This document is a technical specification sheet for the TLS4i Automatic Tank Gauge console manufactured by Veeder-Root. The TLS4i is a self-contained monitoring solution designed for commercial and industrial businesses monitoring up to four tanks, featuring the same graphical user interface as the TLS-450PLUS tank gauge.
The specification details two console variants: model 860199-120 with a 7" color LCD display and model 860199-110 without display, both featuring 12 inputs and Ethernet connectivity. The system includes web-enabled functionality, custom alarms, on-console help, and extended storage capabilities. Hardware specifications include dual configurable RS-232/RS-485 ports, Ethernet port, two USB ports, relay outputs, and operates in temperatures from 32°F to 104°F. Optional software packages include Static In-Tank Leak Detection (SLD), Continuous Statistical Leak Detection (CSLD), and Timed Sudden Loss Detection. The system offers comprehensive monitoring capabilities including inventory control, leak detection, interstitial/sump leak sensing, vapor monitoring, and customizable alarms. The console meets various international certifications including UL, ATEX, IECEx, and others, and requires specific wiring requirements detailed for both power and probe/sensor connections.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S06 36C25725B0016 0003.pdf | ||
| Attachment 3 TLS4 and TLS4B Brocure.pdf | ||
| Attachment 2 UST locations.pdf | ||
| 36C25725B0016 0002.docx | DOCX document | |
| Attachment 4 TLS4 Specs.pdf | ||
| Attachment 1 Waco UST Tank Information.pdf | ||
| 36C25725B0016 0001.docx | DOCX document | |
| Site Visit Sign in Sheet.pdf | ||
| Attachment 3 Wage Determination.pdf | ||
| Attachment 1 Statement of Work.doc | DOC document | |
| 36C25725B0016_1.docx | DOCX document | |
| Attachment 4 Feb 2025 Deviations.docx | DOCX document | |
| Attachment 2 PCRA.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TLS4i Automatic Tank Gauge
Console Description
The TLS4i Automatic Tank Gauge has the same graphical user interface as the TLS-450PLUS tank gauge, increasing technician familiarity for quick setup using the easy-to-navigate color touch screen.
It is a simplified, self-contained solution, ideal for the commercial and industrial businesses monitoring up to four tanks.
TLS4i Consoles, Standard Hardware & Software
Console Part # & Description Standard Hardware & Application Software
1. 860199-120 TLS4i Console, 12 Inputs, Ethernet, 7” Color LCD Display
2. 860199-110 TLS4i Console, 12 Inputs, Ethernet, No Display
Software – 333578-001 TLS4i Application Software (must order one per Console) includes Web-enabled, Custom Alarm, On-Console Help, Extended Storage Hardware – Two Configurable RS-232 or RS-485 Ports, One Ethernet Port, Two USB Ports, 2 Relay Outputs (120/240 VAC 5A; 30 VDC 5A; Fuse Ratings 5A, 250 VAC Type T (Slo-Blo)), 1 Low Voltage Input (max contact closure ratings 12 VDC 0.015A Class I wiring is required for 12 volt closure circuits)
TLS4i Optional Software
Part # & Description
Static In-Tank Leak Detection (SLD) for TLS4i and TLS4c, for USTs only 333410-015
Continuous Statistical Leak Detection (CSLD) for TLS4i and TLS4c, for USTs only 333410-006
Timed Sudden Loss Detection for TLS4i and TLS4c 333410-018
Note: If software features are added to an existing console, the Feature Enhancement will be shipped with a kit that includes a wrist strap, manual, iButton holder and programmed iButton – P/N 333530-002.
Optional Printer for TLS4 Series Consoles
Part # & Description
Direct Connect External Printer for TLS4 Series Consoles (Epson Model: TM-T88V) 330020-832
Wall Mounting Bracket for External Printer for TLS4 Series Consoles 330020-839
Specifications
Operating Temperature +32 to +104°F (0 to +40°C)
Storage Temperature -40 to +158°F (-40 to +70°C)
Installation Location NEMA 4 or indoors
Relative Humidity 0-90% (non-condensing)
External Dimensions 13" x 8" x 3.5" (33.02cm x 20.32cm x 8.89cm)
Construction 16GA (0.060 in/0.1524 cm) powder coated steel
Console Power Wiring Requirements
AC Power Wiring – Wires carrying 120 or 240 VAC from power panel to the console should be #14 AWG (or larger) wire for line, neutral & chassis ground (3); and 4 sq. For barrier ground, 4 sq. mm wire, rated for at least 90C.
Probe & Sensor to Console Wiring Requirements
1. Wire Type – Shielded cable required regardless of conduit material or application. It must be rated less than 100 picofarad per ft manufactured with a suitable material such as Carol C2534 or Belden 88760, 8760, or 8770.
2. Wire Length – Maximum 1,000ft (304.8m) to meet intrinsic safety requirements. Improper system operation could result for runs over 1,000ft (304.8m).
3. Wire Gauges – Color coded – shielded cable used in all installations. Wires should be #14 - #18 AWG stranded copper wire and installed as Class 2 circuits. As an alternate method when approved by the local authority having jurisdiction, #22 AWG wire such as 88761 may be suitable with the following requirements: wire run is less than 750ft (228.6m); Capacitance does not exceed 100 pF/ft; Inductance does not exceed 0.2 uH/ft.
www.veeder.com 1.888.561.7942
125 Powder Forest Drive • PO Box 2003 • Simsbury, CT 06070 • ©2019 Veeder-Root • P/N 577014-454 Rev. A All information contained in this document is subject to change without notice.
Specifications (continued)
System Power Requirements
Either AC input or DC input, but not both.
1. Universal AC power supply: 100 to 249 VAC, 50/60Hz, 2A max.
2. DC power supply: +24 VDC, 2A max. and +5 VDC, 4A max. Um <= 250 Vrms or 250 VDC
Display Specifications 7” (17.78cm) Color WVGA LCD touch screen display
Data Storage Features SD card
Software Security Features Centralized Device Management to protect your network of TLS4 series consoles
Custom User Access Front Panel Display control through user specific log-in;
User defined roles to restrict access / functionality.
Screen permissions can be limited to view, edit, perform
System Security
1. Port availability control: SSH Port (22), HTTPS Port (443), Serial Command Port (10001)
2. Reassign Port Numbers (i.e., HTTPS on 50443)
3. System Integrator CVE Scans & Fixes
4. Periodic System Updates to protect against persistent threats
Customized Alarm Features Customizable for all alarms
Approvals UL cUL, ATEX, IECEx, NEPSI, FCC, FMC, PESO, ANZEx, ULC, INMETRO, IQC, EAC, NWGLDE, CEN
Third Party Evaluations http://www.nwglde.org/evals/veeder_root_zf.html
Product Installation Guide https://www.veeder.com/us/technical-document-library
TLS4i Automatic Tank Gauge
System Compatibilities Guide
Feature/Console TLS4i
CONSOLE DESIGN
Modular/Expandable Features • LCD with Touch Screen 7" WVGA Color Integral Roll Printer Universal Power Supply •
INVENTORY CONTROL
Graphical Inventory Status • Complete Inventory Reports • Programmable Auto Report Times • Inventory Increase Report • Timed Sudden Loss Detection Optional
BUSINESS INVENTORY RECONCILIATION
Shift-Based Reconciliation Reconciliation by Tank
TANK CALIBRATION
Multi-Pass Tank Calibration Single-Pass / Metered Drop Limited Range Calibration Supports Multiple Tank Charts per Tank Supports Multiple Line Manifold Tanks Graphical / Text Calibration Diagnostics Automatic and Manual Meter Mapping
IN-TANK LEAK TEST
0.1 GPH Tank Tightness Testing Optional
0.2 GPH Tank Tightness Testing Optional
Continuous Statistical Leak Detection Optional Selectable Test Rates Optional Programmable Automatic Test Schedules Optional PASS, FAIL, or INVALID Indicators Optional
LINE LEAK DETECTION
Integral Line Leak Detector Programmable Line Test Features
INTERSTITIAL/SUMP LEAK SENSING
Tank Annulus • Sump • Dispenser Pan • Mag Sump • Sensor Location Identifiers •
VAPOR WELL MONITORING
Hydrocarbon Vapor Detection • High Water Level Alarm •
GROUNDWATER MONITORING
Hydrocarbon Liquid Detection • Low Water Alarm •
AIR VAPOR MONITORING
Vapor Collection Monitor
ALARMS
Leak • Overfill • High Level • Sudden Loss Optional High Water • Low Inventory • Programmable Alarm Limits •
Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.
Example Illustrations
Illustrations used in this guide for example sensor installations may contain components that are customer supplied and not included with the sensor. Please check with your Veeder-Root Distributor for recommended installation accessories.
Third Party Evaluations
Third party evaluations of the Veeder-Root sensors contained in this application guide can be found under the Veeder-Root vendor name on the National Work Group on Leak Detection Evaluations (NWGLDE) website:
http://www.nwglde.org
©2019 Veeder-Root. All rights reserved.
http://www.nwglde.org