This solicitation notice announces a firm fixed price construction contract for renovating an outpatient clinic. The project involves renovating an existing VA outpatient clinic and will be 100% set aside for Service Disabled Veteran Owned Small Businesses. The solicitation is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. Responses are due by the date specified in the solicitation documents. The contract will be awarded as a firm fixed price contract.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
1. GENERAL REQUIREMENTS
A. GENERAL
1. DESCRIPTION: FURNISH AND INSTALL ELECTRICAL SYSTEMS, MATERIALS, EQUIPMENT,
AND ACCESSORIES IN ACCORDANCE WITH THE SPECIFICATIONS AND DRAWINGS.
CAPACITIES AND RATINGS OF MOTORS, TRANSFORMERS, CONDUCTORS AND CABLE,
SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, MOTOR CONTROL CENTERS,
GENERATORS, AUTOMATIC TRANSFER SWITCHES, AND OTHER ITEMS AND
ARRANGEMENTS FOR THE SPECIFIED ITEMS ARE SHOWN ON THE DRAWINGS.
2. ELECTRICAL SERVICE ENTRANCE EQUIPMENT AND ARRANGEMENTS FOR TEMPORARY
AND PERMANENT CONNECTIONS TO THE ELECTRIC UTILITY COMPANY’S SYSTEM SHALL
CONFORM TO THE ELECTRIC UTILITY COMPANY’S REQUIREMENTS. COORDINATE FUSES,
CIRCUIT BREAKERS AND RELAYS WITH THE ELECTRIC UTILITY COMPANY’S SYSTEM, AND
OBTAIN ELECTRIC UTILITY COMPANY APPROVAL FOR SIZES AND SETTINGS OF THESE
DEVICES.
3. CONDUCTOR AMPACITIES SPECIFIED OR SHOWN ON THE DRAWINGS ARE BASED ON
COPPER CONDUCTORS, WITH THE CONDUIT AND RACEWAYS SIZED PER NEC. ALUMINUM
CONDUCTORS ARE PROHIBITED.
4. THE LATEST INTERNATIONAL BUILDING CODE (IBC), UNDERWRITERS LABORATORIES, INC.
(UL), INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE), AND NATIONAL
FIRE PROTECTION ASSOCIATION (NFPA) CODES AND STANDARDS ARE THE MINIMUM
REQUIREMENTS FOR MATERIALS AND INSTALLATION.
5. THE DRAWINGS AND SPECIFICATIONS SHALL GOVERN IN THOSE INSTANCES WHERE
REQUIREMENTS ARE GREATER THAN THOSE STATED IN THE ABOVE CODES AND
STANDARDS.
6. TEST STANDARDS: ALL MATERIALS AND EQUIPMENT SHALL BE LISTED, LABELED, OR
CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) TO MEET
UNDERWRITERS LABORATORIES, INC. (UL), STANDARDS WHERE TEST STANDARDS HAVE
BEEN ESTABLISHED. MATERIALS AND EQUIPMENT WHICH ARE NOT COVERED BY UL
STANDARDS WILL BE ACCEPTED, PROVIDING THAT MATERIALS AND EQUIPMENT ARE
LISTED, LABELED, CERTIFIED OR OTHERWISE DETERMINED TO MEET THE SAFETY
REQUIREMENTS OF A NRTL. MATERIALS AND EQUIPMENT WHICH NO NRTL ACCEPTS,
CERTIFIES, LISTS, LABELS, OR DETERMINES TO BE SAFE, WILL BE CONSIDERED IF
INSPECTED OR TESTED IN ACCORDANCE WITH NATIONAL INDUSTRIAL STANDARDS, SUCH
AS ANSI, NEMA, AND NETA. EVIDENCE OF COMPLIANCE SHALL INCLUDE CERTIFIED TEST
REPORTS AND DEFINITIVE SHOP DRAWINGS.
7. MATERIALS AND EQUIPMENT PROTECTION: MATERIALS AND EQUIPMENT SHALL BE
PROTECTED DURING SHIPMENT AND STORAGE AGAINST PHYSICAL DAMAGE, VERMIN,
DIRT, CORROSIVE SUBSTANCES, FUMES, MOISTURE, COLD AND RAIN.
8. WORK PERFORMANCE
a. ALL ELECTRICAL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST NFPA 70
(NEC), NFPA 70B, NFPA 70E, NFPA 99, NFPA 110, OSHA PART 1910 SUBPART J –
GENERAL ENVIRONMENTAL CONTROLS, OSHA PART 1910 SUBPART K – MEDICAL AND
FIRST AID, AND OSHA PART 1910 SUBPART S – ELECTRICAL, IN ADDITION TO OTHER
REFERENCES REQUIRED BY CONTRACT.
b. JOB SITE SAFETY AND WORKER SAFETY IS THE RESPONSIBILITY OF THE
CONTRACTOR.
c. FOR WORK THAT AFFECTS EXISTING ELECTRICAL SYSTEMS, ARRANGE, PHASE AND
PERFORM WORK TO ASSURE MINIMAL INTERFERENCE WITH NORMAL FUNCTIONING OF
THE FACILITY. REFER TO ARTICLE OPERATIONS AND STORAGE AREAS UNDER
SECTION GENERAL REQUIREMENTS.
d. NEW WORK SHALL BE INSTALLED AND CONNECTED TO EXISTING WORK NEATLY, SAFELY AND PROFESSIONALLY. DISTURBED OR DAMAGED WORK SHALL BE REPLACED
OR REPAIRED TO ITS PRIOR CONDITIONS, AS REQUIRED BY SECTION GENERAL
REQUIREMENTS.
e. COORDINATE LOCATION OF EQUIPMENT AND CONDUIT WITH OTHER TRADES TO
MINIMIZE INTERFERENCE.
9. EQUIPMENT INSTALLATION AND REQUIREMENTS:
a. EQUIPMENT LOCATION SHALL BE AS CLOSE AS PRACTICAL TO LOCATIONS SHOWN ON
THE DRAWINGS.
b. WORKING CLEARANCES SHALL NOT BE LESS THAN SPECIFIED IN THE NEC.
c. ELECTRICAL SERVICE ENTRANCE EQUIPMENT AND ARRANGEMENTS FOR TEMPORARY
AND PERMANENT CONNECTIONS TO THE ELECTRIC UTILITY COMPANY’S SYSTEM
SHALL CONFORM TO THE ELECTRIC UTILITY COMPANY'S REQUIREMENTS.
COORDINATE FUSES, CIRCUIT BREAKERS AND RELAYS WITH THE ELECTRIC UTILITY
COMPANY’S SYSTEM, AND OBTAIN ELECTRIC UTILITY COMPANY APPROVAL FOR SIZES
AND SETTINGS OF THESE DEVICES.
10. EQUIPMENT ID
a. IN ADDITION TO THE REQUIREMENTS OF THE NEC, INSTALL AN IDENTIFICATION SIGN
WHICH CLEARLY INDICATES INFORMATION REQUIRED FOR USE AND MAINTENANCE OF
ITEMS SUCH AS SWITCHBOARDS AND SWITCHGEAR, PANELBOARDS, CABINETS,
MOTOR CONTROLLERS, FUSED AND NON-FUSED SAFETY SWITCHES, GENERATORS,
AUTOMATIC TRANSFER SWITCHES, SEPARATELY ENCLOSED CIRCUIT BREAKERS,
INDIVIDUAL BREAKERS AND CONTROLLERS IN SWITCHBOARDS, SWITCHGEAR AND
MOTOR CONTROL ASSEMBLIES, CONTROL DEVICES AND OTHER SIGNIFICANT
EQUIPMENT.
b. INSTALL ADHESIVE ARC FLASH WARNING LABELS ON ALL EQUIPMENT AS REQUIRED BY
THE LATEST NFPA 70E. LABEL SHALL SHOW SPECIFIC AND CORRECT INFORMATION
FOR SPECIFIC EQUIPMENT BASED ON ITS ARC FLASH CALCULATIONS.
B. SUBMITTALS
1. SUBMIT SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES IN APPROPRIATE SUBMITTAL
PACKAGES.
2. APPROVAL SHALL BE OBTAINED FOR ALL MATERIALS AND EQUIPMENT BEFORE DELIVERY
TO THE JOB SITE. DELIVERY, STORAGE OR INSTALLATION OF MATERIALS AND
EQUIPMENT WHICH HAS NOT HAD PRIOR APPROVAL WILL NOT BE PERMITTED.
3. ALL SUBMITTALS SHALL INCLUDE SIX COPIES OF ADEQUATE DESCRIPTIVE LITERATURE,
CATALOG CUTS, SHOP DRAWINGS, TEST REPORTS, CERTIFICATIONS, SAMPLES, AND
OTHER DATA NECESSARY FOR THE TO ASCERTAIN THAT THE PROPOSED MATERIALS AND
EQUIPMENT COMPLY WITH DRAWING AND SPECIFICATION REQUIREMENTS. CATALOG
CUTS SUBMITTED FOR APPROVAL SHALL BE LEGIBLE AND CLEARLY IDENTIFY SPECIFIC
MATERIALS AND EQUIPMENT BEING SUBMITTED.
4. SUBMITTALS FOR INDIVIDUAL SYSTEMS AND EQUIPMENT ASSEMBLIES WHICH CONSIST OF
MORE THAN ONE ITEM OR COMPONENT SHALL BE MADE FOR THE SYSTEM OR ASSEMBLY
AS A WHOLE. PARTIAL SUBMITTALS WILL NOT BE CONSIDERED FOR APPROVAL.
5. SUBMIT AS REQUIRED FOR SYSTEMS AND EQUIPMENT SPECIFIED IN THE TECHNICAL
SECTIONS. FURNISH IN HARDCOVER BINDERS OR AN APPROVED EQUIVALENT.
6. APPROVALS WILL BE BASED ON COMPLETE SUBMISSION OF SHOP DRAWINGS, MANUALS,
TEST REPORTS, CERTIFICATIONS, AND SAMPLES AS APPLICABLE.
