Conduct Campuswide Electrical Coordination Study.pdf
PDF 21 MB Posted
- Attached to
- H261--Triennial Electrical Testing Federal contract opportunity
- Solicitation number
- 36C25926Q0605
About this file
This is a comprehensive electrical coordination study report for the Rocky Mountain VA Medical Center that documents arc-flash hazard calculations, short-circuit analyses, and overcurrent device coordination across multiple facility buildings. The study was conducted by Apogee Consulting Group P.A. and completed on April 29, 2024, utilizing SKM Power*Tools software and IEEE 1584-2018 standards to evaluate electrical system safety and performance.
The report encompasses short-circuit studies, arc-flash incident energy (AFIE) calculations, coordination studies, and existing equipment assessments across Buildings 2 and 3N of the medical center. Key findings include the identification of equipment duty cycle ratings to ensure adequate ampere interrupting capacity, determination of incident energy values at various electrical equipment points ranging from 0 to 37.44 cal/cm², and the generation of arc-flash hazard labels compliant with ANSI 7535, NFPA 70E Article 130.5(C), and NEC 110.16. The utility source data from Xcel Energy indicates maximum 3-phase fault currents of 9,227 to 10,091 amps at the 13.2 kV service. The study identifies critical and low-priority deficiencies through a prioritized Issues Log, with recommendations for equipment modifications and overcurrent protective device (OCPD) setting adjustments to improve system coordination. Additionally, the report includes surveys of automatic transfer switches (ATS), ground resistance analysis, and emergency power system assessment. All arc-flash hazard labels were provided in 4"x6" die-cut vinyl format suitable for indoor/outdoor application, and the study recommends periodic review of incident energy analysis at intervals not exceeding five years or upon any changes to the electrical distribution system.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Triennial Electrical Testing - Additional Questions and Answers 7-23-26.pdf.docx | DOCX document | |
| 36C25926Q0605 0002.docx | DOCX document | |
| 36C25926Q0605 0001.docx | DOCX document | |
| Triennial Electrical Testing - Questions and Answers.docx | DOCX document | |
| Department of Labor Wage Determination - 2015-5419 Rev 32 - 05-13-2026.pdf | ||
| 36C25926Q0605.docx | DOCX document | |
| 480V Cutoff.pdf | ||
| Elect One Line 11x17_2024-04-29.pdf | ||
| Statement of Work - Electrical Testing - 07-01-2026.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
554-22-144
Conduct Campuswide Electrical
Coordination Study
Contract Number: 36C25922D0008
Rocky Mountain VAMC
13611 East Colfax Ave.
Aurora, CO 80045
100% Report – For Review
REPORT BY:
Josh VandenEnde, PE
Beau Browning
ENGINEER OF RECORD: Josh VandenEnde, PE
1000 Centre Avenue
Suite 120
Fort Collins, CO 80526
29 April 2024
TABLE OF CONTENTS
1.0 INTRODUCTION
2.0 MODEL PREPARATION
3.0 SHORT-CIRCUIT ANALYSIS AND ARC-FLASH HAZARD
3.1 SKM Power*Tools Analyses
3.2 Utility Information
3.3 Short Circuit Analysis
3.4 Arc-Flash Hazard
3.5 Arc-Flash Hazard Labels
4.0 COORDINATION STUDY
5.0 EXISTING CONDITIONS ASSESSMENT
5.1 Specif ic Assessments
5.1a ATS
5.1b Ground Resistance
5.1c Emergency Power System
6.0 ISSUES LOG
APPENDIX A – References
APPENDIX B – Source Data
APPENDIX C – Single-Line Diagrams
APPENDIX D – System Data Model Inputs
APPENDIX E – Short-Circuit Reports
APPENDIX F – Arc-Flash Hazard Report
APPENDIX G – Arc-Flash Hazard Labels
APPENDIX H – Coordination Study Time Current Curves
APPENDIX I – Existing Conditions Assessment
APPENDIX J – Issues Log
APPENDIX K – Additional Documents
APPENDIX K – Detailed Electrical Systems Analysis
1.0 INTRODUCTION
The Rocky Mountain VA Medical Center has contracted with Apogee Consulting Group P.A. to provide evaluation and reporting for existing electrical services and distribution within and relevant to specific facilities identified by the scope of work as detailed in the contract documents. Due to the size and scope of the effort, reporting may be divided by Rocky Mountain VA Medical Center facility number and/or name.
Objectives included; identification of electrical system deficiencies, existing overcurrent device coordination, compilation of observed data and calculated analyses into a formal report, production and application of arc-flash hazard labels specific to the equipment specified within the scope of work.
This report outlines the methodology employed for the electrical study and provides the theoretical foundation for analyses.
Further discussion has been included in the appendices; Detailed Electrical Systems Analysis.
Study methodologies were based upon current industry standard best practices and employed the use of computerized power analysis and modeling software distributed by SKM Power*ToolsTM. The technical publication titled, “Complete Guide to Arc-Flash Hazard Calculation Studies- A step-by-step approach packed with examples, tips, and calculation worksheets,” by Jim Phillips, provided a basis for the recommendations included within this report.
Additional references can be found in the appendices; References.
Electrical system analyses were conducted in accordance with the scope of work (SOW) indicated in the contract documents. They included, but were not limited to short-circuit studies, arc-flash incident energy (AFIE) calculation studies, coordination studies, and existing equipment assessments. Other compilations of data and calculations may have been included to indicate aspects of a system more clearly.
Short-circuit studies were conducted and intended as the bases for verification that equipment is adequately sized for the available fault current (AFC) at each location. AFIE calculation studies are conducted and used for arc-flash hazard risk assessment. Calculated AFIE values are visibly communicated at specific equipment by arc-flash labels in accordance with applicable codes and standards, including NFPA 70 National Electrical Code (NEC), NFPA 70E Standard for Electrical Safety in the Workplace, and OSHA publications.
Coordination studies observe the over-current protective device (OCPD) settings to evaluate the order in which fault clearances are expected to occur.
Recommendations regarding OCPD settings may be made and are based on the coordination studies. Existing equipment assessments record and identify through visual inspection the current conditions of equipment and the immediate surrounding area that may affect the function of, access to or path of egress.
Standards-compliant labels indicating calculated arc-flash hazard values will be provided in conjunction with the certified issuance of the electrical study report and are to be affixed to corresponding equipment.
While identification and visible representation of arc-flash hazards were the primary objectives of this study, other inclusions are condition assessments, ATS survey, and coordination plots.
The body of this report is intended to specify analysis methodology. Detailed results can be found in the appendices.
Through the course of a study deficiencies were found at various stages: data collection, modeling, photo review, or analyses. To efficiently capture, summarize, track, and prioritize significant findings and their resolutions, an Issues Log was established. Items were entered in the Issues Log as they were discovered along with further descriptions. An assessment was made to prioritize deficiencies that require correction and was based on severity. The Issues Log can be found in the appendices; Issues Log.
Prioritization was based on a scale of 1-4, 1 representing a critical deficiency and 4 representing a low priority deficiency. Critical deficiency items were deemed to pose an imminent threat to personnel safety and/or property and should be corrected as soon as possible. Low priority deficiency items were deemed as requiring preventative correction and are expected to be addressed when time and funding allow.
2.0 MODEL PREPARATION
Survey data was compiled, and system models were created and edited by Apogee Consulting Group P.A. personnel. Models were developed and updated using survey data and representative drawings for each facility to accurately simulate the function of system components.
Single-line diagrams indicating system arrangement and inputs can be found in the appendices, Single-Line Diagrams.
Tabulated input data can be found in the appendices, System Data Model Inputs.
Where system information was unattainable or omitted from the model and did not prevent system analysis, the client or representatives of was notified, and reasonable efforts were made to acquire the missing information. Where necessary, data assumptions were made in accordance with IEEE 1584.1-2018.
3.0 SHORT-CIRCUIT ANALYSIS AND ARC-FLASH HAZARD
3.1 SKM Power*Tools T M Analyses
Upon completion of model development, models were evaluated using power analysis software. Per industry standard IEEE 1584, the software was used to calculate AFC and further derive relevant values at specified points of the modeled system.
