36C25622R0094 260923 Lighting Controls.docx

DOCX document 32 KB Posted

Attached to
Z2DA--Project #502-19-107 - Replace AHU-104 - Construction - 36C25622R0094 Federal contract opportunity
Solicitation number
502-19-107
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This solicitation package includes specifications for a lighting controls project at a Department of Veterans Affairs health care facility. The project involves replacing an air handling unit and ductwork at Building 7 and installing new lighting controls, including outdoor photoelectric switches, room controllers, low voltage switches, occupancy sensors, and power packs. The room controllers will provide zone-based lighting control via integrated programming. Occupancy sensors will automatically turn lights on and off based on occupancy detection. Low voltage switches will allow for manual multi-way switching control. The solicitation is seeking bids due on September 23, 2022 for the installation of these lighting control system components according to the specifications in order to control lighting zones per the sequence of operations diagram. The agency listed is the Veterans Health Administration VISN 16 within the Department of Veterans Affairs.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Project #502-19-107 - Replace AHU-104 - Construction - 36C25622R0094, newest first.
File Type Posted
36C25622R0094 RFI Register 08292022.docx DOCX document
36C25622R0094 0002.docx DOCX document
36C25622R0094 Brand Name JA 502-19-107 Redacted.pdf PDF
36C25622R0094 COVID-19 Safety Protocols for Federal Contractors Rev 2.docx DOCX document
36C25622R0094 280800 Commissioning of Electronic Safety and Security Systems .docx DOCX document
36C25622R0094 000110 VHA Master Specifications Rev 2.docx DOCX document
36C25622R0094 262726 Wiring Devices .docx DOCX document
36C25622R0094 283100 Fire Detection and Alarm .doc DOC document
36C25622R0094 232500 HVAC WATER TREATMENT .docx DOCX document
36C25622R0094 260511 Requirements for ELEC installation.docx DOCX document
36C25622R0094 234000 HVAC AIR CLEANING DEVICES .docx DOCX document
36C25622R0094 238100 DECENTRALIZED UNITARY HVAC EQUIPMENT.docx DOCX document
36C25622R0094 260800 Commissioning of Electrical Systems.docx DOCX document
36C25622R0094 232113 HYDRONIC PIPING .docx DOCX document
36C25622R0094 230923 DIRECT DIGITAL CONTROL SYSTEM FOR HVAC .doc DOC document
36C25622R0094 014500 Quality Control.docx DOCX document
36C25622R0094 013526 Safety Requirements .docx DOCX document
36C25622R0094 099100 Painting .docx DOCX document
36C25622R0094 095100 Acoustical Ceilings .docx DOCX document
36C25622R0094 087100 Door Hardware .docx DOCX document
36C25622R0094 092216 Non-Structural Metal Framing .docx DOCX document
36C25622R0094 096513 Resilient Base and Accessories.docx DOCX document
36C25622R0094 079200 Joint Sealants .docx DOCX document
36C25622R0094 092900 Gypsum Board .docx DOCX document
36C25622R0094 076000 Flashing and Sheet Metal .docx DOCX document
36C25622R0094 015719 Temporary Environmental Controls .doc DOC document
36C25622R0094 Revised SOW 05202022 .docx DOCX document
36C25622R0094 RFP.docx DOCX document
36C25622R0094 IFC Drawings Part 1 .pdf PDF
36C25622R0094 IFC Drawings Part 2.pdf PDF
36C25622R0094 230593 TESTING ADJUSTING AND BALANCING FOR HVAC.docx DOCX document
36C25622R0094 013323 Shop Drawings Product Data and Samples.docx DOCX document
36C25622R0094 010000 General Requirements .docx DOCX document
36C25622R0094 EXHIBIT E.docx DOCX document
36C25622R0094 323113 Chain Link Fences and Gates .docx DOCX document
36C25622R0094 EXHIBIT B.docx DOCX document
36C25622R0094 265100 Interior Lighting .docx DOCX document
36C25622R0094 262921 Enclosed Switches and Circuit Breakers.docx DOCX document
36C25622R0094 264313 Surge Protective Devices.docx DOCX document
36C25622R0094 260533 Raceways and Boxes for Electrical Systems .docx DOCX document
36C25622R0094 270511 Requirements for Communications Installations .docx DOCX document
36C25622R0094 233400 HVAC FANS.docx DOCX document
36C25622R0094 237300 INDOOR CENTRAL STATION AIR HANDLING UNITS.docx DOCX document
36C25622R0094 232123 HYDRONIC PUMPS.docx DOCX document
36C25622R0094 230511 COMMON WORK RESULTS FOR HVAC.docx DOCX document
36C25622R0094 078400 Firestopping.docx DOCX document
36C25622R0094 081400 Interior Wood Doors .docx DOCX document
36C25622R0094 051200 Structural Steel Framing .docx DOCX document
36C25622R0094 024100 Demolition .docx DOCX document
36C25622R0094 014219 Reference Standards.docx DOCX document
Show all 50

