Attachment 13 - Door inspections 2024.xlsx
XLSX spreadsheet 23 KB Posted
- Solicitation number
- 36C25925Q0360
About this file
The file is a door inspection report for Buildings 154 and 169, documenting fire and smoke door inspections conducted in July 2024. The comprehensive spreadsheet details 154 door inspections across multiple floors (4th, 3rd, 2nd, 1st, and basement) in Building 154 and 5 door inspections in Building 169, using NFPA 101 (2018) and NFPA 80 (2016) standards. Each entry includes a unique location ID, door type (Fire Barrier or Smoke Barrier), and inspection results for doors, frames, locks/latches, operations, glazing, and closers/hinges, with detailed deficiency codes for potential issues.
The related federal contract opportunity is a Request for Quotations (RFQ) from the Department of Veterans Affairs for Fire Alarm and Fire Suppression Systems Monitoring, Inspection, Testing, Maintenance, and Repair (MITMR) at the Ft Harrison VA Medical Center and Miles City VA Community Living Center. The solicitation (Number 36C25925Q0360) is a total set-aside for Service-Disabled Veteran Owned Small Businesses (SDVOSB), with a base year and four one-year option periods, estimated performance from May 15, 2025, to May 14, 2026. Quotations are due May 9, 2025, by 11:00 a.m. Mountain Time, with a NAICS code 561621 and a small business size of $25.0 Million.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
154 door inspection
| Building 154 Fire/Smoke Door Inspection July 2024 | ||||||
| Location | ID | Type | Door | Frame | Other | Initials |
| 4th Floor | ||||||
| Stairwell C | 154-FD-4-1 | FB | Pass | Pass | Pass | KG |
| Stairwell A | 154-FD-4-2 | FB | Pass | Pass | Pass | KG |
| Stairwell B | 154-FD-4-3 | FB | Pass | Pass | Pass | KG |
| Room 473/Elev. Lobby | 154-SM-4-1 | SB | D2 | F2 | Pass | KG |
| East Hall entrance | 154-SM-4-2 | SB | D13,15,16 | F1 | Pass | KG |
| West Hall entrance by 406 | 154-SM-4-3 | SB | D15 | F1 | Pass | KG |
| Room 406 | 154-SM-4-4 | SB | Pass | Pass | Pass | KG |
| West Hall by 410 | 154-SM-4-5 | SB | D13, D15 | F1 | Pass | KG |
| East Hall by 470 | 154-SM-4-6 | SB | Pass | F1 | Pass | KG |
| 3rd Floor | ||||||
| Stairwell C | 154-FD-3-1 | FB | Pass | Pass | Pass | KG |
| Room 318 | 154-FD-3-2 | FB | D15, D18 | F1 | Pass | KG |
| Stairwell A | 154-FD-3-3 | FB | D7 | Pass | Pass | KG |
| Stairwell B | 154-FD-3-4 | FB | D7 | Pass | Pass | KG |
| Room 305A | 154-SM-3-1 | SB | D7,13,18 | F1,F7 | Pass | KG |
| Room 310 | 154-SM-3-2 | SB | D15 | Pass | Pass | KG |
| Room 315 | 154-SM-3-3 | SB | D15, 16 | Pass | Pass | KG |
| Room 315A | 154-SM-3-4 | SB | D2,7,16 | F1, 5, 7 | G2,3,4, O2 | KG |
