Water Tank Inspection Report Summary

This is a Water Tank Inspection Report prepared by TankSpek, LLC for the Veterans Healthcare System of the Ozarks at the VA Medical Center in Fayetteville, Arkansas. The inspection was conducted on May 22, 2026, on a 100,000-gallon elevated water tower with an approximate height of 140 feet. The facility is a multi-column, elevated, double ellipsoidal welded steel tank constructed with an unknown date and erection contractor. The inspection evaluated the tank's condition across multiple categories including structural integrity, sanitary conditions, safety compliance, and coating systems.

Overall condition assessments rate the tank as follows: structural condition is GOOD, sanitary condition is FAIR, interior coating is FAIR, exterior coating is POOR, and safety condition is FAIR. Key findings indicate visible sediment accumulation requiring cleaning, moderate exterior corrosion from UV degradation, interior coating staining from unsealed roof joints, and several safety deficiencies including inadequate fall arrest cable tension, undersized balcony passthrough opening (16 inches versus required 24 inches), and damaged electrical components. Critical safety concerns include RF exposure from cellular equipment exceeding OSHA occupational limits, requiring equipment deenergization during worker presence, and security vulnerabilities including damaged perimeter fencing and an accessible onsite ladder enabling unauthorized access. Recommended corrective actions include scheduled tank draining and cleaning, exterior coating application, interior coating improvements at year four, safety climb device adjustments, roof vent screening replacement, and aviation beacon bulb replacement with FAA-compliant incandescent bulbs. The report notes that cost estimates are not provided and that a supplemental report on cathodic protection system maintenance will be submitted separately.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA Medical Center

Fayetteville, AR

WATER TANK

INSPECTION

REPORT

Prepared for

Veterans Healthcare

System of the Ozarks

1100 North College Avenue

Fayetteville, AR

Prepared by

TankSpek, LLC | PO Box 805 | Berryville, AR 72616

(800) 624-1023 www.tankspek.com

VA Medical Center 100MG Storage Tank 2026 INSPECTION

Inspection report | Copyright 2025 by TankSpek, LLC

Table of Contents

1.0 PROJECT INFORMATION

2.0 CITATIONS, STANDARDS AND REFERENCES

3.0 SUMMARY OF FINDINGS

4.0 SANITARY OBSERVATIONS

5.0 SAFETY EVALUATION

6.0 STRUCTURAL OBSERVATION

7.0 SITE & SECURITY

8.0. INTERIOR COATINGS EVALUATION

9.0 EXTERIOR COATINGS EVALUATION

10.0 SUPPORTING PHOTOS

11.0 PROJECTIONS AND COST ESTIMATIONS

VA Medical Center 100MG Storage Tank 2026 INSPECTION

1.0 PROJECT INFORMATION

PWS ID 1221 Non-transient / Non-community

Project Location 1100 North College Avenue Fayetteville, AR

Name / Designation 100,000 gallon elevated water tower (EWT)

Site Contact/ Representative

Purpose of Inspection Condition Assessment

Inspection Type In-service evaluation

Date of Inspection May 22, 2026

Inspected by Alek N. Gray

Report Prepared by James Brookshire 417-439-6011 jbrookshire@tankspek.com

Report Date May 31, 2025

Tank Description Multi-column, elevated Double Ellipsoidal

Construction Style Welded steel

Construction Date Information Unavailable

Erection Contractor Information Unavailable

Construction Drawings Information Unavailable

Date of Last Inspection November 2024 - ADH Sanitary Survey

Age of Exterior Coating Information Unavailable

Age of Interior Coating Information Unavailable

Last Interior Service Information Unavailable

Tank Height / ft BCL: ~110.0 TCL: ~135.0 Overall: ~140.0 {estimates}

Diameter / ft-in Tank Shell: ~32.0 Riser: ~30.0in Inlet: Unknown

WET INTERIOR COATING EXTERIOR COATING

Coating System Epoxy Epoxy/Urethane1

Thickness Readings Taken No2 Yes2

Adhesion Testing No No

Coating Samples Taken No No

1. Top-coating appears to be Aliphatic Acrylic Polyurethane.

2. Limited to accessible surfaces immediately within reach

VA Medical Center 100MG Storage Tank 2026 INSPECTION

2.0 CITATIONS, STANDARDS AND REFERENCES

All internal equipment used for this inspection is dedicated to the purpose of Potable Water Inspections and suitable for disinfection.

