This solicitation notice is for Project 520-22-169 to upgrade mechanical systems at three Department of Veterans Affairs facilities. The solicitation number is 36C25624R0052 and opportunities are available for pre-solicitation. The project involves upgrading mechanical systems at the Joint Ambulatory Care Clinic in Pensacola, FL, the Magnolia Clinic in Panama City Beach, FL, and the VA Clinic at Eglin Air Force Base in FL. Responses are not being solicited at this time as this is a pre-solicitation notice providing information on the upcoming project to upgrade mechanical systems at the three listed VA facilities under Veterans Integrated Service Network 16.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment A: Basis of Design Submittals

Project: Pensacola VA AHU Modifica Submittal Date: 7/7/2023

Submitted By: Joshua Belt

This submittal sheet reflects only the construction and options selected and is not indicative of all constructions and options that are available for the product. For more information, please contact your local representative or visit us at www.pottorff.com.

Note that performance data in the details section of this submittal are calculated values, and are not AMCA certified.

Information is subject to change without notice or obligation. Note: Dimensions in parentheses ( ) are millimeters.

5101 Blue Mound Rd, Fort Worth TX 76106 Page 1 of 3

Submittal Model EXA-645-MD

Extruded aluminum louver, 6" deep, 37-1/2 degree combination blade

General construction Dimensions: Nominal (approximately 1/2" (12) undersized) Material: 6063-T5 extruded aluminum FrameThickness: 0.125 Frame and blade attachment: Mechanically fastened Blade: Front: 37.5° x 0.081" drainable style; Back: 45° x 0.162" operable airfoil style Screen 1 configuration: Material: Aluminum; Type: Bird screen;

Pattern: 1/2" x 0.063" Options

Installation hardware: Standard; Grout-filled CMU Finish: Baked enamel, Standard color name: TBD Finish warranty: 5 years Sill flashing: Closed end Actuator: 2-position spring return

Ratings Free area: [48" x 48" (1219 x 1219) unit]: 7.7 ft² (0.72 m²) 48.1% (1 side) Velocity @ 0.15 in.wg. Pressure Loss: 1184 fpm (6.01 m/s) Std. Design Load: 120 psf Operating temperature range: -20°F to 180°F

Listings AMCA CRP Listing: Air, Water AMCA: 540 (impact resistant), 550 (high velocity rain resistant)

Performance at beginning point of water penetration

Free area velocity: 1076 fpm (5.47 m/s) Air volume delivered: 8281 cfm (3.91 m³/s) Pressure loss: 0.12 in.wg. (30 Pa)

Model EXA-645-MD

Details

Line item Tag Qty

Louver size (in.xxxx) Sections Actuator Ratings Free area Appro x.

weight (lbs)W x H

Wide x High Qty Model Volt Pos Loc CFM FPM PD (in.w.g.) ft² %

8 AHU-1 OAL 1 82 x 54 2 x 1 1 AFBUP 120V PO Int 11908 766 0.06 15.55 51.4 186 9 AHU-2 OAL 1 108 x 43 2 x 1 1 AFBUP 120V PO Int 11908 747 0.06 15.94 50.2 192 10 2 36 x 24 1 x 1 1 FSLF120 120V PO Int 2367 969 0.1 2.44 42.2 36

Submitted By: Joshua Belt

This submittal sheet reflects only the construction and options selected and is not indicative of all constructions and options that are available for the product. For more information, please contact your local representative or visit us at www.pottorff.com.

Information is subject to change without notice or obligation. Note: Dimensions in parentheses ( ) are millimeters.

5101 Blue Mound Rd, Fort Worth TX 76106 Page 2 of 3

Submittal Model EXA-645-MD Performance

Certified Ratings:

Pottorff certifies that the model EXA-645- MD shown herein is licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings seal applies to air performance and water penetration ratings.

Water penetration AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48" x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. Pottorff recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.

Submitted By: Joshua Belt

This submittal sheet reflects only the construction and options selected and is not indicative of all constructions and options that are available for the product. For more information, please contact your local representative or visit us at www.pottorff.com.

Information is subject to change without notice or obligation. Note: Dimensions in parentheses ( ) are millimeters.