| West Hallway by 310 | 154-SM-3-5 | SB | D2 | Pass | Pass | KG |
| West Hallway by 310 | 154-SM-3-6 | SB | D15 | Pass | Pass | KG |
| East Hallway by 369 | 154-SM-3-7 | SB | Pass | F1 | Pass | KG |
| East Hallway by 369 | 154-SM-3-8 | SB | Pass | F1 | Pass | KG |
| West Hallway by 366 | 154-SM-3-9 | SB | D17 | F1 | Pass | KG |
| West Hallway by 366 | 154-SM-3-10 | SB | D17 | F1 | Pass | KG |
| 2nd Floor | ||||||
| West surgery entrance | 154-SM-2-1 | SB | D2 | F1, F7 | Pass | TM |
| West surgery entrance | 154-SM-2-2 | SB | D2, | F1,F7 | Pass | TM |
| By room 224 | 154-SM-2-3 | SB | D2,13 | F1,5,F7 | Pass | TM |
| Room 227L | 154-SM-2-4 | SB | D2, 13, 16 | Pass | Pass | TM |
| Lab staff entrance sp230L | 154-SM-2-5 | SB | D7, 17,13 | F 7 | Pass | TM |
| Room 238E | 154-SM-2-6 | SB | D2 | Pass | Pass | TM |
| Room 240L | 154-SM-2-7 | SB | D15 | F7 | Pass | TM |
| Room 241L | 154-SM-2-8 | SB | D15 | F1 | Pass | TM |
| By room 241L | 154-SM-2-9 | SB | D15 | F1 | Pass | TM |
| Room 202L | 154-SM-2-10 | SB | D13, 15 | Pass | Pass | TM |
| Room 239B | 154-SM-2-11 | SB | D15 | Pass | Pass | TM |
| Room 239 | 154-SM-2-12 | SB | D15 | F5, F7 | Pass | TM |
| Room 239A | 154-SM-2-13 | SB | Pass | Pass | Pass | TM |
| Room 226 | 154-SM-2-14 | SB | D16 | F 7 | Pass | TM |
| Room 225 | 154-SM-2-15 | SB | D2 | F7 | Pass | TM |
| Room 224 | 154-SM-2-16 | SB | D2, 15 | Pass | Pass | TM |
| Stairwell A | 154-FD-2-1 | FB | Pass | Pass | Pass | TM |
| By room 208L | 154-FD-2-2 | FB | Pass | Pass | Pass | TM |
| By room 231 | 154-FD-2-3 | FB | D15 | F2 | Pass | TM |
| Lab exit stairwell | 154-FD-2-4 | FB | D15 | F2 | Pass | TM |
| Mech. Room 215L | 154-FD-2-5 | FB | Pass | Pass | Pass | TM |
| Outside exit door | 154-FD-2-6 | FB | D2, 15 | F1 | Pass | TM |
| Lab basement B03 | 154-FD-2-7 | FB | D15,16, 18 | Pass | Pass | TM |
| Stairwell B | 154-FD-2-8 | FB | Pass | Pass | Pass | TM |
| Stairwell C | 154-FD-2-9 | FB | Pass | F7 | Pass | TM |
| Room 223L | 154-FD-2-10 | FB | D2, 16 | Pass | Pass | TM |
| 1st Floor | ||||||
| 144 Panel room | 154-FD-1-1 | FB | Pass | Pass | Pass | ZH |
| 144 Panel room | 154-FD-1-2 | FB | Pass | Pass | Pass | ZH |
| By PD office | 154-FD-1-3 | FB | Pass | Pass | Pass | ZH |
| By PD office | 154-FD-1-4 | FB | Pass | Pass | Pass | ZH |
| By Vending machines | 154-FD-1-5 | FB | Pass | Pass | O1 | ZH |
| By Vending machines | 154-FD-1-6 | FB | Pass | Pass | Pass | ZH |
| Canteen kitchen | 154-FD-1-7 | FB | D18 | Pass | Pass | ZH |
| Canteen kitchen | 154-FD-1-8 | FB | Pass | Pass | Pass | ZH |
| By Pharmacy | 154-FD-1-9 | FB | Pass | Pass | Pass | ZH |
| By Pharmacy | 154-FD-1-10 | FB | Pass | Pass | Pass | ZH |
| Pharmacy delivery door | 154-FD-1-11 | FB | Pass | Pass | Pass | ZH |
