36C25918R0592-015.pdf
PDF 4 MB Posted
- Attached to
- Upgrade Site Water Systems (VA-18-00071315)
- Solicitation number
- 36C25918R0592
About this file
36C25918R0592 Water Drawings Part1.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25918C0325-000.docx | DOCX document | |
| 36C25918R0592-0002003.pdf | ||
| 36C25918R0592-0002002.pdf | ||
| 36C25918R0592-0002000.docx | DOCX document | |
| 36C25918R0592-0002001.pdf | ||
| 36C25918R0592-0001000.docx | DOCX document | |
| 36C25918R0592-020.docx | DOCX document | |
| 36C25918R0592-012.docx | DOCX document | |
| 36C25918R0592-014.pdf | ||
| 36C25918R0592-017.pdf | ||
| 36C25918R0592-019.docx | DOCX document | |
| 36C25918R0592-013.docx | DOCX document | |
| 36C25918R0592-024.pdf | ||
| 36C25918R0592-021.pdf | ||
| 36C25918R0592-023.pdf | ||
| 36C25918R0592-018.pdf | ||
| 36C25918R0592-022.pdf | ||
| 36C25918R0592-016.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURE ENGINEERING CONSTRUCTION
PROJECT NUMBER 623-16-113
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
GENERAL NOTES
VA PROJECT TEAM
OWNER: OWNER'S CONTRACTING OFFICER:
INDEX OF DRAWINGS
DRAWING TITLEDWG NO.
GENERAL INFORMATION OF
SHEET OF #
ABBREVIATIONS
GI001
PHASING
GENERAL
1 43
SITE PLAN
OF2
OF 3
OF18
PS101
PLUMBING
PLUMBING SITE PLAN
P-001 PLUMBING AND ELECTRICAL SYMBOLS AND NOTES
52-PP101 PLUMBING PLANS
GI001
WLFDJR, JAV
GENERAL INFORMATION
NORTH
52-PD101 PLUMBING DEMOLITION PLANS
OF19
OF4
18-PD101 PLUMBING DEMOLITION PLANS
18-PP101
OF5
PLUMBING PLANS
OF14
22-P-101 SUB-BASEMENT PLUMBING PLANS
OF15
OF16
24-PD101 SUB-BASEMENT PLUMBING DEMOLITION PLAN
OF17
24-PP101 SUB-BASEMENT PLUMBING PLAN
OF10
1C-PD101 CRAWL SPACE PLUMBING DEMOLITION PLAN
OF11
1C-PD131 THIRD FLOOR FLOOR PLUMBING DEMOLITION PLAN
OF12
1C-PP101 CRAWL SPACE PLUMBING PLAN
OF13
1C-PP131 THIRD FLOOR FLOOR PLUMBING PLAN
OF6
1AB-PD111 FIRST FLOOR PLUMBING DEMOLITION PLAN
OF7
OF8
1AB-PP111 FIRST FLOOR PLUMBING PLAN
OF
OF21
OF20
53-PD100 SUB-BASEMENT PLUMBING DEMOLITION PLAN
OF
53-PD101
OF22
BASEMENT MEZZANINE PLUMBING DEMOLITION PLAN
OF23 43
OF24 43
OF25 43
SECOND FLOOR INTERSTITIAL PLUMBING DEMOLITION PLAN - WEST HALF
THIRD FLOOR INTERSTITIAL PLUMBING DEMOLITION PLAN - WEST HALF
FOURTH FLOOR INTERSTITIAL PLUMBING DEMOLITION PLAN - WEST HALF
FOURTH FLOOR INTERSTITIAL PLUMBING DEMOLITION PLAN - EAST HALF
FIFTH FLOOR INTERSTITIAL PLUMBING DEMOLITION PLAN - WEST HALF
OF39 43
OF40 43
P-401
PLUMBING EQUIPMENT AND FIXTURE SCHEDULES
OF41 43
53-PD121
53-PD122
53-PD131
53-PD132
SECOND FLOOR INTERSTITIAL PLUMBING DEMOLITION PLAN - EAST HALF
THIRD FLOOR INTERSTITIAL PLUMBING DEMOLITION PLAN - EAST HALF
53-PD141
53-PD142
53-PD151
53-PD152 FIFTH FLOOR INTERSTITIAL PLUMBING DEMOLITION PLAN - EAST HALF
OF26 43
OF27 43
OF28 43
OF29 43
OF30 43
OF31 43
OF32 43
OF33 43
OF34 43
OF35 43
OF36 43
OF37 43
OF38 43
OF9
BUILDING 1AB
BUILDING 18
BUILDING 1C
BUILDING 22
BUILDING 24
BUILDING 52
BUILDING 53
53-PP100 SUB-BASEMENT PLUMBING PLAN
53-PP101 BASEMENT MEZZANINE PLUMBING PLAN
SECOND FLOOR INTERSTITIAL PLUMBING PLAN - WEST HALF
THIRD FLOOR INTERSTITIAL PLUMBING PLAN - WEST HALF
FOURTH FLOOR INTERSTITIAL PLUMBING PLAN - WEST HALF
FOURTH FLOOR INTERSTITIAL PLUMBING PLAN - EAST HALF
FIFTH FLOOR INTERSTITIAL PLUMBING PLAN - WEST HALF
53-PP121
53-PP122
53-PP131
53-PP132
SECOND FLOOR INTERSTITIAL PLUMBING PLAN - EAST HALF
THIRD FLOOR INTERSTITIAL PLUMBING PLAN - EAST HALF
53-PP141
53-PP142
53-PP151
53-PP152 FIFTH FLOOR INTERSTITIAL PLUMBING PLAN - EAST HALF
58-P-101 PLUMBING PLANS
BUILDING 58
GENERAL
SIGNATURE BLOCK
P-501 PLUMBING DETAILS
OF
P-601 PLUMBING CONTROLS
PS102 PLUMBING CONTROLS SITE PLAN
OF 43
P-602 INSTRUMENTATION DETAILS
P-502 PLUMBING DETAILS
S
ELECTRICAL LEGEND
JUNCTION BOX, PURPOSE AS NOTED
JUNCTION BOX IN WALL, PURPOSE AS NOTED:
18" AFF STANDARD UNO
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SWITCH: 44" AFF STANDARD UNO
SWITCH MODIFIERS:
M - MOTOR RATED
3 - THREE-WAY
T - DIGITAL TIMER SWITCH
PANELBOARD
VARIABLE FREQUENCY DRIVE, PROVIDED BY MECHANICAL
CONTRACTOR
EQUIPMENT ELECTRICAL CONNECTION
HOMERUN - 120V OR 277V
HOMERUN - 208V OR 480V
120V DUPLEX RECEPTACLE: 18" AFF STANDARD, UNO
RECEPTACLE MODIFIERS:
GFCI - GROUND FAULT CIRCUIT INTERRUPTER
WP - WEATHERPROOF
DED - DEDICATED
TELEPHONE OUTLET
KIRK-KEY MANUAL INTERLOCK
CABLE TRAY
CONNECTION POINT FOR NEW TO EXISTING
CONDUIT, CABLE TRAY, JUNCTION BOXES ETC.
