This pre-solicitation notice provides information for Project 520-22-169 to upgrade mechanical systems at three Department of Veterans Affairs locations. The project involves upgrading mechanical systems at the Joint Ambulatory Care Clinic in Pensacola, Florida, the Magnolia Clinic in Panama City, Florida, and the Eglin Air Force Base VA Clinic in Eglin AFB, Florida. The scope of work includes upgrades to HVAC, plumbing, and electrical systems. The anticipated solicitation date is listed as TBD. Interested parties are advised to monitor the federal business opportunities website for release of the subsequent solicitation containing proposal due dates and other details. The contracting agency is listed as the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

New washer location

Attachment B: Decon Site Prep

New washer location

Remove

Eye-wash

42 [1067]

UNIT WIDTH

80 [2032]

UNIT

HEIGHT

31 [787]

LOADING

HEIGHT

26-1/4 [667]

LOADING

CLEARANCE

HEIGHT

[203]

[305]

91 [2311]

RAISED DOOR

HEIGHT

32 [813]

MAX LENGTH

31 [787]

UNIT LENGTH

94 [2388]

SERVICE AREA

HEIGHT

11 [279]

45 [1143]

WALL OPENING

*(NOTE F)

1-1/2 [38]

MINIMUM

94 (2388)

*(NOTE E, F AND G)

MAX 1 [25]

ADJUSTMENT WITH

WASHER LEGS

(UNIT HEIGHT 81 MAX)

MINIMUM

90 [2286]

*(NOTE E, F AND G)

T I T L E

EQUIPMENT DRAWING OF

AMSCO® 5052 SINGLE-CHAMBER WASHER/DISINFECTOR

ELECTRIC HEATED, NON-VENTED, UNIT OFFSET FROM WALL

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER

& REVISIONA N/A Vincent Carmichael 10232353

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

SERVICE AREA

REQUIRED FOR

DRYING MOTOR

REMOVAL

TYPICAL INSTALLATION

NOTES:

(A) UNLESS OTHERWISE SPECIFIED, ALL DIMENSIONS ARE IN INCHES [MM].

(B) SERVICE ACCESS SIDE OF UNIT IS RECOGNIZED BY THE TOUCH SCREEN AT THE RIGHT OF

WASH CHAMBER. ELECTRICAL AND CONTROL COMPONENTS, AS WELL AS MOST OF

SERVICABLE PARTS ARE ACCESSIBLE FROM THAT SIDE OF UNIT. NON-SERVICE SIDE IS

EQUIPPED WITH THE TOUCH SCREEN ON THE LEFT OF THE WASH CHAMBER.

(C) CUSTOMER MUST BE SURE THAT MACHINE STANDS ON A NON-COMBUSTIBLE FLOOR.

(D) WEIGHTED EQUIVALENT SURFACE SOUND PRESSURE LEVEL: 64.0 db(A) CALCULATED AS DESCRIBED IN ISO 3746.

(E) VERTICAL BARRIER WALL FLANGES ARE PROVIDED WITH UNIT TO FILL GAP BETWEEN

UNIT AND WALL ON BOTH SIDES. DIMENSIONS ARE 3-1/2 [88.9] WIDTH X 82 [2082.8] LONG.

(F) HORIZONTAL BARRIER WALL FLANGES ARE PROVIDED WITH UNIT TO FILL GAP BETWEEN

UNIT AND WALL ON BOTH SIDES. DIMENSIONS ARE 49 [1244.6] WIDTH X 16-3/8 [416] HEIGHT.

(G) FOR A WASHER INSTALLATION WITH BARRIER WALL FLANGES,THE WALL OPENING HEIGHT

MUST BE BETWEEN, 90 AND 95.5 [2286-2426] AND MINIMUM CEILING HEIGHT MUST BE 98 [2489].

FRONT VIEW

SERVICE ACCESS

SIDE OF UNIT

*(NOTE B)

TOP VIEW

PASS THROUGH

DOOR

SIDE VIEWLEVEL FLOOR

*(NOTE C)

W A

LL

O

P E

N

IN

G H

E

IG

H T

C E

IL

IN

G H

E

IG

H T

F O

R D

O O

R R

E M

O V

A L

[102]

Page 1 of 10 10232353.F

Released

2X 36-1/4 [921]

2X 26-1/2 [673]

4-3/8 [111]

1-3/4 [44]

27-1/4 [692]

[533]

6-1/4 [159]

11-1/4 [286]

6X 12 [305]

T I T L E

EQUIPMENT DRAWING OF

AMSCO® 5052 SINGLE-CHAMBER WASHER/DISINFECTOR

ELECTRIC HEATED, NON-VENTED, UNIT OFFSET FROM WALL

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER

& REVISIONA N/A Vincent Carmichael 10232353

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

*NOTES:

(A) CONCRETE FLOOR MUST REMAIN FREE OR DEFECTS IN THESE AREA, AS PER ESR-1917 SECTION 4.1.10

FOR INSTALLATION OF SEISMIC ANCHORS (NOT PROVIDED BY STERIS).

(B) THE FLOOR SINK AND DRAIN SHALL NOT OCCUPY THESE AREAS.

SEISMIC MOUNTS

SEISMIC ANCHORAGE

FOR DETAIL SEE FD085

QTY 4 OR 6 ANCHORS

FINISHED WALL

PREFERENCE

LOCATION OF

FLOOR SINK.

