S05 - Additional Questions Answers for Garland.docx

DOCX document 13 KB Posted

Attached to
Z1NB--Full Service/Preventative Maintenance for Chillers and Boilers Dallas/Garland
Solicitation number
36C25722Q1097
Issued by

About this file

This document contains a federal contract opportunity solicitation for full service preventative maintenance for chillers and boilers at Veteran Affairs medical facilities in Dallas and Garland, Texas. The Department of Veterans Affairs Network Contracting Office 17 is seeking offers for maintenance of chillers and boilers at the North Texas Health Care System facilities. The contract will be a firm-fixed price contract awarded to a service-disabled veteran-owned small business offeror. Site visits will take place on October 12th and technical questions are due by October 14th, with offers due by October 24th. The work will be performed in accordance with the attached statement of work, which includes preventative maintenance for specific chillers and boilers.

View the file

Other files

File Type Posted
36C25722Q1097 0002_1.docx DOCX document
S04 - Site visit Garland Sign In Sheet.pdf PDF
S06 - 36C25722Q1097 0002.pdf PDF
S05 - Technical Questions Answers - 36C25722Q1097.docx DOCX document
36C25722Q1097 0001_1.docx DOCX document
S06 - 36C25722Q1097 0001.pdf PDF
S04 - CHP Blr Chill Site Visit Sign In Sheet.pdf PDF
36C25722Q1097_1.docx DOCX document
S02 - 36C25722Q1097.pdf PDF
S04 - VAMC Dallas Site Visit Map.pdf PDF
P07 - WD 2015-5227 Rev 18.pdf PDF
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Additional Questions Answers - 36C25722Q1097 - Full Service/Preventative Maintenance for Chillers and Boilers Dallas/Garland

On page 31 of document SO2+-+36C25722Q1097 – Pavilion Secondary Chilled Water Pumps #1 & #2 are listed twice, is this a duplicate (typo) or is this meant to refer to a different pump?

Duplicate

On page 31 & 32 of document SO2+-+36C25722Q1097 – West Tower Secondary Chilled Water Pump is listed on page 31 & 32, is this a duplicate (type) or is this meant to refer to a different pump?

Duplicate

Pumps actually onsite that run the Chillers, the Primary Pumps, are not listed on the Scope of Work. There are no Primary Chilled Water Pumps in the Scope, but they were seen onsite running the plant. Is this covered under a different contract or was this an oversight?

Oversight, Chill Water Pumps include:

Primary chilled water pump #1 Armstrong NA Primary chilled water pump #2 NA NA Primary chilled water pump #3 NA NA Primary chilled water pump 3$ Aurora 4 13 BF NA

We would also like to request an extension, after just having the job walk at Garland, of one week if possible.

No extension will be granted at this time.