7. WARRANTY
a. ALL WORK PERFORMED AND ALL EQUIPMENT AND MATERIAL FURNISHED UNDER THIS
DIVISION SHALL BE FREE FROM DEFECTS AND SHALL REMAIN SO FOR A PERIOD OF
ONE YEAR FROM THE DATE OF ACCEPTANCE OF THE ENTIRE INSTALLATION.
2. LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
A. GENERAL
1. DESCRIPTION: FURNISHING, INSTALLATION, CONNECTION, AND TESTING OF THE
ELECTRICAL CONDUCTORS AND CABLES FOR USE IN ELECTRICAL SYSTEMS RATED 600 V
AND BELOW, INDICATED AS CABLE(S), CONDUCTOR(S), WIRE, OR WIRING IN THIS SECTION.
2. SUBMITTALS
a. SHOP DRAWINGS: SUBMIT SUFFICIENT INFORMATION TO DEMONSTRATE COMPLIANCE
WITH DRAWINGS AND SPECIFICATIONS.
b. SHOP DRAWINGS: ELECTRICAL RATINGS AND INSULATION TYPE FOR EACH
CONDUCTOR AND CABLE.
c. SUBMIT THE FOLLOWING DATA FOR APPROVAL: ELECTRICAL RATINGS AND
INSULATION TYPE FOR EACH CONDUCTOR AND CABLE.
d. SUBMIT THE FOLLOWING DATA FOR APPROVAL: SPLICING MATERIALS AND PULLING
LUBRICANT.
B. PRODUCTS
1. CONDUCTORS AND CABLES
a. CONDUCTORS AND CABLES SHALL BE IN ACCORDANCE WITH ASTM, NEMA, NFPA, UL, AS SPECIFIED, AND AS SHOWN ON THE DRAWINGS.
b. ALL CONDUCTORS SHALL BE COPPER.
c. SINGLE CONDUCTOR AND CABLE:
• NO. 12 AWG: MINIMUM SIZE, EXCEPT WHERE SMALLER SIZES ARE SPECIFIED
HEREIN OR SHOWN ON THE DRAWINGS.
• NO. 8 AWG AND LARGER: STRANDED.
• NO. 10 AWG AND SMALLER: SOLID; EXCEPT SHALL BE STRANDED FOR FINAL
CONNECTION TO MOTORS, TRANSFORMERS, AND VIBRATING EQUIPMENT.
• INSULATION: THHN-THWN AND XHHW-2. XHHW-2 SHALL BE USED FOR ISOLATED
POWER SYSTEMS.
d. COLOR CODE:
• NO. 10 AWG AND SMALLER: SOLID COLOR INSULATION OR SOLID COLOR COATING.
• NO. 8 AWG AND LARGER: COLOR-CODED USING ONE OF THE FOLLOWING
METHODS:
• SOLID COLOR INSULATION OR SOLID COLOR COATING.
• STRIPES, BANDS, OR HASH MARKS OF COLOR SPECIFIED.
• COLOR USING 19 MM (0.75 INCHES) WIDE TAPE.
e. FOR MODIFICATIONS AND ADDITIONS TO EXISTING WIRING SYSTEMS, COLOR CODING
SHALL CONFORM TO THE EXISTING WIRING SYSTEM.
f. LIGHTING CIRCUIT “SWITCH LEGS”, AND 3-WAY AND 4-WAY SWITCH “TRAVELING
WIRES,” SHALL HAVE COLOR CODING THAT IS UNIQUE AND DISTINCT (E.G., PINK AND
PURPLE) FROM THE COLOR CODING INDICATED ABOVE. THE UNIQUE COLOR CODES
SHALL BE SOLID AND IN ACCORDANCE WITH THE NEC. COORDINATE COLOR CODING IN
THE FIELD CLIENT PROJECT REPRESENTATIVE.
g. COLOR CODE FOR ISOLATED POWER SYSTEM WIRING SHALL BE IN ACCORDANCE WITH
THE NEC.
• 208/120V PHASE 480/277V
• BLACK A BROWN
• RED B ORANGE
• BLUE C YELLOW
• WHITE NEUTRAL GRAY*
• * OR WHITE WITH COLORED (OTHER THAN GREEN) TRACER.
3. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
A. GENERAL
1. DESCRIPTION: FURNISHING, INSTALLATION, CONNECTION, AND TESTING OF GROUNDING
AND BONDING EQUIPMENT, INDICATED AS GROUNDING EQUIPMENT IN THIS SECTION.
2. “GROUNDING ELECTRODE SYSTEM” REFERS TO GROUNDING ELECTRODE CONDUCTORS
AND ALL ELECTRODES REQUIRED OR ALLOWED BY NEC, AS WELL AS MADE,
SUPPLEMENTARY, AND LIGHTNING PROTECTION SYSTEM GROUNDING ELECTRODES.
3. THE TERMS “CONNECT” AND “BOND” ARE USED INTERCHANGEABLY IN THIS SECTION AND
HAVE THE SAME MEANING.
4. SUBMITTALS
a. SHOP DRAWINGS:
• SUBMIT SUFFICIENT INFORMATION TO DEMONSTRATE COMPLIANCE WITH
DRAWINGS AND SPECIFICATIONS.
• SUBMIT PLANS SHOWING THE LOCATION OF SYSTEM GROUNDING ELECTRODES
AND CONNECTIONS, AND THE ROUTING OF ABOVEGROUND AND UNDERGROUND
GROUNDING ELECTRODE CONDUCTORS.
B. PRODUCTS
1. GROUNDING AND BONDING CONDUCTORS
a. EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSULATED STRANDED COPPER, EXCEPT THAT SIZES NO. 10 AWG AND SMALLER SHALL BE SOLID COPPER. INSULATION
COLOR SHALL BE CONTINUOUS GREEN FOR ALL EQUIPMENT GROUNDING
CONDUCTORS, EXCEPT THAT WIRE SIZES NO. 4 AWG AND LARGER SHALL BE
IDENTIFIED PER NEC.
b. BONDING CONDUCTORS SHALL BE BARE STRANDED COPPER, EXCEPT THAT SIZES
NO. 10 AWG AND SMALLER SHALL BE BARE SOLID COPPER. BONDING CONDUCTORS
SHALL BE STRANDED FOR FINAL CONNECTION TO MOTORS, TRANSFORMERS, AND
VIBRATING EQUIPMENT.
c. CONDUCTOR SIZES SHALL NOT BE LESS THAN SHOWN ON THE DRAWINGS, OR NOT
LESS THAN REQUIRED BY THE NEC, WHICHEVER IS GREATER.
d. INSULATION: THHN-THWN AND XHHW-2. XHHW-2 SHALL BE USED FOR ISOLATED
POWER SYSTEMS.
2. GROUND RODS: CONCRETE ENCASED ELECTRODE SHALL BE NO. 4 AWG BARE COPPER
WIRE, INSTALLED PER NEC.
3. GROUND CONNECTIONS:
a. BELOW GRADE:
• BELOW GRADE AND INACCESSIBLE LOCATIONS: EXOTHERMIC-WELDED TYPE
CONNECTORS.
b. ABOVE GRADE:
• BONDING JUMPERS: LISTED FOR USE WITH ALUMINUM AND COPPER
CONDUCTORS. FOR WIRE SIZES NO. 8 AWG AND LARGER, USE COMPRESSION-
TYPE CONNECTORS. FOR WIRE SIZES SMALLER THAN NO. 8 AWG, USE
MECHANICAL TYPE LUGS. CONNECTORS OR LUGS SHALL USE ZINC-PLATED STEEL
BOLTS, NUTS, AND WASHERS. BOLTS SHALL BE TORQUED TO THE VALUES
RECOMMENDED BY THE MANUFACTURER.
• CONNECTION TO BUILDING STEEL: EXOTHERMIC-WELDED TYPE CONNECTORS.
• CONNECTION TO GROUNDING BUS BARS: LISTED FOR USE WITH ALUMINUM AND
COPPER CONDUCTORS. USE MECHANICAL TYPE LUGS, WITH ZINC-PLATED STEEL
BOLTS, NUTS, AND WASHERS. BOLTS SHALL BE TORQUED TO THE VALUES
RECOMMENDED BY THE MANUFACTURER.
• CONNECTION TO EQUIPMENT RACK AND CABINET GROUND BARS: LISTED FOR USE
WITH ALUMINUM AND COPPER CONDUCTORS. USE MECHANICAL TYPE LUGS, WITH
//ZINC-PLATED//CADMIUM-PLATED// STEEL BOLTS, NUTS, AND WASHERS. BOLTS
SHALL BE TORQUED TO THE VALUES RECOMMENDED BY THE MANUFACTURER.
c. EQUIPMENT RACK AND CABINET GROUND BARS: PROVIDE SOLID COPPER GROUND
BARS DESIGNED FOR MOUNTING ON THE FRAMEWORK OF OPEN OR CABINET-
ENCLOSED EQUIPMENT RACKS. GROUND BARS SHALL HAVE MINIMUM DIMENSIONS
OF 6.3 MM (0.25 INCH) THICK X 19 MM (0.75 INCH) WIDE, WITH LENGTH AS REQUIRED OR
AS SHOWN ON THE DRAWINGS. PROVIDE INSULATORS AND MOUNTING BRACKETS.
d. GROUND TERMINAL BLOCKS: AT ANY EQUIPMENT MOUNTING LOCATION (E.G., BACKBOARDS AND HINGED COVER ENCLOSURES) WHERE RACK-TYPE GROUND BARS
CANNOT BE MOUNTED, PROVIDE MECHANICAL TYPE LUGS, WITH ZINC-PLATED STEEL
BOLTS, NUTS, AND WASHERS. BOLTS SHALL BE TORQUED TO THE VALUES
RECOMMENDED BY THE MANUFACTURER.
e. GROUNDING BUS BAR: PRE-DRILLED RECTANGULAR COPPER BAR WITH STAND-OFF
INSULATORS, MINIMUM 6.3 MM (0.25 INCH) THICK X 100 MM (4 INCHES) HIGH IN CROSS-
SECTION, LENGTH AS SHOWN ON THE DRAWINGS, WITH HOLE SIZE, QUANTITY, AND
SPACING PER DETAIL SHOWN ON THE DRAWINGS. PROVIDE INSULATORS AND
MOUNTING BRACKETS.
4. RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
A. GENERAL
1. DESCRIPTION: FURNISHING, INSTALLATION, AND CONNECTION OF CONDUIT, FITTINGS,
AND BOXES, TO FORM COMPLETE, COORDINATED, GROUNDED RACEWAY SYSTEMS.
RACEWAYS ARE REQUIRED FOR ALL WIRING UNLESS SHOWN OR SPECIFIED OTHERWISE.
2. THE TERM CONDUIT, AS USED IN THIS SPECIFICATION, SHALL MEAN ANY OR ALL OF THE
RACEWAY TYPES SPECIFIED.
3. SUBMITTALS
a. SHOP DRAWINGS: SIZE AND LOCATION OF MAIN FEEDERS, SIZE AND LOCATION OF
PANELS AND PULL-BOXES, LAYOUT OF REQUIRED CONDUIT PENETRATIONS
THROUGH STRUCTURAL ELEMENTS, RACEWAY TYPES AND SIZES, CONDUIT BODIES,
CONNECTORS AND FITTINGS, JUNCTION AND PULL BOXES, TYPES AND SIZES.
B. PRODUCTS
1. MATERIALS:
a. CONDUIT SIZE: IN ACCORDANCE WITH THE NEC, BUT NOT LESS THAN 13 MM (0.5-
INCH) UNLESS OTHERWISE SHOWN.
2. MATERIALS – CONDUIT:
a. SIZE: IN ACCORDANCE WITH THE NEC, BUT NOT LESS THAN 13 MM (0.5-INCH).
b. RIGID STEEL CONDUIT (RMC): SHALL CONFORM TO UL 6 AND NEMA C80.1.
c. RIGID INTERMEDIATE STEEL CONDUIT (IMC): SHALL CONFORM TO UL 1242 AND NEMA
C80.6.
d. ELECTRICAL METALLIC TUBING (EMT): SHALL CONFORM TO UL 797 AND NEMA C80.3.
MAXIMUM SIZE NOT TO EXCEED 105 MM (4 INCHES) AND SHALL BE
e. FLEXIBLE METAL CONDUIT: SHALL CONFORM TO UL 1.
f. LIQUID-TIGHT FLEXIBLE METAL CONDUIT: SHALL CONFORM TO UL 360.
g. DIRECT BURIAL PLASTIC CONDUIT: SHALL CONFORM TO UL 651 AND UL 651A, HEAVY
WALL PVC OR HIGH DENSITY POLYETHYLENE (PE).
h. SURFACE METAL RACEWAY: SHALL CONFORM TO UL 5.
2. SPLICES
a. SPLICES SHALL BE IN ACCORDANCE WITH NEC AND UL.
b. ABOVE GROUND SPLICES FOR NO. 10 AWG AND SMALLER:
• SOLDERLESS, SCREW-ON, REUSABLE PRESSURE CABLE TYPE, WITH INTEGRAL
INSULATION, APPROVED FOR COPPER AND ALUMINUM CONDUCTORS.
• THE INTEGRAL INSULATOR SHALL HAVE A SKIRT TO COMPLETELY COVER THE
STRIPPED CONDUCTORS.
• THE NUMBER, SIZE, AND COMBINATION OF CONDUCTORS USED WITH THE
CONNECTOR, AS LISTED ON THE MANUFACTURER'S PACKAGING, SHALL BE
STRICTLY FOLLOWED.
c. ABOVE GROUND SPLICES FOR NO. 8 AWG TO NO. 4/0 AWG:
• COMPRESSION, HEX SCREW, OR BOLT CLAMP-TYPE OF HIGH CONDUCTIVITY AND
CORROSION-RESISTANT MATERIAL, LISTED FOR USE WITH COPPER AND
ALUMINUM CONDUCTORS.
• INSULATE WITH MATERIALS APPROVED FOR THE PARTICULAR USE, LOCATION,
VOLTAGE, AND TEMPERATURE. INSULATION LEVEL SHALL BE NOT LESS THAN THE
INSULATION LEVEL OF THE CONDUCTORS BEING JOINED.
• SPLICE AND INSULATION SHALL BE PRODUCT OF THE SAME MANUFACTURER.
• ALL BOLTS, NUTS, AND WASHERS USED WITH SPLICES SHALL BE ZINC-PLATED
STEEL.
3. CONNECTIONS:
a. MECHANICAL TYPE OF HIGH CONDUCTIVITY AND CORROSION-RESISTANT MATERIAL, LISTED FOR USE WITH COPPER AND ALUMINUM CONDUCTORS.
b. LONG BARREL COMPRESSION TYPE OF HIGH CONDUCTIVITY AND
CORROSION-RESISTANT MATERIAL, WITH MINIMUM OF TWO COMPRESSION INDENTS
PER WIRE, LISTED FOR USE WITH COPPER AND ALUMINUM CONDUCTORS.
c. ALL BOLTS, NUTS, AND WASHERS USED TO CONNECT CONNECTIONS AND
TERMINATIONS TO BUS BARS OR OTHER TERMINATION POINTS SHALL BE ZINC-PLATED
STEEL.
4. CONTROL WIRING
a. UNLESS OTHERWISE SPECIFIED ELSEWHERE IN THESE SPECIFICATIONS, CONTROL
WIRING SHALL BE AS SPECIFIED HEREIN, EXCEPT THAT THE MINIMUM SIZE SHALL BE
NOT LESS THAN NO. 14 AWG.
b. CONTROL WIRING SHALL BE SIZED SUCH THAT THE VOLTAGE DROP UNDER IN-RUSH
CONDITIONS DOES NOT ADVERSELY AFFECT OPERATION OF THE CONTROLS.
C. EXECUTION
1. GENERAL
a. INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, AS SHOWN ON THE
DRAWINGS, AND MANUFACTURER’S INSTRUCTIONS.
b. INSTALL ALL CONDUCTORS IN RACEWAY SYSTEMS.
c. SPLICE CONDUCTORS ONLY IN OUTLET BOXES, JUNCTION BOXES, PULLBOXES, MANHOLES, OR HANDHOLES.
d. CONDUCTORS OF DIFFERENT SYSTEMS (E.G., 120 V AND 277 V) SHALL NOT BE
INSTALLED IN THE SAME RACEWAY.
e. INSTALL CABLE SUPPORTS FOR ALL VERTICAL FEEDERS IN ACCORDANCE WITH THE
NEC. PROVIDE SPLIT WEDGE TYPE WHICH FIRMLY CLAMPS EACH INDIVIDUAL CABLE
AND TIGHTENS DUE TO CABLE WEIGHT.
f. IN PANELBOARDS, CABINETS, WIREWAYS, SWITCHES, ENCLOSURES, AND EQUIPMENT
ASSEMBLIES, NEATLY FORM, TRAIN, AND TIE THE CONDUCTORS WITH NON-METALLIC
TIES.
g. FOR CONNECTIONS TO MOTORS, TRANSFORMERS, AND VIBRATING EQUIPMENT, STRANDED CONDUCTORS SHALL BE USED ONLY FROM THE LAST FIXED POINT OF
CONNECTION TO THE MOTORS, TRANSFORMERS, OR VIBRATING EQUIPMENT.
h. USE EXPANDING FOAM OR NON-HARDENING DUCT-SEAL TO SEAL CONDUITS
ENTERING A BUILDING, AFTER INSTALLATION OF CONDUCTORS.
i. NO MORE THAN THREE BRANCH CIRCUITS SHALL BE INSTALLED IN ANY ONE CONDUIT.
2. SPLICES AND TERMINATIONS INSTALLATION: SPLICES AND TERMINATIONS SHALL BE
MECHANICALLY AND ELECTRICALLY SECURE, AND TIGHTENED TO MANUFACTURER’S
PUBLISHED TORQUE VALUES USING A TORQUE SCREWDRIVER OR WRENCH.
3. CONDUCTOR IDENTIFICATION: WHEN USING COLORED TAPE TO IDENTIFY PHASE,
NEUTRAL, AND GROUND CONDUCTORS LARGER THAN NO. 8 AWG, APPLY TAPE IN HALF-
OVERLAPPING TURNS FOR A MINIMUM OF 75 MM (3 INCHES) FROM TERMINAL POINTS, AND
IN JUNCTION BOXES, PULLBOXES, AND MANHOLES. APPLY THE LAST TWO LAPS OF TAPE
WITH NO TENSION TO PREVENT POSSIBLE UNWINDING. WHERE CABLE MARKINGS ARE
COVERED BY TAPE, APPLY TAGS TO CABLE, STATING SIZE AND INSULATION TYPE.
4. FEEDER CONDUCTOR IDENTIFICATION: IN EACH INTERIOR PULLBOX AND EACH
UNDERGROUND MANHOLE AND HANDHOLE, INSTALL BRASS TAGS ON ALL FEEDER
CONDUCTORS TO CLEARLY DESIGNATE THEIR CIRCUIT IDENTIFICATION AND VOLTAGE.
THE TAGS SHALL BE THE EMBOSSED TYPE, 40 MM (1-1/2 INCHES) IN DIAMETER AND 40
MILS THICK. ATTACH TAGS WITH PLASTIC TIES.
5. EXISTING CONDUCTORS: UNLESS SPECIFICALLY INDICATED ON THE PLANS, EXISTING
CONDUCTORS SHALL NOT BE REUSED.
6. CONTROL WIRING INSTALLATION: INSTALL A SEPARATE POWER SUPPLY CIRCUIT FOR
EACH SYSTEM, EXCEPT WHERE OTHERWISE SHOWN ON THE DRAWINGS.
