36C25918R0592-017.pdf
PDF 5 MB Posted
- Attached to
- Upgrade Site Water Systems (VA-18-00071315)
- Solicitation number
- 36C25918R0592
About this file
36C25918R0592 Water Drawings Part3.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25918C0325-000.docx | DOCX document | |
| 36C25918R0592-0002003.pdf | ||
| 36C25918R0592-0002002.pdf | ||
| 36C25918R0592-0002000.docx | DOCX document | |
| 36C25918R0592-0002001.pdf | ||
| 36C25918R0592-0001000.docx | DOCX document | |
| 36C25918R0592-020.docx | DOCX document | |
| 36C25918R0592-012.docx | DOCX document | |
| 36C25918R0592-014.pdf | ||
| 36C25918R0592-019.docx | DOCX document | |
| 36C25918R0592-013.docx | DOCX document | |
| 36C25918R0592-024.pdf | ||
| 36C25918R0592-021.pdf | ||
| 36C25918R0592-023.pdf | ||
| 36C25918R0592-015.pdf | ||
| 36C25918R0592-018.pdf | ||
| 36C25918R0592-022.pdf | ||
| 36C25918R0592-016.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BLDG. 53
BLDG. 52
B L
D G
B L
D G
WALLS, ETC. BELOW
(DASHED), TYP.
EX 3/4" TO EYE
WASH BELOW
EX 3/4"CW DN
TO INT HOSE BIB
EX 1" RISER
DRAINS-DN 24"
EX 1 1/2"
EX 4"
EX 6"
EX 1/2"
EX 1/2"
EX 2"
EX 1 1/2"EX 2"
EX 2"
EX 3/4"
3/4" CW TO SUB-BASEMENT WALL HYDRANTS
EX 1"
EX 3/4"
EX 6"
EX 4"
EX 1 1/2"
EX 6"
EX 4"
EX 1 1/2"
SEE BUILDING 58 PLANS
FOR WORK IN THIS
AREA
EX 1 1/4"
EX 6"
EX 4"
EX 1 1/4"
12 21
3/4"
P-8043
PRV-4 1
PRV-1 1
PRV-6
PRV-1
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
53-PP101
WLF / LLPDJR
BASEMENT MEZZANINE PLUMBING
PLAN
1. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
2. SEE EQUIPMENT SCHEDULE ON SHEET P-401
AND DETAIL 4/P-501.
3. ROUTE PIPING DOWN THRU INTERSTITIAL
FLOOR AND MOUNT NEW INSULATED PIPING
EXPOSED ON WALL. SEE DETAIL 4 / P-502 FOR
ADDITIONAL INFORMATION.
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
SYSTEM. PROVIDE SUBMITTAL TO COR FOR
APPROVAL
EX 1 1/4"
EX 3/4"
EX 1 1/4"
EX 3/4"
EX 1 1/2"
EX 3/4"
EX 1 1/4"
EX 1"
EX 1"
EX 1 1/2"
EX 1/2"
EX 1/2"
EX 1 1/2"
EX 3/4"
EX 3/4"
EX 1/2"-DN
EX 1-1/4"-DN
EX 6" VENT RISER
EX 6" SOIL RISER
EX 6" RD RISER
EX 1/2"-DN
EX 1 1/4"-DN
EX 1/2"
EX 6" VENT RISER
EX 6" SOIL RISER
EX 6" RD RISER
EX 1/2"-DN
BLDG. 52
B L
D G
W
E S
T
B L
D G
BLDG. 53 EAST
BLDG. 53 WEST
B L
D G
B L
D G
E
A S
T
BLDG. 60
BLDG. 53 WEST
BLDG. 53 EAST
WALLS, ETC. BELOW
(DASHED), TYP.