Additional explanation of this calculation process can be found in the appendices, Detailed Electrical Systems Analysis.
3.2 Utility Information
Utility source specifics were requested and provided by Xcel EnergyTM.
Source data is generally provided by the utility provider as a representation of the worst-case scenario and is reflective of the highest possible AFC at a given location, which provides a margin of error due to which source system changes may not automatically void utility provided data and thus the dependent electrical study.
It is recommended that caution be taken regarding the continued reliability of the accuracy of utility provided source data as it is subject to system changes without notification by the utility provider. System changes affecting the source may void the foundational input data and the electrical study itself, which may require the study to be conducted using new input data.
NFPA 70E Article 130.5 states that the incident energy analysis shall be updated when changes occur in the electrical distribution system that could affect the results of the analysis. The incident energy analysis shall also be reviewed for accuracy at intervals not to exceed 5 years.
Utility provided information can be found in the appendices, Source Data.
3.3 Short-Circuit Analysis
The short-circuit study indicates the maximum AFC at specified points throughout the system.
Tabulated short-circuit values can be found in the appendices; Short-Circuit Reports.
AFC values were calculated and used to verify that equipment ampere interrupting capacity (AIC) ratings, where provided, were higher than the calculated AFC values to which equipment will be exposed, referred to as equipment duty (EQD), indicated by the calculation 𝐸𝑄𝐷 =
AFC
AIC
and represented as a percentage of the equipment rating. A percentage above 100% indicates overdutied equipment and a violation of the equipment AIC/SCCR rating. A percentage below 100% indicates the equipment AIC/SCCR rating is above the calculated AFC and in compliance.
EQD calculations can be found in the appendices; Short-Circuit Reports, Device Evaluation.
Equipment identified as overdutied has been reported in the Issues Log and can be found in the appendices; Issues Log. Equipment identified to be overdutied by more than 20% was listed as Priority 1.
Sufficiently small short-circuit current/withstand ratings (SCCR or SCWR) of low voltage disconnect switches, such as local equipment disconnects for small motors, were not evaluated as part o f this e lect r ica l study.
Care should be taken to ensure that these devices are applied according to their UL-listed short-circuit withstand ratings. Typical withstand ratings for disconnect switches (safety switches) range from 10kA to 200kA.
Where information was available and could potentially cause a notable difference, inductive loads (i.e. motor loads) were represented within the models. During a fault event, they contribute to the sub-transient fault current. The potential contribution of inductive loads is based on the size of the load. In general, motors 25 hp or larger were modeled.
Further discussion of the calculations and theory involved in the short-circuit analysis can be found in appendices; Detailed Electrical Systems Analysis.
3.4 Arc-Flash Hazard
An Arc-Flash Hazard is the hazard caused by an arcing event. There are multiple contributors that account for the totality of an Arc-Flash Hazard.
Thermal incident energy is the energy converted to heat. During an arcing event, the temperatures experienced can be several thousand degrees.
The heat propagates away from the source and dissipates as a function of exponential decay. It is the primary cause of injury and is currently the only energy considered and estimated as part of an arc-flash study.
Arc Blast is caused by the rapid conversion of electrical energy to heat energy. Pressure and sonic waves are created by the arcing event and can be damaging to the soft tissues of nearby individuals, potentially causing long term damage or death.
There are additional hazards caused by an arcing event not discussed here (e.g shrapnel/projectiles, intense light, toxic fumes, etc.).
Arc-Flash Hazards are quantified by calculating the AFIE (thermal) value.
The IEEE 1584 equation was developed based on test case values and inputs. The most significant factors are AFC, time of exposure, and distance. Other contributing factors are environment, equipment type and arc length.
It is possible for similar arcing events to incur higher AFIE exposure at lesser AFC values. This can be explained by evaluating a time current curve plot and identifying the trip times at different currents. This situation occurs in the immediate area under the curve where the slope is close to vertical and trip times are maximized. To test the effect of lower AFC on the trip time of OCPDs and the corresponding changes to AFIE, IEEE 1584 recommends evaluating AFIE values at both 100% and 85% of the anticipated AFC. All equipment and buses modeled were evaluated at both recommended evaluation percentages. The AFC percentage inducing the greater AFIE value was considered the worst-case and thus the only value reported.
AFIE values can be found in the appendices; Single-Line Diagrams, AFIE and Arc-Flash Hazard Report.
Note: Incident energy values listed in the Arc-Flash Hazard Report are valid only for protective devices configured according to the OCPD coordination study. Changes to upstream OCPDs will void the provided arc-flash labels and will require the affected portion of the system to reevaluated.
Further discussion about calculations and theories regarding an arc-flash calculation hazard study, as well as the physiological implications of an Arc-Flash hazard can be found in the appendices; Detailed Electrical Systems Analysis.
3.5 Arc-Flash Hazard Labels
The industry standard for arc-flash labels is consistent with ANSI 7535.
Labels should have “WARNING” in black letters on orange background where AFIE is below 40 cal/cm2 and “DANGER” in white letters with red background where AFIE is at or above 40 cal/cm2.
NEC 110.16 requires electrical equipment in non-dwelling units which are likely to require examination, adjustment, servicing, or maintenance while energized to be field marked in such a way that the marking is clearly visible to qualified persons before working on the equipment. Per NFPA 70E Article 130.5(C), labels must at minimum include the following information:
• Nominal system voltage
• Arc-flash boundary
• At least one of the following:
o AFIE and corresponding working distance o Minimum required arc rating of clothing o Required level of PPE o Highest Hazard/Risk Category (HRC) for the equipment
Information to be included on Arc-Flash Hazard labels is the subject of debate in the industry. Jim Phillips, the author of “Complete Guide to Arc- Flash Hazard Calculation Studies” and a contributor to many arc-flash related standards, recommends providing as much information as possible to inform qualified persons of the hazard level to which they may be exposed and how to best prepare themselves if it is not possible to de-energize the equipment as emphasized in NFPA 70E. Additionally, Phillips advises that care be taken to comply with the standards defined by ANSI Z535 for safety hazard labeling which is also referenced by NFPA 70 (NEC) Article 110.16.
The ANSI 7535 standard defines the following signal word choice, background and text coloration as it correlates to risk severity:
• CAUTION: Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. (Black letters on safety yellow background)
• WARNING: Indicates a hazardous situation that, if not avoided, could result in death or serious injury. (Black letters on safety orange background)
• DANGER: Indicates a hazardous situation that, if not avoided, will result in death or serious injury. (White letters on safety red background)
Examples: (Above) Warning Label. (Below) Danger Label
The preceding are examples of labels that Apogee Consulting Group P.A.
has provided in cooperation with this study for equipment as required per NEC 110.16. Labels were created using 4” x 6” die-cut UV, chemical and scratch resistant indoor/outdoor vinyl with thermal transfer technology.
Where information was unavailable due to a circumstance that prevented collection of data regarding a device or equipment, a label was issued stating:
“DANGER – DO NOT WORK ON EQUIPMENT WHILE
ENERGIZED!”
Labels were provided in an organized manner and should be affixed to equipment in accordance with NEC 110.16. Equipment ID and other equipment specific information have been included on all labels where it was deemed a benefit to the labeling effort.
Some labels may have been identified as optional. While these labels are not required, they may contribute to a safer work environment.
PDF versions of all arc-flash hazard equipment labels can be found in the appendices, Arc-Flash Hazard Labels.
4.0 COORDINATION STUDY
A coordination study is an effort to identify OCPD settings that will cause systems to be coordinated in a manner such that the nearest upstream OCPD will trip in the event of a fault in a predictable manner and clear the fault.
Many subsystems in existing facilities are not designed expressly for coordination. It is inherent to outdated equipment and designs that full coordination is unachievable. Many OCPDs have fixed settings that are unable to be changed. OCPDs may be identified to exist that provide the availability to better coordinate a subsystem.
Time current curve plots can be found in the appendices, Coordination Study Time Current Curves.
If full OCPD coordination is not able to be achieved, new equipment may be necessary and listed in the Issues Log.
The Issues Log can be found in the appendices, Issues Log.
Findings and recommendations from the coordination study are dependent upon site survey, probable assumptions of equipment specifics and parameters affecting arc-flash and coordination studies, and data provided by the client and/or client representatives. Verification of existing settings as well as potential settings should be conducted prior to any work being completed.