POINT OF DEMOLITION FOR EXISTING
CONDUIT, CABLE TRAY, JUNCTION BOXES ETC.
UNDERGROUND ELECTRICALUGE
POWER METER/MONITOR
CONTACTOR OR MOTOR STARTER
FIRE SYSTEM SMOKE DETECTOR AS INDICATED
LOAD BREAK JUNCTION
DELTA
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY
CONTROL, OR AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP OR A AMPERE
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BFG BELOW FINISH GRADE
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CATV COMMUNITY ANTENNA TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
D DEEP / DEPTH
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX, EXIST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
FMC FLEXIBLE METALLIC CONDUIT
FP FIRE PROTECTION
FT FEET OR FOOT
FS FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GRS GALVANIZED RIGID STEEL
GTB GROUND TERMINAL BOX
H HIGH / HEIGHT
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT OR MICROWAVE
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR PUSHBUTTON
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POS POSITION
PRI, PRIM PRIMARY
PVC POLYVINYL CHLORIDE (PLASTIC)
REC RECESSED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SEC SECONDARY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
ELECTRICAL ABBREVIATION
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT OR WIDTH IN DIMENSION STRING
WH WATER HEATER
WP WEATHERPROOF
WQMP WATER QUALITY MONITORING PANEL
XFER TRANSFER
XFMRTRANSFORMER
P-001
WLFDJR
PLUMBING AND ELECTRICAL
SYMBOLS AND NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
NORTH
EXISTING 8" CITY
WATER METER IN
PIT
EXISTING 8" WATER LOOP
EXISTING 8" HIGH PRESSURE (60 PSI)
CITY WATER SERVICE (BACK-UP
SERVICE LINE).
EXISTING 8" LOW PRESSURE (730 GPM @
20 PSI) CITY WATER SERVICE FROM 24"
CITY MAIN SERVING HOSPITAL.
EXISTING 8" PRV IN PIT
(VALVED OFF) TO BE
REMOVED - SEE DETAIL
THIS SHEET
6"
6"
6"
NEW FIRE HYDRANT
EXISTING 8" WATER LOOP
6"
6"
3"
EXISTING 8" WATER LOOP
EXISTING 8" WATER
SERVICE FROM METER PIT
EXISTING 8" WATER LOOP
EXISTING
WATER
SERVICES
EXISTING
WATER
SERVICES
EXISTING FDC
NEW 2" BRANCH
2"
EXISTING 8" WATER LOOP
4"
EXISTING FDC
EXISTING FDC
EXISTING
FDC
6"
EXISTING FIRE HYDRANT
EXISTING
FIRE
HYDRANT
EXISTING
FIRE
HYDRANT
EXISTING
FDC
EXISTING 8" TO WATER TOWER
EXISTING
8" WATER
LOOP
EXISTING
WATER SERVICE
TO BUILDINGS
22 & 24
EXISTING FDC
EXISTING FIRE HYDRANT
EXISTING FDC
EXISTING FDC
EXISTING FDC
EXISTING FDC
EXISTING FIRE HYDRANT
EXISTING FIRE HYDRANT
EXISTING FIRE HYDRANT
EXISTING FIRE HYDRANT
EXISTING 8" WATER LOOP
EXISTING 4" CURB STOP
VALVE TO BE REPLACED
EXISTING
FDC
4"
EXISTING 1" IRRIGATION
METER IN PIT
EXISTING 1" ANTI-
SIPHON PRESSURE
VACUUM BREAKER
EXISTING FIRE
SERVICE PIV
NC
NO
2"
EXISTING
PIV
EXISTING PIV
EXISTING PIV
EXISTING 2"
SERVICE
EX 8" WATER LOOPEX 8" WATER LOOP EX VAULT
REPLACE EXISTING PRV, ETC.
WITH A NEW SECTION OF 8"
DIAMETER STRAIGHT PIPE
NO
NC - BYPASS VALVES TO
BE NORMALLY OPEN (NO)
AFTER REPLACEMENT OF
PRV WITH STRAIGHT PIPE
NC - BYPASS VALVES TO
BE NORMALLY OPEN (NO)
AFTER REPLACEMENT OF
PRV WITH STRAIGHT PIPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
1. EXISTING PLUMBING WORK TO REMAIN AS IS.
2. EXISTING PLUMBING WORK TO BE CAPPED
AND ABANDONED IN PLACE. PATCH
PAVEMENT, CURB, LANDSCAPING, ETC. AS
REQUIRED TO MATCH ADJACENT AREA
3. EXISTING DOMESTIC WATER SERVICE
ENTRANCE, SIZE AS NOTED.
4. EXISTING FIRE PROTECTION SERVICE
ENTRANCE, SIZE AS NOTED.
5. NEW DOMESTIC WATER SERVICE ENTRANCE,
SIZE AS NOTED.
6. NEW FIRE PROTECTION SERVICE LINE TO
EXISTING P.I.V BEING INSTALLED UNDER A
SEPARATE CONTRACT, NOT PART OF THIS
WORK.THIS CONTRACTOR TO PROVIDE NEW
6" LINE FROM P.I.V. TO FIRE PROTECTION
SERVICE FLANGE INSIDE BUILDING 6" A.F.F.
7. NEW DOMESTIC WATER SERVICE ENTRANCE
BEING INSTALLED UNDER A SEPARATE
CONTRACT, NOT PART OF THIS WORK.
8. EXISTING IRRIGATION WATER METER PIT TO
BE REWORKED TO PROVIDE A NEW WATER
METER WIRED TO THE BUILDING BMS.
9. INSTALL A 2" DRAIN LINE FROM INSIDE WATER
METER PIT SUMP AREA THRU PIT WALL WITH
PIPE SLEEVE, ROUTED BELOW GRADE 24" TO
RETAINING BLOCK WALL. TERMINATE DRAIN
LINE 6" ABOVE SIDEWALK DIRECTING FLOW TO
AREA DRAIN.
10. CURB STOP SERVING UNKNOWN PIPING -
SHOWN FOR REFERENCE ONLY.
11. NEW FIRE HYDRANT. CONNECT NEW 6" F TO
EXISTING 8" MAIN WITH CURB STOP VALVE.
12. PROVIDE 120V DIRECT CONNECTION TO NEW
WATER MONITORING TEST STATION (700W)
FROM EXISTING RECEPTACLE CIRCUIT WITHIN
BUILDING AT BASE OF WATER TOWER
(REPURPOSED ANTENNA EQUIPMENT
BUILDING). COORDINATE EXACT LOCATION
AND REQUIREMENTS WITH PLUMBING
CONTRACTOR.
