Attachment 13 - Door inspections 2024.xlsx

XLSX spreadsheet 23 KB Posted

Attached to
H942--Amendment 0003 | North Montana VA Fire Alarm and Fire Suppression MITMR
Solicitation number
36C25925Q0360
Issued by

About this file

The file is a door inspection report for Buildings 154 and 169, documenting fire and smoke door inspections conducted in July 2024. The comprehensive spreadsheet details 154 door inspections across multiple floors (4th, 3rd, 2nd, 1st, and basement) in Building 154 and 5 door inspections in Building 169, using NFPA 101 (2018) and NFPA 80 (2016) standards. Each entry includes a unique location ID, door type (Fire Barrier or Smoke Barrier), and inspection results for doors, frames, locks/latches, operations, glazing, and closers/hinges, with detailed deficiency codes for potential issues.

The related federal contract opportunity is a Request for Quotations (RFQ) from the Department of Veterans Affairs for Fire Alarm and Fire Suppression Systems Monitoring, Inspection, Testing, Maintenance, and Repair (MITMR) at the Ft Harrison VA Medical Center and Miles City VA Community Living Center. The solicitation (Number 36C25925Q0360) is a total set-aside for Service-Disabled Veteran Owned Small Businesses (SDVOSB), with a base year and four one-year option periods, estimated performance from May 15, 2025, to May 14, 2026. Quotations are due May 9, 2025, by 11:00 a.m. Mountain Time, with a NAICS code 561621 and a small business size of $25.0 Million.

View the file

Other files

File Type Posted
Attachment 15 - Total Devices 20240207.xlsx XLSX spreadsheet
Attachment 14 - Simplex Device Failures.xlsx XLSX spreadsheet
36C25925Q0360 0003.docx DOCX document
Attachment 4 - 154A 2024 Annual Device Testing.docx DOCX document
Attachment 9 - Bldg 141 Fire Sprinkler Zone Layouts.pdf PDF
Attachment 3 - Fire Alarm and Fire Suppression MITMR Price Schedule_Amended.xlsx XLSX spreadsheet
Attachment 12 - Bldg 169 Fire Sprinkler Zone Layouts.pdf PDF
Attachment 8 - Bldg 154 Fire Sprinkler Zone Layouts.pdf PDF
Attachment 11 - BLDG 150 FIRE SPRINKLER ZONE PLANS.pdf PDF
Attachment 16 - US Miles City VA - Fire Alarm v2 - Annual - 2025-03-25.pdf PDF
Attachment 17 - US VA medical center Miles City fire sprinkler 3-11-25.pdf PDF
Attachment 10 - Bldg 154A Fire Sprinkler Zone Layouts.pdf PDF
Attachment 6 - 2024Annualalarms.docx DOCX document
Attachment 7 - Barcode Identification Placement.xlsx XLSX spreadsheet
Attachment 5 - 2024AnnualAlarms.pdf PDF
Attachment 3 - Fire Alarm and Fire Suppression MITMR Price Schedule_ Amended.xlsx XLSX spreadsheet
36C25925Q0360 0002.docx DOCX document
36C25925Q0360 0001.docx DOCX document
36C25925Q0360.docx DOCX document
Attachment 3 - Fire Alarm and Fire Suppression MITMR Price Schedule.xlsx XLSX spreadsheet
Attachment 1 - Statement of Work - Fire Alarm and Fire Suppression MITMR.docx DOCX document
Attachment 2 - VA Notice of Limitation of Subcontracting.docx DOCX document
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