7. ACCEPTANCE CHECKS AND TESTS:
a. AFTER INSTALLATION BUT BEFORE CONNECTION TO UTILIZATION DEVICES, SUCH AS
FIXTURES, MOTORS, OR APPLIANCES, TEST CONDUCTORS PHASE-TO-PHASE AND
PHASE-TO-GROUND RESISTANCE WITH AN INSULATION RESISTANCE TESTER.
EXISTING CONDUCTORS TO BE REUSED SHALL ALSO BE TESTED.
b. PERFORM PHASE ROTATION TEST ON ALL THREE-PHASE CIRCUITS
C. EXECUTION
1. GENERAL
a. INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, AS SHOWN ON THE
DRAWINGS, AND MANUFACTURER’S INSTRUCTIONS.
b. SYSTEM GROUNDING
• SECONDARY SERVICE NEUTRALS: GROUND AT THE SUPPLY SIDE OF THE
SECONDARY DISCONNECTING MEANS AND AT THE RELATED TRANSFORMER.
• SEPARATELY DERIVED SYSTEMS (TRANSFORMERS DOWNSTREAM FROM THE
SERVICE ENTRANCE): GROUND THE SECONDARY NEUTRAL.
• ISOLATION TRANSFORMERS AND ISOLATED POWER SYSTEMS SHALL NOT BE
SYSTEM GROUNDED.
c. EQUIPMENT GROUNDING: METALLIC PIPING, BUILDING STRUCTURAL STEEL, ELECTRICAL ENCLOSURES, RACEWAYS, JUNCTION BOXES, OUTLET BOXES, CABINETS, MACHINE FRAMES, AND OTHER CONDUCTIVE ITEMS IN CLOSE PROXIMITY WITH
ELECTRICAL CIRCUITS, SHALL BE BONDED AND GROUNDED.
2. INACCESSIBLE GROUNDING CONNECTIONS
a. MAKE GROUNDING CONNECTIONS, WHICH ARE NORMALLY BURIED OR OTHERWISE
INACCESSIBLE, BY EXOTHERMIC WELD.
3. SECONDARY VOLTAGE EQUIPMENT AND CIRCUITS
a. MAIN BONDING JUMPER: BOND THE SECONDARY SERVICE NEUTRAL TO THE GROUND
BUS IN THE SERVICE EQUIPMENT.
b. METALLIC PIPING, BUILDING STRUCTURAL STEEL, AND SUPPLEMENTAL ELECTRODE(S)
c. PROVIDE A GROUNDING ELECTRODE CONDUCTOR SIZED PER NEC BETWEEN THE
SERVICE EQUIPMENT GROUND BUS AND ALL METALLIC WATER PIPE SYSTEMS,
BUILDING STRUCTURAL STEEL, AND SUPPLEMENTAL OR MADE ELECTRODES.
PROVIDE JUMPERS ACROSS INSULATING JOINTS IN THE METALLIC PIPING.
d. PROVIDE A SUPPLEMENTAL GROUND ELECTRODE AS SHOWN ON THE DRAWINGS AND
BOND TO THE GROUNDING ELECTRODE SYSTEM.
e. SWITCHGEAR, SWITCHBOARDS, UNIT SUBSTATIONS, PANELBOARDS, MOTOR
CONTROL CENTERS, ENGINE-GENERATORS, AUTOMATIC TRANSFER SWITCHES, AND
OTHER ELECTRICAL EQUIPMENT:
f. CONNECT THE EQUIPMENT GROUNDING CONDUCTORS TO THE GROUND BUS.
g. CONNECT METALLIC CONDUITS BY GROUNDING BUSHINGS AND EQUIPMENT
GROUNDING CONDUCTOR TO THE EQUIPMENT GROUND BUS.
h. EXTERIOR: EXTERIOR TRANSFORMERS SUPPLYING INTERIOR SERVICE EQUIPMENT
SHALL HAVE THE NEUTRAL GROUNDED AT THE TRANSFORMER SECONDARY. PROVIDE
A GROUNDING ELECTRODE AT THE TRANSFORMER.
i. SEPARATELY DERIVED SYSTEMS (TRANSFORMERS DOWNSTREAM FROM SERVICE
EQUIPMENT): GROUND THE SECONDARY NEUTRAL AT THE TRANSFORMER. PROVIDE A
GROUNDING ELECTRODE CONDUCTOR FROM THE TRANSFORMER TO THE NEAREST
COMPONENT OF THE GROUNDING ELECTRODE SYSTEM OR THE GROUND BAR AT THE
SERVICE EQUIPMENT.
4. RACEWAY
a. CONDUIT SYSTEMS
• GROUND ALL METALLIC CONDUIT SYSTEMS. ALL METALLIC CONDUIT SYSTEMS
SHALL CONTAIN AN EQUIPMENT GROUNDING CONDUCTOR.
• NON-METALLIC CONDUIT SYSTEMS, EXCEPT NON-METALLIC FEEDER CONDUITS
THAT CARRY A GROUNDED CONDUCTOR FROM EXTERIOR TRANSFORMERS TO
INTERIOR OR BUILDING-MOUNTED SERVICE ENTRANCE EQUIPMENT, SHALL
CONTAIN AN EQUIPMENT GROUNDING CONDUCTOR.
• METALLIC CONDUIT THAT ONLY CONTAINS A GROUNDING CONDUCTOR, AND IS
PROVIDED FOR ITS MECHANICAL PROTECTION, SHALL BE BONDED TO THAT
CONDUCTOR AT THE ENTRANCE AND EXIT FROM THE CONDUIT.
• METALLIC CONDUITS WHICH TERMINATE WITHOUT MECHANICAL CONNECTION TO
AN ELECTRICAL EQUIPMENT HOUSING BY MEANS OF LOCKNUT AND BUSHINGS OR
ADAPTERS, SHALL BE PROVIDED WITH GROUNDING BUSHINGS. CONNECT
BUSHINGS WITH A EQUIPMENT GROUNDING CONDUCTOR TO THE EQUIPMENT
GROUND BUS.
• FEEDERS AND BRANCH CIRCUITS: INSTALL EQUIPMENT GROUNDING CONDUCTORS
WITH ALL FEEDERS, AND POWER AND LIGHTING BRANCH CIRCUITS.
• BOXES, CABINETS, ENCLOSURES, AND PANELBOARDS: BOND THE EQUIPMENT
GROUNDING CONDUCTOR TO EACH PULLBOX, JUNCTION BOX, OUTLET BOX,
DEVICE BOX, CABINETS, AND OTHER ENCLOSURES THROUGH WHICH THE
CONDUCTOR PASSES (EXCEPT FOR SPECIAL GROUNDING SYSTEMS FOR
INTENSIVE CARE UNITS AND OTHER CRITICAL UNITS SHOWN).
• BOXES, CABINETS, ENCLOSURES, AND PANELBOARDS: PROVIDE LUGS IN EACH
BOX AND ENCLOSURE FOR EQUIPMENT GROUNDING CONDUCTOR TERMINATION.
b. RECEPTACLES SHALL NOT BE GROUNDED THROUGH THEIR MOUNTING SCREWS.
GROUND RECEPTACLES WITH A JUMPER FROM THE RECEPTACLE GREEN GROUND
TERMINAL TO THE DEVICE BOX GROUND SCREW AND A JUMPER TO THE BRANCH
CIRCUIT EQUIPMENT GROUNDING CONDUCTOR.
c. GROUND LIGHTING FIXTURES TO THE EQUIPMENT GROUNDING CONDUCTOR OF THE
WIRING SYSTEM. FIXTURES CONNECTED WITH FLEXIBLE CONDUIT SHALL HAVE A
GREEN GROUND WIRE INCLUDED WITH THE POWER WIRES FROM THE FIXTURE
THROUGH THE FLEXIBLE CONDUIT TO THE FIRST OUTLET BOX.
5. CORROSION INHIBITORS: WHEN MAKING GROUNDING AND BONDING CONNECTIONS,
APPLY A CORROSION INHIBITOR TO ALL CONTACT SURFACES. USE CORROSION
INHIBITOR APPROPRIATE FOR PROTECTING A CONNECTION BETWEEN THE METALS USED.
6. CONDUCTIVE PIPING: BOND ALL CONDUCTIVE PIPING SYSTEMS, INTERIOR AND
EXTERIOR, TO THE GROUNDING ELECTRODE SYSTEM. BONDING CONNECTIONS SHALL BE
MADE AS CLOSE AS PRACTICAL TO THE EQUIPMENT GROUND BUS.
7. LIGHTNING PROTECTION SYSTEM: BOND THE LIGHTNING PROTECTION SYSTEM TO THE
ELECTRICAL GROUNDING ELECTRODE SYSTEM.
8. MAIN ELECTRICAL ROOM GROUNDING: PROVIDE GROUND BUS BAR AND MOUNTING
HARDWARE AT EACH MAIN ELECTRICAL ROOM WHERE INCOMING FEEDERS ARE
TERMINATED, AS SHOWN ON THE DRAWINGS. CONNECT TO PIGTAIL EXTENSIONS OF THE
BUILDING GROUNDING RING, AS SHOWN ON THE DRAWINGS.
9. EXTERIOR LIGHT POLES: PROVIDE 6.1 M (20 FEET) OF NO. 4 AWG BARE COPPER COILED
AT BOTTOM OF POLE BASE EXCAVATION PRIOR TO POUR, PLUS ADDITIONAL UN-SPLICED
LENGTH IN AND ABOVE FOUNDATION AS REQUIRED TO REACH POLE GROUND STUD.
10. GROUND ROD INSTALLATAION:
a. FOR OUTDOOR INSTALLATIONS, DRIVE EACH ROD VERTICALLY IN THE EARTH, UNTIL
TOP OF ROD IS 610 MM (24 INCHES) BELOW FINAL GRADE.
b. FOR INDOOR INSTALLATIONS, LEAVE 100 MM (4 INCHES) OF EACH ROD EXPOSED.
c. WHERE BURIED OR PERMANENTLY CONCEALED GROUND CONNECTIONS ARE
REQUIRED, MAKE THE CONNECTIONS BY THE EXOTHERMIC PROCESS, TO FORM
SOLID METAL JOINTS. MAKE ACCESSIBLE GROUND CONNECTIONS WITH MECHANICAL
PRESSURE-TYPE GROUND CONNECTORS.