13. INSTALL REMOTE CONTROL PANEL. CONNECT
TO EXISTING SIGNAL WIRING. SEE 00-EI501.
14. SKID CONTROL PANEL, CONNECT WITH
EXISTING SIGNAL WIRING. SEE 00-EI501.
SITE
PS101
WLFDJR
PLUMBING SITE PLAN
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
SYSTEM. PROVIDE SUBMITTAL TO COR FOR
APPROVAL
NEW PULSE METER FOR HEATING
WATER MAKE-UP WIRED TO BAS IN
5TH FLOOR INTERSTITIAL SPACE
NEW PULSE METER FOR CHILLED
WATER MAKE-UP WIRED TO BAS IN
5TH FLOOR INTERSTITIAL SPACE
NEW SITRANS WATER METER AND
WQMP-2. SEE SHEET 58-PP101 FOR
LOCATION.
NEW PULSE METER ON HEATING WATER MAKE-UP
PIPE, WIRED TO BAS
NEW PULSE METER ON HEATING WATER
MAKE-UP PIPE, WIRED TO BAS IN
CRAWLSPACE
NEW PULSE METER ON CHILLED WATER MAKE-UP
PIPE, WIRED TO BAS IN 4TH FLOOR PENTHOUSE
EXISTING SITRANS
DOMESTIC WATER METER
NEW PULSE METER ON HEATING WATER
MAKE-UP WATER PIPE, WIRED TO BAS IN
1B03-1
RELOCATED DOMESTIC WATER METER IN HOT WATER
TANK ROOM (1B03-1). METER WILL MONITOR DOMESTIC
COLD WATER FOR ALL OF BUILDING 1A & 1B.
NEW TOTALIZER IRRIGATION WATER METER
IN EXISTING PIT. RUN WIRING INTO HOT
WATER TANK ROOM (1B03-1) AND
CONNECTED TO NEW JACE AND BMS
EXISTING RELOCATED
DOMESTIC WATER METER
EXISTING SITRANS DOMESTIC
WATER METER LOCATED IN THE
SUB-BASEMENT
EXISTING SITRANS WATER METER
FOR BOILER WATER MAKE-UP IN
BASEMENT CORRIDOR (B15-18)
NEW SITRANS WATER METER SERVING BLDG 1C COLD
WATER, WIRED TO BAS
NEW PULSE METER ON HEATING
WATER M/V IN INTERSTITIAL 3COL-1
NEW PULSE METER ADD HEATING
WATER MAKE-UP METER, SB02-22
MOVE PROBES TO BLDG 18 INLET
DOM. WATER
WQMP-1 WQMP-1
WQMP-1
EXISTING SITRANS WATER
METER RADIO TRANSMITTER
LOCATED IN 1B PENTHOUSE
EXISTING SITRANS DOMESTIC WATER METER ON 1ST
FLOOR
EXISTING PULSE METER FOR CHILLED WATER
MAKE-UP, CONNECT TO BMS
EXISTING SITRANS COOLING TOWER MAKEUP WATER
METER CONTROLLER
NEW PULSE METER ON HEATING WATER MAKE-UP
METER B6-24
EXISTING UTILITY COMPANY
CAMPUS WATER METER IN PIT
WATER TOWER LEVEL AND PUMP
CONTROLS STAND ALONE
CONTROL SYSTEM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
1. WATER QUALITY MONITORING PANELS FOR
DOMESTIC COLD, HOT AND HOT WATER
RETURN IN THIS LOCATION ON THE EAST AND
WEST SIDES OF THE 5TH FLOOR INTERSTITIAL
SPACE. REFER TO DETAILS 1 & 2 ON SHEET
P-601 FOR CONNECTIVITY REQUIREMENTS.
2. QUADRUPLEX BOOSTER PUMP AND WATER
QUALITY MONITORING PANEL IN THIS BUILDING.
3. TRI-PLEX BOOSTER PUMP AND THERMOSTATIC
MIXING VALVE IN THIS LOCATION IN THE
SWITCH GEAR ROOM (101-52) ON THE 1ST
FLOOR.
4. THERMOSTATIC MIXING VALVE AND WATER
QUALITY MONITORING PANEL IN THIS LOCATION
IN THE INTERSTITIAL EQUIPMENT ROOM
(3C01-1) ON THE 3RD FLOOR. THERMOSTATIC
MIXING VALVE LOCATED IN THE CRAWLSPACE
WATER HEATER ROOM (ALCOVE).
5. THERMOSTATIC MIXING VALVE, HOT WATER
RECIRC PUMP AND HOT WATER HEAT
EXCHANGER IN THIS LOCATION IN THE HW
TANK ROOM (1B03-1) ON THE 1ST FLOOR.
6 WATER QUALITY MONITORING PANEL FOR THE
WATER TOWER LOCATED IN THE BOILER ROOM
(SB01-18). REFER TO DETAILS 1 & 2 ON SHEET
P-601 FOR CONNECTIVITY REQUIREMENTS.
7. WATER QUALITY ENGINEER CONTRACTOR
PROVIDED COMPUTER STATION LOCATED IN
OFFICE (13C1A1-18).
8. THERMOSTATIC MIXING VALVE LOCATED IN
SUB-BASEMENT MECHANICAL ROOM.
9. THERMOSTATIC MIXING VALVE IN BASEMENT
MECHANICAL ROOM (B10-18).
10. WATER QUALITY MONITORING PANEL FOR
DOMESTIC WATER CONDITIONS FROM CITY
WATER SUPPLY. REFER TO DETAILS 1 & 2 ON
SHEET P-601 FOR CONNECTIVITY
REQUIREMENTS.
11. WATER QUALITY MONITORING PANEL FOR
DOMESTIC COLD, HOT AND HOT WATER
RETURN WATER SERVICE CONDITIONS ON THE
3RD FLOOR INTERSTITIAL EQUIPMENT ROOM
3C01-1. REFER TO DETAILS 1 & 2 ON SHEET
P-601 FOR CONNECTIVITY REQUIREMENTS.
12. WATER QUALITY MONITORING PANEL FOR
DOMESTIC COLD WATER SUPPLY CONDITIONS
FROM THE WATER TOWER. REFER TO DETAILS
1 & 2 ON SHEET P-601 FOR CONNECTIVITY
REQUIREMENTS.
13. PLUMBING SHOP CONTRACTOR PROVIDED
COMPUTER STATION LOCATED IN OFFICE
(B08-18-18). COMPUTER STATION TO DISPLAY
THE WATER QUALITY CONTROL PANELS
AND THERMOSTATIC MIXING VALVE STATION
DATA.
14. THERMOSTATIC MIXING VALVE STATION
LOCATED IN THE BASEMENT / CRAWL SPACE OF
BUILDING 1C.
15. THERMOSTATIC MIXING VALVE STATION
LOCATED ON THE FIRST FLOOR OF BUILDING
52 NEXT TO THE EXISTING DOMESTIC WATER
HEATERS.