EX DHWR BALANCING VALVE
EX 2"
EX 1 1/2"
1 1/2"
2"
EX 1 1/4"
EX (3")FD
EX 3"
5 6
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
53-PP121
WLF / LLPDJR
SECOND FLOOR INTERSTITIAL
PLUMBING PLAN - WEST HALF
1. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
2. SEE EQUIPMENT SCHEDULE ON SHEET P-401
AND DETAIL 4 / P-501.
3. SEE EQUIPMENT SCHEDULE ON SHEET P-401
AND DETAIL 5 / P-501.
4. 4" SANITARY UP TO FLOOR DRAIN ON FLOOR
DRAIN ABOVE.
5. SEE EQUIPMENT SCHEDULE ON P-401 AND
DETAIL ON P-502.
6. NEW 4" DRAIN STANDPIPE IN MECHANICAL
ROOM OFF OF SANITARY RISER. TIE 2" VENT
INTO VENT RISER.
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
EX 53-PRV-1-1
EX 53-PRV-1-2
EX 1"
EX 1"
EX 3/4"
EX 3/4"
EX 1/2"-DN
EX 1/2"-DN
EX 1/2"-DN
EX 1/2"-DN
EX 1/2"
EX 1/2"
EX 1/2"-DN
EX 1/2"-DN
EX 1/2"-DN
EX 3/4"-DN
EX 1 1/2"-DN
EX 1"-DN
EX 1 1/2"
EX 1"
EX 3/4"
EX 1/2"-DN
EX 2"
EX 1 1/4"
EX 1/2"
EX 1/2"
EX 1/2"
EX 1/2"-DN
EX 1 1/4"
EX 2"
EX 1/2"
EX 1 1/4"
EX 2"
EX 1"
EX 1 1/2"-DN
EX 3"FD
EX 3/4"-DN
EX 1/2"
EX 1/2"
EX 1"
EX 1"
EX 1"
EX 1"
EX 3/4"
EX 3/4"
EX 1/2"-DN
EX 1/2"-DN
EX 3/4"
EX 3/4"
EX 1/2"-DN
EX 1/2"-DN
EX 3/4"
EX 1/2"
EX 3/4"
EX 1/2"
EX 3/4"
EX 1"
EX 1/2"-DN
EX 1/2"
EX 1 1/2"-DN
EX 1/2"-DN
EX 1 1/2"
EX 1 1/2"
EX 2"
EX 1 1/4"
EX 2"
EX 1 1/4"
EX 2"
EX 3/4"-DN
EX 3/4"-DN
EX 1/2"
EX 1/2"
EX 1/2"EX 1/2"
EX 3/4"
EX 3/4"
EX 4"
EX 4"
EX 1 1/2"-DN
EX 1/2"-DN
EX 1"
EX 3/4"
EX 1/2"-DN
EX 3/4"
EX 3/4"-DN
EX 1/2"-DN
EX 3/4"-DN EX 3/4"-DN
EX 1/2"-DN
EX 1/2"-DN
EX 8" STORM RISER
EX 6" VENT RISER
EX 6" SANITARY RISER
3" CRP VENT RISER
6" VENT STACK
6" SANITARY RISER
6" STORM RISER
6" ST-UP / 8"-DN
WALLS, ETC. BELOW
(DASHED), TYP.
BLDG. 52
BLDG. 53 EAST
BLDG. 53 WEST
BLDG. 60
BLDG. 53 WEST
BLDG. 53 EAST
B L
D G
B L
D G
W
E S
T
BLDG. 53 EAST
BLDG. 1C
B L
D G
C
B L
D G
E
A S
T
BLDG. 53 EAST
BLDG. 60
6" SANITARY RISER
6" VENT RISER
EX CW, HW & HWR RISERS
PRV-4
PRV-2
EX HWS & HWR RISERS
EX CWS & CWR RISERS
EX 3/4"
EX 2"
EX 3/4"
EX 1 1/2"
EX 1/2"CW & HW
UP TO SINK
EX 1/2"
EX 1/2"
EX 1 1/4"
1/2" 1/2"
1/2"
1/2"
1/2"
0.5 GPM
1/2"
EX 3"
EX (3")FD
BFP-4
BFP-2
1 1
6 72" V
6 74" SS 1
6" DL WITH DRAIN VALVES
P-418F
P-418F
P-418F
EX 3/4"
EX 3/4"
P-804
EX 1/2"-DN
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
53-PP122
WLF / LLPDJR
SECOND FLOOR INTERSTITIAL
PLUMBING PLAN - EAST HALF
1. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
2. SEE EQUIPMENT SCHEDULE ON SHEET
P-401.