3. MATERIALS – CONDUIT FITTINGS
a. RIGID STEEL AND INTERMEDIATE METALLIC CONDUIT FITTINGS: FITTINGS SHALL
MEET THE REQUIREMENTS OF UL 514B AND NEMA FB1.
b. FITTINGS SHALL MEET THE REQUIREMENTS OF UL 514B AND NEMA FB1.
c. STANDARD THREADED COUPLINGS, LOCKNUTS, BUSHINGS, CONDUIT BODIES, AND
ELBOWS: ONLY STEEL OR MALLEABLE IRON MATERIALS ARE ACCEPTABLE. INTEGRAL
RETRACTABLE TYPE IMC COUPLINGS ARE ALSO ACCEPTABLE.
d. LOCKNUTS: BONDING TYPE WITH SHARP EDGES FOR DIGGING INTO THE METAL WALL
OF AN ENCLOSURE.
e. BUSHINGS: METALLIC INSULATING TYPE, CONSISTING OF AN INSULATING INSERT, MOLDED OR LOCKED INTO THE METALLIC BODY OF THE FITTING. BUSHINGS MADE
ENTIRELY OF METAL OR NONMETALLIC MATERIAL ARE NOT PERMITTED.
f. ERICKSON (UNION-TYPE) AND SET SCREW TYPE COUPLINGS: APPROVED FOR USE IN
CONCRETE ARE PERMITTED FOR USE TO COMPLETE A CONDUIT RUN WHERE
CONDUIT IS INSTALLED IN CONCRETE. USE SET SCREWS OF CASE-HARDENED STEEL
WITH HEX HEAD AND CUP POINT TO FIRMLY SEAT IN CONDUIT WALL FOR POSITIVE
GROUND. TIGHTENING OF SET SCREWS WITH PLIERS IS PROHIBITED.
g. SEALING FITTINGS: THREADED CAST IRON TYPE. USE CONTINUOUS DRAIN-TYPE
SEALING FITTINGS TO PREVENT PASSAGE OF WATER VAPOR. IN CONCEALED WORK,
INSTALL FITTINGS IN FLUSH STEEL BOXES WITH BLANK COVER PLATES HAVING THE
SAME FINISHES AS THAT OF OTHER ELECTRICAL PLATES IN THE ROOM.
h. ELECTRICAL METALLIC TUBING FITTINGS:
• FITTINGS AND CONDUIT BODIES SHALL MEET THE REQUIREMENTS OF UL 514B,
NEMA C80.3, AND NEMA FB1.
• ONLY STEEL OR MALLEABLE IRON MATERIALS ARE ACCEPTABLE.
• COMPRESSION COUPLINGS AND CONNECTORS: CONCRETE-TIGHT AND RAIN-
TIGHT, WITH CONNECTORS HAVING INSULATED THROATS.
• SETSCREW COUPLINGS AND CONNECTORS: USE SETSCREWS OF CASE-
HARDENED STEEL WITH HEX HEAD AND CUP POINT, TO FIRMLY SEAT IN WALL OF
CONDUIT FOR POSITIVE GROUNDING.
• INDENT-TYPE CONNECTORS OR COUPLINGS ARE PROHIBITED.
• DIE-CAST OR PRESSURE-CAST ZINC-ALLOY FITTINGS OR FITTINGS MADE OF "POT
METAL" ARE PROHIBITED.
i. FLEXIBLE METAL CONDUIT FITTINGS:
• CONFORM TO UL 514B. ONLY STEEL OR MALLEABLE IRON MATERIALS ARE
ACCEPTABLE.
• CLAMP-TYPE, WITH INSULATED THROAT.
j. LIQUID-TIGHT FLEXIBLE METAL CONDUIT FITTINGS:
• FITTINGS SHALL MEET THE REQUIREMENTS OF UL 514B AND NEMA FB1.
• ONLY STEEL OR MALLEABLE IRON MATERIALS ARE ACCEPTABLE.
• FITTINGS MUST INCORPORATE A THREADED GROUNDING CONE, A STEEL OR
PLASTIC COMPRESSION RING, AND A GLAND FOR TIGHTENING. CONNECTORS
SHALL HAVE INSULATED THROATS.
k. DIRECT BURIAL PLASTIC CONDUIT FITTINGS: FITTINGS SHALL MEET THE
REQUIREMENTS OF UL 514C AND NEMA TC3.
l. SURFACE METAL RACEWAY FITTINGS: AS RECOMMENDED BY THE RACEWAY
MANUFACTURER. INCLUDE COUPLINGS, OFFSETS, ELBOWS, EXPANSION JOINTS,
ADAPTERS, HOLD-DOWN STRAPS, END CAPS, CONDUIT ENTRY FITTINGS,
ACCESSORIES, AND OTHER FITTINGS AS REQUIRED FOR COMPLETE SYSTEM.
4. CONDUIT SUPPORTS
a. PARTS AND HARDWARE: ZINC-COAT OR PROVIDE EQUIVALENT CORROSION
PROTECTION.
b. INDIVIDUAL CONDUIT HANGERS: DESIGNED FOR THE PURPOSE, HAVING A
PRE-ASSEMBLED CLOSURE BOLT AND NUT, AND PROVISIONS FOR RECEIVING A
HANGER ROD.
c. MULTIPLE CONDUIT (TRAPEZE) HANGERS: NOT LESS THAN 38 MM X 38 MM (1.5 X 1.5
INCHES), 12-GAUGE STEEL, COLD-FORMED, LIPPED CHANNELS; WITH NOT LESS THAN
9 MM (0.375-INCH) DIAMETER STEEL HANGER RODS.
5. OUTLET, JUNCTION, AND PULL BOXES:
a. COMPLY WITH UL-50 AND UL-514A.
b. RUSTPROOF CAST METAL WHERE REQUIRED BY THE NEC OR SHOWN ON DRAWINGS.
c. SHEET METAL BOXES: GALVANIZED STEEL, EXCEPT WHERE SHOWN ON DRAWINGS.
C. EXECUTION
1. PENETRATIONS
a. CUT HOLES THROUGH CONCRETE AND MASONRY IN NEW AND EXISTING
STRUCTURES WITH A DIAMOND CORE DRILL OR CONCRETE SAW. PNEUMATIC
HAMMERS, IMPACT ELECTRIC, HAND, OR MANUAL HAMMER-TYPE DRILLS ARE NOT
ALLOWED, EXCEPT WHEN PERMITTED WHERE WORKING SPACE IS LIMITED.
b. FIRESTOP: WHERE CONDUITS, WIREWAYS, AND OTHER ELECTRICAL RACEWAYS
PASS THROUGH FIRE PARTITIONS, FIRE WALLS, SMOKE PARTITIONS, OR FLOORS,
INSTALL A FIRE STOP THAT PROVIDES AN EFFECTIVE BARRIER AGAINST THE SPREAD
OF FIRE, SMOKE AND GASES AS SPECIFIED IN SECTION FIRESTOPPING.
c. WATERPROOFING: AT FLOOR, EXTERIOR WALL, AND ROOF CONDUIT PENETRATIONS, COMPLETELY SEAL THE GAP AROUND CONDUIT TO RENDER IT WATERTIGHT, AS
SPECIFIED WITH APPROVED JOINT SEALANTS.
2. INSTALLATION
a. IN ACCORDANCE WITH NEC, NEMA, UL, AS SHOWN ON DRAWINGS, AND AS SPECIFIED
HEREIN.
b. INSTALL CONDUIT AS FOLLOWS:
• IN COMPLETE MECHANICALLY AND ELECTRICALLY CONTINUOUS RUNS BEFORE
PULLING IN CABLES OR WIRES.
• UNLESS OTHERWISE INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN,
INSTALLATION OF ALL CONDUITS SHALL BE CONCEALED WITHIN FINISHED WALLS,
FLOORS, AND CEILINGS.
• FLATTENED, DENTED, OR DEFORMED CONDUIT IS NOT PERMITTED. REMOVE AND
REPLACE THE DAMAGED CONDUITS WITH NEW CONDUITS.
• ASSURE CONDUIT INSTALLATION DOES NOT ENCROACH INTO THE CEILING
HEIGHT HEAD ROOM, WALKWAYS, OR DOORWAYS.
• CUT CONDUITS SQUARE, REAM, REMOVE BURRS, AND DRAW UP TIGHT.
• DO NOT USE SUSPENDED CEILINGS, SUSPENDED CEILING SUPPORTING
MEMBERS, LIGHTING FIXTURES, OTHER CONDUITS, CABLE TRAY, BOXES, PIPING,
OR DUCTS TO SUPPORT CONDUITS AND CONDUIT RUNS.
• SUPPORT WITHIN 300 MM (12 INCHES) OF CHANGES OF DIRECTION, AND WITHIN
300 MM (12 INCHES) OF EACH ENCLOSURE TO WHICH CONNECTED.
• CLOSE ENDS OF EMPTY CONDUITS WITH PLUGS OR CAPS AT THE ROUGH-IN
STAGE UNTIL WIRES ARE PULLED IN, TO PREVENT ENTRY OF DEBRIS.
• SECURE CONDUITS TO CABINETS, JUNCTION BOXES, PULL-BOXES, AND OUTLET
BOXES WITH BONDING TYPE LOCKNUTS. FOR RIGID STEEL AND IMC CONDUIT
INSTALLATIONS, PROVIDE A LOCKNUT ON THE INSIDE OF THE ENCLOSURE, MADE
UP WRENCH TIGHT. DO NOT MAKE CONDUIT CONNECTIONS TO JUNCTION BOX
COVERS.
