
B002 Misc.
Access to Room was not Obtainable During Inspection;
Not Sure if Flooring Materials are Present in Room?
No Photograph Available
B002 TSI
Access to Room was not Obtainable During Inspection;
Not Sure if Overhead Piping Insulation Materials are Present in Room?
No Photograph
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
B004 TSI
Damage
B005, B005A, B005B, B005E & B005F
Damage with Exposed Materials
Some Areas are Enclosed under Carpeting.
B006 Misc.
Enclosed Under Carpeting – No Visible Damage No Photograph
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
B006 TSI
Damage
B007 Misc.
CB-B2
Central Outside Access to Rooms:
B008, B010 & B012
AHERA 4,
Affected Area has been Sealed with a Wax-Sealer; Substrate Expansion Crack is Present and VFT Material is showing Visible Minor Damaged.
Continue to Maintain the Encapsulant Sealer. Until future repairs can be conducted.
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
B011 Misc.
B016A Misc.
B016 & B016A
Damage
Suspended Ceiling System
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at Time of Visual Inspection Photographs
B018 & B018A
Damage
Suspended Ceiling System
CB-B2 Misc.
CB-B2
North
End Area by
Loading Dock
AHERA 4,
Affected Area has been Sealed with a Wax-Sealer; Substrate Expansion Crack is Still Present, but VFT Material is only Visible Minor Damaged.
Continue to Maintain the Encapsulant Sealer. Until future repairs can be conducted.
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
CB-B2 TSI
Damage
C002, C002A, C002B & C002C
Damage
C003 & C003A
Damage
Mostly Enclosed Hidden Above Suspended Ceiling Tile System;
Partially Exposed in A003A.
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at Time of Visual Inspection Photographs
C004 & C004A
Damage
Suspended Ceiling Tile System.
C005, C005A, C005B, C005C & Area W.
Mech Room
Mostly Intact Condition – Minor Visible Damage
Partially Exposed, Mostly Enclosed Hidden Above Suspended Ceiling Tile System; Mixed with Fiberglass Piping Insulations.
C005 East Side
Adjacent Large Mech.
Contaminated Ground Soil
Exposed Soil; Not Safe Accidental Exposure Possible.
Recommend an AHERA Response Action of Either Abatement or Enclosure.
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - BASEMENT LEVEL INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
CB-C1 Misc.
CB-C1 TSI
Damage
BUILDING 1 - 1ST FLOOR INTERIOR
Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at Time of Visual Inspection Photographs
A102, A102C & A102D
Assumed
ACM, VFT &
Mastic
Intact Condition – No Visible Damage
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - 1ST FLOOR INTERIOR
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at Time of Visual Inspection Photographs
A102, A102B, A102C & A102D
ACM, TSI
Piping
Enclosed Hidden Above Suspended Ceiling Tile System
A102E Misc.
ACM, VFT &
Area & Materials Not Accessible During Inspection. No Photo
A102E TSI
ACM, TSI
Piping
Inspection. No Photo
A119A TSI
ACM, TSI
Piping
Enclosed Hidden Under Newer Carpeting System
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - 1ST FLOOR INTERIOR
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
A122 Misc.
ACM, VFT &
122A Misc.
ACM, VFT &
Enclosed Hidden Under Carpeting
– No Visible Damage
A125 TSI
ACM, TSI
Piping
Materials Not Accessible During Inspection.
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - 1ST FLOOR INTERIOR
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at Time of Visual Inspection Photographs
B101, B101A & B101B
ACM, VFT &
Inspection; Past Inspect Indicated Present Under Carpeting.
B101, B101A & B101B
ACM, TSI
Piping
Inspection. No Photo
Available
B103 & B103A
ACM, VFT &
B116A TSI
ACM, TSI
Piping
Enclosed Hidden Under Newer Flooring System – No Visible Damage
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - 1ST FLOOR INTERIOR
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
B126 Misc.
ACM, VFT &
B128 Misc.
ACM, VFT &
C1-A1, C1-B1 & C1-C1
ACM, VFT &
Materials Enclosed Under Newer Vinyl Flooring System – No Visible Damage
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 - 1ST FLOOR INTERIOR
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at Time of Visual Inspection Photographs
C1-A1, C1-B1 & C1-C1
ACM, TSI
Piping
Materials Not Accessible During Inspection – Hidden Above Suspended Ceiling Tile System.
BUILDING 1 - 2ND FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
A203
1-2%
Chrysotile, 2-4%
Chrysotile
All but 16 ft² of Material has been Properly Abated by IRS Env. in April-May of 2021; Remaining Materials are Present Under IT Floor Mounted Racks - in Intact Good Condition
Next 6-Month ACM Surveillance: Winter 2024/25
Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
A800 TSI
ACM, TSI
Piping
8th Floor Access was Limited During Inspection, No Access Above Interior Suspended Ceilings was Allowed.