| Connecting Coridor 172 | 154-FD-1-12 | FB | D18 | Pass | Pass | ZH |
| Pharmacy South door | 154-FD-1-13 | FB | Pass | Pass | Pass | ZH |
| Coridor Stairwell | 154-FD-1-14 | FB | Pass | Pass | Pass | ZH |
| Stairwell C | 154-FD-1-15 | FB | Pass | Pass | Pass | ZH |
| Laundry chute room | 154-FD-1-16 | FB | Pass | Pass | Pass | ZH |
| Oxygen room loading dock | 154-FD-1-17 | FB | D2 | F1 | O2 | ZH |
| Room 133A next to 133 | 154-FD-1-18 | FB | Pass | Pass | Pass | ZH |
| 144 Panel room | 154-FD-1-19 | FB | Pass | Pass | Pass | ZH |
| Stairwell B | 154-FD-1-20 | FB | Pass | Pass | Pass | ZH |
| B100 Entrance | 154-FD-1-21 | FB | Pass | Pass | Pass | ZH |
| Dental basement entrance | 154-FD-1-22 | FB | D15 | Pass | Pass | ZH |
| Stairwell A | 154-FD-1-23 | FB | Pass | Pass | Pass | ZH |
| Stairwell A basement | 154-FD-1-24 | FB | D18 | Pass | O1 | ZH |
| Stairwell A | 154-FD-1-25 | FB | Pass | Pass | Pass | ZH |
| Next to Stairwell A | 154-FD-1-26 | FB | D-15 | Pass | Pass | ZH |
| 154/169 entrance | 154-FD-1-27 | FB | D2 | F1 | G3 | ZH |
| 154/169 entrance | 154-FD-1-28 | FB | D2 | F1 | G3 | ZH |
| Behav. Health entrance | 154-FD-1-29 | FB | D18 | Pass | G3 | ZH |
| Behav. Health entrance | 154-FD-1-30 | FB | D18 | Pass | G3 | ZH |
| 169 entrance | 154-FD-1-31 | FB | D18 | Pass | G3 | ZH |
| 169 entrance | 154-FD-1-32 | FB | D18 | Pass | G3 | ZH |
| Stairwell C basement | 154-FD-1-33 | FB | Pass | Pass | Pass | ZH |
| Madison Mech. Room 108 | 154B-FD-1-1 | FB | D15 | Pass | Pass | ZH |
| Madison Room 111 | 154B-FD-1-2 | FB | Pass | Pass | Pass | ZH |
| Use the following legend to identify door deficiencies. |
| NFPA 101 (2018 edition) : NFPA 80 (2016 edition) |
| Door: |
| D1 – Missing : NFPA 101 (8.3.3.2.5) |
| D2 – Label Missing : NFPA 101 (8.3.3.3.2) |
| D3 – Label Painted : NFPA 101 (8.3.3.3.3) |
| D4 – Label Covered-Hinge : NFPA 101 (8.3.3.3.3) |
| D5 – Wedge : NFPA 101 (8.3.3.3.5) |
| D6 – Kick-down Holder : NFPA 101 (8.3.3.3.5) |
| D7 – Hole/s : NFPA 80 (5.2.3.5.2(2)) |
| D8 – Rusted : NFPA 80 (5.2.3.5.2(4)) |
| D9 – Delaminated : NFPA 80 (5.2.3.5.2((4)) |
| D10 – Bent/Warped : NFPA 80 (5.2.3.5.2(6)) |
| D11 – Protective Plate too large : NFPA 80 (6.4.5.3) |
| D12–Protective Plate screws miss :NFPA 80 (5.2.3.5.2(5)) |
| D13 – Damaged : NFPA 80 (5.2.3.5.2((4)) |
| D14 – Astragal Missing : NFPA 80 (6.3.1.7) |
| D15 – Clearance Incorrect, top : NFPA 80 (6.3.1.7) |
| D16 – Clearance Incorrect, edge : NFPA 80 (6.3.1.7) |
| D17–Clearance Incorrect meeting edge:NFPA80(6.3.1.7) |
| D18 – Undercut Excessive : NFPA 80 (4.8.4.1) |
| D19 – Signage Screwed/Nailed : NFPA 80 (4.1.4.2.2) |
| D20 – Replace Door : NFPA 101 (8.3.3.2.5) |
| D21 – Louver : NFPA 80 (6.4.6) |
| D22 – DE Signage Missing : NFPA 101 (7.2.1.6.1.1(4)) |
| Frame: |
| F1 – Label Missing : NFPA 101 (8.3.3.2.3) |
| F2 – Label Painted : NFPA 101 (8.3.3.2.3) |
| F3 – Label Covered-Hinge : NFPA 101 (8.3.3.2.3) |
| F4 – Loose : NFPA 80 (5.2.3.5.2(4)) |
| F5 – Damaged/Cut Out : NFPA 80 (5.2.3.5.2(11)) |
| F6 – Rusted : NFPA 80 (5.2.3.5.2(4)) |
| F7 – Unused Fastener Holes : NFPA 80 (5.2.3.5.2(2)) |
| F8 – Sidelight Glass Broken : NFPA 80 (5.2.3.5.2(5)) |
| F9 – Sidelight Glass No Label : NFPA 80 (6.3.3.4) |
| Lock/Latch: |
| L1 – Locked Against Egress : NFPA 101 (7.2.1.5.3) |
| L2 – Hardware Removed : NFPA 80 (5.2.3.5.2(5)) |
| L3 – Latch Missing : NFPA 80 (6.1.3.3.1) |
| L4 – Latch Bolt Binds : NFPA 80 (5.2.3.5.2(9)) |
| L5 – Latch Bolt Throw, NG : NFPA 80 (5.2.3.5.2(9)) |
| L6 – Lever/Knob Loose : NFPA 80 (5.2.3.5.2(4)) |
| L7 – Strike Plate Missing : NFPA 80 (5.2.3.5.2(5)) |
| L8 – Electric Strike Plate not rated : NFPA 80 (6.4.4.11) |
| L9 – Not Fire Exit Hardware (panic) : NFPA 80 (6.4.4.2) |
| L10 – Screws Missing : NFPA 80 (5.2.3.5.2(5)) |
| L11 – Flush Bolt Missing : NFPA 80 (6.4.4.5.1) |
| L12 – Auto-flush Bolt Missing : NFPA 80 (6.4.4.5.1) |
| L13 – Bottom Rod Missing : NFPA 80 (5.2.3.5.2(9)) |
| L14 – Bottom Rod Not Engage : NFPA 80 (5.2.3.5.2(9)) |
| L15 – Top Rod Missing : NFPA 80 (5.2.3.5.2(9)) |
| L16 – Fire Pin Missing : NFPA 80 (6.4.4.5.1) |
| L17 – Fire Pin NG : NFPA 80 (5.2.3.5.2(9)) |
| L19 – Push Bar Not ½-width : NFPA 101 (7.2.1.7.1) |
| L20 – End Cap Missing : NFPA 80 (5.2.3.5.2(5)) |
| L21– Rex Device Missing/Broken: NFPA 101 (7.2.1.6.2(1)) |
| Operation Test: |
| O1 – Does Not Close : NFPA 80 (5.2.3.5.2(7)) |
| O2 – Does Not Latch : NFPA 80 (5.2.3.5.2(9)) |
| O3 – Bottom Drags on Floor : NFPA 80 (5.2.3.5.2(7)) |
| O4 – Rubs Against Frame : NFPA 80 (5.2.3.5.2(7)) |
| O5 – Coordinator NG : NFPA 80 (5.2.3.5.2(8)) |
| O6 – Edges of Doors Overlap : NFPA 80 (5.2.3.5.2(9)) |
| O7 – Assembly Does Not Reset : NFPA 80 (5.2.3.7.2) |
| O8 – Door Slams : NFPA 80 (5.2.3.5.2(7)) |
| O9 – DE w/ auto-relock : NFPA 101(7.1.2.1.6.1(3)) |
| O10 – Fire Alarm Relay Missing : NFPA 80 (5.2.6) |
| O11 – Smoke Detector Missing : NFPA 80 (4.7.2) |
| Glazing: |
| G1 – Broken : NFPA 80 (5.2.3.5.2(5)) |
| G2 – No Label : NFPA 80 (6.3.3.4) |
| G3 – Plain Glass : NFPA 80 (6.3.3.4) |
| G4 – Too Large : NFPA 101 Table 8.3.3.2.2 |
| G5 – Loose : NFPA 80 (5.2.3.5.2(3)) |
| G6 – Lit Kit Screws Missing : NFPA 80 (5.2.3.5.2(5)) |
| Closer/Hinge: |
| C1 – Closer Missing : NFPA 101 (8.3.3.3.5) |
| C2 – Closer Leaking : NFPA 80 (5.2.3.5.2(4)) |
| C3 – Magnetic DH Broken : NFPA 80 (5.2.3.5.2(4)) |
| C4 – Closer Arm Broken : NFPA 80 (5.2.3.5.2(4)) |