SEE PAGE 4 *(NOTE 5)

*(NOTE A AND B)

Page 2 of 10 10232353.F

[2032]

6-1/4 [159]

31-1/2 [800]

31-1/8 [791]

13-7/8 [352]

16-1/2 [419]

[483]

21-1/2 [546]

11-1/4 [286]

HW HOT WATER

CW COLD WATER

PW PURE WATER

A COMPRESSED AIR

D FLOOR DRAIN LOCATION

T I T L E

EQUIPMENT DRAWING OF

AMSCO® 5052 SINGLE-CHAMBER WASHER/DISINFECTOR

ELECTRIC HEATED, NON-VENTED, UNIT OFFSET FROM WALL

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER

& REVISIONA N/A Vincent Carmichael 10232353

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

UTILITY (PLUMBING)

CONNECTION POSITION

FRONT VIEW

A

PW

HW

CW

D

SIDE VIEW

HW

CW

PW

A

D

TOP VIEW

HW

CW

PW

A

D

Page 3 of 10 10232353.F

74-3/4 [1898.7]

35-3/8 [898.5]

[508]

[762]

[228.6]

34-1/8 [866.8]

E ELECTRICAL

N NETWORK

T I T L E

EQUIPMENT DRAWING OF

AMSCO® 5052 SINGLE-CHAMBER WASHER/DISINFECTOR

ELECTRIC HEATED, NON-VENTED, UNIT OFFSET FROM WALL

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER

& REVISIONA N/A Vincent Carmichael 10232353

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

UTILITY (ELECTRICITY)

CONNECTION POSITION

FRONT VIEW SIDE VIEW

EN E

N

TOP VIEW

E

N

Page 4 of 10 10232353.F

[2032]

4-3/4 [121]2-3/4

[70]

T I T L E

EQUIPMENT DRAWING OF

AMSCO® 5052 SINGLE-CHAMBER WASHER/DISINFECTOR

ELECTRIC HEATED, NON-VENTED, UNIT OFFSET FROM WALL

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER

& REVISIONA N/A Vincent Carmichael 10232353

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

UTILITY (VENTILATION)

CONNECTION POSITION

FRONT VIEW SIDE VIEW

TOP VIEW

Page 5 of 10 10232353.F

60 [1524]

REF

8-3/8 [213]

11FT [3.35m]

MAX.

17 [432]

INSTRUMENT UTENSIL

CHEMICAL

(CH)

ENZYME CONSUPTION PER CYCLE

(SEE PAGE 3; *(NOTE 4))

0.94oz (28ml) at 1/10oz/gal (0.8ml/L) 0.58oz (17.2ml) at 1/10oz/gal (0.8ml/L)

DETERGENT CONSUPTION PER CYCLE

(SEE PAGE 3; *(NOTE 4))

0.94oz (28ml) at 1/10oz/gal (0.8ml/L) 0.58oz (17.2ml) at 1/10oz/gal (0.8ml/L)

LUBRICANT CONSUPTION PER CYCLE

(SEE PAGE 3; *(NOTE 4))

0.23oz (7ml) at 1/10oz/gal (0.8ml/L) N/A

T I T L E

EQUIPMENT DRAWING OF

AMSCO® 5052 SINGLE-CHAMBER WASHER/DISINFECTOR

ELECTRIC HEATED, NON-VENTED, UNIT OFFSET FROM WALL

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER

& REVISIONA N/A Vincent Carmichael 10232353

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

*NOTES:

(A) DOSING STATION AND CHEMICAL CONTAINERS MUST BE ON THE SAME FLOOR OF THE BUILDIN AS THE WASHER/DISINFECTOR.

CHEMICAL CONTAINER MUST BE LOCATED AT A LOWER HEIGHT THAN DOSING STATION. MAXIMUM CONTAINER INCLINATION

IS 15 DEG FROM FLOOR. AMBIENT TEMPERATURE SHALL NOT EXCEED 32°C (90°F)

(B) HP PICKUP TUBE SYSTEM CAN PROVIDE UP TO TWO WASHERS WITH CHEMISTRY FROM THE SAME CONTAINER.

DOSING STATION

CEILING

ROUTE CHEMICAL LINES

AND SIGNAL CABLE

THROUGH PIPE TO REACH

BOTTOM OF UNIT

CHEMICAL CONTAINERS

*(NOTE A)

12 FT (3.6M) OF INJECTION LINE

(FROM CONTAINERS TO

DOSING STATION)

*(NOTE B)

DOSING STATION

WEIGHT : 15LBS (6.8KG)

2X FD087 SHOWN

UP TO 5 TUBES

100 FT (30m) OF INJECTION LINE

AND SIGNAL CABLE

DETERGENT LINES SHALL NOT BE IN CONTACT WITH HOT SURFACES.

STERIS RECOMMENDS CUSTOMER TO ROUTE CHEMICAL LINES AND

SIGNAL CABLE THROUGH A 3" (76) ID CONDUIT.

EXCESS LENGTH MUST BE CUT BEFORE CONNECTING TO

WASHER/STATION TO AVOID FORMING BUNDLES THAT COULD

AFFECT THE CHEMICAL INJECTION SYSTEM'S PERFORMANCE

(DO NOT CUT COMMUNICATION CABLES).