3. PROVIDE BATTERY POWERED ELECTRONIC
OPERATED SENSOR FAUCET WITH TIMER
SET TO FLUSH THE PIPING ONCE A DAY FOR
5 MINUTES. SEE PLUMBING FIXTURE
SCHEDULE ON P-401 AND SPECIFICATIONS
FOR ADDITIONAL INFORMATION.
4. SEE EQUIPMENT SCHEDULE ON P-401 AND
DETAIL 5 / P-501.
5. 4" SANITARY UP TO FLOOR DRAIN ON FLOOR
ABOVE.
6. SEE EQUIPMENT SCHEDULE ON P-401 AND
DETAIL ON P-502.
7. NEW 4" DRAIN STANDPIPE IN MECHANICAL
ROOM OFF OF SANITARY RISER. TIE 2" VENT
INTO VENT RISER.
8. PATCH CHASE TO MATCH EXISTING FIRE
RATING PAINT WALL TO MATCH EXISTING
FINISHES.
9. PROVIDE A 303 STAINLESS STEEL
BALANCING VALVE WITH INTEGRATED UNION
BODY, INLET AND OUTLET BALL VALVES.
HIGH TEMP ACTUATOR FOR SANITARY
FLUSHING PROCESS DURING LEGIONELLA
DISINFECTION. LOW-TEMP ACTUATOR TO BE
SET AT 130°F.
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
BLDG. 53 WEST
BLDG. 53 EAST
BLDG. 53 WEST
BLDG. 53 EAST
BLDG. 53 WEST
BLDG. 53 EAST
WALLS, ETC. BELOW
(DASHED), TYP.
EX 1 1/2"
EX CW 1/2"-UP TO
DIALYSIS BFP
ON FLOOR ABOVE
BFP-3
BFP-4
PRV-4
PRV-3
1 1/2"
2"
1/2"
1/2"
1/2" 1/2"
1/2"
1/2"
6 74" SS
6 72" V
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
53-PP131
WLF / LLPDJR
THIRD FLOOR INTERSTITIAL
PLUMBING PLAN - WEST HALF
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
SYSTEM. PROVIDE SUBMITTAL TO COR FOR
APPROVAL
1. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
2. SEE EQUIPMENT SCHEDULE ON SHEET P-401.
3. PROVIDE BATTERY POWERED ELECTRONIC
OPERATED SENSOR FAUCET WITH TIMER SET
TO FLUSH THE PIPING ONCE A DAY FOR 5
MINUTES. SEE PLUMBING FIXTURE SCHEDULE
ON P-401 AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
4. SEE EQUIPMENT SCHEDULE ON P-401 AND
DETAIL 5 / P-501.
5. EX 4" SANITARY UP TO FLOOR DRAIN ON
FLOOR ABOVE.
6. NEW 4" DRAIN STANDPIPE IN MECHANICAL
ROOM OFF OF SANITARY RISER. TIE 2" VENT
INTO VENT RISER.
7. SEE EQUIPMENT SCHEDULE ON P-401 AND
DETAIL ON P-502.
9. PROVIDE A 303 STAINLESS STEEL BALANCING
VALVE WITH INTEGRATED UNION BODY, INLET
AND OUTLET BALL VALVES. HIGH TEMP
ACTUATOR FOR SANITARY FLUSHING
PROCESS DURING LEGIONELLA DISINFECTION.
LOW-TEMP ACTUATOR TO BE SET AT 130°F.