5101 Blue Mound Rd, Fort Worth TX 76106 Page 3 of 3

Pressure loss Data corrected to standard air density. Air Leakage is not AMCA certified. Leakage testing in accordance with Figure 5.4, 5.5 and 6.6A of AMCA Standard 500-L. Data are based on the maximum torque of 2.8 in lb/sq. ft. (3.5 N-m/sq. m) applied to the louver during the test. Air leakage is based on operation between 500 F - 1040 F (100 C - 400 C).)

Standard Finish colors for aluminum products and acoustical louvers

El Cajon Silver M-18155 M-19155

Champagne M-18156 M-19156

Light Bronze M-18157 M-19157

Medium Bronze M-18158 M-19158

Dark Bronze M-18159 M-19159

Sandstone M-18139 M-19139

Nantucket Dune M-18140 M-19140

Beige M-18141 M-19141

Seawolf M-18142 M-19142

Fashion Gray M-18143 M-19143

Colonial Gray M-18144 M-19144

Charcoal Gray M-18145 M-19145

Light Blue M-18146 M-19146

Interstate Blue M-18147 M-19147

Aged Copper M-18148 M-19148

Hartford Green M-18149 M-19149

Brick Red M-18150 M-19150

Burgundy M-18151 M-19151

Sage Brown M-18152 M-19152

Statuary Bronze M-18153 M-19153

Black M-18154 M-19154

The first M number is for the standard Fluoropolymer finish and the second number is for the same color in Polyester.

Premium Pearl colors use mica pigments to simulate the appearance of anodized finishes. The first M number is for the standard Fluoropolymer finish and the second number is for the same color in Polyester.

The color samples shown are not the actual paint. The samples are as close as possible to actual colors offered. Actual coating samples are available upon request. Please call us at 817-509-2300 or e-mail us at info@pottorff.com to request a sample of our color chart.

Premium Pearl finish colors for aluminum products and acoustical louvers

Apollo White M-18136 M-19136

Bone White M-18137 M-19137

Colonial White M-18138 M-19138

Ivory M-18162 M-19162

5101 Blue Mound Road, Fort Worth, Texas 76106 • Phone: 817-509-2300 • Fax: 817-831-3110 • www.pottorff.com CC 7/2018

Finishes enhance louver appearance by matching or contrasting with adjacent surfaces and extending weather resistance. Color matching is available upon request.

Our superior performance paint systems are available in a wide range of colors and we can also custom color match to any of your specifications. Our expertise in applying architectural coatings assures you of a high quality finish. With our color options, you get the color you need when you need it!

Finish Type Description/Application Color Selection Warranty Fluoropolymer Decaflon and Newlar meet AAMA 2605.

Dry film thickness 2 mil.

equivalent to Kynar 500®/Hylar 5000®, Duranar®, Fluoropon®

Polyester Powder Coat meets AAMA 2604 dry film thickness 2 mil. equivalent to Baked Enamel.

Integral Color Anodize AA-M10C22A42 (>0.7 mil)

Clear Anodize 215 R-1 AA-M10C22A41 (>0.7 mil)

Alkyd Prime Coat

Mill

Our premier finish for extruded aluminum. Tough, long lasting, environmentally friendly powder coating has superior color retention and abrasive properties. Resists chalking, fading, chemical abrasion and weathering.

Environmentally friendly powder coating has good color retention and abrasive properties. Resists chalking, fading, chemical abrasion and weathering.

Electrochemically deposited inorganic color pigment which is sealed to convert an aluminum oxidation into a corrosion resistant finish. Some shade variation will occur.

Electrochemically oxidized aluminum surface for uniform clear finish. More resistant to natural oxidizing. Improved luster and less glossy than mill finish.

Preparation for field applied epoxy, vinyl, urethane, or other heavy-duty coatings. Must be finished within 6 months of application. Contamination can occur in transit and in the field;

requires field cleaning prior to painting.

Aluminum or Galvanized Steel. Normal weathering will occur.

Standard Colors: 20 standard colors plus Premium Pearl finishes. Custom colors are available. Consult factory.

20 standard colors for aluminum products and acoustical louvers, 18 colors for steel. Custom colors are available. Consult factory.