16. WATER TOWER LEVEL AND PUMP CONTROL
STAND ALONE SYSTEM INTEGRATED WITH
CONTROL PANEL IN BUILDING 58.
17. WATER TOWER LEVEL AND PUMP CONTROL
STAND ALONE SYSTEM INTEGRATED WITH
CONTROL PANEL IN BUILDING 18.
18. PATIENT TOWER LEVEL AND PUMP CONTROLS
SHALL BE A STAND ALONE SYSTEM.
SITE
PS102
WLFDJR
PLUMBING CONTROLS SITE PLAN
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
SYSTEM. PROVIDE SUBMITTAL TO COR FOR
APPROVAL
1. CONTACT TL SERVICES JOHN SIDES 479-719-7631 FOR REPAIR/RECONFIG OF EXISTING
SITRANS WATER METER INTERFACES AND EXISTING INTEGRATION TO ABS NIAGARA
AX INTERFACE. ALL JACK POINTS WILL BE REINTEGRATED TO NIAGARA AX.
2. ALL NEW METERS SHALL BE INTEGRATE TO ABS NIAGARA AX INTERFACE DIRECTLY.
CONTACT AUTOMATED BUILDING SYSTEMS JOEL KARSTETTER @ 918-665-3974.
3. ALL WATER QUALITY MONITORING SHALL BE PLACED ON THE ENGINEERING NETWORK
WITH THE ENTERPRISE SOFTWARE INSTALLED ON A CONTRACTOR PROVIDED PC IN
ROOM 13C1A1-18 AND THE PLUMBING FOREMAN'S SHOP ROOM B06-18
4. ALL EXISTING SITRANS WATER METERS SHALL HAVE PROPER SETUP VERIFIED BY A
FACTORY AUTHORIZED SIEMENS INSTALLER. ALL NEW SITRANS METERS (TO MATCH
EXISTING METERS) SHALL BE INSTALLED BY A FACTORY AUTHORIZED SIEMENS
INSTALLER.
5. ALL BUILDING WATER METERS SHALL TOTALIZE AND COMPARE TO SITE WATER METER
ON NIAGARA AX ENTERPRISE SERVER GRAPHICS.
5.1. AVERAGE FLOW
5.2. CURRENT FLOW
5.3. TOTAL FLOW
6. FOR INTEGRATION, PROGRAMMING AND PRICING OF ALL EQUIPMENT TO BE
CONNECTED TO THE BAS CONTACT:
JOEL KARSETER
AUTOMATED BUILDING SYSTEMS - TULSA, INC.
918-665-3974
JKARSTETTER@ABSCOMPANIES.COM
EX FDC
EX FDC (ABANDONED?)
EX FDC
B L
D G
A B
B L
D G
C
BLDG. 1AB
BLDG. 1E
BLDG. 1E
B L
D G
A B
B L
D G
C
F
EX DOM WATER HEATER
EX 4" DOM WATER
SERVICE - UP & DN
EX 4"
EX 4" DOM WATER
SERVICE IN HW TANK
ROOM CRAWL SPACE
EX HVAC HOT WATER
HEX TO REMAIN
EX 4" WATER SERVICE
TO BUILDING
EX 1" HWR FROM SPS
EX 3"
13 13
1AB
1AB-PD111
WLF / LLPDJR
FIRST FLOOR PLUMBING
DEMOLITION PLAN
1. EXISTING DOMESTIC SERVICE, VALVING AND
WATER METERS TO BE REMOVED AND OR
REWORKED AS REQUIRED TO ACCOMMODATE
NEW WATER SERVICE ENTRANCE INTO ROOM,
BACKFLOW PREVENTORS AND REPAIR OF THE
WATER METER SYSTEM.
2. REMOVE EXISTING DOMESTIC WATER
HEATER, PIPING AND ASSOCIATED
ACCESSORIES COMPLETE. PREPARE PIPING
TO REMAIN TO ACCOMMODATE INSTALLATION
OF NEW EQUIPMENT.
3. WATER HEATER IS TO BE REMOVED AND NEW
INSTALLED WITHIN FOUR HOURS COORDINATE
WITH COR TWO WEEKS PRIOR TO START OF
WORK.
4. EXISTING 4" DOMESTIC COLD WATER SERVICE
LOCATED IN CRAWL SPACE TO REMAIN AS IS.
EXACT PATH HAS NOT BEEN VERIFIED.
5. EXISTING SITRANS THREE CHANNEL METER
CONTROLLER.
6. EXISTING HOT WATER RE-CIRCULATION PUMP
TO REMAIN.
7. EXISTING 3" HW AND 1" HWR LINES DOWN TO
CRAWL SPACE. (C-WING BY PASS N.C.)
8. REMOVE EXISTING PIPE FITTINGS, VALVES,
AND SUPPORTS COMPLETELY. PATCH FLOOR
AT EXISTING 4" CW SERVICE ENTRANCE TO
MATCH EXISTING FLOOR FIRE RATING.
9. REMOVE EXISTING HEATING WATER MAKE UP
PIPING AND ACCESSORIES COMPLETE.
PREPARE 1" CW PIPING TO REMAIN TO
ACCOMMODATE NEW EQUIPMENT. SEE SHEET
1-PP111 FOR ADDITIONAL INFORMATION.
10. EXISTING 4" CW, 3" HW, 1
" HWR, 1
" CW AND
" HW PIPING UP IN CHASE.
11. EXISTING SITRANS METER ON EXISTING 4"
DCW LINE TO BE REMOVED AND STORED FOR
RELOCATION. CONTRACTOR IS RESPONSIBLE
FOR ANY DAMAGE AND ASSOCIATED COSTS
FOR REPAIRS.
12. EXISTING SITRANS METER ON EXISTING 3"
DHW LINE TO BE REMOVED AND STORED FOR
RELOCATION. CONTRACTOR IS RESPONSIBLE
FOR ANY DAMAGE AND ASSOCIATED COSTS
FOR REPAIRS.
13. REMOVE EXISTING 2
" GAS PIPING STUBBED
AND CAPPED AT 36" A.F.F. TO BELOW SLAB
CAPPED. PATCH FLOOR TO MATCH EXISTING
AND EXISTING RATING OF FLOOR ASSEMBLY.
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
EX FDC
EX FDC (ABANDONED?)