Z2DA--Project #502-19-107 - Replace AHU-104 - Construction - 36C25622R0094 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REPLACE AHU #104 AND DUCTWORK BLDG. 7

DEPARTMENT OF VETERANS AFFAIRS HEALTH CARE SYSTEM-ALEXANDRIA, LA

PROJECT NO.: 502-19-107

SECTION 26 09 23

LIGHTING CONTROLS

PART 1 - GENERAL

1.1 DESCRIPTION

This section specifies the furnishing, installation and connection of the lighting controls.

1.2 RELATED WORK

A.Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General requirements that are common to more than one section of Division 26.
B.Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES: Cables and wiring.
C.Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents.
D.Section 26 27 26, WIRING DEVICES: Wiring devices used for control of the lighting systems.
E.Section 26 51 00, INTERIOR LIGHTING: Luminaire ballast and drivers used in control of lighting systems.

1.3 qualITY ASSURANCE A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS (PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.

1.4 SUBMITTALS

A.Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:
1.Shop Drawings:
a.Submit the following information for each type of lighting controls.
b.Material and construction details.
c.Physical dimensions and description.
d.Wiring schematic and connection diagram.
e.Installation details.
2.Manuals:
a.Submit, simultaneously with the shop drawings, complete maintenance and operating manuals, including technical data sheets, wiring diagrams, and information for ordering replacement parts.
b.If changes have been made to the maintenance and operating manuals originally submitted, submit updated maintenance and operating manuals two weeks prior to the final inspection.
3.Certifications: Two weeks prior to final inspection, submit the following.
a.Certification by the Contractor that the lighting control systems have been properly installed and tested.

1.5 APPLICABLE PUBLICATIONS

A.Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only.
B.National Electrical Manufacturer's Association (NEMA):
C136.10-10American National Standard for Roadway and Area Lighting Equipment—Locking-Type Photocontrol Devices and Mating Receptacles—Physical and Electrical Interchangeability and Testing
ICS-1-15Standard for Industrial Control and Systems General Requirements
ICS-2-05Standard for Industrial Control and Systems: Controllers, Contractors, and Overload Relays Rated Not More than 2000 Volts AC or 750 Volts DC: Part 8 - Disconnect Devices for Use in Industrial Control Equipment
ICS-6-16Standard for Industrial Controls and Systems Enclosures
C.National Fire Protection Association (NFPA):
70-17National Electrical Code (NEC)
D.Underwriters Laboratories, Inc. (UL):
20-10Standard for General-Use Snap Switches
98-16Enclosed and Dead-Front Switches
773-16Standard for Plug-In Locking Type Photocontrols for Use with Area Lighting
773A-16Nonindustrial Photoelectric Switches for Lighting Control
916-15Standard for Energy Management Equipment Systems
917-06Clock Operated Switches
924-16Emergency Lighting and Power Equipment (for use when controlling emergency circuits).

PART 2 - PRODUCTS

2.1 outdoor photoelectric switches

A.Solid state, with DPST dry contacts rated for 1800 VA tungsten or 1000 VA inductive, complying with UL 773A.
1.Light-Level Monitoring Range: 16.14 to 108 lx (1.5 to 10 fc), with adjustable turn-on and turn-off levels.
2.Time Delay: 15-second minimum.
3.Surge Protection: Metal-oxide varistor.
4.Mounting: Twist lock, with base-and-stem mounting or stem-and-swivel mounting accessories as required.

2.2 LIGHTING CONTROL System – Room controller (Stand alone)

A.System Description:
1.The lighting control system shall be a series of stand-alone room controllers for zone level switching. Low voltage switching and sensing devices connect to the room controller. The room controller interprets the various inputs and controls the room lighting based on the programmed sequence of operations. The system includes all interfaces and wiring, room controllers, occupancy sensors, couplers, power packs, relays, low voltage switches, and dimmers. The room controller shall be programmed as shown on the plans.