• CONDUIT BODIES SHALL ONLY BE USED FOR CHANGES IN DIRECTION, AND SHALL
NOT CONTAIN SPLICES.
c. CONDUIT BENDS: MAKE BENDS WITH STANDARD CONDUIT BENDING MACHINES, CONDUIT HICKEY MAY BE USED FOR SLIGHT OFFSETS AND FOR STRAIGHTENING
STUBBED OUT CONDUITS, BENDING OF CONDUITS WITH A PIPE TEE OR VISE IS
PROHIBITED.
d. LAYOUT AND HOMERUNS: INSTALL CONDUIT WITH WIRING, INCLUDING HOMERUNS, AS SHOWN ON DRAWINGS.
3. CONCEALED WORK INSTALLATION
a. IN CONCRETE:
• CONDUIT: RIGID STEEL, IMC, OR EMT. DO NOT INSTALL EMT IN CONCRETE SLABS
THAT ARE IN CONTACT WITH SOIL, GRAVEL, OR VAPOR BARRIERS.
• INSTALLATION OF CONDUIT IN CONCRETE THAT IS LESS THAN 75 MM (3 INCHES)
THICK IS PROHIBITED.
b. ABOVE FURRED OR SUSPENDED CEILINGS AND IN WALLS:
• CONDUIT FOR CONDUCTORS 600 V AND BELOW: RIGID STEEL, IMC, OR EMT.
MIXING DIFFERENT TYPES OF CONDUITS IN THE SAME SYSTEM IS PROHIBITED.
• ALIGN AND RUN CONDUIT PARALLEL OR PERPENDICULAR TO THE BUILDING LINES.
• CONNECT RECESSED LIGHTING FIXTURES TO CONDUIT RUNS WITH MAXIMUM 1.8
M (6 FEET) OF FLEXIBLE METAL CONDUIT EXTENDING FROM A JUNCTION BOX TO
THE FIXTURE.
• FOR CONDUITS RUNNING THROUGH METAL STUDS, LIMIT FIELD CUT HOLES TO NO
MORE THAN 70% OF WEB DEPTH. SPACING BETWEEN HOLES SHALL BE AT LEAST
457 MM (18 INCHES). CUTS OR NOTCHES IN FLANGES OR RETURN LIPS SHALL NOT
BE PERMITTED.
4. EXPOSED WORK INSTALLATION
a. UNLESS OTHERWISE INDICATED ON DRAWINGS, EXPOSED CONDUIT IS ONLY
PERMITTED IN MECHANICAL AND ELECTRICAL ROOMS.
b. CONDUIT FOR CONDUCTORS 600 V AND BELOW: RIGID STEEL, IMC OR EMT. MIXING
DIFFERENT TYPES OF CONDUITS IN THE SYSTEM IS PROHIBITED.
c. ALIGN AND RUN CONDUIT PARALLEL OR PERPENDICULAR TO THE BUILDING LINES.
d. INSTALL HORIZONTAL RUNS CLOSE TO THE CEILING OR BEAMS AND SECURE WITH
CONDUIT STRAPS.
5. WET OR DAMP LOCATIONS
a. USE RIGID STEEL OR IMC CONDUITS UNLESS AS SHOWN ON DRAWINGS.
b. PROVIDE SEALING FITTINGS TO PREVENT PASSAGE OF WATER VAPOR WHERE
CONDUITS PASS FROM WARM TO COLD LOCATIONS, I.E., REFRIGERATED SPACES,
CONSTANT-TEMPERATURE ROOMS, AIR-CONDITIONED SPACES, BUILDING EXTERIOR
WALLS, ROOFS, OR SIMILAR SPACES.
6. MOTORS AND VIBRATING EQUIPMENT
a. USE FLEXIBLE METAL CONDUIT FOR CONNECTIONS TO MOTORS AND OTHER
ELECTRICAL EQUIPMENT SUBJECT TO MOVEMENT, VIBRATION, MISALIGNMENT,
CRAMPED QUARTERS, OR NOISE TRANSMISSION.
b. USE LIQUID-TIGHT FLEXIBLE METAL CONDUIT FOR INSTALLATION IN EXTERIOR
LOCATIONS, MOISTURE OR HUMIDITY LADEN ATMOSPHERE, CORROSIVE
ATMOSPHERE, WATER OR SPRAY WASH-DOWN OPERATIONS, INSIDE AIRSTREAM OF
HVAC UNITS, AND LOCATIONS SUBJECT TO SEEPAGE OR DRIPPING OF OIL, GREASE,
OR WATER.
c. PROVIDE A GREEN EQUIPMENT GROUNDING CONDUCTOR WITH FLEXIBLE AND
LIQUID-TIGHT FLEXIBLE METAL CONDUIT.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
APPROVING OFFICIAL:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
O'Brien Engineering, Inc.
2340 E. Trinity Mills Rd. Ste 200
Carrollton, TX 75006
972-233-2288 www.obrieneng.com
OEI - LBL Joint Venture LLC
2340 E. Trinity Mills Rd. Ste 200
Carrollton, TX 75006
972-233-2288 www.obrieneng.com
O'Brien Engineering, Inc., Managing Partner
COR, Mr. JOSHUA JUNKIN
B
IM
/V
A B ig S p ri n g
O u tp a ti e n t
E x a m
R o o m s /0
.0
V
A B
S O u tp a ti e n t E x a m R o o m s E
L E
C
R
.r v t
/1
/2
:1
:1
A
M
E001
COVER SHEET - GENERAL NOTES
- SHEET LOG
OUTPATIENT CLINIC
Big Spring, TX
519-19-700
03/17/2023 LRL JRM
100% ISSUE FOR BID
WEST TEXAS VETERANS HEALTH CARE SYSTEM
OUTPATIENT CLINIC
519-19-700
BIG SPRING, TEXAS
SHEET INDEX
NUMBER NAME
EP104 ELECTRICAL POWER HVAC PHASE II
E003 COVER SHEET - GENERAL NOTES - ABBREVIATIONS
E002 COVER SHEET - GENERAL NOTES - ABBREVIATIONS
E001 COVER SHEET - GENERAL NOTES - SHEET LOG
E004 COVER SHEET - SYMBOLS
ED101 FIRST FLOOR PLAN DEMOLITION
EP100 FIRST FLOOR PLAN OVERALL
EP101 FIRST FLOOR PLAN POWER
EP102 ELECTRICAL ENLARGED VIEWS
EP103 ELECTRICAL POWER HVAC PHASE I
EL101 FIRST FLOOR PLAN LIGHTING
E901 ELECTRICAL RISER DIAGRAM
E601 ELECTRICAL PANEL SCHEDULES
SHEET LOG
SHEET REVISION
NUMBER NAME REV DATE DESCRIPTION
E001 COVER SHEET - GENERAL NOTES - SHEET LOG 1 03/06/2023 ISSUE FOR BID
E002 COVER SHEET - GENERAL NOTES - ABBREVIATIONS 1 03/06/2023 ISSUE FOR BID
E003 COVER SHEET - GENERAL NOTES - ABBREVIATIONS 1 03/06/2023 ISSUE FOR BID
E004 COVER SHEET - SYMBOLS 1 03/06/2023 ISSUE FOR BID
E601 ELECTRICAL PANEL SCHEDULES 1 03/06/2023 ISSUE FOR BID
E901 ELECTRICAL RISER DIAGRAM 1 03/06/2023 ISSUE FOR BID
ED101 FIRST FLOOR PLAN DEMOLITION 1 03/06/2023 ISSUE FOR BID
EL101 FIRST FLOOR PLAN LIGHTING 1 03/06/2023 ISSUE FOR BID
EP100 FIRST FLOOR PLAN OVERALL 1 03/06/2023 ISSUE FOR BID
EP101 FIRST FLOOR PLAN POWER 1 03/06/2023 ISSUE FOR BID
EP102 ELECTRICAL ENLARGED VIEWS 1 03/06/2023 ISSUE FOR BID
EP103 ELECTRICAL POWER HVAC PHASE I 1 03/06/2023 ISSUE FOR BID
EP104 ELECTRICAL POWER HVAC PHASE II 1 03/06/2023 ISSUE FOR BID
Revisions: Date:
ISSUE FOR BID 03/06/2023
3/17/23
ABBREVIATIONS
1PH SINGLE PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY
CONTROL, OR AVAILABLE FAULT CURRENT
AFCI ARC-FAULT CURRENT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFIB ARC FAULT CIRCUIT INTERRUPTER CIRCUIT BREAKER.
AF/GF ARC FAULT AND GROUND FAULT CIRCUIT INTERRUPTER
Ah AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BRK RBREAKER
BYP BYPASS
C CONDUIT
CAB CABINET (MOUNTED)
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTRACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FINISHED
CF/CI CONTRACTOR FINISHED/CONTRACTOR INSTALLED
CFE CONTRACTOR FINISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
OR C/B
CLF CURRENT LIMITING FUSE
CLG CEILING
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CUR CURRENT
dB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELCIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST OR (E) EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FIXT FIXTURE
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FP FIRE PROTECTION
FSD FIRE SMOKE DAMPER
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G ELECTRICAL GROUND
GEN GENERATOR
GFI GROUND FAULT INTERRUPTER
GFIB GROUND FAULT CIRCUIT INTERRUPTER VIA CIRCUIT
BREAKER.
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF
NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAh KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR kWhM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MD MOTORIZED DAMPER
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLA MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PB PULL BOX
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
RE RELOCATED EXISTING
REC RECESSED
RECPT RECEPTACLE
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
USB RECEPTACLE w/INTEGRATED UNIVERSAL SERIAL BUS
PORT
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
GENERAL NOTES
5. LIGHTING CONTROLS
A. GENERAL
1. DESCRIPTION: FURNISHING, INSTALLATION AND CONNECTION OF THE LIGHTING
CONTROLS.
2. SUBMITTALS
a. SUBMIT THE FOLLOWING INFORMATION FOR EACH TYPE OF LIGHTING CONTROLS:
MATERIAL AND CONSTRUCTION DETAILS, PHYSICAL DIMENSIONS AND DESCRIPTION,
PHYSICAL DIMENSIONS AND DESCRIPTION, WIRING SCHEMATIC AND CONNECTION
DIAGRAM, INSTALLATION DETAILS.
B. PRODUCTS
1. ELECTRONIC TIME SWITCHES: ELECTRONIC, SOLID-STATE PROGRAMMABLE UNITS WITH
ALPHANUMERIC DISPLAY; COMPLYING WITH UL 916 AND OR 917.
2. OUTDOOR PHOTOELECTRIC SWITCHES: SOLID STATE, WITH SPST, DPST DRY CONTACTS
RATED FOR 1800 VA TUNGSTEN OR 1000 VA INDUCTIVE, COMPLYING WITH UL 773A.
3. TIMER SWITCHES: DIGITAL SWITCHES WITH BACKLIT LCD DISPLAY, 120/277 VOLT RATED, FITTING AS A REPLACEMENT FOR STANDARD WALL SWITCHES.
4. CEILING-MOUNTED PHOTOELECTRIC SWITCHES: SOLID-STATE, LIGHT-LEVEL SENSOR
UNIT, WITH SEPARATE RELAY UNIT.
5. INDOOR OCCUPANCY SENSOR: DUAL-TECHNOLOGY TYPE: CEILING MOUNTING;
COMBINATION PIR AND ULTRASONIC DETECTION METHODS, FIELD-SELECTABLE.
a. DETECTION COVERAGE: SHALL BE SUFFICIENT TO PROVIDE COVERAGE AS REQUIRED
BY SENSOR LOCATIONS SHOWN ON DRAWING.
6. LIGHTING CONTROL SYSTEM – DISTIBUTIVE RELAY TYPE SYSTEM DESCRIPTION
a. THE LIGHTING CONTROL SYSTEM SHALL BE A NETWORK OF REMOTE RELAY MODULES
CONNECTED TO A DIGITAL NETWORK VIA NETWORK HUBS AND CONTROLLED THROUGH
A SYSTEM SERVER / CENTRAL STATION. LIGHTING DIGITAL NETWORK WITH THE
SYSTEM SERVER. SYSTEM INCLUDES ALL ASSOCIATED CONTROL DEVICES CONNECT
TO THE RELAY MODULES AND COMMUNICATE VIA THE NETWORK INTERFACES AND
WIRING, HUBS, RELAY MODULES, RELAYS, PHOTOCELLS, SWITCHES, DIMMERS, TIME
CLOCK, AND OCCUPANCY SENSORS. SYSTEM SHALL UTILIZE DISTRIBUTED RELAYS
MODULES, ALLOWING THESE RELAY MODULES TO BE LOCATED ABOVE ACCESSIBLE
CEILINGS IN OR ADJACENT TO ROOMS THEY ARE CONTROLLING.
b. SYSTEM SHALL INCLUDE SERVER / CENTRAL STATION WITH OPERATING SOFTWARE, DATA NETWORK, AND BACNET IP COMMUNICATION WITH OTHER SYSTEMS AS
DESCRIBED. SYSTEM COMMUNICATION PROTOCOL SHALL BE COMPATIBLE WITH THE
BUILDING AUTOMATION SYSTEM SPECIFIED IN SECTION 23 09 23, DIRECT-DIGITAL
CONTROL SYSTEM FOR HVAC.
c. SYSTEM SERVER / CENTRAL STATION SHALL PROVIDE PROGRAMMABLE OPERATION OF
LIGHTS CONNECTED VIA SYSTEM RELAYS AND CONTROLLED WITH SYSTEM DEVICES.
SYSTEM SOFTWARE SHALL PROVIDE CONTROL OF RELAYS AND CONTROL DEVICES,
TIME AND SEQUENCE SCHEDULING, TIMED OUT AND BLINK LIGHT OPERATION AND
MONITORING AND REPORTING OF SYSTEM EVENTS AND COMPONENTS. INITIAL
PROGRAMMING SHALL BE AS SHOWN ON PLANS AND SCHEDULES.
d. RELAY MODULES: MOUNTED IN NEMA ENCLOSURE WITH PHYSICALLY SEPARATE
120/277 VOLT WIRING COMPARTMENT FROM LOW VOLTAGE CONTROL WIRING.
PROVIDE LOW VOLTAGE DIGITAL COMMUNICATION TO CONTROL DEVICES AS SHOWN
ON DRAWINGS AND SCHEDULES. SUPPLEMENTAL POWER PACKS SHALL BE PROVIDED
AS REQUIRED FOR MULTIPLE CONTROL DEVICES. THIS EQUIPMENT SHALL BE
IDENTIFIED IN SHOP DRAWING SUBMISSION. DIMMABLE RELAY MODULES SHALL BE
PROVIDED WHERE INDICATED. RELAY MODULES SHALL CONTAIN UP TO 4 RELAYS.
RELAY MODULES SHALL BE LABELED WITH ROOM NUMBER THAT RELAYS CONTROL
LIGHTING WITHIN.
e. SINGLE-POLE RELAYS: MECHANICALLY HELD UNLESS OTHERWISE INDICATED; SPLIT-
COIL, MOMENTARY-PULSED TYPE, RATED 20 A, 125 VOLT AC FOR TUNGSTEN FILAMENTS
AND 20 A, 277 VOLT AC FOR ELECTRONIC BALLASTS, 50,000 CYCLES AT RATED
CAPACITY.
f. CONTROL DEVICES: ALL OCCUPANCY SENSORS (ULTRASONIC, IR AND DUAL
TECHNOLOGY TYPE), PHOTOCELLS, SWITCHES AND TIMERS SHALL BE PROVIDED WITH
SYSTEM AND DESIGNED TO OPERATE ON SYSTEM NETWORK. SUPPLEMENTAL POWER
PACKS SHALL BE PROVIDED AS REQUIRED FOR MULTIPLE CONTROL DEVICES. THIS
EQUIPMENT SHALL BE IDENTIFIED IN SHOP DRAWING SUBMISSION.
C. EXECUTION
1. INSTALLATION
a. INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, MANUFACTURER'S
INSTRUCTIONS, AS SHOWN ON THE DRAWINGS, AND AS SPECIFIED.
b. AIMING FOR WALL-MOUNTED AND CEILING-MOUNTED MOTION SENSOR SWITCHES
SHALL BE PER MANUFACTURER’S RECOMMENDATIONS.
c. LOCATE PHOTOELECTRIC SENSORS AS INDICATED AND IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS. ADJUST SENSOR FOR THE AVAILABLE LIGHT
LEVEL AT THE TYPICAL WORK PLANE FOR THAT AREA.
2. ACCEPTANCE CHECKS AND TESTS
a. PERFORM IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
b. UPON COMPLETION OF INSTALLATION, CONDUCT AN OPERATING TEST TO SHOW THAT
EQUIPMENT OPERATES IN ACCORDANCE WITH REQUIREMENTS OF THIS SECTION.
6. LOW VOLTAGE TRANSFORMERS
A. GENERAL
1. DESCRIPTION: FURNISHING, INSTALLATION, CONNECTION, AND TESTING OF LOW-
VOLTAGE DRY-TYPE GENERAL-PURPOSE TRANSFORMERS, INDICATED AS
TRANSFORMERS IN THIS SECTION.
2. SUBMITTALS
a. INCLUDE ELECTRICAL RATINGS, DIMENSIONS, MOUNTING DETAILS, MATERIALS, REQUIRED CLEARANCES, TERMINATIONS, WEIGHT, TEMPERATURE RISE, WIRING
AND CONNECTION DIAGRAMS, PLAN, FRONT, SIDE, AND REAR ELEVATIONS,
ACCESSORIES, AND DEVICE NAMEPLATE DATA.
B. PRODUCTS
1. TRANSFORMERS
a. UNLESS OTHERWISE SPECIFIED, TRANSFORMERS SHALL BE IN ACCORDANCE WITH
NEMA, NFPA, UL AND AS SHOWN ON THE DRAWINGS.
b. TRANSFORMERS SHALL HAVE THE FOLLOWING FEATURES:
• SELF-COOLED BY NATURAL CONVECTION, ISOLATING WINDINGS, //INDOOR//AND
OUTDOOR// DRY-TYPE. AUTOTRANSFORMERS WILL NOT BE ACCEPTED, EXCEPT
AS SPECIFICALLY ALLOWED FOR BUCK-BOOST APPLICATIONS.
• 2. RATING AND WINDING CONNECTIONS SHALL BE AS SHOWN ON THE
DRAWINGS.
• 3. RATINGS SHOWN ON THE DRAWINGS ARE FOR CONTINUOUS DUTY WITHOUT
THE USE OF COOLING FANS.
• 4. COPPER WINDINGS.
c. INSULATION SYSTEMS:
• TRANSFORMERS 30 KVA AND LARGER: UL RATED 220 °C (428 °F) SYSTEM WITH
AN AVERAGE MAXIMUM RISE BY RESISTANCE OF 150 °C (302 °F) IN A MAXIMUM
AMBIENT OF 40 °C (104 °F).
• TRANSFORMERS BELOW 30 KVA: SAME AS FOR 30 KVA AND LARGER OR UL
RATED 185 °C (365 °F) SYSTEM WITH AN AVERAGE MAXIMUM RISE BY
RESISTANCE OF 115 °C (239 °F) IN A MAXIMUM AMBIENT OF 40 °C (104 °F).
d. IF NOT SHOWN ON DRAWINGS, NOMINAL IMPEDANCE SHALL BE AS PERMITTED BY
NEMA.
e. SINGLE PHASE TRANSFORMERS RATED 15 KVA THROUGH 25 KVA SHALL HAVE TWO
5% FULL CAPACITY TAPS BELOW NORMAL RATED PRIMARY VOLTAGE. ALL
TRANSFORMERS RATED 30 KVA AND LARGER SHALL HAVE TWO 2.5% FULL
CAPACITY TAPS ABOVE, AND FOUR 2.5% FULL CAPACITY TAPS BELOW NORMAL
RATED PRIMARY VOLTAGE.
f. CORE ASSEMBLIES SHALL BE GROUNDED TO THEIR ENCLOSURES WITH ADEQUATE
FLEXIBLE GROUND STRAPS.