BLDG. 53 WEST
BLDG. 53 EAST
BLDG. 53 WEST
BLDG. 53 EAST
BLDG. 53 EAST
BLDG. 1C
B L
D G
C
B L
D G
E
A S
T
WALLS, ETC. BELOW
(DASHED), TYP.
EX 1 1/2"
EX 1/2"
BFP-2
BFP-4
4 52" V
4 54" SS 1
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
53-PP132
WLF / LLPDJR
THIRD FLOOR INTERSTITIAL
PLUMBING PLAN - EAST HALF
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
SYSTEM. PROVIDE SUBMITTAL TO COR FOR
APPROVAL
1. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
2. SEE EQUIPMENT SCHEDULE ON SHEET P-401
AND DETAIL 5 / P-501.
3. SEE EQUIPMENT SCHEDULE ON SHEET P-401
AND DETAIL 4 / P-501.
4. NEW 4" DRAIN STANDPIPE IN MECHANICAL
ROOM OFF OF SANITARY RISER. TIE 2" VENT
INTO VENT RISER.
5. SEE EQUIPMENT SCHEDULE ON P-401 AND
DETAIL ON P-502.
6. PROVIDE A 303 STAINLESS STEEL BALANCING
VALVE WITH INTEGRATED UNION BODY, INLET
AND OUTLET BALL VALVES. HIGH TEMP
ACTUATOR FOR SANITARY FLUSHING
PROCESS DURING LEGIONELLA DISINFECTION.
LOW-TEMP ACTUATOR TO BE SET AT 130°F.
7. SEE PLUMBING FIXTURE SCHEDULE ON SHEET
P-401 AND DETAIL 4/P-502
EX 1 1/4"
BLDG. 53 EAST
BLDG. 53 WEST
BLDG. 53 EAST
WALLS, ETC. BELOW
(DASHED), TYP.
BLDG. 53 EAST
BLDG. 53 WEST
1/2"
5 64" SS
5 62" V
5 6
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
53-PP141
WLF / LLPDJR
FOURTH FLOOR INTERSTITIAL
PLUMBING PLAN - WEST HALF
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
SYSTEM. PROVIDE SUBMITTAL TO COR FOR
APPROVAL
1. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
2. SEE EQUIPMENT SCHEDULE ON SHEET P-401
AND DETAIL ON P-501.
3. PROVIDE BATTERY POWERED ELECTRONIC
OPERATED SENSOR FAUCET WITH TIMER SET
TO FLUSH THE PIPING ONCE A DAY FOR 5
MINUTES. SEE PLUMBING FIXTURE SCHEDULE
ON P-401 AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
4. 4" SANITARY UP TO NEW FLOOR DRAIN ON
FLOOR ABOVE.
5. SEE EQUIPMENT SCHEDULE ON P-401 AND
DETAIL 5 / P-502.
6. NEW 4" DRAIN STANDPIPE IN MECHANICAL
ROOM OFF OF SANITARY RISER. TIE 2" VENT
INTO VENT RISER.
7. PROVIDE A 303 STAINLESS STEEL BALANCING
VALVE WITH INTEGRATED UNION BODY, INLET
AND OUTLET BALL VALVES. HIGH TEMP
ACTUATOR FOR SANITARY FLUSHING
PROCESS DURING LEGIONELLA DISINFECTION.
LOW-TEMP ACTUATOR TO BE SET AT 130°F.