EX FDC
B L
D G
A B
B L
D G
C
BLDG. 1AB
BLDG. 1E
BLDG. 1E
B L
D G
A B
B L
D G
C
F
EX 4"
EX 4" WATER SERVICE
TO BUILDING
EX 3" HW
EX 4"
EX 1 1/2" HWR
EX 3" HW
EX 1 1/2"
EX 4" CW
EX 3" HW
EX 1"
EX 3"
EX 1 1/2"
EX 1" HWR FROM SPSEX 4" CW-UP
HWR
EX 3"
F
DHWH-1
BFP-7 X (2)
4"
TMV-2
EX HVAC HOT
WATER HEAT
EXCHANGER
WATER METER
SENSOR
EX FIRE PROTECTION
RISER AND ALARMED
CHECK VALVE TO REMAIN
7 8
EX HWRP
EX 3" HW
EX 4"
EX 1 1/2" HWR
EX 3" HW
EX 1 1/2"
EX 4" CW
EX 3" HW
EX 1"
EX 3"
EX 1 1/2"
EX 1" HWR FROM SPS
EX 1"HWR & 3"HW-DN
(C WING BY-PASS) NC
EX 4" CW-UP
HWR
EX 3"
BFP-1
FRV-1
1"
EX 4"
BELOW GRADE
1AB
1AB-PP111
WLF / LLPDJR
FIRST FLOOR PLUMBING PLAN
1. CUT EXISTING FLOOR SLAB AS REQUIRED TO
CONNECT TO EXISTING GALVANIZED DOMESTIC
WATER SERVICE LINE BELOW IN CRAWL SPACE.
PATCH FLOOR TO MATCH EXISTING ROOM
RATING.
2. EXISTING WATER RISER TO BE REWORKED AS
REQUIRED TO ACCOMMODATE NEW WATER
SERVICE LOCATION AND ACCESSORIES.
3. CONNECT NEW DOMESTIC WATER HEATER TO
EXISTING DOMESTIC WATER AND STEAM PIPING.
NEW DOMESTIC WATER HEATER REPLACEMENT
NOT TO EXCEED FOUR HOURS AND SHALL BE
SCHEDULE WITH COR TWO WEEKS PRIOR TO
START OF WORK.
4. EXISTING 4" DOMESTIC COLD WATER SERVICE
LOCATED IN CRAWL SPACE TO REMAIN AS IS.
EXACT PATH HAS NOT BEEN VERIFIED.
5. A SIEMENS FACTORY TRAINED AND CERTIFIED
TECHNICIAN SHALL RELOCATE THE EXISTING
SITRANS WATER METER. PROVIDE ALL WIRING,
CONDUITS, FITTINGS AND HARDWARE
NECESSARY TO CONNECT METER TO BUILDING
AUTOMATION SYSTEM. CONTRACTOR MUST
INTEGRATE FUNCTIONALITY WITH AUTOMATED
BUILDING SYSTEMS - TULSA, INC., THE CURRENT
BUILDING AUTOMATION PROVIDER FOR THE
FACILITY. CONTACT JOEL KARSETTER -
918-665-3974, JKARSETTER@
ABSCOMPANIES.COM. BUILDING
AUTOMATION SYSTEM TO BE PROGRAMMED TO
LOG THE FOLLOWING DATA AND DISPLAY THE
DATA ON THE VA ACCESSIBLE BUILDING
AUTOMATION INTERFACE:
5.1. CURRENT FLOW RATE IN GALLONS PER MINUTE
(GPM).
5.2. AVERAGE FLOW AT DAILY, MONTHLY AND
YEARLY INTERVALS.
5.3. COMPARISON OF TOTAL FLOW OF BRANCH
METERS TO THE TOTAL OF ANY METERS
FEEDING THE BRANCH OVER HOURLY,
DAILY AND MONTHLY INTERVALS.
6. EXISTING 4" CW, 3" HW, 1
" HWR, 1
" CW, AND 1
" HW PIPING UP IN CHASE.
7. EXISTING SITRANS METER CONTROLLER
8. TL SERVICES TO REMAP ALL POINTS
CURRENTLY CONNECTED TO THE SITRANS
SYSTEM.
9. SEE DETAILS 7/P-502 AND 8/P-502 FOR
INSTALLATION OF THERMOSTATIC MIXING
VALVE STATION AND WATER HEATER.
10. PROVIDE A PULSE METER INTEGRATED
DIRECTLY TO NIAGARA AX GUI. SEE SHEET
PS102 FOR ADDITIONAL INFORMATION. PROVIDE
STRAINER, ISOLATION VALVES, AND FULL LINE
SIZE BY-PASS AT METER.
11. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE OF PIPE
PRIOR TO START OF NEW WORK.
12. PROVIDE FULL LINE SIZE BY-PASS WITH
NORMALLY CLOSED (NC) BALL VALVE. SEE
DETAIL 4/P-501.
13. ROUTE DRAIN LINE TO EXISTING FLOOR DRAIN
WITH AIR GAP. SEE DETAIL 5/P-501.
14. CONNECT TO 120V POWER SOURCE AT J-BOX
USING 2-12AWG, 12AWG EG IN 3/4" C.
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
B L
D G
A B
B L
D G
C
BLDG. 1C
BLDG. 1E
BLDG. 1E
B L
D G
A B
B L
D G
C
BLDG. 1C
BLDG. 52
BLDG. 1C
BLDG. 52
B L
D G
B L
D G
C
D
BLDG. 1C (D)
BLDG. 53
BLDG. 53
B L
D G
B L
D G
C
D
EX 2" DCW UP
EX 2"-BYPASS TO BUILDING 1AB
EX DCW, DHW, & DHWR CAPPED DEAD LEG, TYP.
EX 1/2" DHW UPEX 4" DCW FROM BUILDING 52EX 2-PUMP BOOSTER PUMP SYSTEM
EX DOMESTIC WATER HEATER
EX 6" DCW
EX 2-1/2" DCW
EX 8" DCW
EX 6" DCW
EX 4" DCW
EX 1"
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
1C
1C-PD101
WLF / LLPDJR
CRAWL SPACE PLUMBING
DEMOLITION PLAN
1. REMOVE EXISTING METER AND PREPARE
PIPING TO ACCOMMODATE NEW PULSE
METER. SEE 1C-PP101 FOR ADDITIONAL
INFORMATION.
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
D G
A B
B L
D G
C
BLDG. 1C
BLDG. 1E
BLDG. 1E
B L
D G
A B
B L
D G
C
B L
D G
B L
D G
C
D
BLDG. 1C (D)
BLDG. 53
BLDG. 53
B L
D G
B L
D G
C
D
EX 3/4"
EX 3/4"
EX 2"
EX 3/4"
EX 1"
EX 1"
EX 3/4"
EX 3/4"
EX 1 1/4"
DEAD LEG
EX 2"
EX AHU
EX (3")FD
EX 3/4"
EX 3/4" DCW-DN TO HUMIDIFIER
DISCHARGE COOLER
EX 3/4" DCW-DN TO HUMIDIFIER
DISCHARGE COOLER
EX (3")FD
EX 2"CW-DN
EX 2
" 140°F UP & DN
EX 2
" 130°F UP & DN
EX 1
" HWR UP & DN
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
1C
1C-PD131
WLF / LLPDJR
THIRD FLOOR PLUMBING
DEMOLITION PLAN
1. REWORK EXISTING 2" CW, 2 1/2" 140°F HW,
2 1/2" 130°F HW AND 1 1/4"HWR PIPING,
HANGERS AND SUPPORTS AS REQUIRED TO
ACCOMMODATE INSTALLATION OF NEW
THERMOSTATIC MIXING VALVE STATION. SEE
SHEET 1C-PP131 FOR ADDITIONAL
INFORMATION.
