Equipment Schedule.pdf

PDF 230 KB Posted

Attached to
Boiler / Chiller Maintenance Services Federal contract opportunity
Solicitation number
36C25726Q0073
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17

About this file

This document is a comprehensive maintenance contract specification for mechanical equipment at a VA healthcare facility, detailing annual and quarterly preventative maintenance requirements for multiple critical systems. The contract covers maintenance of two Cleaver-Brooks fire tube boilers, six Evapco and one Marley cooling towers, three electric chillers (two R-22 and one R-134a York YK 900-ton units), and multiple pump systems including 10 chill water, 7 condenser, and 3 heating hot water pumps.

The maintenance scope requires detailed inspections, testing, and service tasks to be completed annually and quarterly, with most work mandated to be performed before May 1st each year. Key maintenance activities include vibration analysis, motor testing, refrigerant charge evaluation, electrical control inspections, tube cleaning, strainer maintenance, cooling tower basin cleaning and disinfection, and comprehensive performance assessments. Each equipment type has a specific, structured inspection checklist with requirements for data collection, performance verification, and reporting, with contractors required to provide detailed reports documenting findings and potential corrective actions for each piece of equipment serviced.

View the file

Other files for this federal contract opportunity

Other files attached to Boiler / Chiller Maintenance Services, newest first.
File Type Posted
P09 Equipment Schedule.pdf PDF
Questions and Answers.pdf PDF
S02 36C25726Q0073 0002.pdf PDF
36C25726Q0073 0001.pdf PDF
Questions and Answers.pdf PDF
S02 36C25726Q0073.pdf PDF
Attachment A Equipment and Equipment Schedule.pdf PDF
Attachment B Inspection Task Sheets.pdf PDF
S02 36C25726Q0073.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Equipment Schedule

Equipment BLDG QTY SERIAL MONTHLY

INSPECTION

QUARTERLY SEMI

ANNUAL

ANNUAL EMERGENCY

COVERAGE

ADDITIONAL

TASKS

BOILER # 3&4

Cleaver Brooks Steam Fire Tube Boiler 5175 lbs per hour. Fireye

YB110/230

Burner Mgmt.

Boiler Plant

2 L94624

L94623 x x x x

CHILLER# 5

R-134a

YKHFGDJ1CZFS

900 ton

Equip

Room

1 SHMM037090 x x x Annual

Condenser and Evaporator

Tube Brushing

CHILLER# 1&4

York YK

YKQ2Q2H1CZ8S

YKQ4Q3H1CZC

R22

Centrifugal

Electric Driven 900 ton

Boiler Plant

Equip

Room

SCCM9315211801

SLFN612830

x x x x Annual

Condenser and Evaporator

Tube Brushing

Evapco Cooling Towers

USS212-724

1-4

Cooling Tower Yard

4 10348765

10348766

10348767

10348768 x x Tower

Basin

Cleaning

Before 5/1

Condenser Pumps 1-4

Cooling Tower Yard

4 Weinman 472979

Paco G821256 x x Annual Strainer Cleaning

Marley NC Series

Cooling Tower #5

Cooling Tower Yard

1 116726-002

NC6211GM-97

x x Tower

Pump #5

Cooling Tower Yard

1 Aurora

411-BF

Ser# 9713459 x x Annual Strainer

QUARTERLY SEMI

ANNUAL

ANNUAL EMERGENCY

COVERAGE

ADDITIONAL

TASKS

Evapco Cooling

USS 212-

724-S

Tower #6

Cooling Tower Yard

1 10348769 x x Tower

Pump #6

Yard

1 Paco 296012214007128921P x x Annual

Cleaning

Evapco

Cooling

USS 212-

724-S

Cooling Tower Yard

1 10348770 x x Tower

Tower #7

Pump #7

Yard

Paco

296012214007128921 x x Annual Strainer Cleaning

Main Chilled water pump #1

Boiler

Plant

1 Paco Inline

Model: 17-80123- 150101-191

Cleaning

Main Chilled water pump

#2

Boiler

Plant

1 Armstrong

10x12 Inline x x Annual Strainer Cleaning

Main chilled water pump

#3

Boiler

Plant

1 Aurora Split Case

Vertical 413 BF

97-43458 x x Annual Strainer Cleaning

Main chilled water pump

#4

Boiler

Plant

1 Aurora Split Case

Vertical 413 BF

97-43458 x x Annual Strainer Cleaning

East Tower

Secondary

Chilled water pump #1

Boiler

Plant

1 Weinman

Centrifugal x x Annual Strainer Cleaning

East Tower

Secondary

Chilled water pump #2

Boiler

Plant

1 Weinman

Centrifugal x x Annual Strainer Cleaning

Surgery secondary chilled

Equip

Taco T1A922AB2J1A2L

Split Case water pump #3

QUARTERLY SEMI

ANNUAL

ANNUAL EMERGENCY

COVERAGE

ADDITIONAL

TASKS

Surgery secondary chilled water pump #4

Equip

Taco T1A922AB2J1A2L

Split Case

Cleaning

CLC

Secondary chilled water pump #1

Equip

Room

1 Aurora Split Case

411-BF

97-13-60-1 x x Annual Strainer

Cleaning

CLC

Secondary chilled water pump #2

Equip

Room

1 Aurora Split Case

411-BF

97-13-60-1 x x Annual Strainer

Cleaning

CLC

Heating Hot

Water Pump

#1

Equip

Room

1 Aurora Split Case

411-BF

97-43164-2 x x Annual Strainer

Cleaning

CLC

Heating Hot

Water Pump

#2

Equip

Room

1 Aurora Split Case

411-BF

97-43164-2 x x Annual Strainer

Cleaning

CLC

Heating Hot Water Pump

#3

Equip

Room

1 Weinman

4l2-200P14G x x Annual

Critical Equipment Scope

Annual Electric Chiller Operational Tests & Inspections - Preventative Maintenance

Electric Driven, Centrifugal 900-ton units. Model: York YK (2ea R-22 1ea R-134a)

YORK YK. To be completed before May 1 of each year. Contractor shall provide all consumables, personnel, transportation, supplies, cranes, rigging, scaffolding and labor as required to successfully complete the Annual Preventative Maintenance inspections. Required tasks/check points are outlined below. One (1) report per each chiller is required and shall contain pertinent results and/or comments along with any recommendations for corrective maintenance actions. Contractor shall log any circumstances that may prevent completion of an inspection.

Oil Level % Evap Inlet Temp Oil Pressure Evap Outlet Temp Oil Added /Removed Evap Inlet Pressure Oil Temp Evap Outlet Pressure High Oil Pressure Low Oil Pressure Cond Refrigerant Pressure Discharge Temp High Pressure Liquid Temp Oil Supply Temp Cond Approach Proximity Probe (MILS) Cond Refrigerant Level Discharge Superheat Seal Bottle Level (IN) Cond Inlet Temp

Cond Outlet Temp Output Volts Phase A Delta T Output Volts Phase B Sub Cooler Temp Output Volts Phase C Cond Inlet Pressure Amps: Phase A Cond Outlet Pressure Amps: Phase B Delta P Amps: Phase C % of FLA Run Hours Number of Starts

Evap Refrigerant Pressure Evap Saturation Temp Evap Approach Evap Refrigerant Level Refrigerant Added

Cooler Refrigerant

Evaluate Refrigerant charge. Adjust / trim as necessary.

Calibrate and set chilled water and condensing water flows using ultrasonic meters.

Inspect all electrical controls.

Compressor

Cooler Water

Condenser Refrigerant

Condenser Water

Motor

Inspections and tasks to Perform

Draw Oil Sample for analysis each year. Provide Report.

VA Staff to perform Eddy Current Inspection on Evaporator and Condenser tubes every three (3) years.

Perform Vibration Analysis. Provide Report.

Measure Mechanical Seal Leakage, document and determine need for replacements.

Perform leak tests on machine, repair leaks.

Change Oil Filter and Refrigerant Dehydrators.

Electric Driven, Centrifugal 900-ton units. Model: York YK (2ea R-22 1ea R-134a)

YORK YK. Contractor shall provide all consumables, personnel, transportation, supplies, cranes, rigging, scaffolding and labor as required to successfully complete eleven (11) monthly Preventative Maintenance inspections. Required tasks/check points are outlined below. One (1) report per each chiller is required and shall contain pertinent results and/or comments along with any recommendations for corrective maintenance actions. Contractor shall log any circumstances that may prevent completion of an inspection.

Entering Water Temp Purge Operation and Condition Leaving Water Temp Operation of Chiller Controls Entering Water Pressure Operation of lube system Leaving Water Pressure Motor & starter operation & condition Refrigerant Pressure System Operation Refrigerant Temperature Maintains leaving fluid setpoint Subcooled Liquid Temperature Present setting of leaving fluid setpoint Cooler Pressure Out Other operating conditions Refrigerant Level Reviewed with operator Approach Slide Valve/Vane Position % Delta T Discharge Temperature Delta P Discharge Superheat Actual GPM Oil Temperature Approximate Tons Oil Pressure Phase A: Volts & Amps Oil Level Phase B: Volts & Amps Hours of Operation Phase C: Volts & Amps Number of Starts % full Load Amps Purge

Purge Count Design FLA

HOP

LOP

Prox Sensor Pos / Ref Supply Oil Temperature

Heat Exchanger Data

Cooler and Condenser

Inspection

Motor Data Other Data

Annual Preventative Maintenance for Cooling Towers, Chill Water, Condenser and

Heating Hot Water Pumps

(6) Evapco and (1) Marley Cooling Towers,

(10) Chill Water, (7) Condenser and

(3) Heating Hot Water Pumps

To be completed before May 1 of each year. Contractor shall provide all consumables, personnel, transportation, supplies, cranes, rigging, scaffolding and labor as required to successfully complete the Annual Preventative Maintenance inspections. Required tasks/check points are outlined below. One (1) report is required per each Cooling Tower, Chill Water, Condenser and Heating Hot Water Pumps and shall contain pertinent results and/or comments along with any recommendations for corrective maintenance actions. Contractor shall log any circumstances that may prevent completion of an inspection.

NOTE: These PM inspections are to be scheduled within the same 2 – 4-week time frame each year;

unless otherwise directed by the COR.

Heating Hot Water Pumps

Megger Motor

Inspect/record voltage & amperage.

Additional Annual Tasks (Completed before May 1 of each year):

1. Cleaning and disinfection of (6) Evapco and (1) Marley Cooling Towers.

2. Cleaning or Replacement of all Chilled Water, Condenser and Heating Hot Water Pump Strainers (listed in equipment schedule).

Check proper operation/adjust blowdown intervals if needed.

Inspect /record voltage & amperage.

Annual Cooling Tower

PM tasks.

Perform vibration analysis of cooling tower fans.

Balance cooling water flows, VA personnel to assist.

Meggar Motor Inspect /record voltage & amperage.

Megger fan motor and inspect contacts Re-pitch blades and achieve optimum performance as required.

Condenser Water Pumps

Chill Water Pumps

Meggar Motor

Boilers: Annual Service, Cleaning, and Testing

Contract covers a total of 2 Cleaver-Brooks fire tube boilers.

To be performed between May 1 and October 31 and must be completed before November 1 of each year.

Contractor shall provide all consumables, personnel, transportation, supplies, cranes, rigging, scaffolding and labor as required to successfully complete the Annual Preventative Maintenance Inspections, Cleaning and Testing. Required tasks/check points are outlined below.

One (1) report per each boiler is required and shall contain pertinent results and/or comments along with any recommendations for corrective maintenance actions. Contractor shall log any circumstances that may prevent or delay completion of a task.

Semi Annual and Annual Fuel Train and Air Train Testing.

Each boiler to undergo fuel train & air train testing Two (2) times per year as per current VHA DIRECTIVE 1810. Using the current VHA boiler and associated plant safety device testing manual and provide testing results on the forms provided in Appendix A of TESTING MANUAL.

Pre-purge setting of flue gas recirculation damper.

Burner Control.

Low-oxygen alarm and/or cut-out.

Boiler outlet damper wide open for purge.

Purge air flow interlock.

Timing for pre-purge Timing for post purge.

Ignition timer.

Low fire position interlock.

Combustion air interlock.

Main flame out, i.e., time to close valves.

Ignition flame out, i.e., time to close valves.

Minimum ignition flame test.

Scanner not sensing ignition spark.

High-steam pressure cut-out (non-recycle).

Forced fan damper wide open for purge.

High-gas fuel pressure cut-off.

Low-gas fuel pressure cut-off.

Gas fuel safety shut-off valves proof closure.

Leak test gas fuel safety shut off valves.

Low-atomizing pressure for fuel oil.

High fuel oil pressure cut-off.

Fuel safety shut off valve proof of closure.

Leak test fuel oil safety shut off valve.

Check operation of liquid petroleum gas pilot.

Low pilot gas pressure cut off.

Forced draft fan motor interlock

1. Annual PM Service for (5) Clever Brooks water tube & fire tube boilers.

Check gas vents for leaks.

Calibrate oxygen analyzer, provide two (2) certified Cal gases.

Test/adjust low oxygen level alarm.

Perform comb. analysis under gas & fuel oil operation. Calibrate fuel/air mixture.

Calibrate steam, oil, gas and feed water press. gauges & industrial controls.

Adjust ignition electrode gap.

Vibration analysis of blower motors.

Operational test of all boiler safety devices.

Check vibration of burner fans Calibrate instrumentation, monitoring, and control systems.

High-steam pressure cut-out (recycle).

Annual Cleaning of all boilers Perform between May 1 and October 31. Complete before November 1.

Cleaning services (Mechanically punched tubes). Once each per boiler.

Boilers: Quarterly Preventative Maintenance

To be performed four (4) times per year during each calendar quarter. When conducting Semi-Annual and Annual PM tasks, the quarterly is to be added to the overall scope of work. Contractor shall provide all consumables, personnel, transportation, supplies, cranes, rigging, scaffolding and labor as required to successfully complete the Quarterly Preventative Maintenance inspections. Required tasks/check points are outlined below. One (1) report per each boiler is required and shall contain pertinent results and/or comments along with any recommendations for corrective maintenance actions. Contractor shall log any circumstances that may prevent or delay completion of a task.

Oct-Dec Jan-March Apr-June July-Sept w/ Annual w/ Annual w/ Annual w/ Annual w/ AnnualTest and adjust low oxygen alarms.

Perform combustion analysis in all fuel modes, gas and oil, with and without VFD.

1. Quarterly PM services. Four (4) times per year for each boiler.

Calibrate steam, feed water and gas flow transmitters, reset totalized values if directed by

Inspect fuel-burning equipment.

Calibrate all sensors Calibrate operating controls.

Calibrate safety controls.

CHILLERS

Location: Date of Service:

Chil ler #: Company:

Model #: Technician:

Serial #:

Heat Exchanger Data Cooler Condenser Inspected Checked Entering Water Temp Purge Operation and Condition Leaving Water Temp Operation of Chil ler Controls Entering Water Pressure Operation of lube system Leaving Water Pressure Motor and starter oper. and cond.

Refrigerant Pressure System Operation Refrigerant Temperature Maintains leaving fluid setpoint Subcooled Liquid Temperature Present setting of leaving fluid setpoint Cooler Pressure Out Other operating conditions Refrigerant Level Reviewed with operator Approach Delta T Delta P Actual GPM Approximate Tons

Motor Comp Data Volts Amps Other Data Check Phase A HOP Phase B LOP Phase C Prox Sensor Pos / Ref

Supply Oil Temperature % full Load Amps Slide Valve/Vane Position % Discharge Temperature Discharge Superheat Oil Temperature Oil Pressure Oil Level Hours of Operation Number of Starts Purge Purge Count Design FLA Comments: (Fill Out Refrigerant Logs each Month)

York ELECTRIC Chil ler. Monthly Run Inspection Service Task List

Location: Date of Service:

Chil ler#: Company:

Model # Technician:

Serial #

Check

Perform vibration analysis.

Comments:

Calibrate and set chil led water and condensing water flows using ultrasonic meters.

Change Oil fi lter and refrigerant dehydrators.

Evaluate refrigerant charge adjust /trim as needed.

Task Comments Consult COR for schedule verification

Instructions

Annual YK Electric Chil ler Inspection Service Task List

The scheduled annual inspection of each chil ler is to include all items as l isted on the monthly tasks l ists as well as the items l isted below as scheduled per contract agreement and/or as requested by the COR.

York YK Electric Chil lers

Inspect all electrical controls.

Perform Eddy Current Inspection on evaporator and condenser tubes every three (3) years or as contracted.

(VA staff to brush tubes) Measure mechanical leakage, document and determine need for replacement.

Draw Oil Samples and provide separate report to the VANTXHCS

Perform leak tests of machine and repair any leaks.

COOLING TOWERS, CONDENSER PUMPS, HEATING HOT WATER, AND CHILL WATER PUMPS

Annual Cooling Tower Inspections & Service Task List Location: Date:

CT #: Company:

Model # Technician:

Serial #

Instructions The scheduled inspections of each cooling tower is to include all items as listed below as scheduled per contract agreement and/or as requested by the COR.

Cooling Tower

Task Check Comments

Perform vibration analysis of cooling tower fans.

Megger fan motor and inspect contacts

Re-pitch blades and achieve optimum performance as required.

Balance cooling water flows, VA personnel to assist.

Check proper operation/adjust blowdown intervals if needed.

Vibration Analysis reports to be processed and submitted back to the VA within 2 weeks

Clean and Disinfect Cooling Tower basins

Additional Notes & Comments

Annual Chill, Condenser and Heating Hot Water Pumps Inspections & Service Task List Location: Date:

Pump #: Company:

Model # Technician:

Serial #

Instructions The scheduled inspections of each Pump is to include all items as listed below as scheduled per contract agreement and/or as requested by the COR.

Chill, Condenser and Heating Hot Water Pumps

Task Check Comments

Megger the Motor and record results

Inspect and record voltage and amperage

Clean or if Damaged Replace Strainers

Additional Notes & Comments