EX 1 1/2"
EX 1/2"
EX 1/2"
EX 1/2"
EX 1/2"
EX 1/2"
EX 2"
EX 1/2"
EX 1 1/2"
EX 1 1/4"
EX 2"
EX 1 1/4"
EX 1"
EX 1 1/4"
EX 1"
EX 2"
EX 1/2"
EX 1/2"
EX 3/4"
EX 1"
EX 2"
EX 1/2"
EX 1 1/2"-DN
EX 1"
EX 1/2"
EX 3/4"
EX 1/2"
EX 3/4"
EX 1 1/4"
EX 1/2"
EX 3/4"
EX 1/2"
EX 3/4"
EX 1 1/4"
EX 1 1/4"
EX 1/2"
EX 1/2"
EX 1 1/2"
EX 3/4"
EX 1/2"
EX 2"
EX 1 1/2"
EX 1/2"
EX 1/2"
EX 1/2"
EX 1/2"
EX 1/2"
EX 1/2"
EX 1 1/2"
EX 1/2"
EX 1 1/2"
EX 2"
EX 3/4"
EX 3/4"
EX 1 1/2"
EX 2"
EX 1 1/4"
EX 3/4"
EX 1 1/4"
EX 3/4"
EX 1/2"
EX 1/2"
EX 1 1/2"
EX 2"
3" CRP VENT RISER
6" STORM RISER
6" SANITARY RISER
6" VENT RISER
EX CW, HW & HWR RISERS
6" STORM RISER
6" SANITARY RISER
6" VENT RISER
EX 1/2"
EX 1/2"
EX 1/2"
EX CW, HW &
EX 4" VENT RISER
EX 4" SP RISER
EX 1/2"
EX 1/2"
EX 1/2"
EX 1 1/4"
EX 1 1/4"
EX 1/2"
EX 1/2"
EX 1 1/2"
EX 2"
EX 1 1/2"
EX 3/4"
EX 1/2"
HWR RISERS
VALVES CLOSED
VALVES OFF
EX 2"
BFP-3
BFP-4
EX 3/4"
EX 2"
EX 1/2"
EX 1 1/4"
BLDG. 53 WEST
BLDG. 53 EAST
BLDG. 53 WEST
BLDG. 53 EAST
BLDG. 53 EAST
BLDG. 1C
B L
D G
C
B L
D G
E
A S
T
WALLS, ETC. BELOW
(DASHED), TYP.
BLDG. 53 EAST
BLDG. 53 WEST
EX 1/2"
EX 1/2"
EX 1/2"
EX 1/2"
EX 1/2"
EX 1/2"
6" SANITARY RISER
6" VENT RISER
EX HWS & HWR RISERS
EX CWS & CWR RISERS
EX 3"
EX (3")FD
EX 1 1/2"
6 5
5 6
2" V
6 54" SS 1
EX DHWR BALANCING VALVE
P-418F
P-418F
P-418F
P-418F
P-418F
P-418F
P80476
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
53-PP142
WLF / LLPDJR
FOURTH FLOOR INTERSTITIAL
PLUMBING PLAN - EAST HALF
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
SYSTEM. PROVIDE SUBMITTAL TO COR FOR
APPROVAL
1. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
2. SEE EQUIPMENT SCHEDULE ON SHEET P-401
AND DETAIL ON P-501.
3. PROVIDE BATTERY POWERED ELECTRONIC
OPERATED SENSOR FAUCET WITH TIMER SET
TO FLUSH THE PIPING ONCE A DAY FOR 5
MINUTES. SEE EQUIPMENT SCHEDULE ON
P-401 AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
4. NOTE NOT USED YET.
5. NEW 4" DRAIN STANDPIPE IN MECHANICAL
ROOM OFF OF SANITARY RISER. TIE 2" VENT
INTO VENT RISER.
6. SEE EQUIPMENT SCHEDULE ON SHEET P-401
AND DETAIL ON SHEET P-502.
7. PROVIDE A
" HW AND CW TO EACH HOSE BIB
FROM NEAREST HW AND CW OF EQUAL OR
LARGER SIZE PRIOR TO SERVING MOP BASIN
FAUCET CONNECTIONS.