All inspection equipment entering the facility is disinfected before entry as dened in the AWWA C652 standard.

This storage tank was evaluated for compliance, conformance and overall condition with the latest revisions of the applicable following agencies, standards or criteria.

• Company operating procedures and safety protocols

• Arkansas Department of Health (ADH)

− Rules and Regulations Pertaining to Public Water Systems − Checklist and Guidance for Water Storage Tank Inspections − Policy for Maintaining Water Quality

• OSHA Occupational Safety and Health Standards, Part 1910

• OSHA Safety and Health Regulations for Construction, Part 1926

• General guidelines of AWWA Manual M42- Steel Water Storage Tanks

• AWWA D101 -Inspecting & Repairing Water Storage Tanks

• SSPC-PA 2-2022 Coating System Application, Maintenance, & Inspection

• AWWA D102 -Painting and Repainting Steel Tanks

• AWWA D100- Welded steel storage tanks

• US DOT- FAA Advisory on Obstruction Marking & Lighting

• AWWA D104—Automatically Controlled, Impressed-Current Cathodic Protection

• NFPA 22 – Standard for Water Tanks for Private Fire Protection

• 10 States Standards when applicable

• General industry recognized standards and practices

VA Medical Center 100MG Storage Tank 2026 INSPECTION

4 Inspection report | Copyright 2025 by TankSpek, LLC

3.0 SUMMARY OF FINDINGS

Overview of ndings and observations. Detailed information, exceptions, and recommendations are provided at the conclusion of each item’s information section.

INTERIOR COATING

Overall Condition: FAIR

Recommendation: Maintain planned coating improvement schedule

EXTERIOR COATING

Overall Condition: POOR

Recommendation: Consider coating the exterior.

SANITARY CONDITION:

Overall Assessment: FAIR

Recommendation: Proceed with scheduled routine maintenance

SAFETY CONDITION

Overall Assessment: FAIR

Recommendation: a.) Proceed with scheduled routine maintenance b.) Impose/Enforce restrictions on telecommunications

STRUCTURAL CONDITION:

Overall Assessment: GOOD

Recommendation: Continue with a periodic maintenance schedule

VA Medical Center 100MG Storage Tank 2026 INSPECTION

4.0 SANITARY OBSERVATIONS

ITEM FINDING REMARKS

WATER LEVEL Tank level was at approx. 75% capacity during time of inspection. No action

WATER QUALITY

Visible solids were observed on water surface. Objects in tank. No visible indication of biolm on wall surfaces. Clean and sanitize interior surface.

Corrective Action Base Bid 0006

{Scheduled Tank Draining & Clean}

SEDIMENT LEVEL

A uniform sediment layer was observed in tank bowl. Estimation of total volume is not considered excessive (moderate) but should be scheduled for cleaning and removal.

Corrective Action Base Bid 0006

{Scheduled Tank Draining & Clean}

WATER CLARITY

Presence of some solids was noted; water clarity was adequate to complete inspection. Residual or turbidity testing was not performed by inspectors.

No action

RETENTION

Total usage / turnover rate was unavailable at time of inspection. No internal mixing or circulation system.

No action

ROOF SURFACE

Inspection plates were adjusted during inspection. Damaged inspection plates are allowing surface water to enter. No visible pinholing or damage from corrosion. Replace any damaged plates as needed.