Page 6 of 10 10232353.F

AMSCO 5052 SINGLE CHAMBER WASHER/DISINFECTOR

UTILITY REQUIREMENTS CHART (PLUMBING)

UTILITY PARAMETER REQUIREMENT NOTES

HOT WATER

(HW)

*(NOTE 6)

CONNECTION SIZE / TYPE 1/2 in / FEMALE NPT [1/2 in / MALE BSPT]

1. STERIS REQUIRES TO INSTALL WATER HAMMER

ARRESTOR, UNION & PRESSURE GAUGE.

2. CUSTOMER MUST PROVIDE UTILITY

CONNECTIONS WITH SHUTOFFS DISCONNECTS

WITHIN 2 FEET OF THE PERIMETER OF THE

EQUIPMENT AND BELOW THE CEILING DECK.

*STERIS OFFERS FLEXIBLE HOSES

ACCESSORY (FD088 OR FD037)

WITH INSTRUCTIONS.

3. BACK FLOW PREVENTER AGAINST BACK

SIPHONAGE MAY BE REQUIRED (LOCAL

PLUMBING CODE). FOR COLD WATER ONLY.

PRESSURE RANGE

15 - 50 psig DYNAMIC

[103-345 kPa] MAX. 90 psig STATIC [620 kPA]

OPERATING FLOW RATE 12.8 US GPM [48.5 L/min] TO

23.8 US GPM [90.1 L/min]

TOTAL CONSUMPTION PER

INSTRUMENT CYCLE

*(NOTE 4)

28.5 US GAL [108.0L]

TEMPERATURE RANGE 110°F [43°C] TO 150°F [65.5°C]

WATER QUALITY *(NOTE 5) HARDNESS (CaCO3) : 50-80 ppm (MAX. 120 ppm)

COLD WATER

(CW)

*(NOTE 6)

(NOTE 3)

CONNECTION SIZE / TYPE 1/2 in / FEMALE NPT [1/2 in / MALE BSPT]

4. CONSUMPTION BASED ON INSTRUMENT CYCLE WITH

PROLYSTICA ULTRA CONCENTRATE CHEMICALS (PUC)

WITH THE FOLLOWING UTILITY CONDITIONS:

(CW) COLD WATER PRESSURE: 30 psig DYNAMIC [207 kPa]

(CW) COLD WATER TEMPERATURE: 60°F [16°C]

(HW) HOT WATER TEMPERATURE: 110°F [43°C]

(PW) PURE WATER TEMPERATURE 70°F [21°C]

(S) STEAM SUPPLY: 50 psig DYNAMIC [345 kPa]

UTENSIL CYCLE CONSUMPTION:

CW: 17.4 US GAL [66.0L]

HW: 5.8 US GAL [22.2L]

PW: 5.8 US GAL [22.0L]

S: 16.7 LB [7.5KG]

5. STERIS RECOMMENDS THE FOLLOWING WATER

QUALITY PARAMETERS:

TOTAL DISSOLVED SOLIDS: 100-200 ppm (MAX. 500 ppm) TOTAL ALKALINITY (CaCO3) : 70-120 ppm (MAX. 180 ppm) pH : 6.8-7 (MAX. 7.5 ppm) TOTAL SILICA : 0.1-0.5 ppm (MAX. 1 ppm)

6. SAMPLING VALVES INSTALLATION AS CLOSE AS

POSSIBLE TO WASHER WATER CONNECTIONS IS

RECOMMENDED. STERIS OFFERS SAMPLING VALVE

OPTION (FD089)

PRESSURE RANGE

30 - 50 psig DYNAMIC

[206-345 kPa] MAX. 90 psig STATIC [620 kPA]

OPERATING FLOW RATE 18.4 US GPM [69.7 L/min] TO

23.8 US GPM [90.1 L/min]

TOTAL CONSUMPTION PER

INSTRUMENT CYCLE

*(NOTE 4)

FOR SUMP FILLING

9.5 US GAL [108.0L]

ADD. FOR DRAIN COOLDOWN (OPTION)

13.2 US GAL [50.0L]

ADD. FOR NON-VENTED SYSTEM:

16.9 US GAL [64.0 L]

TEMPERATURE RANGE 70°F [21°C] MAXIMUM

WATER QUALITY *(NOTE 5) HARDNESS (CaCO3) : 50-80 ppm (MAX. 120 ppm)

PURE WATER

(PW)

*(NOTE 6)

CONNECTION SIZE / TYPE 1/2 in / FEMALE NPT [1/2 in / MALE BSPT]

7. PW IS OPTIONAL. IF UNAVAILABLE, UNIT WILL

PROCESS THERMAL RINSE USING HOT WATER

SUPPLY.