BLDG. 53 WEST
BLDG. 53 EAST
BLDG. 53 EAST
BLDG. 53 WEST
TOTALIZER METER
1 11
10 12
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
53-PP151
WLF / LLPDJR
FIFTH FLOOR INTERSTITIAL
PLUMBING PLAN - WEST HALF
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
SYSTEM. PROVIDE SUBMITTAL TO COR FOR
APPROVAL
1. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
2. SEE EQUIPMENT SCHEDULE ON SHEET P-401.
3. PROVIDE BATTERY POWERED ELECTRONIC
OPERATED SENSOR FAUCET WITH TIMER SET
TO FLUSH THE PIPING ONCE A DAY FOR 5
MINUTES. SEE PLUMBING FIXTURE SCHEDULE
ON SHEET P-401 AND SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
4. SEE DETAIL ON SHEET P-501.
5. SEE DETAIL ON SHEET P-502.
6. NEW 4" DRAIN STANDPIPE IN MECHANICAL
ROOM OFF OF SANITARY RISER. TIE 2" VENT
INTO VENT RISER.
7. PROVIDE A 303 STAINLESS STEEL BALANCING
VALVE WITH INTEGRATED UNION BODY, INLET
AND OUTLET BALL VALVES. HIGH TEMP
ACTUATOR FOR SANITARY FLUSHING
PROCESS DURING LEGIONELLA DISINFECTION.
LOW-TEMP ACTUATOR TO BE SET AT 130°F.
8. PROVIDE DOMESTIC HOT WATER
TEMPERATURE SENSING STATION ON THE
130°F, 140°F, AND HOT WATER RETURN
RISERS. WIRED BACK TO WQMP-1.
9. PROVIDE OXIDANT RESIDUAL MONITOR
STATION WIRED BACK TO WQMP-1.
10. ROUTE DRAIN LINE TO NEW HUB DRAIN IN 5TH
FLOOR EAST MECHANICAL ROOM.
11. PROVIDE A NEW PULSE METER INTEGRATED
DIRECTLY TO THE NIAGARA GUI. SEE SHEET
PS-102 FOR ADDITIONAL INFORMATION.
12. PROVIDE 120V DIRECT CONNECTION TO NEW
WATER MONITORING TEST STATION (700W).
EXTEND NEAREST NORMAL POWER
RECEPTACLE CIRCUIT TO LOCATION AND
CONNECT. COORDINATE EXACT LOCATION
AND REQUIREMENTS WITH PLUMBING
CONTRACTOR.
13. CONNECT TO 120V POWER SOURCE AT J-BOX
USING 2-12AWG, 12AWG EG IN 3/4" C.
BLDG. 53 WEST
BLDG. 53 EAST
BLDG. 53 EAST
BLDG. 1C
B L
D G
C
B L
D G
E
A S
T
BLDG. 53 EAST
BLDG. 53 WEST
UP TO HOSE BIBB
ABOVE
1/2" 1/2"
1/2"
1/2"
TOTALIZER METER
BFP-1 @ 4'-0" A.F.F.
2 4
PRV-1
4" STANDPIPE
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
53-PP152
WLF / LLPDJR
FIFTH FLOOR INTERSTITIAL
PLUMBING PLAN - EAST HALF
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
SYSTEM. PROVIDE SUBMITTAL TO COR FOR
APPROVAL
1. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
2. SEE EQUIPMENT OR FIXTURE SCHEDULE ON
SHEET P-401.
3. PROVIDE NEW SENSOR FAUCET P-418-F ON
LAVATORY OR SINK ON FLOOR BELOW
INTERSTITIAL LEVEL. SET TIMER TO FLUSH
THE PIPING ONCE A DAY FOR 5 MINUTES. SEE
SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
4. SEE DETAIL ON SHEET P-501.
5. SEE DETAIL ON SHEET P-502.
6. PROVIDE TWO (2) NEW HOSE BIBBS P-804 AT
MOP SERVICE BASE FOR FLOOR MACHINE
CONNECTION.
7. NEW 4" DRAIN STANDPIPE IN MECHANICAL
ROOM OFF OF SANITARY RISER. TIE 2" VENT
INTO VENT RISER.