Existing settings can be found in the appendices, System Data Model Inputs.
It is recommended to notify the site supervisor if contrasting device settings or equipment is found. System models should be updated with new information and reevaluated when changes are made.
While it is possible to adjust OCPD settings with the system is energized, planned outages should be scheduled prior to adjusting settings. It is recommended that OCPDs be adjusted only while the system is deenergized.
Neither Apogee Consulting Group P.A. nor any of its personnel nor subcontractor can assume any liability for the occurrence of an unscheduled outage in conjunction with adjustment of trip devices. It is recommended to schedule outages before adjusting settings on trip devices.
Reducing trip settings on an OCPD can increase the likelihood that the OCPD may trip. Future circuit loading was not considered as part of this study, but is an important factor when choosing to implement any recommended settings.
Arc-flash hazard and device coordination are closely tied and suffer from competing interests. Maximization in regards to one is usually to the detriment of the maximization of the other.
When complete system coordination is achieved, distribution and mid-level OCPD settings often will be near or at their maximum settings. This allows downstream devices the opportunity to clear faults before upstream devices. It is also common for downstream devices not to feature adjustable settings that would allow a technician to reduce the maximum current and/or clearing time, which results in distribution and mid-level OCPDs being set at or near their maximum settings. Coordinating a system minimizes the effect of outages in the event of a fault. But in doing so, the elevated distribution and mid-level OCPD settings increase clearing times, which in turn increases the AFIE.
Further discussion of calculations and theory involved in the coordination study can be found in the appendices, Detailed Electrical Systems Analysis.
5.0 EXISTING CONDITIONS ASSESSMENTS
The Existing Condition Assessment is a compilation of observations about existing equipment noted during site survey and is presented in a tabulated format. Documents identify equipment name, general location, and specific information relevant to the assessment type (i.e ATS Survey).
Assessments can be found in the appendices; Existing Conditions Assessment.
5.1 Specific Assessments
Specific assessments; ATS, ground resistance analysis, and emergency power system analysis were included and conducted per the SOW and have been included to aid in the overall completeness of the electrical study.
Tabulations and Summarizations can be found in the appendices, Existing Conditions Assessment.
5.1a ATS
ATS design (3-pole or 4-pole) was noted during site survey.
The assessment can be found in the appendices, Existing Conditions Assessment – ATS Survey.
Findings have been summarized and recommendations can be found in the appendices, Issues Log.
5.1b Ground Resistance Analysis
Visual inspection of the grounding system was conducted during site survey. Issues were recorded and have been reported in the Issues Log along with recommendations for resolution. The grounding system and bonding should be professionally tested for proper resistance across all points in the system.
The assessment can be found in the appendices, Existing Conditions Assessment – Ground Resistance Analysis.
5.1c Emergency Power System Analysis
The configuration of the essential electrical system was evaluated as part of this study. Testing of the operational status of generators and transfer switches should be evaluated more completely by the generator maintainers and triennial tests.
A summary of the assessment can be found in the appendices, Existing Conditions Assessment – Emergency Power System.
6.0 ISSUES LOG
The Issues Log is a compiled list of issues that were identified throughout the course of the study. The document identifies equipment name, general location, condition assessment, maintenance issues, access issues, relevant notes, prioritization, and recommendations.
Prioritization is indicated by a numerical scale, 1-4, where 1 indicates a critical deficiency and 4 indicates a low priority deficiency. Critical deficiency items are deemed to pose an imminent threat to the safety of personnel and/or damage to property and should be corrected as soon as possible. Low priority deficiency items indicate an issue requiring preventative maintenance and are expected to be addressed as time and budget allow.
The Issues Log can be found in the appendices, Issues Log.
INTENTIONALLY BLANK
APPENDIX A – References
1. IEEE Standard 1584-2018 – Guide for Performing Arc Flash Hazard Calculations
2. NFPA 70 (2020) – National Electrical Code
3. NFPA 70E (2021) – Standard for Electrical Safety in the Workplace
4. OSHA CFR Title 29, Part 1910, Subpart S
5. IEEE 551-2006 – Recommended Practice for Calculating AC Short-Circuit Currents in Industrial and Commercial Power Systems [The Violet Book]
6. ANSI/IEEE C37.5-1979 – IEEE Guide for calculation of Fault Currents for Application of AC High-Voltage Circuit Breakers Rated on a Total Current Basis
7. ANSI/IEEE C37.13-1981 – IEEE Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures
8. ANSI/IEEE C37.10-2011 – IEEE Guide for Investigation, Analysis, and Reporting of Power Circuit Breaker Failures
9. ANSI Z535.4 – American Standard for Product Signs and Labels
10. ANSI/NETA MTS – Standard for Maintenance Testing Specifications for Electrical Power Equipment and Systems
11. ANSI/NETA ATS – Standard for Maintenance Testing Specifications for Electrical Power Equipment and Systems
APPENDIX B – Source Data
As provided by Xcel EnergyTM
DATE:
TO: VA Hospital
Sincerely, Logan Heinen Area Engineer
Arc Flash Data Request
Voltage at the service is 13.2 kV line-line and 7.62 kV line-ground.
Calculated maximum available 3-phase fault current is 9227 amps.
Calculated maximum available 1-phase fault current is 6335 amps.
Calculated positive sequence X/R ratio at the primary service point is 9.066.
2/9/2024
The following information is provided in response to your request for utility data to perform arc flash calculations on the primary service point which is located at 1700 Wheeling St, Aurora
Calculated zero sequence X/R ratio at the primary service point is 2.512.
Xcel Energy personnel shall not be held responsible for any damage to property or person resulting from the use of this data.
If you have additional questions, please feel free to contact me at telephone number 303-716-2120 or email address Logan.Heinen@xcelenergy.com
The first over-current device upstream from this service point is:
SEL-351S
The Company does not provide minimum fault current information or associated protective device clearing times.
It is understood that this data is provided for arc flash calculations, and is based on how the distribution system is currently known to be arranged. It should be understood by parties using this data that it can and will change due to various circumstances.
The Company will not notify the customer when such changes occur.
DATE:
TO: VA Hospital
Sincerely, Logan Heinen
Area Engineer
Calculated zero sequence X/R ratio at the primary service point is 2.042.
Xcel Energy personnel shall not be held responsible for any damage to property or person resulting from the use of this data.
If you have additional questions, please feel free to contact me at telephone number
303-716-2120 or email address Logan.Heinen@xcelenergy.com
The first over-current device upstream from this service point is:
SEL-351S
The Company does not provide minimum fault current information or associated protective device clearing times.
It is understood that this data is provided for arc flash calculations, and is based on how the distribution system is currently known to be arranged. It should be understood by parties using this data that it can and will change due to various circumstances.
The Company will not notify the customer when such changes occur.
Arc Flash Data Request
Voltage at the service is 13.2 kV line-line and 7.62 kV line-ground.
Calculated maximum available 3-phase fault current is 10091 amps.
Calculated maximum available 1-phase fault current is 6641 amps.
Calculated positive sequence X/R ratio at the primary service point is 7.2.
2/9/2024
The following information is provided in response to your request for utility data to perform arc flash calculations on the primary service point which is located at
1700 Wheeling St, Aurora
APPENDIX C – Single-Line Diagrams
Single-line diagrams with component names, nominal voltage, incident energy, 3ph bolted fault current and other notable data points.
Some sections may be boxed to differentiate elements that are notably different in some regard. Commonly, boxed sections are used to separate single phase parts of a system that have been modeled to provide further information are not normally included in the electrical study. Box colors indicate voltage at the lowest point. Text tags may also be present to provide further information.
Single phase box colors:
• Black - 120V
• Blue - 208V
• Red - 240V
Riser diagrams (PDFs) provided by client and updated per request.