• COMPRISED OF NOT LESS THAN CODE GAUGE STEEL.
• OUTDOOR ENCLOSURES SHALL BE NEMA 3R.
g. STANDARD NEMA FEATURES AND ACCESSORIES, INCLUDING GROUND PAD, LIFTING
PROVISIONS, AND NAMEPLATE WITH THE WIRING DIAGRAM AND SOUND LEVEL
INDICATED.
7. LOW VOLTAGE SWITCHGEAR
A. GENERAL
1. DESCRIPTION: FURNISHING, INSTALLATION, CONNECTION, AND TESTING OF LOW-
VOLTAGE SWITCHGEAR, INDICATED AS SWITCHGEAR IN THIS SECTION.
2. SUBMITTALS
a. PRIOR TO FABRICATION OF SWITCHGEAR, SUBMIT THE FOLLOWING DATA FOR
APPROVAL:
• COMPLETE ELECTRICAL RATINGS, CIRCUIT BREAKER SIZES, INTERRUPTING
RATINGS, SAFETY FEATURES, ACCESSORIES AND NAMEPLATE DATA.
• SWITCHGEAR ONE LINE DIAGRAM, SHOWING AMPERE RATING, NUMBER OF BARS
PER PHASE AND NEUTRAL IN EACH BUS RUN (HORIZONTAL AND VERTICAL), BUS
SPACING, EQUIPMENT GROUND BUS, AND BUS MATERIAL.
• PROVISIONS AND REQUIRED LOCATIONS FOR EXTERNAL CONDUIT AND WIRING
ENTRANCES.
B. PRODUCTS
1. SHALL BE IN ACCORDANCE WITH IEEE, NEMA, NFPA, UL, AS SHOWN ON THE DRAWINGS
2. SWITCHGEAR SHALL BE A COMPLETE, GROUNDED, CONTINUOUS-DUTY, INTEGRAL
ASSEMBLY, METAL CLAD, DEAD-FRONT, DEAD-REAR, SELF-SUPPORTING, INDOOR TYPE
SWITCHGEAR ASSEMBLY, TAMPERPROOF, WEATHERPROOF, OUTDOOR TYPE
SWITCHGEAR ASSEMBLY WITH METAL HOUSING AND A WALK-IN PROTECTED AISLE AS
DESIGNED. INCORPORATE DEVICES SHOWN ON THE DRAWINGS AND ALL RELATED
COMPONENTS REQUIRED TO FULFILL OPERATIONAL AND FUNCTIONAL REQUIREMENTS.
3. RATINGS SHALL NOT BE LESS THAN SHOWN ON THE DRAWINGS.
4. COORDINATE ALL REQUIREMENTS WITH THE ELECTRIC UTILITY COMPANY SUPPLYING
ELECTRICAL SERVICE TO THE SWITCHGEAR. THE INCOMING ELECTRIC UTILITY FEEDER
AND REVENUE METERING INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF
THE ELECTRIC UTILITY COMPANY.//
5. CIRCUIT BREAKER COMPARTMENTS: AN INDIVIDUAL COMPARTMENT SHALL BE
SUPPLIED FOR EACH CIRCUIT BREAKER AND EACH FUTURE CIRCUIT BREAKER AS
SHOWN ON THE DRAWINGS. COMPARTMENTS SHALL BE PROVIDED WITH ISOLATED
WIREWAYS FOR CONTROL WIRING BETWEEN DEVICES.
6. AUXILIARY COMPARTMENTS: COMPARTMENTS SHALL BE PROVIDED FOR AUXILIARIES,
METERING, AND TRANSITION OR TERMINATION SECTIONS AS REQUIRED BY THE
MANUFACTURER, AND AS SHOWN ON DRAWINGS. COMPARTMENTS SHALL BE PROVIDED
WITH ISOLATED WIREWAYS FOR CONTROL WIRING BETWEEN DEVICES.
7. COMPARTMENT DOORS: THE DOORS SHALL PERMIT CONVENIENT REMOVAL AND
INTERCHANGING OF CIRCUIT BREAKERS BETWEEN COMPARTMENTS. THE DOORS SHALL
BE CAPABLE OF A SWING APPROACHING
8. BUS BARS AND INTERCONNECTIONS:
a. PROVIDE COPPER PHASE AND NEUTRAL BUSES, FULLY RATED FOR THE AMPERAGE
AS SHOWN ON THE DRAWINGS FOR THE ENTIRE LENGTH OF THE SWITCHGEAR. BUS
LAMINATIONS SHALL HAVE A MINIMUM OF 6 MM (1/4 INCH) SPACING.
b. THE BUS AND BUS COMPARTMENT SHALL BE DESIGNED SO THAT THE ACCEPTABLE
NEMA STANDARD TEMPERATURE RISES ARE NOT EXCEEDED.
c. INSTALL A COPPER GROUND BUS THE FULL LENGTH OF THE SWITCHGEAR
ASSEMBLY.
d. MAIN BONDING JUMPER: AN UN-INSULATED COPPER BUS, SIZE AS SHOWN ON
DRAWINGS, SHALL INTERCONNECT THE NEUTRAL AND GROUND BUSES, WHEN THE
SWITCHGEAR IS USED TO ESTABLISH THE SYSTEM COMMON GROUND POINT.
e. ALL BOLTS, NUTS, AND WASHERS SHALL BE ZINC-PLATED STEEL. BOLTS SHALL BE
TORQUED TO THE VALUES RECOMMENDED BY THE MANUFACTURER.
f. MAKE PROVISIONS FOR FUTURE BUS EXTENSIONS BY MEANS OF BOLT HOLES OR
OTHER APPROVED METHOD.
9. LOW VOLTAGE POWER CIRCUITS BREAKERS
a. GENERAL: CIRCUIT BREAKERS SHALL BE DEAD FRONT, DRAWOUT, STORED ENERGY
TYPE WITH SOLID STATE TRIP DEVICES. ARCING CONTACTS SHALL BE RENEWABLE.
b. RATING: CIRCUIT BREAKERS SHALL BE 3 POLE, 600 VOLTS AC AND BELOW, 60 CYCLE
WITH FRAME SIZE, TRIP RATING AND FUNCTIONS, AND SYSTEM VOLTAGE AS SHOWN
ON DRAWINGS. BREAKERS SHALL HAVE 30 CYCLE SHORT TIME CURRENT RATINGS.
c. DRAWOUT MOUNTING: PROVIDE A RACKING MECHANISM TO POSITION AND HOLD THE
BREAKER IN THE CONNECTED, TEST, OR DISCONNECTED POSITION. PROVIDE AN
INTERLOCK TO PREVENT MOVEMENT OF THE BREAKER INTO OR OUT OF THE
CONNECTED POSITION UNLESS THE BREAKER IS TRIPPED OPEN.
d. TRIP DEVICES: BREAKERS SHALL BE ELECTRICALLY AND MECHANICALLY TRIP FREE
AND SHALL HAVE TRIP DEVICES IN EACH POLE. UNLESS OTHERWISE INDICATED ON
DRAWINGS, EACH BREAKER SHALL HAVE OVERCURRENT AND SHORT-CIRCUIT, AND
INTEGRAL GROUND FAULT TRIP DEVICES AS NOTED. TRIP DEVICES SHALL BE OF THE
SOLID STATE TYPE WITH ADJUSTABLE PICK-UP SETTINGS, WITH BOTH LONG TIME
AND SHORT TIME ELEMENTS, AND INTEGRAL TRIP UNIT TESTING PROVISIONS.
DEVICES SHALL HAVE TIME-DELAY BAND ADJUSTMENT. LONG-TIME DELAY ELEMENT
SHALL HAVE INVERSE TIME CHARACTERISTICS. MAIN CIRCUIT BREAKERS SHALL NOT
HAVE INSTANTANEOUS TRIP FUNCTION.
e. PADLOCKING: PROVISIONS SHALL BE INCLUDED FOR PADLOCKING THE BREAKER IN
THE OPEN POSITION.
f. OPERATION: UNLESS OTHERWISE INDICATED HEREIN OR ON THE DRAWINGS, BREAKERS 1600 AMPERE FRAME SIZE AND LESS SHALL BE MANUALLY OPERATED.
BREAKERS LARGER THAN 1600 AMPERE FRAME SIZE SHALL BE ELECTRICALLY
OPERATED.
10. ELECTRIC UTILITY COMPANY EQUIPMENT
a. PROVIDE SEPARATE COMPARTMENT FOR ELECTRIC UTILITY COMPANY METERING
EQUIPMENT AS SHOWN ON DRAWINGS.
11. METERING
a. REFER TO SECTION ADVANCED UTILITY METERING. REFER TO DRAWINGS FOR
METER LOCATIONS.
b. AS NECESSARY, PROVIDE COMPARTMENT WITH A FRONT HINGED DOOR TO PROVIDE
SAFE ISOLATED ACCESS TO METERS AND ALL ASSOCIATED TERMINAL AND FUSE
BLOCKS FOR MAINTENANCE, CALIBRATION, OR TESTING.
c. PROVIDE CURRENT TRANSFORMERS FOR EACH METER. CURRENT TRANSFORMERS
SHALL BE WIRED TO SHORTING-TYPE TERMINAL BLOCKS.
d. PROVIDE VOLTAGE TRANSFORMERS INCLUDING PRIMARY FUSES AND SECONDARY
PROTECTIVE DEVICES FOR METERING AS SHOWN ON THE DRAWINGS.
C. EXECUTION
1. INSTALLATION
a. INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, AS SHOWN ON THE
DRAWINGS, AND MANUFACTURER’S INSTRUCTIONS.
b. ANCHOR SWITCHGEAR WITH…