Champagne; Light, Medium or Dark Bronze; Black

Clear

N/A

N/A

10 Years (consult factory for availability of extended warranty up to 20 years).

5 Years

5 Years

5 Years

N/A

N/A

PRODUCT FACTS

3" (76) Overlap (see note 3)

Sill Flashing Overlap Detail

Louver

Sill Flashing

Head Flashing

End Dam Details

Material: 20 ga. (1.0) thick 5052-H32 aluminum louvers or 20 ga. (1.0) thick galvannealed for formed metal louvers.

Finish: To match louver finish.

Minimum Size: See appropriate louver minimum.

Maximum Size: See appropriate louver maximum.

Information is subject to change without notice or obligation. NOTE: Dimensions in parentheses ( ) are millimeters.

S ill

/H e a d F la s h in g I

IS

H

F (1

/1

F e b ru a ry sill/head flashing aluminum or galvannealed

Open or closed end for use with extruded aluminum or formed steel louver models.

Application and Design

Standard Construction

Head Flashing

Sill Flashing

POTTORFF® 5101 Blue Mound Road, Fort Worth, Texas 76106 www.pottorff.com

Typical Details

Views show closed end on extruded aluminum louver - formed steel louver similar.

1.

2.

3.

4.

Sill Flashing Detail Notes

Pottorff’s standard louver sill flashing is 20 ga. (1.0) aluminum material that is finished to match the louver.

Pottorff strongly recommends sill flashing be used under louvers that are multi-section wide.

Pottorff provides sufficient flashing length for a minimum overlap of

3" (76) where lengths of flashing are joined under section(s).

The installer must adequately seal this overlap joint with sealant.

End dams are optional. The extra length must be formed in the field.

Rear vertical seam must be sealed by installer after shaping.

Slit in Field

Cut-Out in Field

Crease-Line to Form End Dam

(see note 4)

Caulk Seam for Water Leak

End Dam (see note 4)

End Dam Details

Louver Depth + 1/4" (6)

1" (25)

Front Height

1" (25)

Back Height

1/2" (13)

45o

Standard Sill Flashing Profile

Side View

Louver (with Head and Sill Flashing)

Exploded View Interior Elevation

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA/CARIBBEAN

Application The type FSLF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper and will meet requirements of UBC for 15 second opening and closing. Square footage of damper operated will depend on make and model and the temperature required.

Operation Mounting of the actuator to the damper axle shaft or jackshaft is via a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an anti-rotation strap or by a stud provided by the damper manufacturer.

The actuator is mounted in its fail safe position with the damper blade(s) closed. Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position.

SAFETY NOTES

The actuator contains no components which the user can replace or repair.

24 VAC Connect via safety isolating transformer, Class 2 supply.

1/2" Threaded Connector Screw a conduit fi tting into the actuator’s metal bushing. Jacket the actuator’s input wiring with suitable fl exible conduit. Properly terminate the conduit in a suitable junction box.

3/8" Flex Connector (-FC models) Mount the fl exible conduit into the actuator’s metal bushing by means of the provided screw with a torque of 1.2 Nm. Jacket the actuator’s input wiring with suitable fl exible conduit. Properly terminate the conduit in a suitable junction box.

Dimensions (Inches [mm])

[57] 2.24"

[19]0.75"

[6]0.24"

[179] 7.03"

[173] 6.81"

[11]0.45" [28] 1.1"

[12.7] min 0.5"

[20] max 0.79"

[98] 3.86"

[138] 5.42"

[60] 2.37"

[5] 0.2

FS

LF

0D im s

FSLF24(-S)(-FC) US, FSLF120(-S)(-FC) US

On/Off, Spring Return, 350°F for Half Hour, 15 Seconds Cycle Time

Technical Data FSLF24(-S)(-FC) US, FSLF120(-S)(-FC) US

Power supply FSLF24(-S)(-FC) US 24 VAC ± 20%, 50/60 Hz FSLF120(-S)(-FC) US 120 VAC ± 10%, 50/60 Hz

Power consumption running 50/60 Hz, 15 VA 24 VAC holding 50/60 Hz, 3.5 VA end stop 50/60 Hz 25 VA 120 VAC running 50/60 Hz 18 VA holding 50/60 Hz 6.5 VA end stop 50/60 Hz 27 VA