2-ATS-EQ3_N
2-ATS-EQ2_N
2-ATS-EQ1_N2-ATS-SB1_N2-ATS-LS1_N
TCC 2-PNL-NLS2 (partial)
Fed from A1-EC6A
2-ATS-LS1_E 2-ATS-CR1_E 2-ATS-EQ1_E 2-ATS-EQ2_E 2-ATS-EQ3_E
Fed from B1-EE6A Fed from GA4-EC6B Fed from GB4-EE6B
Open Open
Bldg 2 - Research (B)
TCC 2-PNL-NLS5 (partial)
UTIL-1-52-GA4
3P 1448.4 Amps
UTIL-2-52-GB4
3P 1448.4 Amps
MVBUS: 2-SWG-EMDCP1
13200.0 V Nom
AFIE 3.6 Cal/cm 2̂ 3ph SC (Sym) 1448.40 A ArcFC 1.495 kA Trip Time 0.100 s
MVMCB: 2-EMDCP1-S1_Relay
GE MULTILIN
Frame/Model 350 CT Ratio 100 / 5 A Settings 51P TOC Pickup 0.55 (55A) ANSI Norm Inv 1; 0.5 (S;M) 50P IOC Pickup 6 (600A)
MVMCB: 2-EMDCP1-S2_Relay
GE MULTILIN
Frame/Model 350 CT Ratio 100 / 5 A Settings 51P TOC Pickup 0.55 (55A) ANSI Norm Inv 1; 0.5 (S;M) 50P IOC Pickup 6 (600A)
2-SWG-EMDCP1
480.0 V Nom
AFIE 7.44 Cal/cm^2 3ph SC (Sym) 17457.64 A ArcFC 17.746 kA Trip Time 0.083 s
Open MVMCB: 2-EMDCP1-S1
SQUARE D
Frame/Model VR-15050-12 Settings
MVMCB: 2-EMDCP1-S2
SQUARE D
Frame/Model VR-15050-12 Settings
CB: 2-ATS-LS1_E
GE
Frame/Model WPS-08 Sensor/Trip 150.0 A
100.0 A
Settings
LTPU 1.00X (100A)
LTD C-2
STPU 8.5X (850A)
STD ST07-Min (Î s T Off)
INST ST(ON) 10X (1000A)
CB: 2-ATS-SB1_E
GE
Frame/Model WPS-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-12
STPU 7X (4200A)
STD ST06-Min (Î s T Off)
INST ST(ON) 11X (6600A)
CB: 2-ATS-EQ1_E
GE
Frame/Model WPS-08 Sensor/Trip 8 00.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-9
STPU 7X (4200A)
STD ST06-Min (Î s T Off)
INST ST(ON) 9X (5400A)
CB: 2-ATS-EQ2_E
GE
Frame/Model WPS-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-9
STPU 7X (4200A)
STD ST06-Min (Î s T Off)
INST ST(ON) 9X (5400A)
CB: 2-ATS-EQ3_E
GE
Frame/Model WPS-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-9
STPU 7X (4200A)
STD ST06-Min (Î s T Off)
INST ST(ON) 9X (5400A)
PD-0025
GE
Frame/Model WPS-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-9
STPU 7X (4200A)
STD ST06-Min (Î s T Off)
INST ST(ON) 10X (6000A)
2-SWG-NDCP1
480.0 V Nom
AFIE 6.69 Cal/cm^2 3ph SC (Sym) 40292.63 A ArcFC 27.580 kA Trip Time 0.058 s
MCB: 2-SWG-NDCP1
GE
Frame/Model WPS-32 Sensor/Trip 3200.0 A
3000.0 A
Settings
LTPU 1.00X (3000A)
LTD C-3
STPU 2.5X (7500A)
STD ST05-Min (Î s T Off)
INST ST(ON) 3.5X (10500A)
MVBUS: 2-SWG-NDCP1
13200.0 V Nom
AFIE 22.84 Cal/cm 2̂ 3ph SC (Sym) 9926.09 A ArcFC 9.416 kA Trip Time 0.100 s
MVMCB: 2-NDCP1-S1
SQUARE D
Frame/Model VR-15050-12 Settings
Open
MVMCB: 2-NDCP1-S2
SQUARE D
Frame/Model VR-15050-12 Settings
MVMCB: 2-NDCP1-S1_Relay
GE MULTILIN
Frame/Model 350 CT Ratio 100 / 5 A Settings 51P TOC Pickup 0.55 (55A) ANSI Norm Inv 1; 0.5 (S;M) 50P IOC Pickup 1 (400A)
MVMCB: 2-NDCP1-S2_Relay
GE MULTILIN
Frame/Model 350 CT Ratio 100 / 5 A Settings 51P TOC Pickup 0.55 (55A) ANSI Norm Inv 1; 0.5 (S;M) 50P IOC Pickup 1 (400A)
UTIL-1-52-A1
3P 9738.8 Amps
UTIL-2-52-B1
3P 10045.0 Amps
Open
CB-G: 2-SWG-NDCP1-SPARE1
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings GFPU (0.2 - 0.6 x In) 0.3 (240A) GFD I2T (1-13 Bands) GFD03 (Î s T Off)
CBL: 2-PNL-NHP1
500 kcmil 2 Sets
44.0 ft
CBL: 2-PNL-NHP2
500 kcmil 2 Sets
54.0 ft
Open
CB: 2-SWG-NDCP1-SPARE1
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-12
STPU 7X (4200A)
STD ST06-Min (Î s T Off)
INST ST(ON) 11X (6600A)
2-PNL-NHP1
480.0 V Nom
AFIE 3.57 Cal/cm 2̂ 3ph SC (Sym) 35331.06 A ArcFC 25.111 kA Trip Time 0.058 s
CB: 2-PNL-NL37
GE
Frame/Model SEHA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CBL: 2-PNL-NL37
1 AWG
1 Sets
136.0 ft
2-PNL-NL37
208.0 V Nom
AFIE 0.13 Cal/cm 2̂ 3ph SC (Sym) 4373.98 A ArcFC 1.594 kA Trip Time 0.037 s
CB: 2-PNL-NL21
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-NL21
3/0 AWG
1 Sets
138.0 ft
2-PNL-NL21
208.0 V Nom
AFIE 0.14 Cal/cm 2̂ 3ph SC (Sym) 4972.77 A ArcFC 1.832 kA Trip Time 0.034 s
CB: 2-PNL-NL22
GE
Frame/Model SFHA Sensor/Trip 1 50.0 A
150.0 A
Settings
MAX
CBL:2-PNL-NL22
3/0 AWG
1 Sets
138.0 ft
2-PNL-NL22
208.0 V Nom
AFIE 0.14 Cal/cm^2 3ph SC (Sym) 5117.73 A ArcFC 1.891 kA Trip Time 0.033 s
CB: 2-PNL-NL23
GE
Frame/Model SFHA Sensor/Trip 1 50.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-NL23
3/0 AWG
1 Sets
138.0 ft
2-PNL-NL23
208.0 V Nom
AFIE 0.14 Cal/cm^2 3ph SC (Sym) 5117.73 A ArcFC 1.891 kA Trip Time 0.033 s
CB: 2-PNL-NHP1-SPARE1
GE
Frame/Model SELA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CB: 2-PNL-NHP1-SPARE2
GE
Frame/Model SELA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CB: 2-PNL-NHP1-SPARE3
GE
Frame/Model SELA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CB: 2-PNL-NH31
GE
Frame/Model SGLC Sensor/Trip 150.0 A
100.0 A
Settings
LTPU 0.50X (50A)
LTD F-4
STPU 9X (450A)
STD Int ST11-Int (I ŝ T Off)
INST 10X (1500A)
2-PNL-NH31
480.0 V Nom
AFIE 0.16 Cal/cm^2 3ph SC (Sym) 4078.41 A ArcFC 2.986 kA Trip Time 0.025 s
CBL: 2-PNL-NH31
6 AWG
1 Sets
126.0 ft
CB: 2-PNL-NHS1
GE
Frame/Model SFLA Sensor/Trip 200.0 A
200.0 A
Settings
MAX
2-PNL-NHS1
480.0 V Nom
AFIE 0.52 Cal/cm^2 3ph SC (Sym) 12002.11 A ArcFC 9.226 kA Trip Time 0.025 s
CBL: 2-PNL-NHS1
250 kcmil 1 Sets
178.0 ft
CB: TX-2-TNDLP1