154 door inspection

Building 154 Fire/Smoke Door Inspection July 2024
LocationIDTypeDoorFrameOtherInitials
4th Floor
Stairwell C154-FD-4-1FBPassPassPassKG
Stairwell A154-FD-4-2FBPassPassPassKG
Stairwell B154-FD-4-3FBPassPassPassKG
Room 473/Elev. Lobby154-SM-4-1SBD2F2PassKG
East Hall entrance154-SM-4-2SBD13,15,16F1PassKG
West Hall entrance by 406154-SM-4-3SBD15F1PassKG
Room 406154-SM-4-4SBPassPassPassKG
West Hall by 410154-SM-4-5SBD13, D15F1PassKG
East Hall by 470154-SM-4-6SBPassF1PassKG
3rd Floor
Stairwell C154-FD-3-1FBPassPassPassKG
Room 318154-FD-3-2FBD15, D18F1PassKG
Stairwell A154-FD-3-3FBD7PassPassKG
Stairwell B154-FD-3-4FBD7PassPassKG
Room 305A154-SM-3-1SBD7,13,18F1,F7PassKG
Room 310154-SM-3-2SBD15PassPassKG
Room 315154-SM-3-3SBD15, 16PassPassKG
Room 315A154-SM-3-4SBD2,7,16F1, 5, 7G2,3,4, O2KG
West Hallway by 310154-SM-3-5SBD2PassPassKG
West Hallway by 310154-SM-3-6SBD15PassPassKG
East Hallway by 369154-SM-3-7SBPassF1PassKG
East Hallway by 369154-SM-3-8SBPassF1PassKG
West Hallway by 366154-SM-3-9SBD17F1PassKG
West Hallway by 366154-SM-3-10SBD17F1PassKG
2nd Floor
West surgery entrance154-SM-2-1SBD2F1, F7PassTM
West surgery entrance154-SM-2-2SBD2,F1,F7PassTM
By room 224154-SM-2-3SBD2,13F1,5,F7PassTM
Room 227L154-SM-2-4SBD2, 13, 16PassPassTM
Lab staff entrance sp230L154-SM-2-5SBD7, 17,13F 7PassTM
Room 238E154-SM-2-6SBD2PassPassTM
Room 240L154-SM-2-7SBD15F7PassTM
Room 241L154-SM-2-8SBD15F1PassTM
By room 241L154-SM-2-9SBD15F1PassTM
Room 202L154-SM-2-10SBD13, 15PassPassTM
Room 239B154-SM-2-11SBD15PassPassTM
Room 239154-SM-2-12SBD15F5, F7PassTM
Room 239A154-SM-2-13SBPassPassPassTM
Room 226154-SM-2-14SBD16F 7PassTM
Room 225154-SM-2-15SBD2F7PassTM
Room 224154-SM-2-16SBD2, 15PassPassTM
Stairwell A154-FD-2-1FBPassPassPassTM
By room 208L154-FD-2-2FBPassPassPassTM
By room 231154-FD-2-3FBD15F2PassTM
Lab exit stairwell154-FD-2-4FBD15F2PassTM
Mech. Room 215L154-FD-2-5FBPassPassPassTM
Outside exit door154-FD-2-6FBD2, 15F1PassTM
Lab basement B03154-FD-2-7FBD15,16, 18PassPassTM
Stairwell B154-FD-2-8FBPassPassPassTM
Stairwell C154-FD-2-9FBPassF7PassTM
Room 223L154-FD-2-10FBD2, 16PassPassTM
1st Floor
144 Panel room154-FD-1-1FBPassPassPassZH
144 Panel room154-FD-1-2FBPassPassPassZH
By PD office154-FD-1-3FBPassPassPassZH
By PD office154-FD-1-4FBPassPassPassZH
By Vending machines154-FD-1-5FBPassPassO1ZH
By Vending machines154-FD-1-6FBPassPassPassZH
Canteen kitchen154-FD-1-7FBD18PassPassZH
Canteen kitchen154-FD-1-8FBPassPassPassZH
By Pharmacy154-FD-1-9FBPassPassPassZH