PRESSURE RANGE

5 - 30 psig DYNAMIC

[30 - 206 kPa] MAX. 90 psig STATIC [620 kPA]

OPERATING FLOW RATE 5.0 US GPM [18.2 L/min] TO

23.7 US GPM [90 L/min]

TOTAL CONSUMPTION PER

INSTRUMENT CYCLE

*(NOTE 4)

9.5 US GAL [36.0 L]

TEMPERATURE RANGE 70°F [21.1°C] TO 150°F [65.5°C]

RESISTIVITY

(CONDUCTIVITY) 0.5-0.1 M -cm [2-10 µS/cm] pH 6.8 - 7.5

T I T L E

EQUIPMENT DRAWING OF

AMSCO® 5052 SINGLE-CHAMBER WASHER/DISINFECTOR

ELECTRIC HEATED, NON-VENTED, UNIT OFFSET FROM WALL

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER

& REVISIONA N/A Vincent Carmichael 10232353

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

Page 7 of 10 10232353.F

UTILITY REQUIREMENTS CHART (PLUMBING)

UTILITY PARAMETER REQUIREMENT NOTES

COMPRESSED

AIR

(A)

CONNECTION SIZE / TYPE 1/8 in / FEMALE NPT [1/8 in / MALE BSPT]

1. AIR SPECIFICATIONS (AS PER ISO-8573-1

CLASS 5):

MAX. PARTICLES SIZE 40 microns MAX. PARTICULATE DENSITY 10 mg/m³

MAX. DEW POINT FOR WATER CONTENT

45°F [7°C]

MAX. OIL CONCENTRATION FOR THE OIL

CONTENT 25 mg/m³

2. STERIS RECOMMENDS A REFRIGERATED AIR

DRYER WHERE ENVIRONMENTAL DEW POINT

CONDITIONS ARE HIGHER THAN

RECOMMENDED (CONTACT STERIS SALES

REPRESENTATIVE).

PRESSURE RANGE MIN 80 psig DYNAMIC [552 kPa] MAX. 125 psig STATIC [860 kPA]

OPERATING FLOW RATE 1.75 SCFM [50 L/min]

DRAIN

(D)

CONNECTION SIZE / TYPE 1 1/2 in / MALE NPT

3. STERIS REQUIRES 4 in [102 m] DRAIN.

4. MAX OFFSET OF 3/4 in [19 mm] FROM

OUTLET [PAGE 2, D).

5. STERIS REQUIRES 8 in x 8 in [204 mm x 204 mm] FLOOR SINK

OPERATING FLOW RATE GRAVITY DRAIN : 50 US GPM

[189.3L/min]

T I T L E

EQUIPMENT DRAWING OF

AMSCO® 5052 SINGLE-CHAMBER WASHER/DISINFECTOR

ELECTRIC HEATED, NON-VENTED, UNIT OFFSET FROM WALL

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER

& REVISIONA N/A Vincent Carmichael 10232353

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

CHEMICAL

DOSING

SYSTEM

CEILING ROUTING

CONDUIT 3 in CONDUIT

11. STERIS RECOMMENDS TO ROUTE CHEMICAL

LINES AND SIGNAL CABLE THROUGH A

3 in [76 mm] ID CONDUIT (BY OTHERS).

100 ft [ 30m] OF INJECTION LINE AND

SIGNAL CABLE ARE PROVIDED WITH THE UNIT.

Page 8 of 10 10232353.F

30-1/2 [775]

[406]

21-3/4 [552]

[178]

[330]

[686]

[635]

[584]

T I T L E

EQUIPMENT DRAWING OF

AMSCO® 5052 SINGLE-CHAMBER WASHER/DISINFECTOR

ELECTRIC HEATED, NON-VENTED, UNIT OFFSET FROM WALL

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER

& REVISIONA N/A Vincent Carmichael 10232353

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

POWER (kVA) 30

INPUT (HV) (V 3~, 60Hz) 208/240/600

OUTPUT (LV) (V 3~, 60Hz) 480

WEIGHT LB (KG) 445 (202)

NOISE LEVEL (dBa) 45

NO LOAD LOSS (WATTS) 188.7

LOAD LOSS

302°F (150°C)

(WATTS) 606.9

TOTAL LOSSES (WATTS) 795.6

EXCITATION

CURRENT

(%) 3.13

INSTALLATION WALL/FLOOR

SIZE IN (MM) SEE RIGHT

PRIMARY CONNECTORS

PER PHASE

(AWG) 1X #2 AWG-#14 AWG

SECONDARY CONNECTORS

PER PHASE

(AWG) 2X #0 AWG-#6 AWG

TEMPERATURE

CLASS

°F (°C) 428° (220°)

WINDING (HV) (LV) COPPER

AMSCO 5052 SINGLE CHAMBER WASHER/DISINFECTOR

UTILITY REQUIREMENTS CHART (ELECTRIC)

UTILITY

PARAMETER AND REQUIREMENT NOTES

CONNECTION

SIZE/TYPE

NOMINAL

AMPERAGE

RECOMMENDED

CIRCUIT

ELECTRICITY

(EL)

208-240-600V 60 Hz, 3-Ph

CONVERTED TO

480V

THROUGH TRANSFORMER

(OPTIONAL) FD01-600

N/A 24A

(NOTE 7)

40A

(NOTE 7)

1. ALL CONNECTIONS SHOULD BE IN

ACCORDANCE WITH LOCAL CODES.

2. NEUTRAL WIRE NOT REQUIRED.

3. ALWAYS FOLLOW LOCAL ELECTRICAL CODES

AND SAFETY-RELATED WORK PRATICES TO

DETERMINE THE VALUE OF PROTECTION.

4. WIRING ON THE EQUIPMENT TERMINATES AT

A JUNCTION BOX. WIRING BETWEEN JUNCTION

BOX AND BUILDING SERVICE LINES ARE NOT

SUPPLIED BY STERIS.