No Photo
A800A TSI
ACM, TSI
Piping
Inspection, No Access Above Interior Suspended Ceilings was Allowed.
No Photo
A800B TSI
ACM, TSI
Piping
Inspection, No Access Above Interior Suspended Ceilings was Allowed.
No Photo
A800C TSI
ACM, TSI
Piping
Inspection, No Access Above Interior Suspended Ceilings was Allowed.
No Photo
A800D TSI
ACM, TSI
Piping
Inspection, No Access Above Interior Suspended Ceilings was Allowed.
Next 6-Month ACM Surveillance: Winter 2024/25
Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
B800 TSI
ACM, TSI
Piping
B800 Misc.
ACM, VFT &
Recent Asbestos Testing in IT Closet A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.
Not tested in this area; but should reflect recent survey findings. In Good Condition.
B800A Misc.
ACM, VFT &
A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.
Not Accessible During Inspection; Past Inspect Indicated Present Under Carpeting.
No Photo
Next 6-Month ACM Surveillance: Winter 2024/25
Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
B802 Misc.
ACM, VFT &
A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.
Not Accessible During Inspection; Past Inspect Indicated Present Under Carpeting.
No Photo
B804 Misc.
ACM, VFT &
A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.
Not Accessible During Inspection; Past Inspect Indicated Present Exposed in Good Condition.
B804 TSI
ACM, TSI
Piping
Next 6-Month ACM Surveillance: Winter 2024/25
Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
B807 TSI
ACM, TSI
Piping
B808 TSI
ACM, TSI
Piping
Inspection, No Access Above Interior Suspended Ceilings was Allowed.
No Photo
B812 Misc.
ACM, VFT &
A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.
Our Inspection Identifies ACM Flooring Present Under Carpeting. In Good
B814 Misc.
ACM, VFT &
A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.
Our Inspection Identifies ACM Flooring Present Under Carpeting. In Good
Next 6-Month ACM Surveillance: Winter 2024/25
Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
B816 Misc.
ACM, VFT &
A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.
Our Inspection Identifies ACM Flooring Present Under Carpeting. In Good
B818 Misc.
ACM, VFT &
A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.
Our Inspection Identifies Suspect ACM Flooring Present Exposed. In Good
C8-A1
ACM, TSI
Piping
Next 6-Month ACM Surveillance: Winter 2024/25
Building 1 - 8TH FLOOR INTERIOR, REGULATED ASBESTOS MATERIAL PRESENT
Room Material
Category & Friability
Asbestos Content
AHERA
Assessment Categories
Material Condition at
C8-A1 Misc.
ACM, VFT &
A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.
Our Inspection Identifies Suspect ACM Flooring Present Exposed. In Good
C8-B1 Misc.
ACM, VFT &
A800D found Black Flooring Mastic to Contain 2-3% Chrysotile Asbestos; but 9”x 9” VFT was proven Asbestos-Free.
Our Inspection Identifies Suspect ACM Flooring Present Exposed. In Good
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 1 – 9TH FLOOR MECHANICAL ROOM, REGULATED ASBESTOS MATERIAL PRESENT
Room or Area
Material Category &
Friability Asbestos Content
AHERA
Assessment Categories
Material Condition at
A900 TSI
ACM, TSI Piping
9th Floor South Vertical Mechanical Chase Access; Piping Running Down to the Basement Laundry Chute Room A005 Area.
Intact Fair Condition – No Visible Damage, Other Than Peeling Paint.
Limited Access Material.
BUILDING 2 – N. HALF LAUNDRY OPERATIONS, REGULATED ASBESTOS MATERIAL PRESENT
Room or Area
Material Category &
Friability Asbestos Content
AHERA
Assessment Categories
Material Condition at
Exterior Misc.