By Pharmacy154-FD-1-10FBPassPassPassZH
Pharmacy delivery door154-FD-1-11FBPassPassPassZH
Connecting Coridor 172154-FD-1-12FBD18PassPassZH
Pharmacy South door154-FD-1-13FBPassPassPassZH
Coridor Stairwell154-FD-1-14FBPassPassPassZH
Stairwell C154-FD-1-15FBPassPassPassZH
Laundry chute room154-FD-1-16FBPassPassPassZH
Oxygen room loading dock154-FD-1-17FBD2F1O2ZH
Room 133A next to 133154-FD-1-18FBPassPassPassZH
144 Panel room154-FD-1-19FBPassPassPassZH
Stairwell B154-FD-1-20FBPassPassPassZH
B100 Entrance154-FD-1-21FBPassPassPassZH
Dental basement entrance154-FD-1-22FBD15PassPassZH
Stairwell A154-FD-1-23FBPassPassPassZH
Stairwell A basement154-FD-1-24FBD18PassO1ZH
Stairwell A154-FD-1-25FBPassPassPassZH
Next to Stairwell A154-FD-1-26FBD-15PassPassZH
154/169 entrance154-FD-1-27FBD2F1G3ZH
154/169 entrance154-FD-1-28FBD2F1G3ZH
Behav. Health entrance154-FD-1-29FBD18PassG3ZH
Behav. Health entrance154-FD-1-30FBD18PassG3ZH
169 entrance154-FD-1-31FBD18PassG3ZH
169 entrance154-FD-1-32FBD18PassG3ZH
Stairwell C basement154-FD-1-33FBPassPassPassZH
Madison Mech. Room 108154B-FD-1-1FBD15PassPassZH
Madison Room 111154B-FD-1-2FBPassPassPassZH
Use the following legend to identify door deficiencies.
NFPA 101 (2018 edition) : NFPA 80 (2016 edition)
Door:
D1 – Missing : NFPA 101 (8.3.3.2.5)
D2 – Label Missing : NFPA 101 (8.3.3.3.2)
D3 – Label Painted : NFPA 101 (8.3.3.3.3)
D4 – Label Covered-Hinge : NFPA 101 (8.3.3.3.3)
D5 – Wedge : NFPA 101 (8.3.3.3.5)
D6 – Kick-down Holder : NFPA 101 (8.3.3.3.5)
D7 – Hole/s : NFPA 80 (5.2.3.5.2(2))
D8 – Rusted : NFPA 80 (5.2.3.5.2(4))
D9 – Delaminated : NFPA 80 (5.2.3.5.2((4))
D10 – Bent/Warped : NFPA 80 (5.2.3.5.2(6))
D11 – Protective Plate too large : NFPA 80 (6.4.5.3)
D12–Protective Plate screws miss :NFPA 80 (5.2.3.5.2(5))
D13 – Damaged : NFPA 80 (5.2.3.5.2((4))
D14 – Astragal Missing : NFPA 80 (6.3.1.7)
D15 – Clearance Incorrect, top : NFPA 80 (6.3.1.7)
D16 – Clearance Incorrect, edge : NFPA 80 (6.3.1.7)
D17–Clearance Incorrect meeting edge:NFPA80(6.3.1.7)
D18 – Undercut Excessive : NFPA 80 (4.8.4.1)
D19 – Signage Screwed/Nailed : NFPA 80 (4.1.4.2.2)
D20 – Replace Door : NFPA 101 (8.3.3.2.5)
D21 – Louver : NFPA 80 (6.4.6)
D22 – DE Signage Missing : NFPA 101 (7.2.1.6.1.1(4))
Frame:
F1 – Label Missing : NFPA 101 (8.3.3.2.3)
F2 – Label Painted : NFPA 101 (8.3.3.2.3)
F3 – Label Covered-Hinge : NFPA 101 (8.3.3.2.3)
F4 – Loose : NFPA 80 (5.2.3.5.2(4))
F5 – Damaged/Cut Out : NFPA 80 (5.2.3.5.2(11))
F6 – Rusted : NFPA 80 (5.2.3.5.2(4))
F7 – Unused Fastener Holes : NFPA 80 (5.2.3.5.2(2))