5. DISCONNECT SWITCHES WITH OFF POSITION

LOCKOUT (SUPPLIED BY OTHERS) MUST BE

INSTALLED IN ELECTRIC SUPPLY LINES NEAR

THE EQUIPMENT.

6. STERIS RECOMMENDS A LIGHT IN SERVICE

AREA.

7. THESE VALUES ARE FOR THE WASHER UNIT,

NOT FOR THE PRIMARY OF THE TRANSFORMER

460-480V 60 Hz, 3-Ph

3/4 in [21 mm] OR 1 in [27 mm]

CONDUIT

24A 40A

380-400-415V 50 Hz, 3-Ph

3/4 in [21 mm] OR 1 in [27 mm]

CONDUIT

24.9A 40A

380-400V 60 Hz, 3-Ph

3/4 in [21 mm] OR 1 in [27 mm]

CONDUIT

29.8A 40A

NETWORK

(N)

OPTIONAL

100/1000 BASE T SUPPORTING

TCP/IP PROTOCOL

RJ45F CONNECTION

8. NETWORK CONNECTION (IF APPLICABLE)

- ACTIVE NETWORK DROP WITH CAT 5/6 CABLE

WITHIN 10FT [3m] OF UNIT

- STATIC OR DHCP RESERVED IP ADDRESS

(FOR EACH UNIT)

- NETWORK CABLE SUPPLIED BY FACILITY

ENGINEERING DATA-RECOMMENDED

TRANSFORMER TRANSFORMER

Page 9 of 10 10232353.F

UTILITY REQUIREMENTS CHART

UTILITY PARAMETER REQUIREMENT NOTES

VENTILATION

EXHAUST

(EX)

CONNECTION SIZE 3 in [76 mm]

OUTSIDE DIAMETER

1. NOT REQUIRED WITH NON-VENTED UNITS.

2. STERIS REQUIRES CORROSION-RESISTANT AND

WATER-TIGHT DUCT:

- MIN OPERATING TEMPERATURE 210°F [99°C]

- SLOPED TOWARDS THE WASHER AND NO DEAD LEGS

- INSTALL DRAIN PART AT LOWEST POINT NEAR UNIT

*STERIS OFFERS VENTILATION P-TRAP

ACCESSORY (FD84-1)

3. EXHAUST FAN NORMALLY OPEN-AUXILIARY CONTACTS

IS AVAILABLE TO SUPPLY A SIGNAL TO THE FACILITY HVAC

CONTROL SYSTEM WHENEVER THE WASHER VENTILATION

EXHAUST FAN IS IN OPERATION.

PRESSURE RANGE 1/2 in [50 mm]

VACUUM AT CONNECTION

OPERATING FLOW RATE 60 SCFM [1.7m³/min]

TEMPERATURE RANGE MAX. 240°F [116°C]

PHYSICAL SPECIFICATIONS

SHIPPING DIMENSION W x H x L 50 in x 91 in x 42 in [1270 mm x 2311 mm x 1067 mm]

1. LEVELING FEET ARE PROVIDED FOR PROPER INSTALLATION.

2. PERMISSIBLE ENVIRONMENTAL CONDITIONS.

THIS EQUIPMENT IS DESIGNED TO GIVE OPTIMAL RESULTS

UNDER THE FOLLOWING CONDITIONS:

- INDOOR USE ONLY;

- ALTITUDE OF OPERATION UP TO 6562 ft [2000 m];

- TEMPERATURE OF 41 TO 104°F [5 to 40°C];

- MAXIMUM RELATIVE HUMIDITY IS 80% FOR TEMPERATURE UP

TO 88°F [31°C], DECREASING LINEARLY TO 50% RELATIVE

HUMIDITY AT 104°F [40°C];

- POLLUTION DEGREE 2: EQUIPMENT MUST BE INSTALLED IN AN

ENVIRONMENT WHERE NORMALLY ONLY NON-CONDUCTIVE

POLLUTION OCCURS BUT WHERE OCCASIONAL, TEMPORARY

CONDUCTIVITY CAUSED BY CONDENSATION CAN BE EXPECTED

(AS DETERMINED ACCORDING TO INTERNATIONAL STANDARD

EN/IEC 61010-1).

3. STERIS ASSUMES NO RESPONSIBILITY FOR CHANGES MADE TO,

OR FAILURE TO OBSERVE THE SPECIFICATIONS ON EQUIPMENT

DRAWING AND NOTE PAGES. SPECIFICATIONS AND

DESCRIPTIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

4. FOR SINGLE WASHER USING STANDARD BARRIER WALL FLANGE

SHIPPING WEIGHT 1000 LB [453 KG]

OPERATING DIMENSION W x H x L 42 in x 80 in x 31 in [1067 mm x 2032 mm x 787 mm]

OPERATING WEIGHT

(WITH WATER AND FULLY LOADED) 1050 LB [476 KG]

NOISE LEVEL:

WEIGHTED EQUIVALENT

SURFACE SOUND PRESSURE LEVEL

60.2 db(A)

CALCULATED AS DESCRIBED

IN ISO 3746.

OPENING AREA FROM CLEAN SIDE

TO SOILED SIDE

(NOTE 4)

170.7 in² [0.11 m²]

CONTINUOUS OPERATION

TYPICAL HEAT LOSS AT 75°F [24°C]

CLEAN SIDE SOILED SIDE TOTAL UNITS

NON-VENTED

UNIT

1878 3808 5686 ± 683 [Btu/Hr]

550 1115 1665 ± 200 [W]

VALUES INCLUDE HEAT LOSS DURING DOOR OPENING FOR LOADING AND UNLOADING OPERATIONS.