GE
Frame/Model SGLA Sensor/Trip 500.0 A
500.0 A
Settings
MAX
CBL: TX-2-TNDL1
350 kcmil 2 Sets
39.0 ft
TX-2-TNLDP1_P
480.0 V Nom
AFIE 1.4 Cal/cm^2 3ph SC (Sym) 31556.42 A ArcFC 23.000 kA Trip Time 0.025 s
TX-2-TNLDP1_S
208.0 V Nom
AFIE 18.75 Cal/cm^2 3ph SC (Sym) 20606.80 A ArcFC 8.127 kA Trip Time 0.984 s
CBL: 2-PNL-NLDP1
350 kcmil 4 Sets
37.0 ft
S
P
TX-2-TNLDP1
300 kVA Impedance 2.9000 % Primary 480 V Secondary 208 V
MCB: 2-PNL-NLDP1
GE
Frame/Model SKHA Sensor/Trip 1000.0 A
1000.0 A
Settings
MAX
2-PNL-NLDP1-S1
208.0 V Nom
AFIE 35.17 Cal/cm^2 3ph SC (Sym) 18967.25 A ArcFC 7.538 kA Trip Time 2.000 s
CB: 2-PNL-NLP1
GE
Frame/Model SEHA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CBL: 2-PNL-NLP1
1 AWG
1 Sets
24.0 ft
2-PNL-NLP1
208.0 V Nom
AFIE 0.35 Cal/cm^2 3ph SC (Sym) 13018.07 A ArcFC 6.031 kA Trip Time 0.025 s
CB: 2-PNL-NL31
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-NL31
3/0 AWG
1 Sets
122.0 ft
2-PNL-NL31
208.0 V Nom
AFIE 0.14 Cal/cm^2 3ph SC (Sym) 5636.23 A ArcFC 2.453 kA Trip Time 0.025 s
CB: 2-PNL-NL32
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-NL32
3/0 AWG
1 Sets
122.0 ft
2-PNL-NL32
208.0 V Nom
AFIE 0.14 Cal/cm^2 3ph SC (Sym) 5449.73 A ArcFC 2.023 kA Trip Time 0.030 s
CB: 2-PNL-NL33
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-NL33
3/0 AWG
1 Sets
122.0 ft
2-PNL-NL33
208.0 V Nom
AFIE 0.14 Cal/cm^2 3ph SC (Sym) 5636.23 A ArcFC 2.453 kA Trip Time 0.025 s
CB: 2-PNL-NL27
GE
Frame/Model SEHA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CBL: 2-PNL-NL27
1 AWG
1 Sets
152.0 ft
2-PNL-NL27
208.0 V Nom
AFIE 0.6 Cal/cm^2 3ph SC (Sym) 3993.56 A ArcFC 1.444 kA Trip Time 0.191 s
CB: 2-PNL-NL11
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-NL11
3/0 AWG
1 Sets
154.0 ft
2-PNL-NL11
208.0 V Nom
AFIE 1.08 Cal/cm 2̂ 3ph SC (Sym) 4563.06 A ArcFC 1.669 kA Trip Time 0.294 s
CB: 2-PNL-NL12
GE
Frame/Model SFHA Sensor/Trip 1 50.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-NL12
3/0 AWG
1 Sets
154.0 ft
2-PNL-NL12
208.0 V Nom
AFIE 1.07 Cal/cm^2 3ph SC (Sym) 4684.80 A ArcFC 1.718 kA Trip Time 0.281 s
CB: 2-PNL-NLS7
GE
Frame/Model SEHA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CBL: 2-PNL-NLS7
1 AWG
1 Sets
188.0 ft
2-PNL-NLS7
208.0 V Nom
AFIE 0.67 Cal/cm^2 3ph SC (Sym) 3337.64 A ArcFC 1.188 kA Trip Time 0.259 s
CB: 2-PNL-NL17
GE
Frame/Model SEHA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CBL: 2-PNL-NL17
1 AWG
1 Sets
168.0 ft
2-PNL-NL17
208.0 V Nom
AFIE 0.63 Cal/cm^2 3ph SC (Sym) 3673.17 A ArcFC 1.319 kA Trip Time 0.220 s
CB: 2-PNL-NLS1
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-NLS1
3/0 AWG
1 Sets
174.0 ft
2-PNL-NLS1
208.0 V Nom
AFIE 1.15 Cal/cm^2 3ph SC (Sym) 4135.54 A ArcFC 1.500 kA Trip Time 0.350 s
CB: 2-PNL-NLS2
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-NLS2
3/0 AWG
1 Sets
174.0 ft
2-PNL-NLS2
208.0 V Nom
AFIE 1.14 Cal/cm^2 3ph SC (Sym) 4235.23 A ArcFC 1.539 kA Trip Time 0.336 s
CB: 2-PNL-NH21
GE
Frame/Model SGLC Sensor/Trip 1 50.0 A
100.0 A
Settings
LTPU 0.50X (50A)
LTD F-4
STPU 9X (450A)
STD Int ST11-Int (Î s T Off)
INST 10X (1500A)
2-PNL-NH21
480.0 V Nom
AFIE 0.14 Cal/cm^2 3ph SC (Sym) 3652.43 A ArcFC 2.659 kA Trip Time 0.025 s
CBL: 2-PNL-NH21
6 AWG
1 Sets
141.0 ft
CB: 2-PNL-NH11
GE
Frame/Model SGLC Sensor/Trip 150.0 A
100.0 A
Settings
LTPU 0.50X (50A)
LTD F-4
STPU 9X (450A)
STD Int ST10-Int (Î s T Off)
INST 10X (1500A)
2-PNL-NH11
480.0 V Nom
AFIE 0.13 Cal/cm^2 3ph SC (Sym) 3296.72 A ArcFC 2.387 kA Trip Time 0.025 s
CBL: 2-PNL-NH11
6 AWG
1 Sets
157.0 ft
2-PNL-NHP2
480.0 V Nom
AFIE 3.48 Cal/cm 2̂ 3ph SC (Sym) 34320.86 A ArcFC 24.566 kA Trip Time 0.058 s
CB: TX-2-TNLDP2
GE
Frame/Model SGLA Sensor/Trip 500.0 A
500.0 A
Settings
MAX
CBL: TX-2-TNLDP2
350 kcmil 2 Sets
31.0 ft
S
P
TX-2-TNLDP2
300 kVA Impedance 2.9000 % Primary 480 V Secondary 208 V
TX-2-TNLDP2_P
480.0 V Nom
AFIE 1.39 Cal/cm^2 3ph SC (Sym) 31400.35 A ArcFC 22.908 kA Trip Time 0.025 s
CBL: 2-PNL-NLDP2
350 kcmil 4 Sets
37.0 ft
MCB: 2-PNL-NLDP2
GE
Frame/Model SKHA Sensor/Trip 1000.0 A
1000.0 A
Settings
MAX
TX-2-TNLDP2_S
208.0 V Nom
AFIE 18.78 Cal/cm^2 3ph SC (Sym) 20580.54 A ArcFC 8.118 kA Trip Time 0.987 s
2-PNL-NLDP2-S1
208.0 V Nom
AFIE 35.45 Cal/cm^2 3ph SC (Sym) 19127.02 A ArcFC 7.597 kA Trip Time 2.000 s
CB: 2-PNL-NL34
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
2-PNL-NL34
208.0 V Nom
AFIE 0.18 Cal/cm^2 3ph SC (Sym) 7090.45 A ArcFC 2.685 kA Trip Time 0.024 s
CBL: 2-PNL-NL34
3/0 AWG
1 Sets
113.0 ft
CB: 2-PNL-NL35
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
2-PNL-NL35
208.0 V Nom
AFIE 0.2 Cal/cm^2 3ph SC (Sym) 8013.67 A ArcFC 3.599 kA Trip Time 0.020 s
CBL: 2-PNL-NL35
3/0 AWG
1 Sets
113.0 ft
CB: 2-PNL-NL36
GE
Frame/Model SEHA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
2-PNL-NL36
208.0 V Nom
AFIE 0.13 Cal/cm^2 3ph SC (Sym) 5259.01 A ArcFC 2.274 kA Trip Time 0.025 s
CBL: 2-PNL-NL36
1 AWG
1 Sets
113.0 ft
CB: 2-PNL-NL24
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
2-PNL-NL24
208.0 V Nom