F8 – Sidelight Glass Broken : NFPA 80 (5.2.3.5.2(5))
F9 – Sidelight Glass No Label : NFPA 80 (6.3.3.4)
Lock/Latch:
L1 – Locked Against Egress : NFPA 101 (7.2.1.5.3)
L2 – Hardware Removed : NFPA 80 (5.2.3.5.2(5))
L3 – Latch Missing : NFPA 80 (6.1.3.3.1)
L4 – Latch Bolt Binds : NFPA 80 (5.2.3.5.2(9))
L5 – Latch Bolt Throw, NG : NFPA 80 (5.2.3.5.2(9))
L6 – Lever/Knob Loose : NFPA 80 (5.2.3.5.2(4))
L7 – Strike Plate Missing : NFPA 80 (5.2.3.5.2(5))
L8 – Electric Strike Plate not rated : NFPA 80 (6.4.4.11)
L9 – Not Fire Exit Hardware (panic) : NFPA 80 (6.4.4.2)
L10 – Screws Missing : NFPA 80 (5.2.3.5.2(5))
L11 – Flush Bolt Missing : NFPA 80 (6.4.4.5.1)
L12 – Auto-flush Bolt Missing : NFPA 80 (6.4.4.5.1)
L13 – Bottom Rod Missing : NFPA 80 (5.2.3.5.2(9))
L14 – Bottom Rod Not Engage : NFPA 80 (5.2.3.5.2(9))
L15 – Top Rod Missing : NFPA 80 (5.2.3.5.2(9))
L16 – Fire Pin Missing : NFPA 80 (6.4.4.5.1)
L17 – Fire Pin NG : NFPA 80 (5.2.3.5.2(9))
L19 – Push Bar Not ½-width : NFPA 101 (7.2.1.7.1)
L20 – End Cap Missing : NFPA 80 (5.2.3.5.2(5))
L21– Rex Device Missing/Broken: NFPA 101 (7.2.1.6.2(1))
Operation Test:
O1 – Does Not Close : NFPA 80 (5.2.3.5.2(7))
O2 – Does Not Latch : NFPA 80 (5.2.3.5.2(9))
O3 – Bottom Drags on Floor : NFPA 80 (5.2.3.5.2(7))
O4 – Rubs Against Frame : NFPA 80 (5.2.3.5.2(7))
O5 – Coordinator NG : NFPA 80 (5.2.3.5.2(8))
O6 – Edges of Doors Overlap : NFPA 80 (5.2.3.5.2(9))
O7 – Assembly Does Not Reset : NFPA 80 (5.2.3.7.2)
O8 – Door Slams : NFPA 80 (5.2.3.5.2(7))
O9 – DE w/ auto-relock : NFPA 101(7.1.2.1.6.1(3))
O10 – Fire Alarm Relay Missing : NFPA 80 (5.2.6)
O11 – Smoke Detector Missing : NFPA 80 (4.7.2)
Glazing:
G1 – Broken : NFPA 80 (5.2.3.5.2(5))
G2 – No Label : NFPA 80 (6.3.3.4)
G3 – Plain Glass : NFPA 80 (6.3.3.4)
G4 – Too Large : NFPA 101 Table 8.3.3.2.2
G5 – Loose : NFPA 80 (5.2.3.5.2(3))
G6 – Lit Kit Screws Missing : NFPA 80 (5.2.3.5.2(5))
Closer/Hinge:
C1 – Closer Missing : NFPA 101 (8.3.3.3.5)
C2 – Closer Leaking : NFPA 80 (5.2.3.5.2(4))
C3 – Magnetic DH Broken : NFPA 80 (5.2.3.5.2(4))
C4 – Closer Arm Broken : NFPA 80 (5.2.3.5.2(4))
C5 – Closer Cover Missing : NFPA 80 (5.2.3.5.2(5))
C6 – Closer Screw/s Missing : NFPA 80 (5.2.3.5.2(5))
C7 – Hold-Open Closer : NFPA 80 (6.1.3.3)
H1 – Hinge Missing : NFPA 80 (5.2.3.5.2(5))
H2 – Hinge Loose : NFPA 80 (5.2.3.5.2(4))
H3 – Hinge Screw/s Missing : NFPA 80 (5.2.3.5.2(5))
H4 – Hinge Bolt : NFPA 80 (5.2.3.5.2(4))
Type:
FB – Fire Barrier Door
CCFB – Cross-Corridor Fire Barrier Doors
SB – Smoke Barrier Door