| C5 – Closer Cover Missing : NFPA 80 (5.2.3.5.2(5)) |
| C6 – Closer Screw/s Missing : NFPA 80 (5.2.3.5.2(5)) |
| C7 – Hold-Open Closer : NFPA 80 (6.1.3.3) |
| H1 – Hinge Missing : NFPA 80 (5.2.3.5.2(5)) |
| H2 – Hinge Loose : NFPA 80 (5.2.3.5.2(4)) |
| H3 – Hinge Screw/s Missing : NFPA 80 (5.2.3.5.2(5)) |
| H4 – Hinge Bolt : NFPA 80 (5.2.3.5.2(4)) |
| Type: |
| FB – Fire Barrier Door |
| CCFB – Cross-Corridor Fire Barrier Doors |
| SB – Smoke Barrier Door |
169 door inspection
| Building 169 Fire/Smoke Door Inspection July 2024 | ||||||
| Location | ID | Type | Door | Frame | Other | Initials |
| Electrical room | 169-FD-1-1 | FB | D4 | Pass | Pass | JB |
| Mechanical room | 169-FD-1-2 | FB | D2,4 | Pass | Pass | JB |
| Mechanical room | 169-FD-1-3 | FB | D2,4 | Pass | Pass | JB |
| Inside Mech. Room | 169-FD-1-4 | FB | Pass | Pass | Pass | JB |
| Southwest Hall | 169-SM-1-1 | SB | Pass | Pass | Pass | JB |
| Southwest Hall | 169-SM-1-2 | SB | Pass | Pass | Pass | JB |
| Lockdown entrance | 169-SM-1-3 | SB | D2 | Pass | Pass | JB |
| Lockdown nurs. Ent | 169-SM-1-4 | SB | D2 | F1 | Pass | JB |
| Use the following legend to identify door deficiencies. |
| NFPA 101 (2018 edition) : NFPA 80 (2016 edition) |
| Door: |
| D1 – Missing : NFPA 101 (8.3.3.2.5) |
| D2 – Label Missing : NFPA 101 (8.3.3.3.2) |
| D3 – Label Painted : NFPA 101 (8.3.3.3.3) |
| D4 – Label Covered-Hinge : NFPA 101 (8.3.3.3.3) |
| D5 – Wedge : NFPA 101 (8.3.3.3.5) |
| D6 – Kick-down Holder : NFPA 101 (8.3.3.3.5) |
| D7 – Hole/s : NFPA 80 (5.2.3.5.2(2)) |
| D8 – Rusted : NFPA 80 (5.2.3.5.2(4)) |
| D9 – Delaminated : NFPA 80 (5.2.3.5.2((4)) |
| D10 – Bent/Warped : NFPA 80 (5.2.3.5.2(6)) |
| D11 – Protective Plate too large : NFPA 80 (6.4.5.3) |
| D12–Protective Plate screws miss :NFPA 80 (5.2.3.5.2(5)) |
| D13 – Damaged : NFPA 80 (5.2.3.5.2((4)) |
| D14 – Astragal Missing : NFPA 80 (6.3.1.7) |
| D15 – Clearance Incorrect, top : NFPA 80 (6.3.1.7) |
| D16 – Clearance Incorrect, edge : NFPA 80 (6.3.1.7) |
| D17–Clearance Incorrect meeting edge:NFPA80(6.3.1.7) |
| D18 – Undercut Excessive : NFPA 80 (4.8.4.1) |
| D19 – Signage Screwed/Nailed : NFPA 80 (4.1.4.2.2) |
| D20 – Replace Door : NFPA 101 (8.3.3.2.5) |
| D21 – Louver : NFPA 80 (6.4.6) |
| D22 – DE Signage Missing : NFPA 101 (7.2.1.6.1.1(4)) |
| Frame: |
| F1 – Label Missing : NFPA 101 (8.3.3.2.3) |
| F2 – Label Painted : NFPA 101 (8.3.3.2.3) |
| F3 – Label Covered-Hinge : NFPA 101 (8.3.3.2.3) |
| F4 – Loose : NFPA 80 (5.2.3.5.2(4)) |
| F5 – Damaged/Cut Out : NFPA 80 (5.2.3.5.2(11)) |
| F6 – Rusted : NFPA 80 (5.2.3.5.2(4)) |
| F7 – Unused Fastener Holes : NFPA 80 (5.2.3.5.2(2)) |
| F8 – Sidelight Glass Broken : NFPA 80 (5.2.3.5.2(5)) |