"TOTAL" WILL VARY DEPENDING ON DISINFECTION TIME AND TEMPERATURE, DRYING TIME AND

TEMPERATURE AND USE RATE OF UNIT.

T I T L E

EQUIPMENT DRAWING OF

AMSCO® 5052 SINGLE-CHAMBER WASHER/DISINFECTOR

ELECTRIC HEATED, NON-VENTED, UNIT OFFSET FROM WALL

Corporation

SIZE: SCALE: DRAWN BY: DRAWING NUMBER: PART NUMBER

& REVISIONA N/A Vincent Carmichael 10232353

This document contains confidential and proprietary information of STERIS Corporation. Neither this document nor the information herein are to be reproduced, either in part or in whole, except as specifically authorized by STERIS Corporation.

Page 10 of 10 10232353.F

| 1

USER MANUAL

WASHER-DISINFECTOR

CUSTOMER

REQUIREMENTS

NORTH AMERICA

ENDODRY™

Storage & Drying Sytem

2 |

50098-678-EN Rev E

© 2019 All rights reserved. This publication is protected by copyright. Copying, disclosure to others, or the use of this publication is prohibited without the express written consent of Medivators Inc.

ADVANTAGE PLUS™

is a trademark of Medivators Inc.

DSD EDGE™

is a trademark of Medivators Inc.

ENDODRY™

is a trademark of Medivators Inc.

All other company or product names referenced in this document are trademarks of their respective owner.

Medivators reserves the right to make changes in the specifications shown herein without notice or obligation. Contact your Medivators representative or Medivators customer service for more information.

| 3SITE REQUIREMENTS

This purpose of this document is to provide the facility with requirements to ensure correct installation and subsequent proper performance of the ENDODRY™ Storage and Drying System.

READ THE ENTIRE DOCUMENT.

APPLICABLE DOCUMENTS

• ENDODRY Storage and Drying System User Manual.

Any deviation from these specifications may cause operational issues that would not be covered by the Warranty.

4 |

BY SIGNING BELOW CUSTOMER ACKNOWLEDGES THAT:

1. Customer reviewed these Site Requirements for the ENDODRY™ Storage and Drying System as indicated in this document.

2. The customer assumes complete responsibility for meeting the specifications and requirements set forth in the Site Requirements documentation to ensure proper installation and performance of the ENDODRY Storage and Drying System. Failure of the customer to comply with these Site Requirements and any deviation from the specifications set forth herein may compromise the functionality of the system, and/or may cause operational issues which will not be covered by the Cantel Medical warranty, and are hereby disclaimed by Cantel Medical.

3. The customer assumes complete responsibility for meeting the specifications and requirements set forth in the Site Requirements documentation by the agreed upon installation date between the Customer and Cantel Medical. If the Cantel Medical installation team encounters any delays due to site requirements not meeting specifications and requirements, the Customer will be charged Medivators current rates for stand-by fees, until the site requirements are met and installation activity resumes; or, if it is determined that the delay results in rescheduling the installation to a later date, the Customer will be charged for all expenses at current Medivators rates (flights, lodging, and car rental, if applicable), and travel and labor time related to the return installation dispatch.

4. If installation is canceled or moved 48 hours prior to the agreed upon installation date, no fee will be charged.

5. For customers who request or accept Medivators space planning suggestions for the site prior to installation (“Space Planning Services”), Customer agrees that the Disclaimer, indicated in this document on Page 9, will apply to such Space Planning Services.

Customer Representative

Title

Signature Date Email

| 5

AIR SUPPLY

1. Quality: ISO 8573-1:2010 class 1.2.1

• Particle Size: Incoming air filtered down to <1 micron in size.

• Moisture Content: Pressure dew point (PDP) of -40°C or better required and no liquid water.

• Oil Content: < 0.01mg of oil per cubic meter of compressed air (liquid, aerosol or vapor oil).

2. Pressure: The below pressures are required at the point of cabinet connection. Facility should consult with their Maintenance Department or their qualified air vendor to identify potential issues with the air supply.

• ENDODRY™ Cabinet for ADVANTAGE PLUS™ Endoscope Reprocessor: 58-145 psi (4-10 bar).

• ENDODRY Cabinet for DSD EDGE™ Automated Endoscope Reprocessor: 72-145 psi (5-10 bar).

3. Volume: The below volumes are required at the point of cabinet connection.

• ADVANTAGE PLUS Endoscope Reprocessor/ENDODRY Cabinet: Minimum requirement of 4.2 scfm (120 l/min ANR) per cabinet.

• DSD EDGE Automated Endoscope Reprocessor/ENDODRY Cabinet: Minimum requirement of 7 scfm (200 l/min ANR) per cabinet.

4. Flexible Air Hose: A 5 foot (1.5 Meter) line is included with each cabinet.

• One end will be pre-configured to connect to ENDODRY™ Drying Cabinet.

• Open end will be ¼” or 6mm inner diameter and it is the responsibility of the facility to make that connection to their air supply line.

The compressors listed below are suggestions that the facility can purchase directly from either the compressor manufacturer or authorized dealer. Medivators is not responsible for air compressor warranty, service and maintenance.