Fusing* FSLF24 1 amp slow blow FSLF120 0.25 amp slow blow

Transformer sizing 25 VA per 24 VAC actuator Electrical connection

FSLF24 US 3 ft, 18 ga, 2 color coded leads FSLF120 US 3 ft, 18 ga, 3 color coded leads FSLF...-S US 3 ft, 18 ga, appliance cable

Overload protection electronic throughout 0 to 95° rotation auto-restart after temporary overload (FSLF120 US grounded enclosure)

Control microprocessor Angle of rotation 95° Torque 30 in-lb [3.5 Nm] minimum from 32°F to 350°F [0°C to 177°C] Direction of rotation spring can be selected by CCW/CW mounting Position indication visual indicator, 0° to 95° Running time motor spring

< 15 sec at rated voltage and torque 32°F to +122°F [0°C to +50°C] <15 seconds at rated voltage and torque

Humidity 5 to 95% RH non-condensing Ambient temperature 32°F to 122°F [0°C to 50°C] Storage temperature -40°F to 176°F [-40°C to 80°C] Housing NEMA type 1 Housing material zinc coated steel Gears permanently lubricated Agency listings cULus acc. to UL60730-1A/-2-14, CAN/CSA

E60730-1, CSA C22.2 No.24-93 Servicing maintenance free Quality standard ISO 9001 Weight

FSLF24(-S) US 3.4 lbs [1.7 kg], (+ 0.3 lbs [+0.14 kg]) FSLF120(-S) US 4.0 lbs [1.8 kg], (+ 0.3 lbs [+0.14 kg])

FSLF24(-S)(-FC) US, FSLF120(-S)(-FC) US

Auxiliary switch 2 x SPST 0.5 A inductive, 3A resistive @ 120/ 250VAC, minimum 1 mA @ 5 VDC, .3 A ind, .5A res @ 24VDC, UL listed, 10° and 85°.

Double insulated

4-

1D

*Individual Fusing or Breakers are not required by Belimo.

The FSLF24 draws higher peak current when driving against any type of stop. Given the technology of fuses & breakers, this requires the value of fuse or breaker to be increased to avoid nuisance opening or tripping. A 1 amp slow blow should be used for 24VAC. A 0.25 amp slow blow should be used for 120VAC.

Su bj ec t t o ch an ge

B el im o Ai rc on tro ls

(U

SA

In c.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA/CARIBBEAN

Typical Applications

The typical fi re and smoke damper requires from 5-15 in-lb of torque per square foot at 250°F - 350°F under dynamic load (2000 fpm velocity). The FSLF is a single section damper actuator. For the multi section dampers, use the FSNF series.

This is a direct coupled actuator. If linkages are needed use the FSNF series.

Single section for one

FSLF actuator

Two section for two FSLF actuators

Typical Specification Smoke Control and Combination Fire and Smoke Control Damper Actuators

All smoke and combination fi re and smoke dampers shall be provided with Belimo FSLF, FSNF, or FSAF actuators. No substitutions allowed. Damper and actuator shall have UL555S Listing for 250°F (350°F) and shall comply with UBC if required by local codes. Where proof of closure switches are required, blade switches, actuator auxiliary switches, or proximity switches are allowed.

Replacement Applications

The number one "equal or better" requirement for use as a replacement for obsolete defective motors is the UL555S listing of the Belimo actuator with the damper for the application. The local authority having jurisdiction sets the requirements. In some cases a permit and inspection may be required.

Go to www.belimo.us/fi resmoke for a Cross Reference from old damper actuators to Belimo. Extensive retrofi t installation instructions are available, along with technical training information.

CAUTION

Caution must be used when replacing failed motors with new Belimo actuators.

Many old motors did not have internal springs and depended on external springs on the side of the damper or wrapped around the damper shaft to close the damper. Old motor springs must be removed or disabled. Do not remove fusible link springs if they had only fi re and no smoke functions

In some cases, a BAE 165 or equal thermal sensor must be installed.

Wiring Diagrams

1 Provide overload protection and disconnect as required.

2 CAUTION Equipment Damage!

Actuators may be connected in parallel.

Power consumption and input impedance must be observed.

3 No ground on 24 V models

4 S4 makes to S6 when the actuator is powered open.

For end position indication, interlock control, fan startup, etc., FSLF24-S US and FSLF120-S US incorporate two built-in auxiliary switches.

