5. Fire Safety Matrix.xlsx

XLSX spreadsheet 23 KB Posted

Attached to
S202-- Preventative Maintenance Fire Alarm & Suppression Federal contract opportunity
Solicitation number
36C25920Q0723
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

This document contains a federal contract opportunity solicitation for preventative maintenance fire alarm and suppression services. The solicitation is a 100% set-aside for Service-Disabled Veteran Owned Small Businesses to provide recurring inspection, testing, and maintenance of the fire alarm and suppression systems at the Salt Lake City Veterans Administration Medical Center in Utah. Quotes are due by September 23, 2020 and the contract will have a one-year base period of performance plus four optional one-year extensions. Evaluation will be based solely on price, and the contract will be awarded to the responsible offeror providing the lowest priced quote that is within available funding and determined reasonable. The solicitation identifies specialized experience, training, and licensing requirements for contractor personnel as well as responsibility factors relating to safety equipment and subcontractor certifications.

View the file

Other files for this federal contract opportunity

Other files attached to S202-- Preventative Maintenance Fire Alarm & Suppression, newest first.
File Type Posted
2. SLCVA_FIRE_ALARMS DRAWING PDF.pdf PDF
36C25920Q0723 0001.doc DOC document
1. Joint Commission Accreditation_Reports.pdf PDF
3. FIRE PROTECTION RECORD DRAWINGS.pdf PDF
36C25920Q0723 0001_1.docx DOCX document
4. SLC VAMC Fire Alarm Inventory 2020_0915.xlsx XLSX spreadsheet
Questions and Answers.doc DOC document
VHA Directive 7701.pdf PDF
Joint Commission Life Safety and Environment of Care.pdf PDF
VHA Directive 7703.pdf PDF
36C25920Q0723.docx DOCX document
36C25920Q0723_1.docx DOCX document
WD 2015-5489 REV 11.pdf PDF
QASP_Fire alarm and supression.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EC 02.03.03 & 02.03.05

Device DescriptionEPTest FrequencyCode Ref.Conducted ByTest Date 1st QtrCommentsTest Date 2nd QtrCommentsTest Date 3rd QtrCommentsTest Date 4th QtrCommentsSOC ReferenceComments
Supervisory signal devices1AnnualNFPA 72 '16 14.4.3.2TBD11/1/19
Water flow devices and Valve tamper switches2SemiannualNFPA 72 '16 14.4.3.2TBD11/7/196/30/20
Duct, Heat, smoke detectors and fire alarm pull boxes3AnnualNFPA 72 '16 14.4.3.2TBD11/23/19
Notification appliances and door releasing devices4AnnualNFPA 72 '16 14.4.3.2TBD11/23/19
Emergency services notification transmission equipment5AnnualNFPA 72 '16 14.4.3.2TBD12/6/19
Fire pump churn test6Monthly (Elec) Weekly (Diesel)NFPA 25 17'
8.3.1.1-.2VACompliant10/18 11/11 12/17Compliant1/15 2/12 3/18Compliant4/16 5/13
Water storage tank level alarms7AnnualNFPA 25 17' 9.3.5N/A
Water tank low temp alarm (cold weather only)8Monthly during cold weatherNFPA 25 17' 9.3.3N/A
Sprinkler systems main drain tests9AnnualNFPA 25 17' 13.2.5 &2.5.2TBD11/7/19
Fire department connection inspection10QuarterlyNFPA 25 17' 13.8.1VACompliant10/18 11/11 12/173/12/206/30/20
Fire pumps tested under flow11AnnualNFPA 25 17' 8.3.3TBD10/15/19
Automatic Standpipe Systems125 yearsNFPA 25 17' 6.3.1.1TBD11/1/19
Kitchen extinguishing Systems13SemiannualNFPA 96 17' 11.2.1TBD10/1/19multiple3/16/2020 B8
3/23/2020 B5multiple9/?/2020 B8

9/8/2020 B5

Gaseous extinguishing Systems14AnnualNAN/A
Portable fire extinguishers inspected15MonthlyNFPA 10 18' 7.2Covered under separate contractmultiplemultiplemultiplemultiple
Portable fire extinguishers maintained16AnnualNFPA 10 18' 7.3Covered under separate contract1/15/20
Fire hoses hydrostatically tested175 years after install, 3 years thereafterNFPA 25 17' 6.1.1.2N/A
Fire and smoke dampers181yr > install / HAP 6yrs thereafter. BUS: every 4yrsNFPA 105 16' & 80 16'N/ALSS Feb 2015
Smoke detecting shut down devices for HVAC19AnnualNFPA 90A 18' 6.4.1TBD11/1/19
Horizontal & vertical rolling and sliding fire doors20AnnualNFPA 80 16' 5.2.4Covered under separate contract2/12/20
Fire & Smoke door assemblies inspections25AnnualNFPA 101 18' 8.3.3.3.1VAmultipleFMS maintains list of deficienciesmultiplemultiplemultipleInspections are done quarterly in different areas to avoid all coming due at one time
Fire HydrantsAnnualNFPA 25 17' 7.1.1.2TBD2-Nov
Fire Drills for occupancies where patients are treatedQuarterlyNFPA 101 18' 18/19 7.1SafetymultipleAll required drill were conducted for 1st QtrmultipleAll required drill were conducted for 2nd QtrmultipleAll required drill were conducted for 2nd Qtrmultiple

FY2020 Quick Reference Fire Protection and Suppression System Testing / Inspection / Maintenance Log Roseburg VA Health Care System Salt Lake CityVA Health Care System