ADVANTAGE HOOKUPS DSD HOOKUPS

# of Cabinets

BeaconMedaes (Requires Additional Dryer)

Powerex (w/ Dryer)

# of Cabinets

BeaconMedaes (Requires Additional Dryer)

Powerex (w/ Dryer)

1 LES03-145T-RD-xxx SES0308TM** 1 LES05-145T-RD-xxx SES0508TM**

2 LES05-145T-RD-xxx SES05058TM** 2 LES10-145RD LSE1504

3 LES07-145T-RD-xxx LSE1504 3 LES15-145RD LSE1504

4 LES07-145T-RD-xxx LSE1504 4 LES20-145RD LSE2005

5 LES15-145RD LSE1504 5 LES20-145RD LSE2005

6 |

ELECTRICAL SUPPLY

• 100-240 VAC ± 10%, single phase, 50/60 Hz, 15 amp circuit (120v), 10 amp circuit (230v).

• Power input: 75W

• A NEMA 5-15 power cord for the North America market and a CEE 7 power cord for the European market is included with the ENDODRY™ Storage and Drying System. The cord is approximately 6 feet (1.8 meters) in length.

• A GFI/RCD protected outlet located on the wall above the ENDODRY Storage and Drying System, see Floor & Wall Section.

• Medivators equipment must be on dedicated circuits.

NETWORKING

• The ENDODRY Storage and Drying System is a networkable piece of equipment and has the capabilities to communicate to other Medivators technologies via a LAN interface (RJ45, 10/100 Mbit).

• A 6.5 foot (2 meter) cable is included with the cabinet.

• A RJ45 wall mounted network jack located on the wall above the ENDODRY Storage and Drying System, see Floor & Wall section.

DIMENSIONS

Shipping Dimensions

• Crate Dimensions: H84”x W47”x D31”

• Crate Weight: 583 lbs.

Reprocessor Dimensions

• Dimensions: H74.8” X W23.6” X D21.3”

• Weight: 375 lbs (170 kg)

FLOOR & WALL

• The floor must be level.

• For optimal user-safety and operation, it is recommended that the ENDODRY Storage and Drying System always be placed directly on the floor, and not on an elevated platform.

• The back of the one-sided ENDODRY Storage and Drying System will be placed flush against the wall. All electrical, network and air connections must be placed a minimum of 78.7 inches (200 cm) off of the floor above the cabinet.

• The two-sided ENDODRY Storage and Drying System is designed to fit into an opening in the wall. The rough opening for a single unit is H75.2” X W24” (191cm x 61cm). All electrical, network and air connections must be placed a minimum of 78.7 inches (200 cm) off of the floor above the cabinet. The electrical, network and air connections must be located on the loading side of the ENDODRY Storage and Drying System.

| 7

.6

21.3"

41.7"

EN

D

O D

R Y

St or ag e an d

D ry in g

Sy st em

TM

El ec tri ca l C on ne ct io n

Ai r C on ne ct io n

N et w or k C on ne ct io n

2 3

O ne

-S id ed V er si on

C 3D

V ie w

M in im um fa ci lit y w al l c on ne ct io ns he ig ht is

8.

7” fr om fl oo r.

O pt io ns fo r D oo rs

O pe n Le ft -O

L O pe n

R ig ht -O

R

B To p Vi ew

A Fr on t 3

D V ie w

.6

.3

3.

9” w w w .e nd oi nf ec tio np re ve nt io n.

co m to d ow nl oa d th e R ev it fil e.

Fo r c la rif ic at io n an d/ or q ue st io ns pl ea se c on ta ct T ec hn ic al

S up po rt at

.8

.4

.4

9.

4.5”12” 4.8”

1 3

.8

8 |

62.2"

21.3"

.6

EN

D

O D

R Y

St or ag e an d

D ry in g

Sy st em

TM

El ec tri ca l C on ne ct io n

Ai r C on ne ct io n

N et w or k C on ne ct io n

2 3

Tw o-

Si de d Ve rs io n (P as s-

Th ru

O pt io ns fo r D oo rs

O pe n Le ft/ O pe n

Le ft

-O

LU

L O pe n

R ig ht /O pe n

Le ft

-O R

U L

O pe n Le ft/ O pe n

R ig ht

O

LU

R O pe n

R ig ht /O pe n

R ig ht

O R

U R

B To p Vi ew

A Fr on t 3

D V ie w

W et

S id e

D ry

S id e

W et

S id e

C 3D

V ie w

W et

S id e D ry S id e

1 3

3.

9"

M in im um fa ci lit y w al l c on ne ct io ns he ig ht is

8.

7” fr om fl oo r.

*M ea su re m en t u si ng a

” w al l.

4.5” 12”4.8”

.6

*1

5.

3"

.8 w w w .e nd oi nf ec tio np re ve nt io n.

co m to d ow nl oa d th e R ev it fil e.