6 Double insulated

WARNING Live Electrical Components!G During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

W

Gnd

Gnd

H=Red L1=Blk

24V 120V C=Blk N=Wht

FS

LF

0_

Pa ra lle l_

Au x_ w iri ng

Parallel Actuator Wiring

NO

S6

FSLF24-S US

FSLF120-S US

S1

S2

S4

NC

10°

85°

Violet

Violet

Gray

Gray

FS

LF

0_

Pa ra lle l_

Au x_ w iri ng

Auxiliary switch wiring for FSLF24-S US, FSLF120-S US

1 Common, Neutral

2 Hot 3 Ground

FSLF24 US

FSLF120 US

No ground on 24 V models

H=Red L1=Blk

24V 120V

C=Blk N=Wht

FSLF24(-S)(-FC) US, FSLF120(-S)(-FC) US

On/Off, Spring Return, 350°F for Half Hour, 15 Seconds Cycle Time

S ub je ct to c ha ng e.

B el im o

Ai rc on tro ls (U

SA

In c.

Company

Contact

Phone No.

Email

QUOTATION

Project 2023-05-23

21BF2L5C0 | Configuration Summary

PUMP

Pump Size 2 1/2 x 3 - 9 Installation Close Coupled

Speed 1750

MOTOR

Frequency (Hz) 60 Poles 4 Enclosure TEFC Frame Size 215JM

Power 10 hp Phase (~) 3 Voltage 230/460 V Service Factor 1.15

MATERIALS

Construction BF (Bronze Fitted)

SEAL

Seal Design Mechanical Seal Type of Seal Type 21

Rotating Face Carbon Stationary Face Ceramic Elastomers BUNA-N Metal Components 316 SS

STANDARD OPTIONS

Casing Rotation 12 o'clock

21BF2L5C0 | Product Details

Material Details

Shaft sleeve (126) AISI 300 Stainless Steel

Pipe plug 1/4" or 3/8" (408) Zinc Plated Steel

Impeller bolt (198) AISI 300 Stainless Steel

Mechanical seal (383) See Mechanical Section

Casing wear ring (103) Bismuth Bronze – Lead Free

Hex head cap screw (adapter to case) (370)

Zinc Plated Steel Grade 5

Adapter/seal housing (108) Cast iron ASTM A48 CL20

Impeller key (178) AISI 300 Stainless Steel

Casing (100) Cast iron ASTM A48 CL30

Impeller washer (199) AISI 300 Stainless Steel

Impeller (101) ASTM B584, Modified C87500 – Lead Free

Hex head cap screw (adapter to motor) (371)

Zinc Plated Steel Grade 5

O-ring (513) BUNA-N (Std.)/EPR (opt.)/Viton (opt.)

Motor Data

Enclosure TEFC Speed 1,800 rpm Rated Power 10 hp Rated Voltage 230/460 V Frame Size 215JM

Phase 3

FLA 24/12

SLA 27.8/13.9

21BF2L5C0 | Hydraulic Data & Performance Curve

Selection Criteria Fluid Data

H@QMax 41 ft Operating Pumps 1 Total Head 82 ft Stages 1 System Type Single Pump Max Impeller Diameter 10.062 in Max P2 6 Hp Pump Head 82 ft Pump Flow 132 USgpm Min Impeller Diameter 7.688 in Series 3656/3756 M - L Group H@QMin 104 ft Total Flow 132 USgpm Impeller Diameter 9.5 in System Units US Model 21BF 1750rpm Frequency 60 Hz Rated Power 10 Hp Max Operating Pressure 40 psi

Fluid Vapor Pressure 0.33929 psi Fluid Service Dynamic Viscosity 1.00165 cP Fluid Name Fluid Type Water Fluid Temperature 68 °F Density 62.31322 lb/ft³ Specific Gravity 1

Design Curve Data Design Point Series 3656/3756 M - L Group BEP Flow 204.64 USgpm BEP Head 68.86 ft Max Flow 318 USgpm Rated Motor Speed 1750

BEP 69.8 %

Head 82.01 ft Efficiency 64.09 % NPSHr 2.73 ft Flow 132.01 USgpm Shaft power (P2) 4.27 Hp

21BF2L5C0 | Dimensional Data & Drawing

Dimensions

Suction 3 inch A 9.75 inch AB 9.61 inch B 8.88 inch D 5.25 inch E 4.25 inch F 3.5 inch Y 2.75 inch

NPT

Drain

0.38 inch

G 0.63 inch X 7.5 inch DC Max. 7.12 inch H 0.44 inch W 5 inch CP 36.33 inch

Discharge 2.5 inch P Max. 11.25 inch R 3.5 inch DD Max. 6 inch L 12.25 inch Weight (Motor) 81.19 kg Weight (Pump only) 38.56 kg Z 5.5 inch

Company

Contact

Phone No.