8. PROVIDE A NEW PULSE METER INTEGRATED
DIRECTLY TO THE NIAGARA GUI. SEE SHEET
PS-102 FOR ADDITIONAL INFORMATION.
9. PROVIDE STRAINER, ISOLATION VALVES AND
FULL LINE SIZE BY-PASS AT NEW METER.
10. PROVIDE 120V DIRECT CONNECTION TO NEW
WATER MONITORING TEST STATION (700W).
EXTEND NEAREST NORMAL POWER
RECEPTACLE CIRCUIT TO LOCATION AND
CONNECT. COORDINATE EXACT LOCATION
AND REQUIREMENTS WITH PLUMBING
CONTRACTOR.
11. CONNECT TO 120V POWER SOURCE AT J-BOX
1 1
1 1
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
FULLY SPRINKLERED 58-P-101
WLF/LLPDJR
PLUMBING PLANS
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
SYSTEM. PROVIDE SUBMITTAL TO COR FOR
APPROVAL
1. SEE DRAWING PS101 FOR CONTINUATION.
2. REMOVE EXISTING PIPING AND ACCESSORIES
COMPLETE. PREPARE EXISTING PIPING TO
REMAIN TO ACCOMMODATE NEW EQUIPMENT
TO BE INSTALLED. EXISTING BOOSTER PUMP
TO BE REMOVED AND NEW PUMP INSTALLED
WITHIN FOUR HOURS. COORDINATE AND
RECEIVE APPROVAL TWO WEEKS PRIOR TO
START OF WORK.
3. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
4. SEE EQUIPMENT SCHEDULE ON SHEET P-401.
5. SKID CONTROL PANEL. SEE P-602
6. A SIEMENS FACTORY TRAINED AND CERTIFIED
TECHNICIAN SHALL INSTALL A NEW 8"
SITRANS WATER METER AND CONTROLLER.
TL SERVICES SHALL MAP THE NEW METER TO
THE EXISTING SITRANS SYSTEM.
7. ROUTE
" DRAIN LINE TO NEAREST FLOOR
DRAIN WITH AIR GAP AND A
" COPPER LINE
TO THE INCOMING CITY WATER SERVICE LINE.
8. PROVIDE 120V DIRECT CONNECTION TO NEW
WATER MONITORING TEST STATION (700W)
FROM EXISTING RECEPTACLE CIRCUIT AS
INDICATED. COORDINATE EXACT LOCATION
AND REQUIREMENTS WITH PLUMBING
CONTRACTOR.
9. APPROXIMATE LOCATION OF EXISTING 200A
WALL MOUNTED DISCONNECT SERVING PUMP
SKID. REWORK LOAD SIDE FEEDER AS NOTED
TO RECONNECT NEW PUMP SKID.
10. APPROXIMATE ROUTING OF EXISTING
(3-3/0AWG, 6AWG EG IN 2 INCH CONDUIT)
FEEDER SERVING PUMP SKID FROM WALL
MOUNTED DISCONNECT SWITCH AS
INDICATED. PROVIDE NEW FEEDER (3-3/0AWG,
6AWG EG IN 1-1/2 INCH CONDUIT) FROM
EXISTING DISCONNECT SWITCH TO NEW PUMP
CONTROLLER. COORDINATE EXACT
REQUIREMENTS WITH PLUMBING
CONTRACTOR.
11. DISCONNECT EXISTING PUMP SKID
CONTROLLER AND REMOVE EXISTING
FEEDER. CONNECT NEW PUMP SKID
CONTROLLER TO EXISTING DISCONNECT
SWITCH USING NEW FEEDER AS NOTED
ABOVE. COORDINATE WITH PLUMBING
CONTRACTOR.
12. CONNECT TO 120V POWER SOURCE AT J-BOX
| 2018-03-29T13:34:33-0700 | |
| DocuSign, Inc. | |
| Digitally verifiable PDF exported from www.docusign.com |
File details come from the government source that posted it.