Fo r c la rif ic at io n an d/ or q ue st io ns pl ea se c on ta ct T ec hn ic al

S up po rt at

.8

.4

.4

9.

| 9

SPACE-PLANNING SERVICES

For customers who request or accept Medivators space planning suggestions for the site prior to installation (“Space Planning Services”), Customer agrees that the following Disclaimer will apply to such Space Planning Services:

CUSTOMER ACKNOWLEGES AND ACCEPTS THAT SPACE PLANNING SERVICES ARE OFFERED AND

PROVIDED “AS IS” WITH NO REPRESENTATION OR WARRANTY, EXPRESS OR IMPLIED, OF ANY KIND WHATSOEVER, INCLUDING, WITHOUT LIMITATION, ANY WARRANTIES OR REPRESENTATIONS AS TO THE ADEQUACY OF ANY DESIGN, MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, OR THAT ANY OF THE SERVICES WILL MEET CUSTOMER’S NEEDS OR REQUIREMENTS OR BE CAPABLE OF IMPLEMENTATION.

IN NO EVENT SHALL MEDIVATORS BE LIABLE TO CUSTOMER OR ANY THIRD PARTY FOR LOSS OF PROFITS, LOSS OF USE, OR ANY DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES OF ANY KIND, WHETHER OR NOT A PARTY WAS, IS, OR SHOULD BE AWARE OF SUCH LOSS OR DAMAGES.

CUSTOMER AGREES THAT IT WILL RELY ON, USE AND OR OTHERWISE EMPLOY ARCHITECTS, ENGINEERS, CONSTRUCTION PROFESSIONALS AND OTHER VENDORS OR SERVICE PROVIDERS (COLLECTIVELY, “PROJECT PROFESSIONALS”) REGARDING THE FEASIBILITY OR IMPLEMENTATION OF ANYSPACE PLANNING SERVICES PROVIDED BY MEDIVATORS. By accepting the Space Planning Services, (i) Customer agrees to hold Medivators and its affiliates entirely free from any liability, including financial responsibility, for all claims, losses, damages, suits, actions, costs, liabilities, or expenses incurred by Customer or its agents or affiliates as a result of any design defect, any requirement of corrective or other action or its use, reliance on, modification or implementation of any of the Space Planning Services; (ii) Customer acknowledges that Medivators is not a licensed architect or engineer or otherwise in the business of construction or space design and Customer accepts the risks involved in using such Space Planning Services from Medivators; and (iii) Customer agrees to communicate to the Project Professionals the content of all the Space Planning Services including, without limitation, all designs and plans, specifications and attachments, and to have such Project Professionals check, review, verify and approve such content prior to incorporating, using or otherwise implementing any Space Planning Service.

10 |

ENDODRY™ STORAGE AND DRYING SYSTEM

PRE-SITE REQUIREMENTS CHECKLIST

INITIAL AND SIGN AT THE TIME OF PRE-SITE INSPECTION

Customer Site Requirements Criteria Initials

ENDODRY™ Cabinet for ADVANTAGE PLUS™ Endoscope Reprocessor provides air supply of 58-145 psi (4-10 bar).

ENDODRY Cabinet for DSD EDGE™ Automated Endoscope Reprocessor provides air supply of 72-145 psi (5-10 bar).

Air supply provides a flow rate of 4.2 scfm (120 l/min ANR) for the Advantage and 7 scfm (200 l/min ANR) for the DSD.

Air supply maximum particle size is <1 micron, maximum dew point is -40°C, maximum oil content is 0.01 mg/m3.

Air Supply plumbed to the wall a minimum of 78.7 inches (200 cm) off of the floor above the cabinet.

GFI/RCD protected outlet located on the wall a minimum of 78.7 inches (200 cm) off of the floor above the cabinet.

RJ45 wall mounted network jack located on the wall a minimum of 78.7 inches (200 cm) off of the floor above the cabinet (ENDODRY™ Cabinet for ADVANTAGE PLUS™ Endoscope Reprocessor only).

Installation site has a level floor.

Installation site accommodates the dimensions of H74.8” x W23.6” x D21.3” (190cm x 60cm x 54cm)

Customer Site

Customer Representative

Title

Signature Date Email

Serial #

Serial #

Serial #

Serial #

Serial #

Serial #

Medivators Customer and Technical Support: Toll Free: 1-800-444-4729 · FAX: 1-866-421-7696

Medivators BV Sourethweg 11 6422PC Heerlen The Netherlands Tel: +31.45.5.471.471

Cantel Medical Asia/Pacic Pte. Ltd.

1A International Business Park #05-01 Singapore 609933 Tel: +65.6227.9698 www.medivators.com

Medivators Inc.

14605 28th Avenue North Minneapolis, MN 55447 USA Toll Free: +1.800.444.4729

ESCAD Medical GmbH Zur Ohmdwiesen 5 88633 Heiligenberg Germany Tel: +49.7554.9999.500 Fax: +49.7554.9999.558

Relocate Sketch.pdf
AMSCO 5052 Washer footprint and utilities_3681740.pdf
Feuille 1
Vues
new_view_35
new_view_37
new_view_57
new_view_67
Zones
A1
Feuille 2
Vues
new_view_55
Zones
A1
Feuille 3
Vues
new_view_38
new_view_39
new_view_40
Zones
A1
Feuille 4
Vues
new_view_44
new_view_45
new_view_46
Zones
A1
Feuille 5
Vues
new_view_41
new_view_42
new_view_43
new_view_65
Zones
A1
Feuille 6
Vues
new_view_47
Zones
A1
Feuille 7
Zones
A1
Feuille 8
Zones
A1
Feuille 9
Vues
new_view_64
Zones
A1
Feuille 10
Zones
A1

EndoDry Site Requirements (004).pdf