AFIE 0.16 Cal/cm^2 3ph SC (Sym) 6572.01 A ArcFC 2.872 kA Trip Time 0.022 s
CBL: 2-PNL-NL24
3/0 AWG
1 Sets
129.0 ft
CB: 2-PNL-NL25
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
2-PNL-NL25
208.0 V Nom
AFIE 0.18 Cal/cm^2 3ph SC (Sym) 7356.96 A ArcFC 3.280 kA Trip Time 0.020 s
CBL: 2-PNL-NL25
3/0 AWG
1 Sets
129.0 ft
CB: 2-PNL-NL26
GE
Frame/Model SEHA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
2-PNL-NL26
208.0 V Nom
AFIE 0.12 Cal/cm^2 3ph SC (Sym) 4721.87 A ArcFC 2.021 kA Trip Time 0.026 s
CBL: 2-PNL-NL26
1 AWG
1 Sets
129.0 ft
CB: 2-PNL-NL14
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
2-PNL-NL14
208.0 V Nom
AFIE 0.15 Cal/cm^2 3ph SC (Sym) 6121.71 A ArcFC 2.660 kA Trip Time 0.025 s
CBL: 2-PNL-NL14
3/0 AWG
1 Sets
145.0 ft
CB: 2-PNL-NL15
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
2-PNL-NL15
208.0 V Nom
AFIE 0.17 Cal/cm^2 3ph SC (Sym) 6796.38 A ArcFC 2.592 kA Trip Time 0.025 s
CBL: 2-PNL-NL15
3/0 AWG
1 Sets
145.0 ft
CB: 2-PNL-NL16
GE
Frame/Model SEHA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
2-PNL-NL16
208.0 V Nom
AFIE 0.14 Cal/cm^2 3ph SC (Sym) 4282.44 A ArcFC 1.558 kA Trip Time 0.040 s
CBL: 2-PNL-NL16
1 AWG
1 Sets
145.0 ft
CB: 2-PNL-NL13
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
2-PNL-NL13
208.0 V Nom
AFIE 0.14 Cal/cm^2 3ph SC (Sym) 5163.27 A ArcFC 1.906 kA Trip Time 0.032 s
CBL: 2-PNL-NL13
3/0 AWG
1 Sets
188.0 ft
CB: 2-PNL-NLS4
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
2-PNL-NLS4
208.0 V Nom
AFIE 0.14 Cal/cm^2 3ph SC (Sym) 5636.37 A ArcFC 2.453 kA Trip Time 0.025 s
CB: 2-PNL-NLS5
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
2-PNL-NLS5
208.0 V Nom
AFIE 0.15 Cal/cm^2 3ph SC (Sym) 6202.31 A ArcFC 2.699 kA Trip Time 0.024 s
CBL: 2-PNL-NLS5
3/0 AWG
1 Sets
165.0 ft
CB: 2-PNL-NLS6
GE
Frame/Model SEHA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
2-PNL-NLS6
208.0 V Nom
AFIE 0.64 Cal/cm^2 3ph SC (Sym) 3623.39 A ArcFC 1.299 kA Trip Time 0.226 s
CBL: 2-PNL-NLS6
1 AWG
1 Sets
165.0 ft
CB: 2-PNL-NLS3
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
2-PNL-NLS3
208.0 V Nom
AFIE 1.05 Cal/cm^2 3ph SC (Sym) 4810.77 A ArcFC 1.765 kA Trip Time 0.268 s
CBL: 2-PNL-NLS3
3/0 AWG
1 Sets
208.0 ft
CB: 2-PNL-NLP2
GE
Frame/Model SEHA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
2-PNL-NLP2
208.0 V Nom
AFIE 0.24 Cal/cm^2 3ph SC (Sym) 9325.05 A ArcFC 4.239 kA Trip Time 0.025 s
CBL: 2-PNL-NLP2
1 AWG
1 Sets
37.0 ft
S
P
TX-2-NDCP1
2000 kVA Impedance 6.1000 % Primary 13200 V Secondary 480 V
TX-2-NDCP1_P
13200.0 V Nom
AFIE 1.17 Cal/cm 2̂ 3ph SC (Sym) 9925.85 A ArcFC 9.416 kA Trip Time 0.100 s
TX-2-NDCP1_S
480.0 V Nom
AFIE 6.69 Cal/cm 2̂ 3ph SC (Sym) 40298.73 A ArcFC 27.582 kA Trip Time 0.100 s
CBL: 2-SWG-NDCP1
750 kcmil 25 Sets
1.0 ft
CBL: TX-2-NDCP1
750 kcmil 25 Sets
1.0 ft
MCB: 2-SWG-EMDCP1
GE
Frame/Model WPS-20 Sensor/Trip 2000.0 A
2000.0 A
Settings
LTPU 1.00X (2000A)
LTD C-4
STPU 3X (6000A)
STD ST01-Min (Î s T Off)
INST ST(ON) 3.5X (7000A)
S
P
TX-2-EMDCP1
1500 kVA Impedance 5.8200 % Primary 13200 V Secondary 480 V
TX-2-EMDCP1_P
13200.0 V Nom
AFIE 0.2 Cal/cm^2 3ph SC (Sym) 1448.39 A ArcFC 1.495 kA Trip Time 0.100 s
TX-2-EMDCP1_S
480.0 V Nom
AFIE 7.44 Cal/cm^2 3ph SC (Sym) 17459.35 A ArcFC 17.747 kA Trip Time 0.209 s
CBL: 2-SWG-EMDCP1
750 kcmil 25 Sets
1.0 ft
CBL: TX-2-EMDCP1
750 kcmil 25 Sets
1.0 ft
MCB-G: 2-SWG-NDCP1
GE
Frame/Model WPH-32 Sensor/Trip 3200.0 A
3000.0 A
Settings GFPU (0.2 - 0.37 x In) 0.3 (960A) GFD I2T (1-13 Bands) GFD05 (Î s T Off)
CB: 2-ATS-LS1_N
GE
Frame/Model WPX-08 Sensor/Trip 1 50.0 A
100.0 A
Settings
LTPU 0.50X (50A)
LTD C-1
STPU 1.5X (75A)
STD ST01-Min (Î s T Off)
INST ST(ON) 2X (200A)
CB-G: 2-ATS-LS1_N
GE
Frame/Model WPX-08 Sensor/Trip 1 50.0 A
100.0 A
Settings GFPU (0.2 - 0.6 x In) 0.3 (45A) GFD I2T (1-13 Bands) GFD03 (Î s T Off)
CB: 2-ATS-SB1_N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-12
STPU 7X (4200A)
STD ST06-Min (Î s T Off)
INST ST(ON) 11X (6600A)
CB-G: 2-ATS-SB1_N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings GFPU (0.2 - 0.6 x In) 0.3 (240A) GFD I2T (1-13 Bands) GFD03 (Î s T Off)
CB: 2-ATS-EQ1_N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-9
STPU 7X (4200A)
STD ST06-Min (Î s T Off)
INST ST(ON) 10X (6000A)
CB-G: 2-ATS-EQ1_N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings GFPU (0.2 - 0.6 x In) 0.3 (240A) GFD I2T (1-13 Bands) GFD03 (Î s T Off)
CB: 2-PNL-NHP1_N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-17
STPU 9X (5400A)
STD ST11-Min (Î s T Off)
INST ST(ON) 12.5X (7500A)
CB-G: 2-PNL-NHP1_ N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings GFPU (0.2 - 0.6 x In) 0.3 (240A) GFD I2T (1-13 Bands) GFD03 (Î s T Off)
CB: 2-PNL-NHP2_N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-17
STPU 9X (5400A)
STD ST11-Min (I^s T Off)
INST ST(ON) 12.5X (7500A)
CB-G: 2-PNL-NHP2_ N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings GFPU (0.2 - 0.6 x In) 0.3 (240A) GFD I2T (1-13 Bands) GFD03 (Î s T Off)
CB: 2-ATS-EQ2_N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-9
STPU 7X (4200A)