Corrective Action Base Bid 0004

{Scheduled Temporary Roof Patch}

ROOF VENT

12 inch roof vent installed onto a 24 inch NFPA fan ange at roof apex is adequately protected with 24 mesh, stainless screening. No visible contamination or internal corrosion.

No action

ROOF VENT

16 inch secondary roof vent with fail-safe features is installed adjacent to original roof vent. Oversized screening does not meet ADH requirements. Screening assemblies will require removal and adjustment to fully seal. Replace screening with 24 mesh and adjust as needed.

Corrective Action Base Bid 0005

{Scheduled Replace Vent Screen}

ROOF HATCH- Primary

24 inch roof entry hatch meets ADH design standards. Hatch cover was noted closed and secured at time of inspection (bolted in place) and secured on completion. Hatch opening is not gasketed or sealed weather tight. Install weather seal

Corrective Action Base Bid 0006

{Scheduled Tank Draining & Clean}

VA Medical Center 100MG Storage Tank 2026 INSPECTION

OVERALL SANITARY CONDITION FAIR, with exceptions as noted

No evidence of any contamination was found during inspection. Deciencies or sanitary items indicated for any Corrective Action or Maintenance are documented and ready for scheduled service.

4.0 Sanitary Observations (Cont.)

OVERFLOW PIPING

8 inch overow piping is extended to grade and adequately screened with 24 mesh. Discharge is accessible from ground level, terminating into a separate drainage pipe with adequate air break.

No action

SAMPLING PORT An adequate sampling tap / port is present and functional. No action

DRAINING /

ISOLATING

Adequate or functional drainage method /valving in place. No action

LEVEL INDICATOR

Existing mechanical oat system is immobilized and non-functional.

Repair is not recommended. Removal of internal components and sealing openings is recommended at the next scheduled interior coating procedure.

Maintenance needed Option 3008 Option 3009

{Year 3- Misc. Repairs Not to Exceed / Interior Coatings}

VA Medical Center 100MG Storage Tank 2026 INSPECTION

5.0 SAFETY OBSERVATIONS

TOWER ACCESS LADDER

Ladder was found in good condition with no visible damage or defects and is currently safe for use with maintenance needed.

Fall arrest cable system was observed in place with no visible damage. Cable & guides are not adequately tensioned and scheduled for maintenance.

Corrective Action Base Bid 0003

{Scheduled -Adjust safety climb device}

BALCONY ENTRY

16 inch width of the balcony passthrough opening from the access ladder does not meet the OSHA minimum of 24 inch.

Minor modications are recommended to enlarge ladder opening and install a self-closing gate.

Maintenance Needed Base Bid 0008

{Scheduled Misc. Repairs Not to Exceed}

ROOF ACCESS

LADDER

Ladder was found in good condition with no visible damage or defects and is currently safe for use with maintenance needed.

Ladder siderail is sectioned (not continuous) with a minimal gap.

A cover plate should be welded in place to fully join ladder sections, providing a continuous side rail.

Fall arrest cable system was observed in place with no visible damage. Cable & guides are not adequately tensioned and scheduled for maintenance.

Corrective Action Base Bid 0003 Base Bid 0008

{Adjust safety climb device/ Misc. Repairs not to Exceed)

RAILINGS- Balcony

Railing observed in good condition with no visible damage.

Railing meets OSHA standards for top rail height of 42 in. Midrail and toeboard are in place. See additional balcony information below in TELECOM ITEMS

See telecom notes

INTERIOR ACCESS

LADDER

Ladder is mechanically connected to tank bottom to meet NFPA 22 requirements. Ladder was found in fair condition with moderate corrosion noted on upper three rungs. No other visible damage or defects and is currently safe for limited use with maintenance needed. Stainless fall arrest cable system was observed in place with no visible damage. Cable & guides are not adequately tensioned and scheduled for maintenance.