169 door inspection

Building 169 Fire/Smoke Door Inspection July 2024
LocationIDTypeDoorFrameOtherInitials
Electrical room169-FD-1-1FBD4PassPassJB
Mechanical room169-FD-1-2FBD2,4PassPassJB
Mechanical room169-FD-1-3FBD2,4PassPassJB
Inside Mech. Room169-FD-1-4FBPassPassPassJB
Southwest Hall169-SM-1-1SBPassPassPassJB
Southwest Hall169-SM-1-2SBPassPassPassJB
Lockdown entrance169-SM-1-3SBD2PassPassJB
Lockdown nurs. Ent169-SM-1-4SBD2F1PassJB
Use the following legend to identify door deficiencies.
NFPA 101 (2018 edition) : NFPA 80 (2016 edition)
Door:
D1 – Missing : NFPA 101 (8.3.3.2.5)
D2 – Label Missing : NFPA 101 (8.3.3.3.2)
D3 – Label Painted : NFPA 101 (8.3.3.3.3)
D4 – Label Covered-Hinge : NFPA 101 (8.3.3.3.3)
D5 – Wedge : NFPA 101 (8.3.3.3.5)
D6 – Kick-down Holder : NFPA 101 (8.3.3.3.5)
D7 – Hole/s : NFPA 80 (5.2.3.5.2(2))
D8 – Rusted : NFPA 80 (5.2.3.5.2(4))
D9 – Delaminated : NFPA 80 (5.2.3.5.2((4))
D10 – Bent/Warped : NFPA 80 (5.2.3.5.2(6))
D11 – Protective Plate too large : NFPA 80 (6.4.5.3)
D12–Protective Plate screws miss :NFPA 80 (5.2.3.5.2(5))
D13 – Damaged : NFPA 80 (5.2.3.5.2((4))
D14 – Astragal Missing : NFPA 80 (6.3.1.7)
D15 – Clearance Incorrect, top : NFPA 80 (6.3.1.7)
D16 – Clearance Incorrect, edge : NFPA 80 (6.3.1.7)
D17–Clearance Incorrect meeting edge:NFPA80(6.3.1.7)
D18 – Undercut Excessive : NFPA 80 (4.8.4.1)
D19 – Signage Screwed/Nailed : NFPA 80 (4.1.4.2.2)
D20 – Replace Door : NFPA 101 (8.3.3.2.5)
D21 – Louver : NFPA 80 (6.4.6)
D22 – DE Signage Missing : NFPA 101 (7.2.1.6.1.1(4))
Frame:
F1 – Label Missing : NFPA 101 (8.3.3.2.3)
F2 – Label Painted : NFPA 101 (8.3.3.2.3)
F3 – Label Covered-Hinge : NFPA 101 (8.3.3.2.3)
F4 – Loose : NFPA 80 (5.2.3.5.2(4))
F5 – Damaged/Cut Out : NFPA 80 (5.2.3.5.2(11))
F6 – Rusted : NFPA 80 (5.2.3.5.2(4))
F7 – Unused Fastener Holes : NFPA 80 (5.2.3.5.2(2))
F8 – Sidelight Glass Broken : NFPA 80 (5.2.3.5.2(5))
F9 – Sidelight Glass No Label : NFPA 80 (6.3.3.4)
Lock/Latch:
L1 – Locked Against Egress : NFPA 101 (7.2.1.5.3)
L2 – Hardware Removed : NFPA 80 (5.2.3.5.2(5))
L3 – Latch Missing : NFPA 80 (6.1.3.3.1)
L4 – Latch Bolt Binds : NFPA 80 (5.2.3.5.2(9))
L5 – Latch Bolt Throw, NG : NFPA 80 (5.2.3.5.2(9))