STD ST06-Min (Î s T Off)
INST ST(ON) 10X (6000A)
CB-G: 2-ATS-EQ2_N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings GFPU (0.2 - 0.6 x In) 0.3 (240A) GFD I2T (1-13 Bands) GFD03 (Î s T Off)
CB: 2-ATS-EQ3_N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings
LTPU 1.00X (600A)
LTD C-9
STPU 7X (4200A)
STD ST06-Min (Î s T Off)
INST ST(ON) 10X (6000A)
CB-G: 2-ATS-EQ3_N
GE
Frame/Model WPX-08 Sensor/Trip 800.0 A
600.0 A
Settings GFPU (0.2 - 0.6 x In) 0.3 (240A) GFD I2T (1-13 Bands) GFD03 (Î s T Off)
2-PNL-NLDP2-S2
208.0 V Nom
AFIE 31.68 Cal/cm^2 3ph SC (Sym) 14866.53 A ArcFC 6.907 kA Trip Time 2.000 s
CBL: 2-PNL-NL18
350 kcmil 4 Sets
145.0 ft
2-PNL-NLDP1-S2
208.0 V Nom
AFIE 37.44 Cal/cm^2 3ph SC (Sym) 17489.36 A ArcFC 8.104 kA Trip Time 2.000 s
CBL: 2-PNL-NLDP1-S2
350 kcmil 4 Sets
37.0 ft
MCB: 2-PNL-NL31
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL32
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL33
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL34
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL35
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL21
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL22
GE
Frame/Model TQD Sensor/Trip 1 50.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL23
GE
Frame/Model TQD Sensor/Trip 1 50.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL24
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL25
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL13
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL14
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL12
GE
Frame/Model TQD Sensor/Trip 1 50.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NL15
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NLS1
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NLS2
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NLS3
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
CBL: 2-PNL-NLS4
3/0 AWG
1 Sets
165.0 ft
MCB: 2-PNL-NLS5
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-NLS4
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
CB: 2-ATS-SB1_NCB: 2-ATS-LS1_N
TCC 2-PNL-CLS2
CB: 2-ATS-LS1_E CB: 2-ATS-CR1_E
TCC 2-PNL-LSL31 (partial)
TCC 2-PNL-CL11 (partial)
TCC 2-PNL-CLS2 (Em)
Bldg 2 - ATSes LS1 and SB1
EN ATS: 2-LS1
Position - Normal On
CBL: TX-2-TLSL11
10 AWG
1 Sets
15.0 ft
CBL: 2-PNL-LSH11
1 AWG
1 Sets
40.0 ft
CBL: 2-PNL-LSH31
1 AWG
1 Sets
142.0 ft
2-ATS-LS1_E
480.0 V Nom
AFIE 1.71 Cal/cm^2 3ph SC (Sym) 13484.22 A ArcFC 12.697 kA Trip Time 0.058 s
2-ATS-LS1_N
480.0 V Nom
AFIE 2.09 Cal/cm^2 3ph SC (Sym) 20049.71 A ArcFC 15.368 kA Trip Time 0.058 s
2-ATS-LS1_LOAD
480.0 V Nom
AFIE 2.09 Cal/cm^2 3ph SC (Sym) 20049.66 A ArcFC 15.368 kA Trip Time 0.058 s
2-PNL-LSH31
480.0 V Nom
AFIE 0.74 Cal/cm^2 3ph SC (Sym) 7595.22 A ArcFC 5.738 kA Trip Time 0.058 s
CB: TX-2-TLSL31
GE
Frame/Model TEY Sensor/Trip 20.0 A
20.0 A
Settings Fixed
CBL: TX-2-TLSL31
10 AWG
1 Sets
18.0 ft
2-PNL-LSH11
480.0 V Nom
AFIE 0.17 Cal/cm^2 3ph SC (Sym) 6436.11 A ArcFC 4.824 kA Trip Time 0.016 s
CB: TX-2-TLSL11
GE
Frame/Model TEY Sensor/Trip 25.0 A
25.0 A
Settings Fixed
S
P
TX-2-TLSL11
15 kVA Impedance 5.5000 % Primary 480 V Secondary 208 V
TX-2-TLSL11_P
480.0 V Nom
AFIE 0.12 Cal/cm^2 3ph SC (Sym) 4617.49 A ArcFC 3.403 kA Trip Time 0.016 s
S
P
TX-2-TLSL31
15 kVA Impedance 5.5000 % Primary 480 V Secondary 208 V
TX-2-TLSL31_P
480.0 V Nom
AFIE 0.12 Cal/cm^2 3ph SC (Sym) 4878.28 A ArcFC 3.605 kA Trip Time 0.016 s
CBL: 2-PNL-LSL31
6 AWG
1 Sets
16.0 ft
2-PNL-LSL31
208.0 V Nom
AFIE 1.02 Cal/cm^2 3ph SC (Sym) 706.20 A ArcFC 0.257 kA Trip Time 2.000 s
MCB: 2-PNL-LSL31
GE
Frame/Model TEY Sensor/Trip 50.0 A
50.0 A
Settings Fixed
TX-2-TLSL31_S
208.0 V Nom
AFIE 1.05 Cal/cm^2 3ph SC (Sym) 724.87 A ArcFC 0.264 kA Trip Time 2.000 s
CBL: 2-PNL-LSL11
6 AWG
1 Sets
14.0 ft
TX-2-TLSL11_S
208.0 V Nom
AFIE 1.04 Cal/cm^2 3ph SC (Sym) 722.71 A ArcFC 0.263 kA Trip Time 2.000 s
MCB: 2-PNL-LSL11
GE
Frame/Model TEY Sensor/Trip 50.0 A
50.0 A
Settings Fixed
2-PNL-LSL11
208.0 V Nom
AFIE 1.02 Cal/cm^2 3ph SC (Sym) 706.43 A ArcFC 0.257 kA Trip Time 2.000 s
2-ATS-SB1_N
480.0 V Nom
AFIE 3.54 Cal/cm^2 3ph SC (Sym) 35023.50 A ArcFC 24.946 kA Trip Time 0.058 s
EN ATS: 2-SB1
Position - Normal On
CBL: 2-PNL-CHP1
500 kcmil 2 Sets
43.0 ft
2-ATS-SB1_LOAD
480.0 V Nom
AFIE 3.54 Cal/cm^2 3ph SC (Sym) 35023.38 A ArcFC 24.946 kA Trip Time 0.058 s
2-PNL-CHP1
480.0 V Nom
AFIE 3.22 Cal/cm^2 3ph SC (Sym) 31316.31 A ArcFC 22.859 kA Trip Time 0.058 s
CB: TX-2-TCLDP1
GE
Frame/Model SGLA Sensor/Trip 350.0 A
350.0 A
Settings
MAX
CBL: TX-2-TCLDP1
4/0 AWG
2 Sets
32.0 ft
TX-2-TCLDP1_P
480.0 V Nom
AFIE 1.27 Cal/cm^2 3ph SC (Sym) 28301.53 A ArcFC 21.017 kA Trip Time 0.025 s
TX-2-TCLDP1_S
208.0 V Nom
AFIE 20.95 Cal/cm^2 3ph SC (Sym) 10156.60 A ArcFC 4.646 kA Trip Time 2.000 s
CBL: 2-PNL-CLDP1
350 kcmil 3 Sets
26.0 ft
CB: TX-2-TCLDP2
GE
Frame/Model SGLC Sensor/Trip 400.0 A
225.0 A
Settings
LTPU 1.00X (225A)
LTD F-4
STPU 6X (1350A)
ZSI Int ST06-Int (I ŝ T Off)
INST 8.5X (3400A)
CBL: TX-2-TCLDP2