Email

Medical Scroll Compressor System

Duplex 7.5 – 10 HP with Premium Controls

Powerex • 150 Production Drive • Harrison, OH 45030 • USA

(T) 1.888.769.7979 • (F) 513.367.3125 • www.powerexinc.com

10/2019

Dimensions

MODEL DIM A DIM A1 DIM B DIM B1 DIM C INLET OUTLET

MSD0754 59.8" 60.8" 66.2" 69.6" 75.0" 1 1/2" 3/4"

MSD10B4 59.8" 60.8" 66.2" 69.6" 75.0" 1 1/2" 3/4"

Notes:

1 – ICFM and SCFM values @ 50 PSIG are shown with one compressor in reserve per NFPA 99.

2 – BTU/Hr levels are shown with reserve compressor(s) on standby.

3 – Powerex recommends using performance ratings in SCFM (Standard Cubic Feet per Minute) when sizing medical air systems 4 – dB(A) levels are shown with one compressor in reserve.

5 – 3 Year Limited Warranty.

6 – ICFM as standardly defined within the Medical Air Compressor Industry

Medical Scroll Compressor System

Model HP

ICFM @ 50

PSIG(1, 6)

SCFM @ 50

PSIG(1, 3)

Tank Size (gal)

BTU/Hr (2) dB(A) Level (4)

System F.L.A. System Weight (lbs)208V 230V 460V

MSD0754 7.5 (2) 25.8 23.8 120 19,084 74 40.4 36.6 19.34 1800

MSD10B4 10 (2) 34.1 31.6 120 25,445 76 55 50 26 1900

VHABILBazoL Highlight

VHABILBazoL Highlight

Medical Scroll Skidmount Package Quadplex with Premium Controls

Powerex • 150 Production Drive • Harrison, OH 45030 • USA

(T) 1.888.769.7979 • (F) 513.367.3125 • www.powerexinc.com

8/2018

Dimensions Model Dim. A Dim. B Dim. C Inlet Outlet

MSQ05A4 73” 51” 75” 1.5” 1”

MSQ10A5 73” 60” 83” 2” 1.5”

MSQ10A6 73” 60” 95” 2” 1.5”

MSQ15A5 73” 85” 83” 2” 2”

MSQ15A6 73” 85” 95” 2” 2”

Medical Scroll Skidmount Package Quadplex with Premium Controls

Model HP ICFM @ 50

PSIG(1,6)

SCFM @ 50

PSIG(1,3)

Tank Size (gal) BTU/Hr (2) dB(A)

Level (3) System F.L.A. System

Weight (lbs)208V 230V 460V

MSQ05A4 5 (4) 55.2 49.8 120 38175 77 58 52.8 27.3 2200

MSQ10A5 10 (4) 110.4 99.6 200 76350 80 114 103.6 52.6 3800

MSQ10A6 10 (4) 110.4 99.6 240 76350 80 114 103.6 52.6 3900

MSQ15A5 15 (4) 165.6 149.4 200 114525 82 170 154.4 78 5600

MSQ15A6 15 (4) 165.6 149.4 240 114525 82 170 154.4 78 5700

Notes:

1 – ICFM and SCFM values @ 50 PSIG are shown with one compressor in reserve per NFPA 99.

*Powerex recommends using performance ratings in SCFM (Standard Cubic Feet per Minute) when sizing medical air systems.

*ICFM is standardly defined within the Medical Air Compressor Industry.

2 – BTU/Hr levels are shown with reserve pump(s) on standby.

3 – dB(A) levels are shown with one pump in reserve per NFPA 99.

4 – 3 Year Limited Warranty.

5 – Drawing is representative and not exact.