L6 – Lever/Knob Loose : NFPA 80 (5.2.3.5.2(4))
L7 – Strike Plate Missing : NFPA 80 (5.2.3.5.2(5))
L8 – Electric Strike Plate not rated : NFPA 80 (6.4.4.11)
L9 – Not Fire Exit Hardware (panic) : NFPA 80 (6.4.4.2)
L10 – Screws Missing : NFPA 80 (5.2.3.5.2(5))
L11 – Flush Bolt Missing : NFPA 80 (6.4.4.5.1)
L12 – Auto-flush Bolt Missing : NFPA 80 (6.4.4.5.1)
L13 – Bottom Rod Missing : NFPA 80 (5.2.3.5.2(9))
L14 – Bottom Rod Not Engage : NFPA 80 (5.2.3.5.2(9))
L15 – Top Rod Missing : NFPA 80 (5.2.3.5.2(9))
L16 – Fire Pin Missing : NFPA 80 (6.4.4.5.1)
L17 – Fire Pin NG : NFPA 80 (5.2.3.5.2(9))
L19 – Push Bar Not ½-width : NFPA 101 (7.2.1.7.1)
L20 – End Cap Missing : NFPA 80 (5.2.3.5.2(5))
L21– Rex Device Missing/Broken: NFPA 101 (7.2.1.6.2(1))
Operation Test:
O1 – Does Not Close : NFPA 80 (5.2.3.5.2(7))
O2 – Does Not Latch : NFPA 80 (5.2.3.5.2(9))
O3 – Bottom Drags on Floor : NFPA 80 (5.2.3.5.2(7))
O4 – Rubs Against Frame : NFPA 80 (5.2.3.5.2(7))
O5 – Coordinator NG : NFPA 80 (5.2.3.5.2(8))
O6 – Edges of Doors Overlap : NFPA 80 (5.2.3.5.2(9))
O7 – Assembly Does Not Reset : NFPA 80 (5.2.3.7.2)
O8 – Door Slams : NFPA 80 (5.2.3.5.2(7))
O9 – DE w/ auto-relock : NFPA 101(7.1.2.1.6.1(3))
O10 – Fire Alarm Relay Missing : NFPA 80 (5.2.6)
O11 – Smoke Detector Missing : NFPA 80 (4.7.2)
Glazing:
G1 – Broken : NFPA 80 (5.2.3.5.2(5))
G2 – No Label : NFPA 80 (6.3.3.4)
G3 – Plain Glass : NFPA 80 (6.3.3.4)
G4 – Too Large : NFPA 101 Table 8.3.3.2.2
G5 – Loose : NFPA 80 (5.2.3.5.2(3))
G6 – Lit Kit Screws Missing : NFPA 80 (5.2.3.5.2(5))
Closer/Hinge:
C1 – Closer Missing : NFPA 101 (8.3.3.3.5)
C2 – Closer Leaking : NFPA 80 (5.2.3.5.2(4))
C3 – Magnetic DH Broken : NFPA 80 (5.2.3.5.2(4))
C4 – Closer Arm Broken : NFPA 80 (5.2.3.5.2(4))
C5 – Closer Cover Missing : NFPA 80 (5.2.3.5.2(5))
C6 – Closer Screw/s Missing : NFPA 80 (5.2.3.5.2(5))
C7 – Hold-Open Closer : NFPA 80 (6.1.3.3)
H1 – Hinge Missing : NFPA 80 (5.2.3.5.2(5))
H2 – Hinge Loose : NFPA 80 (5.2.3.5.2(4))
H3 – Hinge Screw/s Missing : NFPA 80 (5.2.3.5.2(5))
H4 – Hinge Bolt : NFPA 80 (5.2.3.5.2(4))
Type:
FB – Fire Barrier Door
CCFB – Cross-Corridor Fire Barrier Doors
SB – Smoke Barrier Door

File details come from the government source that posted it. Updated .