350 kcmil 1 Sets
22.0 ft
TX-2-TCLDP2_P
480.0 V Nom
AFIE 1.25 Cal/cm^2 3ph SC (Sym) 27906.37 A ArcFC 20.768 kA Trip Time 0.025 s
TX-2-TCLDP2_S
208.0 V Nom
AFIE 1.31 Cal/cm^2 3ph SC (Sym) 8594.48 A ArcFC 3.118 kA Trip Time 0.190 s
CBL: 2-PNL-CLDP2
350 kcmil 2 Sets
42.0 ft
MCB: 2-PNL-CLDP1
GE
Frame/Model SKHA Sensor/Trip 700.0 A
700.0 A
Settings
MAX
MCB: 2-PNL-CLDP2
GE
Frame/Model SGHC Sensor/Trip 600.0 A
500.0 A
Settings
LTPU 1.00X (500A)
LTD F-4
STPU 6.5X (3250A)
STD Int ST06-Int (I ŝ T Off)
INST 9X (5400A)
2-PNL-CLDP1
208.0 V Nom
AFIE 20.07 Cal/cm^2 3ph SC (Sym) 9769.23 A ArcFC 4.457 kA Trip Time 2.000 s
2-PNL-CLDP2
208.0 V Nom
AFIE 1.56 Cal/cm^2 3ph SC (Sym) 8011.29 A ArcFC 2.903 kA Trip Time 0.214 s
S
P
TX-2-TCLDP2
150 kVA Impedance 4.2000 % Primary 480 V Secondary 208 V
S
P
TX-2-TCLDP1
225 kVA Impedance 5.2000 % Primary 480 V Secondary 208 V
CB: 2-PNL-CLS1
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-CLS1
3/0 AWG
1 Sets
135.0 ft
2-PNL-CLS1
208.0 V Nom
AFIE 0.14 Cal/cm^2 3ph SC (Sym) 5382.35 A ArcFC 1.928 kA Trip Time 0.032 s
CB: 2-PNL-CLS3
GE
Frame/Model FGN Sensor/Trip 250.0 A
100.0 A
Settings LTPU Fixed (100A)
LTD 10
STPU 12X (1200A)
STD 0.42 (Î s T Off)
INST 12X (3000A)
CBL: 2-PNL-CLS3
1 AWG
1 Sets
134.0 ft
2-PNL-CLS3
208.0 V Nom
AFIE 6.15 Cal/cm^2 3ph SC (Sym) 3893.79 A ArcFC 1.411 kA Trip Time 2.000 s
CB: 2-PNL-CL11
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-CL11
3/0 AWG
1 Sets
115.0 ft
2-PNL-CL11
208.0 V Nom
AFIE 1.05 Cal/cm^2 3ph SC (Sym) 4779.76 A ArcFC 1.706 kA Trip Time 0.284 s
CB: 2-PNL-CL13
GE
Frame/Model FGN Sensor/Trip 250.0 A
100.0 A
Settings LTPU Fixed (100A)
LTD 10
STPU 12X (1200A)
STD 0.42 (I ŝ T Off)
INST 12X (3000A)
CBL: 2-PNL-CL13
1 AWG
1 Sets
114.0 ft
2-PNL-CL13
208.0 V Nom
AFIE 1.82 Cal/cm^2 3ph SC (Sym) 4331.49 A ArcFC 1.839 kA Trip Time 0.455 s
CB: 2-PNL-CL21
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-CL21
3/0 AWG
1 Sets
99.0 ft
2-PNL-CL21
208.0 V Nom
AFIE 0.15 Cal/cm^2 3ph SC (Sym) 6174.23 A ArcFC 2.709 kA Trip Time 0.024 s
CB: 2-PNL-CL23
GE
Frame/Model FGN Sensor/Trip 250.0 A
100.0 A
Settings LTPU Fixed (100A)
LTD 10
STPU 12X (1200A)
STD 0.42 (I ŝ T Off)
INST 12X (3000A)
CBL: 2-PNL-CL23
1 AWG
1 Sets
98.0 ft
2-PNL-CL23
208.0 V Nom
AFIE 2.03 Cal/cm^2 3ph SC (Sym) 4752.21 A ArcFC 2.036 kA Trip Time 0.455 s
CB: 2-PNL-CL31
GE
Frame/Model SFHA Sensor/Trip 150.0 A
150.0 A
Settings
MAX
CBL: 2-PNL-CL31
3/0 AWG
1 Sets
82.0 ft
CB: 2-PNL-CL33
GE
Frame/Model FGN Sensor/Trip 250.0 A
100.0 A
Settings LTPU Fixed (100A)
LTD 10
STPU 12X (1200A)
STD 0.42 (I ŝ T Off)
INST 12X (3000A)
CBL: 2-PNL-CL33
1 AWG
1 Sets
74.0 ft
2-PNL-CL33
208.0 V Nom
AFIE 2.41 Cal/cm^2 3ph SC (Sym) 5539.06 A ArcFC 2.407 kA Trip Time 0.455 s
2-PNL-CL31
208.0 V Nom
AFIE 0.16 Cal/cm^2 3ph SC (Sym) 6623.63 A ArcFC 2.776 kA Trip Time 0.023 s
CB: 2-PNL-CLS2
GE
Frame/Model SFHA Sensor/Trip 250.0 A
250.0 A
Settings
MAX
CBL: 2-PNL-CLS2
3/0 AWG
1 Sets
155.0 ft
2-PNL-CLS2
208.0 V Nom
AFIE 6.8 Cal/cm^2 3ph SC (Sym) 4534.52 A ArcFC 1.609 kA Trip Time 1.971 s
CB: 2-PNL-CL12
GE
Frame/Model SFHA Sensor/Trip 250.0 A
250.0 A
Settings
MAX
CBL: 2-PNL-CL12
3/0 AWG
1 Sets
135.0 ft
2-PNL-CL12
208.0 V Nom
AFIE 6.42 Cal/cm^2 3ph SC (Sym) 3997.07 A ArcFC 1.638 kA Trip Time 1.841 s
CB: 2-PNL-CL32
GE
Frame/Model SFHA Sensor/Trip 250.0 A
250.0 A
Settings
MAX
CBL: 2-PNL-CL32
3/0 AWG
1 Sets
103.0 ft
2-PNL-CL32
208.0 V Nom
AFIE 2.24 Cal/cm^2 3ph SC (Sym) 5366.25 A ArcFC 1.919 kA Trip Time 0.539 s
CB: 2-PNL-CL22
GE
Frame/Model SFHA Sensor/Trip 250.0 A
250.0 A
Settings
MAX
CBL: 2-PNL-CL22
3/0 AWG
1 Sets
119.0 ft
2-PNL-CL22
208.0 V Nom
AFIE 4.87 Cal/cm^2 3ph SC (Sym) 5083.13 A ArcFC 1.814 kA Trip Time 1.248 s
CB: 2-PNL-CH31
GE
Frame/Model SELA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CB: 2-PNL-CH21
GE
Frame/Model SELA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CBL: 2-PNL-CH21
1 AWG
1 Sets
132.0 ft
2-PNL-CH21
480.0 V Nom
AFIE 0.43 Cal/cm^2 3ph SC (Sym) 9956.99 A ArcFC 7.608 kA Trip Time 0.025 s
2-PNL-CH31
480.0 V Nom
AFIE 0.61 Cal/cm^2 3ph SC (Sym) 13794.68 A ArcFC 10.630 kA Trip Time 0.025 s
CBL: 2-PNL-CH31
1 AWG
1 Sets
83.0 ft
CB: 2-PNL-CH11
GE
Frame/Model SELA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CB: 2-PNL-CHS1
GE
Frame/Model SELA Sensor/Trip 100.0 A
100.0 A
Settings
MAX
CBL: 2-PNL-CHS1
1 AWG
1 Sets
134.0 ft
2-PNL-CHS1
480.0 V Nom
AFIE 0.42 Cal/cm^2 3ph SC (Sym) 9843.48 A ArcFC 7.518 kA Trip Time 0.025 s
2-PNL-CH11
480.0 V Nom
AFIE 0.47 Cal/cm^2 3ph SC (Sym) 10964.12 A ArcFC 8.405 kA Trip Time 0.025 s
CBL: 2-PNL-CH11
1 AWG
1 Sets
116.0 ft
2-ATS-SB1_E
480.0 V Nom
AFIE 2.25 Cal/cm^2 3ph SC (Sym) 16396.03 A ArcFC 16.421 kA Trip Time 0.058 s
CB: TX-02-TLSL32
GE
Frame/Model TEY Sensor/Trip 25.0 A
25.0 A
Settings Fixed
MCB: 2-PNL-CL31
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-CL21
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB: 2-PNL-CL32
GE
Frame/Model TQD Sensor/Trip 150.0 A
150.0 A
Settings Fixed
MCB:…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .