M301_HVAC Details.pdf

PDF 489 KB Posted

Attached to
Y1NE| SOLICIATION | 36C25626R0015 | CONSTRUCT NEW WATER STORAGE FACILITY
Solicitation number
36C25626R0015
Issued by

About this file

This document is a construction drawing set for a new water storage facility project for the U.S. Department of Veterans Affairs located in Fayetteville, Arkansas. The construction documents, issued on 05-05-2025, contain mechanical HVAC details and system specifications for the facility.

The project requires contractor furnishing and installation of a Building Automation System (BAS) featuring web-enabled native BACnet building controllers and equipment controllers capable of integrating and monitoring all new HVAC systems. The BAS must integrate into the existing campus front end network. Ductless split system monitoring (DSFC/DSCU) equipment shall be controlled by wall-mounted, hard-wired manufacturer-supplied thermostats with a 78-degree space temperature setpoint, with DDC monitoring space temperature and alarming when space temperature exceeds 90°F. HVAC installations include ductless mini-split systems with specified refrigerant piping requirements, including insulation of suction lines and liquid lines (liquid lines insulated only on ductless mini-splits), water-tight aluminum jacketing on all exterior refrigerant piping, and proper expansion valve configuration with bulb placement. Piping supports utilize P100 Unistrut channels with unicushion insulation material for copper piping, wing-shape fittings secured with masonry anchor bolts, and Schedule 40 PVC piping as noted on plans. The A/E of record is JohnsonDanforth & Associates, Little Rock, Arkansas, with project number 2018.001 and drawing number M301. The document is marked as Controlled Unclassified Information (CUI) and indicates the facility is fully sprinklered.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AIR ADMITTANCE

VALVE EQUAL TO

STUDOR MINI-VENT

CLEANOUT PLUG

CEILING SLOPE 1/8" PER FT. SLOPE

HANGER (TYP.)

SCH. 40 PVC (SIZE

AS NOTED ON

PLANS)

FLEX TUBING

COVER EQUAL TO AIRTEC TYPE

A EXPOSED LINESET WITH 90

DEG. ELBOW

LIQUID LINE

MINI-PUMP

SUCTION LINE

MINISPLIT

FAN COIL

5'-0" MIN

1.

2.

3.

4.

NOTES:

WRAP EXPANSION VALVE, BULB AND FITTINGS WITH ARMAFLEX INSULATION TAPE

AND SECURE WITH BLACK CABLE TIES.

TRAP AND LOOP AT EVAPORATOR COIL IS NOT REQUIRED FOR UNITS WITH LIQUID

LINE SOLENOID VALVES.

SUCTION LINES SHALL BE INSULATED. LIQUID LINES SHALL BE INSULATED ONLY

ON DUCTLESS MINI-SPLITS.

INSTALL WATER-TIGHT ALUMINUM JACKETING ON ALL EXTERIOR REFRIGERANT

PIPING.

LOOP SUCTION LINE TO

ABOVE TOP OF

EVAPORATOR COIL

EXTERNAL EQUALIZER

SIGHT GLASS

LIQUID LINE SERVICE

GAUGE PORT

FILTER / DRYER

SERVICE VALVES

SLOPE TO UNIT

REFRIGERANT ACCESSORIES FURNISHED

WITH THE UNIT WILL BE ACCEPTABLE FOR

USE. NO DUPLICATION OF ACCESSORIES

WILL BE REQUIRED.

CONDENSIN

G UNIT

EVAPORATOR

COIL

THERMAL ELEMENT

LOCATE BULB AS CLOSE TO COIL OUTLET AS

POSSIBLE. INSTALL EQUALIZER LINE

DOWNSTREAM OF BULB. LOCATE BULB ON

TOP OF SUCTION PIPE FOR 5/8" O.D. AND

LESS ALL SUCT. PIPING LARGER THAN 5/8"

O.D. SHALL BE INSTALLED ON SIDE AT 3

O'CLOCK POSITION.

DRAIN PAN

CONDENSATE DRAIN

SMALL TRAP IN SUCTION LINE TO PREVENT ERRATIC

OPERATION OF EXP. VALVE DURING START-UP

R L

R S

P100 UNISTRUT CHANNEL,

LENGTH AS REQUIRED

SINGLE PIECE PIPE STRAP,

SECURED TO UNISTRUT WITH HEX

HEAD CAP SCREWS AND CHANNEL

NUTS WITH SPRINGS

UNICUSHION INSULATION MATERIAL

FOR COPPER PIPING

PIPE - SEE PLAN FOR SIZE AND

ROUTING

P2345 WING SHAPE FITTING, SECURED TO

CHANNEL WITH HEX HEAD CAP SCREW

AND CHANNEL NUT WITH SPRING AND TO

CONCRETE WITH 5/16" MASONRY ANCHOR

BOLTS

CONCRETE OR FLOOR

MSTPMSTPMSTP

MSTP

Existing Unitary Controllers

Existing Unitary Controllers

Existing Unitary Controllers

Existing Unitary Controllers

Existing BACnet Network

Building 49 Existing BACnet Network

Building 3

Existing BACnet Network Administration

Building

OTHER NETWORKS ARE TOO LARGE TO

REFLECT ON THIS SHEET. AS-BUILT

DRAWINGS ON FILE AT NORTHWEST

CONTROLS. CONTACT JOSH DAVIS

(479) 872-9000 AS NEEDED FOR MORE

INFORMATION.

Mini-Split

BACnet Interface Typical of 3

Existing Unitary Controllers

Existing Unitary Controllers

Ethernet

Existing BAS Server

Windows 10 PC

BACnet Global Controller

System Architecture

S

PL101 -

Chlorination Closet 103 Vent Fan Status w/ Fail Alarm

HVAC CONTROLS GENERAL NOTES:

CONTRACTOR SHALL FURNISH AND INSTALL BUILDING

AUTOMATION SYSTEM (BAS) AS FOLLOWS:

· WEB ENABLED NATIVE BACNET BUILDING CONTROLLER AND

EQUIPMENT CONTROLLERS CAPABLE OF ALL NEW HVAC

SYSTEMS INTEGRATION AND MONITORING AS SHOWN.

· INTEGRATION OF BUILDING CONTROLLER INTO EXISTING

CAMPUS FRONT END.

· DUCTLESS SPLIT SYSTEM MONITORING (DSFC / DSCU):

·· EQUIPMENT SHALL BE CONTROLLED BY WALL MOUNTED,

HARD-WIRED MANUFACTURER SUPPLIED THERMOSTAT

WITH 78 DEG SPACE TEMPERATURE SETPOINT.

·· DDC SHALL MONITOR SPACE TEMPERATURE AND ALARM

ON SPACE TEMP ABOVE 90°F.

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

CONTROLLED UNCLASSIFIED INFORMATION - CUI

CONTROLLED UNCLASSIFIED INFORMATION - CUI

FULLY SPRINKLERED

4/

/2

2:

:5

PM

CONSTRUCTION

DOCUMENTS

CONSTRUCT NEW WATER

STORAGE FACILITY

FAYETTEVILLE, AR

05-05-2025

564-19-101

JDA PROJECT #: 2018.001

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

STRUCTURAL ENGINEER

BERNHARD TME

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

GENERAL NOTES

SHEET NOTES

PARTITION LEGEND

SECURITY

GRW

801 CORPORATE DRIVE

LEXINGTON, KY 40503

CIVIL ENGINEER

HODGES ENGINEERING

231 SHORELINE DRIVE

MOUNTAIN HOME, AR 72653

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 BURLINGTON STREET, STE. 200

NORTH KANSAS CITY, MO 64116

NEW UNRATED PARTITION

NEW / EXISTING 1 HOUR BARRIER

BB CD

MECHANICAL

HVAR DETAILS

M301

Sheets and Views
Layout1

File details come from the government source that posted it. Updated .