2. REMOVE PIPING TO POINT INDICATED AND
PREPARE PIPING TO ACCOMMODATE
INSTALLATION OF NEW BACKFLOW
PREVENTOR PIPING. SEE SHEET 1C-PP131
FOR ADDITIONAL INFORMATION.
3. REMOVE EXISTING DEAD LEG PIPING BACK TO
MAIN. CAP PIPING AS CLOSE TO MAIN AS
POSSIBLE.
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
D G
A B
B L
D G
C
BLDG. 1C
BLDG. 1E
BLDG. 1E
B L
D G
A B
B L
D G
C
BLDG. 1C
BLDG. 52
BLDG. 1C
BLDG. 52
B L
D G
B L
D G
C
D
BLDG. 1C (D)
BLDG. 53
BLDG. 53
B L
D G
B L
D G
C
D
EX 2" DCW UP
EX 2"-BYPASS TO BUILDING 1AB
EX DCW, DHW, & DHWR CAPPED DEAD LEG, TYP.
EX 1/2" DHW UPEX 4" DCW FROM BUILDING 52EX 2-PUMP BOOSTER PUMP SYSTEM
EX DOMESTIC WATER HEATER
EX 6" DCW
EX 2-1/2" DCW
EX 8" DCW
EX 6" DCW
EX 4" DCW
EX 1"
PULSE
METER
TMV-1
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
1C
1C-PP101
WLF / LLPDJR
CRAWL SPACE PLUMBING PLAN
1. SEE DETAILS 7/P-502 AND 8/P-502 FOR
INSTALLATION OF THE THERMOSTATIC MIXING
VALVE STATION AT THE EXISTING WATER
HEATER.
2. PROVIDE NEW PULSE METER INTEGRATED
DIRECTLY TO NIAGARA AX GU1. SEE SHEET
PS102 FOR ADDITIONAL INFORMATION.
PROVIDE STRAINER, ISOLATION VALVES, AND
FULL LINE SIZE BY-PASS AT METER.
3. CONNECT TO 120V POWER SOURCE AT J-BOX
USING 2-12AWG, 12AWG EG IN 3/4" C.
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
D G
A B
B L
D G
C
BLDG. 1C
BLDG. 1E
BLDG. 1E
B L
D G
A B
B L
D G
C
B L
D G
B L
D G
C
D
BLDG. 1C (D)
BLDG. 53
BLDG. 53
B L
D G
B L
D G
C
D
EX 3/4"
EX 3/4"
EX 2"
EX 3/4"
EX 1"
EX 1"
EX 3/4"
EX 3/4"
EX 2"
EX AHU
2"
2"
EX (3")FD
EX 3/4"
EX 3/4" DCW-DN TO HUMIDIFIER
DISCHARGE COOLER
EX 3/4" DCW-DN TO HUMIDIFIER
DISCHARGE COOLER
EX (3")FD
EX 2"CW-DN
EX 2
" 140°F UP & DN
EX 2
" 130°F UP & DN
EX 1
" HWR UP & DN
T
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
1C
1C-PP131
WLF / LLPDJR
THIRD FLOOR PLUMBING PLAN
1. CONNECT NEW PIPING TO EXISTING. FIELD
VERIFY EXACT LOCATION AND SIZE PRIOR TO
START OF NEW WORK.
2. SEE EQUIPMENT SCHEDULE FOR ADDITIONAL
INFORMATION.
3. ROUTE DRAIN LINE TO NEAREST FLOOR DRAIN
NEAR EXISTING WATER HEATER SKIDS OR
CONDENSATE PUMP.
4. SEE DETAILS 7/P-502 AND 8/P-502.
5. SEE DETAIL 5/P-501.
6. ROUTE A
" COPPER LINE FROM THE WATER
QUALITY MONITOR PANEL TO THE DOMESTIC
COLD, HOT AND HOT WATER RETURN RISERS
ALONG WEST WALL EACH LINE 20'-0" LONG.
7. PROVIDE OXIDANT RESIDUAL MONITOR
STATION WIRED BACK TO WQMP-1
8. PROVIDE DOMESTIC HOT WATER
TEMPERATURE SENSING STATION ON THE
130°F RISER. WIRED BACK TO WQMP-1.
9. PROVIDE NEW PULSE METER INTEGRATED
DIRECTLY TO NIAGARA GUI. SEE SHEET PS102
FOR ADDITIONAL INFORMATION. PROVIDE
STRAINER, ISOLATION VALVES, AND FULL SIZE
LINE BY-PASS AT METER.
10. PROVIDE 120V DIRECT CONNECTION TO NEW
WATER MONITORING TEST STATION (700W).
EXTEND NEAREST NORMAL POWER
RECEPTACLE CIRCUIT TO LOCATION AND
CONNECT. COORDINATE EXACT LOCATION
AND REQUIREMENTS WITH PLUMBING
CONTRACTOR.
11. PROVIDE 120V DIRECT CONNECTION TO NEW
THERMOSTATIC MIXING VALVE. EXTEND
NEAREST NORMAL POWER RECEPTACLE
CIRCUIT TO LOCATION AND CONNECT.
COORDINATE EXACT LOCATION AND
REQUIREMENTS WITH PLUMBING
CONTRACTOR.
12. CONNECT TO 120V POWER SOURCE AT J-BOX
USING 2-12AWG, 12AWG EG IN 3/4" C.
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
NORTH
EX 6" FIRE SERVICE FROM PIV
ABANDONED EX 6" FIRE SERVICE
EX FIRE DEPARTMENT CONNECTION
WITH EX 2" DRAIN BELOW
EX 4" F WITH EX 2" DRAIN BELOW
RACKED ON WALL AT 3' AFF
EX 4" F WITH CHECK VALVE IN
VERTICAL PIPE
EX 6" RISER CHECK VALVE IN
VERTICAL PIPE
EX 6" FLOW AND TAMPER (ABOVE CEILING)
EX 6" F TO BUILDING (ABOVE CEILING)
EX 6" WATER SERVICE
EX 6" CURB STOP VALVE
EX BOILER, TYP OF (3)
EX 6" WATER TO BUILDING AT 78" AFF
EX 1" DCW TO HOSE BIBBS AT 68" AFF
(SHOWN OFFSET FOR CLARITY)
EX 6" DCW
EX HOSE BIBB
EX DOMESTIC
WATER HEATER
EX 1" DCW HIGH ON WALL
EX WALL HYDRANT
CAP EX 2" BRANCH6
EX HB
EX SINK
EX EWH
EX EWS/SH
EX TMV
EX 6" MAIN
SHUT-OFF IN
VERTICAL PIPE
4 7
EX 3/4"
DEADLEG
EX 2" 8
EX 2" 8
EX 2" 6 EX 1" 6
EX ELECTRIC WATER COOLER
EX 3/4" DCW UP
EX 3/4" DCW DOWN TO COOLER FEED
EX 1-1/2" DCW HIGH ON WALL 2
EX 1" DCW DOWN ON WALL 2
EX 1-1/2" HOSE CONNECTION
EXISTING REMOTE
BOOSTER PUMP
CONTROL PANEL
EXISTING 2 CHANNEL
SITRANS CONTROLLER
EX SITRANS WATER METER
EX SITRANS WATER METER
ON MEZZANINE ABOVE FOR
SCW MAKE-UP TO BOILERS
1. EXISTING PLUMBING WORK TO REMAIN AS IS.
2. EXISTING HOSE BIB, PIPING, HANGERS AND
SUPPORTS TO BE REMOVED COMPLETE.
PREPARE EXISTING PIPING TO REMAIN TO
ACCOMMODATE NEW WORK. SEE SHEET
18-PP101 FOR ADDITIONAL INFORMATION.
3. REMOVE EXISTING FIRE PROTECTION RISER
CHECK VALVE ASSEMBLY AND PREPARE
EXISTING PIPE AND FITTINGS TO REMAIN TO
ACCOMMODATE NEW EQUIPMENT TO BE
INSTALLED. SEE SHEET 18-PP101 FOR
ADDITIONAL INFORMATION.
4. REMOVE BRANCH AND REPLACE TEE FITTING
WITH STRAIGHT CONNECTOR OR CAP BRANCH
PIPE AS CLOSE TO ACTIVE MAIN AS POSSIBLE.
5. SEE NEW PIPING AS INDICATED ON 18-PP101
FOR MORE INFORMATION REGARDING PIPING
TO BE REMOVED.
6. REMOVE EXISTING 6" MAIN PIPING, 2" BRANCH
FROM MAIN, AND 1" TO HOSE BIBBS AS
NEEDED FOR INSTALLATION OF NEW
BACKFLOW PREVENTORS.
7. REMOVE EXISTING 2" ISOLATION VALVE AND
1-1/2" HOSE CONNECTION AND STORE FOR
REINSTALLATION IN NEW LOCATION.
8. REMOVE SECTION OF 2" PIPE TO MAKE ROOM
FOR NEW CONNECTIONS. SEE SHEET
18-PP101 FOR ADDITIONAL INFORMATION.
9. REMOVE EXISTING STEAM FIRED WATER
HEATER, HWR PUMP, STORAGE TANK AND
ASSOCIATED PIPING AND ACCESSORIES
COMPLETE. PREPARE EXISTING STEAM, DCW,
DHW AND DHWR FOR CONNECTION TO NEW
WATER HEATER. SEE SHEET 18-PP101 FOR
ADDITIONAL INFORMATION.
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
18-PD101
WLF / LLPDJR
PLUMBING DEMOLITION PLANS
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
NORTH
EX 6" FIRE SERVICE FROM PIV
ABANDONED EX 6" FIRE SERVICE
EX FIRE DEPARTMENT CONNECTION
WITH EX 2" DRAIN BELOW
EX 4" F WITH EX 2" DRAIN BELOW
RACKED ON WALL AT 3' AFF
EX 4" F WITH CHECK VALVE IN
VERTICAL PIPE
EX 6" FLOW AND TAMPER (ABOVE CEILING)
EX 6" F TO BUILDING (ABOVE CEILING)
DCVA-343
EX 6" WATER SERVICE
EX 6" CURB STOP VALVE
EX BOILER, TYP OF (3)
EX 6" WATER TO BUILDING AT 78" AFF
EX 1" DCW TO HOSE BIBBS AT 68" AFF
(SHOWN OFFSET FOR CLARITY)
EX WALL HYDRANT
EX HB
EX SINK
EX EWH
EX EWS/SH
EX TMV
BFP-8
BFP-8
BFP-4
EX 6" MAIN
SHUT-OFF IN
VERTICAL PIPE
62" TO EX 2" 6
62" TO EX 2" 6
62" TO EX 2" 6
61" TO EX 1" 6
EX ELECTRIC WATER COOLER
EX 3/4" DCW UP
EX 1-1/2" HOSE CONNECTION
1" UP TO EX 1" AT TEE 6 8
2" TO BOILER BLOWDOWN
2" TO SINK
P-804 2
1" DCW DOWN ON WALL
1" DCW ON WALL ABOVE DOOR
1" DCW DOWN
DHWH-2
HWCP-1
TMV-1
REMOTE BOOSTER PUMP
CONTROL PANEL
WQMP-2
EXISTING 2 CHANNEL
SITRANS CONTROLLER
EX SITRANS WATER METER
EX SITRANS WATER METER
ON MEZZANINE ABOVE FOR
SCW MAKE-UP TO BOILERS
1/2"
1/2"
1. EXISTING PLUMBING WORK TO REMAIN AS
IS.UNLESS OTHERWISE NOTED
2. CONNECT NEW PIPING AND EQUIPMENT TO
EXISTING. FIELD VERIFY EXACT LOCATION
AND SIZE OF PIPING PRIOR TO START OF NEW
WORK.
3. INSTALL NEW BFP IN VERTICAL PIPE IN
LOCATION SIMILAR TO REMOVED CHECK
VALVE. TIE IN MAIN DRAIN PER NFPA
REQUIREMENTS.
4. SEE EQUIPMENT SCHEDULE ON SHEET P-401.
5. SEE DETAIL ON SHEET P-502.
6. CONNECT NEW PIPING TO EXISTING IN THIS
LOCATION.
7. RELOCATE EXISTING 2" ISOLATION VALVE AND
1-1/2" HOSE CONNECTION AT THIS LOCATION.
8. ROTATE EXISTING TEE FITTING TO TIE NEW
PIPING INTO EXISTING.
9. PIPING SHOW OFFSET FOR CLARITY. RACK
ON WALL. FIELD VERIFY EXACT LOCATION
AND ROUTE BEFORE FABRICATION.
10. NEW HOSE BIB ON WALL AT 4 FEET AFF.
11. SEE DETAIL 7 / P502 AND 8/P502.
12. NEW REMOTE PUMP CONTROL PANEL.
CONNECT TO EXISTING SIGNAL WIRING. SEE
P-602.
13. EXISTING 2 CHANNEL SITRANS WATER METER
CONTROLLER TL SERVICES TO REPAIR /
REMAP ALL POINTS CURRENTLY CONNECTED
TO THE SITRANS SYSTEM.
14. EXISTING SITRANS WATER METER. CONTACT
TL SERVICES FOR REPAIR /
RECONFIGURATION OF EXISTING METER
INTERFACES AND EXISTING INTEGRATION TO
ABS NIAGARA AX INTERFACE.
15. EXISTING SITRANS BOILER MAKE-UP WATER
METER. CONTACT TL SERVICES FOR REPAIR /
RECONFIGURATION OF EXISTING METER
INTERFACES AND EXISTING INTEGRATION TO
ABS NIAGARA AX INTERFACE.
16. WATER QUALITY ENGINEER OFFICE. THIS
CONTRACTOR TO PROVIDE A PC WITH
WINDOWS 10 OPERATING SYSTEM TO RUN
THE WATER QUALITY MONITORING SYSTEM
SOFTWARE.
17. PLUMBING SHOP OFFICE - THIS CONTRACTOR
TO PROVIDE A PC WITH WINDOWS 10
OPERATING SYSTEM TO VIEW THE WATER
QUALITY MONITORING SYSTEM SOFTWARE
AND THERMOSTATIC MIXING VALVE BUILDING
AUTOMATION SYSTEM INFORMATION.
18. CONNECT TO 120V POWER SOURCE AT J-BOX
USING 2-12AWG, 12AWG EG IN 3/4" C.
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
18-PP101
WLF / LLPDJR
PLUMBING PLANS
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
EX DOMESTIC
WATER METER
EX 2 1/2" SERVICE LINE
EX FDC
EX 4" FIRE PROTECTION SERVICE LINE
F F
PIPING TO
BLDG. 24
EXISTING
EX 3/4"
EX 3/4"
EX 2 1/2"
EX CW, HWR, HW & CW
EX CW, HWR, HW & CW
NORTH
EX FDC
EX 4" FIRE PROTECTION SERVICE LINE
F
PIPING TO
BLDG. 24
EXISTING
EX 3/4"
EX 3/4"
F
F
EX CW, HWR, HW & CW
EX CW, HWR, HW & CW
EX 2 1/2"
BFP-5 x (2)
DCVA-1
WATER METER
SEE SHEET PS101
FOR CONTINUATION
SEE SHEET PS101
FOR CONTINUATION
EX SITRANS 1 CHANNEL
METER CONTROLLER
EX 1"
EX 1" BFP
EX HEATING MAKEUP
WATER METER
EX 1"
EX 1" BFP
TOTALIZER METER7
2 1/2"
F
8 9
4"
NORTH
KEY PLAN:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date: Apogee Project #
SHEET NOTES:
SHEET KEY NOTES:
100% CONSTRUCTION
DOCUMENTS
March 29, 2018
Upgrade Site Water Systems VA #623-16-113
FULLY SPRINKLERED
Muskogee, OK
Apogee Consulting Group 1152 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde
17-119
22-P-101
WLFDJR
PLUMBING PLANS
1. REMOVE EXISTING DOMESTIC WATER PIPING,
VALVES, FITTINGS, HANGERS AND SUPPORTS
COMPLETE.
2. REMOVE PIPING TO THE POINT INDICATED ON
DRAWING. FIELD VERIFY EXACT LOCATION AND
SIZE OF PIPE. FIELD VERIFY EXISTING
CONDITIONS PRIOR TO STARTING NEW WORK.
3. A SIEMENS FACTORY TRAINED AND CERTIFIED
TECHNICIAN SHALL RELOCATE THE EXISTING
SITRANS WATER METER. TL SERVICES TO
REMAP ALL POINTS CURRENTLY CONNECTED
TO THE SITRANS SYSTEM.
4. SEE EQUIPMENT SCHEDULE ON SHEET P-401
AND PIPING DETAIL ON 2 / P-502.
5. SEE EQUIPMENT SCHEDULE ON SHEET P-401
AND DETAIL 6 / P-502.
6. REMOVE EXISTING MAKEUP WATER METER AND
PREPARE PIPING TO ACCOMMODATE NEW
EQUIPMENT TO BE INSTALLED.
7. PROVIDE A PULSE METER INTEGRATED
DIRECTLY TO THE NIAGARA GUI. SEE SHEET
PS102 FOR ADDITIONAL INFORMATION.
PROVIDE STRAINER, ISOLATION VALVES, AND
FULL SIZE LINE BY-PASS AT METER.
8. CONNECT TO EXISTING 4" FIRE PROTECTION
RISER.
9. CONNECT TO EXISTING 3" FIRE PROTECTION
RISER.
10. CONNECT TO EXISTING PIPING. FIELD VERIFY
EXACT LOCATION AND SIZE OF PIPE PRIOR
TO START OF NEW WORK.
1. THE ENTIRE PLUMBING SYSTEM SHALL
CONFORM WITH ALL VA STANDARDS.
2. COORDINATE WORKING HOURS ALLOWED
WITH VA COR AS INSTRUCTED IN GENERAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS PRIOR TO CUTTING
EXISTING WALLS AND FLOOR SLABS. IF
EXISTING TO REMAIN SERVICES ARE CUT /
DAMAGED, PATCH AND REPAIR THE SERVICE
AT NO ADDITIONAL COST TO THE VA.
4. CONTRACTOR SHALL REMOVE ALL EXISTING
PLUMBING SYSTEMS AND INSULATION WHERE
INDICATED AND MADE OBSOLETE BY NEW
CONSTRUCTION INCLUDING ALL PIPING,
HANGERS, SUPPORTS AND ACCESSORIES.
REFERENCE ALL DRAWINGS AND
SPECIFICATIONS AND FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO START OF
WORK.
5. ALL EXISTING PIPING SHOWN ON THE
DOCUMENTS ARE FROM EXISTING
DRAWINGS AND FIELD OBSERVATIONS. THE
CONTRACTOR IS RESPONSIBLE FOR FIELD
VERIFYING THE EXACT LOCATION, SIZE AND
ELEVATION OF ALL EXISTING PIPING PRIOR
TO START OF NEW WORK.
6. THESE PLANS ARE DIAGRAMMATIC.
CONTRACTOR SHALL PROVIDE ALL
NECESSARY OFFSET, TEES, ELBOWS, ETC
FOR A COMPLETE WORKING PLUMBING
EX 3/4"
3/4"
EX 3/4"
3/4"
EX 2-1/2"
EX 2-1/2"
EX 2-1/2"
EX HWRC
PUMP
EX 1-1/2"UP
EX 3/4"
1-1/2" FROM ABOVE
SUMP PUMP
EX 2-1/2"2-1/2"
1/2"
EX 2 1/2" SERVICE LINE EX 4" DOMESTIC SERVICE LINE
WATER SOFTENERS
F
EX FDC
EX 6" FIRE PROTECTION SERVICE LINE
EX 3/4"
EX 4"
EX DOM WATER METER(SITRANS)
EX HWRC PUMP
SOFTENED
WATER HEATER FOR SPS
EX DOM WATER HEATER
EX 3/4"-UP
EXISTING
PIPING TO
BLDG. 22
EX 6" FP
EX 4"…