Tannish-Gray Non-Pliable
Caulking Sealant
4-6% Chrysotile
Present with remaining original ext.
window-frame & door-frame to concrete wall joints (approx. 300 lf present w/17 windows & 3 doors)
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 2 – N. HALF LAUNDRY OPERATIONS, REGULATED ASBESTOS MATERIAL PRESENT
Room or Area
Material Category &
Friability Asbestos Content
AHERA
Assessment Categories
Material Condition at
Tar & Felts Built-up Roofing
System
ASSUMED
Containing
Enclosed Hidden Under White Membrane Roofing System (approx. 6,100 ft² present)
No Visible Damage
BUILDING 3 – EMS & MAINTENANCE SHOPS, REGULATED ASBESTOS MATERIAL PRESENT
Area
Material Category &
Friability Asbestos Content
AHERA
Assessment Categories
Material Condition at Time of Visual Inspection Photographs
SE Office Rooms through
Black Flooring
3-5% Chrysotile
Remaining Material is Present -in Intact Good Condition Enclosed Hidden Under Carpeting & ACM-Free White 12” VFT (approx. 1,320 ft² is still present)
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 3 – EMS & MAINTENANCE SHOPS, REGULATED ASBESTOS MATERIAL PRESENT
Room or Area
Material Category &
Friability Asbestos Content
AHERA
Assessment Categories
Material Condition at
Membrane Roofing System (approx. 8,200 ft² present)
BUILDING 6 – HUMAN RECOURSES, REGULATED ASBESTOS MATERIAL POTENTIALLY PRESENT
Area
Material Category &
Friability Asbestos Content
AHERA
Assessment Categories
Material Condition at Time of Visual Inspection Photographs
Interior Thermal Systems
(TSI)
Loose-Fill Vermiculite
AHERA 6,
Potentially Present, Hidden Within Exterior Inner-Wall Cavities (approx. 3,500 ft² present)
Next 6-Month ACM Surveillance: Winter 2024/25
BUILDING 7 – SUBSTANCE ABUSE TREATMENT CENTER, REGULATED ASBESTOS MATERIAL PRESENT
Room or Area
Material Category &
Friability Asbestos Content
AHERA
Assessment Categories
Material Condition at
Membrane Roofing System (approx. 8,400 ft² potentially present)
During this AHERA 3-Year Reinspection, prior identified Regulated ACMs were assessed for existing condition & newly uncovered suspect ACMs were inspected and added to ongoing documentation. An assessment of each ACM was attempted or carried out and recorded in this report.
Seven (7) categories are required for assessing RACM as mandated by 40 CFR Section 763.88, Assessment.
Defined as follows:
(1) Damaged or significantly damaged TSI-ACM.
(2) Damaged friable Surfacing-ACM.
(3) Significantly damaged friable Surfacing-ACM.
(4) Damaged or significantly damaged Friable Miscellaneous-ACM.
(5) ACM with potential for damage.
(6) ACM with potential for significant damage.
(7) Any remaining Friable ACM or Friable suspected ACM.
Next 6-Month ACM Surveillance: Winter 2024/25
After field assessments, a Priority Level Determination (PLD) is made and assigned for each asbestos containing material (ACM).
The PLD is a judgment, based on our experience and expertise in asbestos evaluations, which provides a framework for assessing material condition and exposure potential.
The PLD ranking prioritizes the nature and immediacy of any corrective actions for repair/removal activities that may be required.
Mountain Consulting utilizes several techniques to approach the PLD. All materials were rated on the PLD scale, which describes the relative comparable risk of material location, condition and potential for occupant’s exposure to asbestos.
The PLD scale is numerical and is prioritized as follows:
1 = Damage extensive or severe; exposure potential high.
2 = Localized damage (Contact, age, repair, vibration); exposure potential intermediate.
3 = Minimal or slight damage (age deterioration); exposure potential low.
4 = No visible damage, or non-friable in good condition; minimal exposure potential for undisturbed materials.
Mountain Consulting Services, LLC hereby certifies that the AHERA Based Asbestos 3-Year Reinspection conducted for the known regulated asbestos-containing building materials present throughout the interior of Buildings 1, 2, 3, 5 & 7 located on the Mann Grandstaff Veteran Affairs Medical Center at 4815 North Assembly Street in Spokane, Washington was conducted under modified protocols of 40 CFR 763.85.
All statements contained herein are certified true and correct to the best of Mountain Consulting Services ability, using "State-of-the- Art" practices.
Inspector: __________________________________ Date: June 12th of 2024
Samuel W. Bailey Jr.
AHERA Building Inspector Certification: BIR20230907-05 Expiration: September 9, 2024
Certifications attached.
Certificate of Completion
Samuel Bailey, Jr has successfully completed
4-Hr AHERA Certified Building Inspector Refresher Training
In compliance with TSCA Title II AHERA 40 CFR Part 763 as approved by the State of Missouri
Kyron Environmental Accreditation #MO-129 Date of Training & Exam: September 7, 2023, in Spokane, WA
Certificate # BIR20230907-05
Tim Lee, Instructor
Expires: 9/07/2024
| 24-046.2 MGVAMC; Summer 2024, AHERA 3-Year Reinspection Rpt. |
| Sam Bailey_AHERA BIR Cert 2023-24 |
| AHERA Bldg. Insp. PDF |