Corrective Action Base Bid 0003

{Scheduled -Adjust safety climb device}

INTERIOR RISER LADDER

Ladder is inaccessible for inspection and noted as ‘in place’ only with fall protection cable system bracket visible. Condition of ladder and fall arrest system is unknown. A full condition assessment is needed at the next scheduled interior cleaning.

Corrective Action Base Bid 0006

{Scheduled Tank Draining & Clean}

INTERIOR RISER

RAILING

No perimeter railing or guard in tank bottom at riser opening.

Consider installing a safety component at next major renovation.

Maintenance needed Option 3008 Option 3009

{Year 3- Misc. Repairs Not to Exceed / Interior Coatings}

VA Medical Center 100MG Storage Tank 2026 INSPECTION

5.0 Safety Observations (Cont.)

AUXILIARY ROOF

ENTRY

No secondary access hatch. 24” NFPA vent flange will suffice as an additional opening when needed but is not practical.

No action

EXTERIOR ROOF

RAILING

No handrails or perimeter guard rail in place. Rigging/ painters ring in place at roof perimeter was observed in good condition with no visible damage. Roof has adequate points for safe tie-off.

No action

SHELL MANWAY-

BALCONY

No auxiliary entry / egress at balcony level. Consider installation at next major renovation in lieu of any additional roof hatch.

Maintenance needed Option 3008 Option 3009

{Year 3- Misc. Repairs Not to Exceed / Interior Coatings}

GROUND LEVEL ENTRY

18” pressure-style opening at base of 30” riser. No visible leaks.

Note: 24” is considered minimum safe opening for rescue.

No action

PLACARDS /SIGNAGE

No warning signage for EM or RF exposure as required by OSHA Confined Space placard in place at Riser Manway Entry.

Maintenance needed

TELECOM ITEMS

Components installed onto balcony railing create added lateral wind loads and stresses. Additional supports should be added to prevent damage to balcony railing and floor. Alternatively, components should be installed at roof level to a dedicated corral. Balcony floor is a structural component and is at risk of damage or cracking from repeated or continuous movement generated by telecom items attached to railing.

Maintenance needed All costs should be absorbed by Telecom Installer(s)

RF EXPOSURE

Electromagnetic (EM) and Radio Frequency (RF) readings taken during inspection show the existing cellular components emit frequencies exceeding occupational exposure limits for personnel as defined by OSHA. Future work for any extended period will require these components to be deenergized in accordance with OSHA Lock Out/ Tag Out Procedures during the presence of workers.

Corrective Action for Worker Safety to be implemented and enforced

OBSTRUCTIONS

Impediments and safety obstructions were observed and noted.

Telecom connectors and wiring connected to siderail of roof ladder. Various trip hazards noted -poorly secured wiring/coax.

Maintenance needed All costs should be absorbed by Telecom Installer(s)

VA Medical Center 100MG Storage Tank 2026 INSPECTION

OVERALL SAFETY CONDITION : FAIR with exceptions as noted

Some deciencies indicated for any Corrective Action or Maintenance are documented and ready for scheduled service. Other items can be progressively corrected as needed under a Not to Exceed option of a proposed maintenance plan.

Testing showed that RF levels near the cellular equipment exceed occupational safe distance requirements. Equipment will need to be isolated if workers are near this equipment for longer than a few moments. Safety conditions relating to telecommunication installation and improvement should be corrected by the telecom equipment owner (e.g., provider, contractor, company, etc.). ALL costs should be on the equipment owner. Future work should be restricted or limited access should be enforced, along with a detailed work plan for any additions, changes or modications. Oversight and follow-up inspection by a neutral third party will ensure proper installation and procedures are followed.

5.0 Safety Observations (Cont.)

ELECTRICAL

COMPONENTS

Sections of rigid and flex conduit were observed damaged or exposed. Exposed wiring and open junction boxes were observed. 120V service was tested and found active to the tank roof level. Age of GFCI breaker is unknown and should be upgraded as a precaution. Repairs are recommended for safety of personnel.