| F9 – Sidelight Glass No Label : NFPA 80 (6.3.3.4) |
| Lock/Latch: |
| L1 – Locked Against Egress : NFPA 101 (7.2.1.5.3) |
| L2 – Hardware Removed : NFPA 80 (5.2.3.5.2(5)) |
| L3 – Latch Missing : NFPA 80 (6.1.3.3.1) |
| L4 – Latch Bolt Binds : NFPA 80 (5.2.3.5.2(9)) |
| L5 – Latch Bolt Throw, NG : NFPA 80 (5.2.3.5.2(9)) |
| L6 – Lever/Knob Loose : NFPA 80 (5.2.3.5.2(4)) |
| L7 – Strike Plate Missing : NFPA 80 (5.2.3.5.2(5)) |
| L8 – Electric Strike Plate not rated : NFPA 80 (6.4.4.11) |
| L9 – Not Fire Exit Hardware (panic) : NFPA 80 (6.4.4.2) |
| L10 – Screws Missing : NFPA 80 (5.2.3.5.2(5)) |
| L11 – Flush Bolt Missing : NFPA 80 (6.4.4.5.1) |
| L12 – Auto-flush Bolt Missing : NFPA 80 (6.4.4.5.1) |
| L13 – Bottom Rod Missing : NFPA 80 (5.2.3.5.2(9)) |
| L14 – Bottom Rod Not Engage : NFPA 80 (5.2.3.5.2(9)) |
| L15 – Top Rod Missing : NFPA 80 (5.2.3.5.2(9)) |
| L16 – Fire Pin Missing : NFPA 80 (6.4.4.5.1) |
| L17 – Fire Pin NG : NFPA 80 (5.2.3.5.2(9)) |
| L19 – Push Bar Not ½-width : NFPA 101 (7.2.1.7.1) |
| L20 – End Cap Missing : NFPA 80 (5.2.3.5.2(5)) |
| L21– Rex Device Missing/Broken: NFPA 101 (7.2.1.6.2(1)) |
| Operation Test: |
| O1 – Does Not Close : NFPA 80 (5.2.3.5.2(7)) |
| O2 – Does Not Latch : NFPA 80 (5.2.3.5.2(9)) |
| O3 – Bottom Drags on Floor : NFPA 80 (5.2.3.5.2(7)) |
| O4 – Rubs Against Frame : NFPA 80 (5.2.3.5.2(7)) |
| O5 – Coordinator NG : NFPA 80 (5.2.3.5.2(8)) |
| O6 – Edges of Doors Overlap : NFPA 80 (5.2.3.5.2(9)) |
| O7 – Assembly Does Not Reset : NFPA 80 (5.2.3.7.2) |
| O8 – Door Slams : NFPA 80 (5.2.3.5.2(7)) |
| O9 – DE w/ auto-relock : NFPA 101(7.1.2.1.6.1(3)) |
| O10 – Fire Alarm Relay Missing : NFPA 80 (5.2.6) |
| O11 – Smoke Detector Missing : NFPA 80 (4.7.2) |
| Glazing: |
| G1 – Broken : NFPA 80 (5.2.3.5.2(5)) |
| G2 – No Label : NFPA 80 (6.3.3.4) |
| G3 – Plain Glass : NFPA 80 (6.3.3.4) |
| G4 – Too Large : NFPA 101 Table 8.3.3.2.2 |
| G5 – Loose : NFPA 80 (5.2.3.5.2(3)) |
| G6 – Lit Kit Screws Missing : NFPA 80 (5.2.3.5.2(5)) |
| Closer/Hinge: |
| C1 – Closer Missing : NFPA 101 (8.3.3.3.5) |
| C2 – Closer Leaking : NFPA 80 (5.2.3.5.2(4)) |
| C3 – Magnetic DH Broken : NFPA 80 (5.2.3.5.2(4)) |
| C4 – Closer Arm Broken : NFPA 80 (5.2.3.5.2(4)) |
| C5 – Closer Cover Missing : NFPA 80 (5.2.3.5.2(5)) |
| C6 – Closer Screw/s Missing : NFPA 80 (5.2.3.5.2(5)) |
| C7 – Hold-Open Closer : NFPA 80 (6.1.3.3) |
| H1 – Hinge Missing : NFPA 80 (5.2.3.5.2(5)) |
| H2 – Hinge Loose : NFPA 80 (5.2.3.5.2(4)) |
| H3 – Hinge Screw/s Missing : NFPA 80 (5.2.3.5.2(5)) |
| H4 – Hinge Bolt : NFPA 80 (5.2.3.5.2(4)) |
| Type: |
| FB – Fire Barrier Door |
| CCFB – Cross-Corridor Fire Barrier Doors |
| SB – Smoke Barrier Door |