Maintenance Needed Schedule with any option year {Misc. Repairs Not to

Exceed}

FALLING OBJECTS

Loose items, hardware, spare telecom parts, etc. should be removed to protect passers-by from potentially falling objects.

Primary roof vent cover should have a permanent tether installed to prevent accidental drops during maintenance or complete removal in the event of wind/storm damage.

Maintenance Needed Schedule with any option year {Misc. Repairs Not to

Exceed}

ABANDONDED or

OUT-OF SERVICE

ITEMS

Components no longer in use, abandoned, or damaged should be removed periodically as part of routine maintenance.

Insistence that any Telecom accessories, including wiring/coax, loose hardware on balcony, etc., be removed as a condition of any new component being installed. Waste telecom cables discarded at the tank base should immediately be removed from the site by technicians on completion of their service.

Maintenance Needed Schedule with any option year {Misc. Repairs Not to

Exceed}

VA Medical Center 100MG Storage Tank 2026 INSPECTION

6.0 STRUCTURAL OBSERVATIONS

OVERALL STRUCTURAL CONDITION : GOOD with exceptions as noted

No observable structural deciencies were found during visual inspection. Additional information is needed on interior riser piping and inlet/outlet piping to be obtained during a scheduled Interior Tank Clean & Drain. A supplemental report of the existing cathodic protection system, maintenance and components will be submitted.

SITE DRAINAGE

Adequate site drainage; no evidence of ponding, standing water, or soil erosion near foundation piers.

No action

FOUNDATION PIERS

Concrete foundation pads observed in good condition. No spalling or visible damage. Tops of concrete footings are 6 inches or greater above nished grade.

No action

ANCHORORAGE

Anchor bolts were found sufficiently tightened. No visible damage or excess corrosion was observed on anchors or connectors.

No action

DIAGONAL BRACING

Tower wind rods were observed to be sufficiently tensioned with no visible damage.

No action

ROOF VENTING

Secondary vent has failsafe / vacuum release. No low spots on roof surface; No visible damage from vacuum pressure.

No action

OVERFLOW PIPING

8” overow piping. Inlet piping was not accessible at inspection and size unknown. Inlet pipe size will be needed to determine if overow is sufficient for maximum discharge.

Additional info needed {Scheduled during Tank

Drain & Clean}

VORTEX BREAKER

Presence of a vortex breaker on the outlet pipe as required by NFPA 22 is unknown. Inlet/Outlet piping was not accessible at inspection.

Additional info needed {Scheduled during Tank

Drain & Clean}

GIRDERS/STIFFENERS No observable damage. No action

GROUNDING Ground cable observed connected in place. No action

WATER TIGHTNESS No evidence of leaks, past or present. No action

CATHODIC PROTECTION Supplemental maintenance summary provided See additional summary

VA Medical Center 100MG Storage Tank 2026 INSPECTION

7.0 SITE & SECURITY

OVERALL SITE SECURITY & VULNERABILITY: GOOD with improvements needed

Address any immediate security vulnerabilities as allowable. Remove/ repair / correct ground level items within the scope of facility or groundskeeping maintenance. Maintain existing schedule of repair for items at upper levels.

SITE ACCESS Controlled or limited access; not secure No action

PERIMETER

FENCING

Perimeter fencing is unsecure, damaged or not fully in place. Access gate is locked.

See below

TOWER ACCESS

A locking cover is in place at base of access ladder. Access ladder height-from-ground is ~12ft.

A sufficient length aluminum extension ladder is available inside the fenced perimeter to provide access to unauthorized personnel. Repairing of fencing and removal of ladder should be completed as a priority.

Immediate Corrective Action to eliminate a known vulnerability

ROOF HATCH

ENTRY

Roof entry hatch is bolted in place- Install a padlock as needed for additional security.

Maintenance recommended

ROOF VENTING

Primary roof vent cover is not tamper-proof. Cover could be easily removed. Secondary roof vent is exposed and readily accessible to vandalism. Install vandal-proof devices on venting as necessary.

Maintenance recommended

WARNING

BEACON

An FAA, L810, steady burning dual obstruction beacon is in place with globes intact. No visible damage with power supply at the unit. Full functionality will be tested at the scheduled bulb replacement.

Existing LED bulbs do not meet FAA requirement for NVG (infrared emitting). Replacement with approved incandescent bulbs with a minimum requirement of 120V, ~ 8000hr, krypton lled.

Corrective Action Base Bid 0007

{Scheduled Aviation Bulb Replacement}

LIGHTING Street lighting and basic perimeter lighting. No action

CAMERAS Unknown No action

VA Medical Center 100MG Storage Tank 2026 INSPECTION

8.0 INTERIOR COATING EVALUATION

OVERALL INTERIOR COATING CONDITION : FAIR

Recommendation: Proceed with scheduled interior coating improvements at year four of an ongoing maintenance plan. Specify sealing of the open roof joints with an NSF approved urethane (exible) joint sealant during the coating procedure to prolong coating life and prevent unsightly staining.

Fair Condition = Light-to- moderate coating damage; Localized or isolated areas of debonding; (Acceptable) weathering on aged coatings; (Acceptable) abrasions on aged coatings. Light-to-Moderate mold or debris staining. No excessive corrosion, No large areas of debonding. Acceptable adhesion of existing coatings; Often repairable with maintenance coatings; Typically, acceptable for overcoating.

SURFACE CONDITION Damaged Surface Area

Avg. Coating Thickness

ROOF PLATES

No visible coating damage or debonding. Moderate staining is present from surface corrosion along the unwelded/unsealed roof joints.

<1% 9.0 mils DFT

ROOF SUPPORT N/A N/A

ROOF KNUCKLE No visible corrosion or debonding observed. Minor staining 0%

SHELL PLATES Moderate staining. No visible debonding. Localized abrasions noted. <2%

BOWL KNUCKLE

Not fully visible due to sediment layer. No coating damage observed over visible areas.

BOWL BOTTOM

Not fully visible due to sediment layer. No coating damage observed over visible areas.

RISER PIPING Inaccessible ------

Thickness readings limited to surfaces within immediate reach

APPURTENANCES

ROOF VENT

Primary central roof vent shows no visible corrosion or coating damage.

Newly installed secondary roof vent shows nearly 100% coating failure on the internal surface.

100%

ROOF HATCH

Minor coating abrasions and corrosion on interior hatch frame and interior perimeter.

5%

ACCESS LADDER

Visible coating loss and corrosion on upper three rungs and upper connecting hardware. Minor abrasions overall.

10%

OVERFLOW WEIR Visible corrosion and possible metal loss on the overow intake weir box. 15%

VA Medical Center 100MG Storage Tank 2026 INSPECTION

9.0 EXTERIOR COATING EVALUATION

OVERALL EXTERIOR COATING CONDITION : POOR

Recommendation Consider coating the exterior. Existing coating is no longer adequately protecting the exterior surfaces. The existing coating is likely still in a condition that maintenance or overcoating will extend the lifespan another 7-12 years. A full exterior renovation is inevitable. Coating samples were not collected and tested for presence of lead or heavy metals during this inspection process. Sampling will be necessary to determine if containment & abatement procedures are necessary in the event of a full renovation.

Poor Condition = Large % of surface area damage, debonding or (Unacceptable) weathering on aged coatings. Heavy mold, mildew, or mineral staining. Poor adhesion of existing coatings; Often prolonged with maintenance coatings; Conditionally acceptable for overcoating.

EXTERIOR CONDITION Damaged Surface Area

Avg. Coating Thickness

ROOF PLATES

Coating shows moderate cracking/ checking and surface corrosion; Likely age-related UV degradation and weathering.

Coating appears tightly adhered with no visible debonding.

75% 8.0 mils DFT

ROOF KNUCKLE

Coating shows moderate cracking/ checking and surface corrosion; Likely age-related UV degradation and weathering.

Coating appears tightly adhered with no visible debonding.

40% 8.0 mils DFT

SHELL PLATES

Localized, minor coating damage. Visible debris and staining. No visible debonding.

10% 9.0 mils DFT

BALCONY

Minor abrasions on upper surfaces (typical) with no visible debonding.

Localized corrosion noted on underside of balcony oor.

10% -----

BOWL PLATES No visible coating damage. No visible debonding. ---- -----

RISER PIPING

Coating shows moderate cracking/ checking and surface corrosion; Likely age-related UV degradation and weathering. Coating appears tightly adhered with no visible debonding.

65% -----

COLUMNS/

LEGS/ SUPPORTS

Moderate cracking/ checking and surface corrosion; Likely age-related UV degradation and weathering. Coating appears tightly adhered with exceptions as noted: Localized debonding of top coating noted on sections of legs/columns appear to damage caused by previously installed telecom bracketry and not being considered a failure of the coating.

20% ------

APPURTENANCES Localized, minor coating damage. No visible debonding -----

Thickness readings limited to surfaces within immediate reach

VA Medical Center 100MG Storage Tank 2026 INSPECTION

Roof Vent Corrosion

Weir Box Corrosion

INTERIOR ROOF SURFACES

Staining as a result of unsealed, unwelded roof joints

VA Medical Center 100MG Storage Tank 2026 INSPECTION

Meets NFPA standard

Uniform sediment layer Interior ladder corrosion

INTERIOR VIEWS, Typical

VA Medical Center 100MG Storage Tank 2026 INSPECTION

ROOF EXTERIOR

VA Medical Center 100MG Storage Tank 2026 INSPECTION

ROOF EXTERIOR

VA Medical Center 100MG Storage Tank 2026 INSPECTION

ROOF VENTING

Oversized screening Oversized screening

VA Medical Center 100MG Storage Tank 2026 INSPECTION

1. ROOF HATCH COVER & FRAME

2. TELECOM ITEMS ATTACHED TO LADDER RAIL

VA Medical Center 100MG Storage Tank 2026 INSPECTION

1. ROOF ACCESS LADDER & FALL ARREST

2. BALCONY TOP RAIL & TOE BOARD

VA Medical Center 100MG Storage Tank 2026 INSPECTION

BALCONY, Typical

OBSTRUCTIONS

VA Medical Center 100MG Storage Tank 2026 INSPECTION

BALCONY PASS THROUGH OPENING

ACCESS LADDER & FALL ARREEST

24” Min. OPENING NEEDED

VA Medical Center 100MG Storage Tank 2026 INSPECTION

EXTERIOR SURFACE CORROSION

VA Medical Center 100MG Storage Tank 2026 INSPECTION

EXTERIOR SURFACE CORROSION

VA Medical Center 100MG Storage Tank 2026 INSPECTION

EXTERIOR GROUND AND LADDER ACCESS

VANDAL DETERRENT

Onsite ladder for unauthorized access

Damaged perimeter fencing

VA Medical Center 100MG Storage Tank 2026 INSPECTION

OVERFLOW PIPING & DISCHARGE

VA Medical Center 100MG Storage Tank 2026 INSPECTION

PREVIOUSLY DROPPED OR FALLEN ITEMS

DISCARDED & ABANDONED TELECOM COAXIAL CABLES

Grounding cable in place

Falling Object Hazard

VA Medical Center 100MG Storage Tank 2026 INSPECTION

DAMAGED OR EXPOSED ELECTRICAL

VA Medical Center 100MG Storage Tank 2026 INSPECTION

Cost estimates are not provided as part of this report.

11.0 PROJECTIONS & COST ESTIMATIONS