B. System Components:

1. Room Controller: Comply with UL 508; programmable, solid-state, astronomic 365-day control unit with non-volatile memory, mounted in preassembled relay panel with low-voltage inputs, (3) separate line voltage contacts and (3) 0-10V dimming outputs for separate control of lighting zones. Unit shall be rated for 120/277V input with 120/277V 20A output. The Room Controller shall have (6) RJ45 inputs for connecting low voltage switches and sensors. Room Controllers are fully functional out-of-the-box to the connected devices in the space without commissioning or the use of any tools. Low voltage connections to devices shall be made using RJ45 cables. Room Controller assembly shall be capable of locating above the finished ceiling in plenum rated areas.
2. Low Voltage Switch / Dimmer: Low voltage momentary pushbutton switches in 2, 3, and 4 button configurations as detailed on the drawings. Ivory switches with ivory decorator cover plates. Two RJ-45 ports for connection to the Room Controller local network input. Multiple low voltage switches may be installed in a room by connecting them to the Room Controller local network. No additional configuration will be required to achieve multi-way switching. Pre-defined functions shall include (all on, all off, half lights, full lights, raise, and lower). See drawings for details. Switch inputs shall be cable of programming VIA the Room Controller to match the lighting sequence of operations on the plans.
3. Occupancy Sensor: Wall- or ceiling-mounting, solid-state class 2 device - Dual Technology (combination PIR and ultrasonic detection methods) units with an occupancy coupler device and relay unit, suitable for the environmental conditions in which installed. Controls incorporate non-volatile memory. Settings and parameters shall not be lost in the event of power interruptions. Unless otherwise indicated in the lighting control sequence of operations, turn lights on when covered area is occupied and off when unoccupied; with a 1-to-15-minute adjustable time delay for turning lights off. Sensor shall output through #18 AWG shielded conductors to an occupancy coupler device. This device shall convert the signal over to CAT 5E cable. Sensor shall be powered from the room controller associated with the space. When multiple sensors are to be used with a single room controller, only one occupancy sensor coupler may be used in tandem with the line voltage power pack. This power pack will provide power for up to 5 occupancy sensors.
a.Sensor: Suitable for mounting in any position on a standard outlet box.
b.Time-Delay and Sensitivity Adjustments: Recessed and concealed behind hinged door.
c.Indicator: LED, to show when motion is being detected during testing and normal operation of the sensor.
d.Bypass Switch: Override the on function in case of sensor failure.
e.Manual/automatic selector switch.
f.Automatic Light-Level Sensor: Adjustable from 21.5 to 2152 lx (2 to 200 fc); keep lighting off when selected lighting level is present.
g.Faceplate for Wall-Switch Replacement Type: Refer to wall plate material and color requirements for toggle switches, as specified in Section 26 27 26, WIRING DEVICES.
h. Detector Sensitivity: Detect occurrences of 150 mm (6-inch) minimum movement of any portion of a human body that presents a target of not less than 232 sq. cm (36 sq. in), and detect a person of average size and weight moving not less than 305 mm (12 inches) in either a horizontal or a vertical manner at an approximate speed of 305 mm/s (12 inches/s).
i. Detection Coverage: Shall be sufficient to provide coverage as required by sensor locations shown on drawing.
4. Power Packs: Low voltage power pack used for powering multiple low voltage devices connected to the same room controller.
a. Device shall be capable of converting line voltage (120/277VAC) to 24VDC, 225mA.
b. Device to be mounted above the finished ceiling and shall be plenum rated.
c. Power Pack shall be a compatible product with the lighting control system and shall be located and identified on the lighting control shop drawing submission.
C.System Devices: All occupancy sensors (Ultrasonic, IR and Dual Technology type), photocells, switches and timers shall be provided with system and designed to operate on system network. Supplemental power packs shall be provided as required for multiple control devices. This equipment shall be identified in shop drawing submission. All devices shall be marked and identified to indicate lighting zones that are controlled by that device.

PART 3 - EXECUTION

3.1 INSTALLATION

A.Installation shall be in accordance with the NEC, manufacturer's instructions, as shown on the drawings, and as specified.
B.Aim outdoor photoelectric sensor according to manufacturer's recommendations. Set adjustable window slide for 1 footcandle turn-on.
C.Aiming for wall-mounted and ceiling-mounted motion sensor switches shall be per manufacturer’s recommendations.
D.Set occupancy sensor "on" duration to values specified in the lighting control sequence matrix.
E.Label time switches and contactors with a unique designation.
F.Program room controllers per lighting control sequence matrix .

3.2 Acceptance Checks and Tests

A.Perform in accordance with the manufacturer's recommendations.
B.Upon completion of installation, conduct an operating test to show that equipment operates in accordance with requirements of this section.
C.Test for full range of dimming driver and dimming controls capability. Observe for visually detectable flicker over full dimming range.
D.Test occupancy sensors for proper operation. Observe for light control over entire area being covered.

3.3 Follow-Up Verification

Upon completion of acceptance checks and tests, the Contractor shall show by demonstration in service that the lighting control devices are in good operating condition and properly performing the intended function in the presence of the COR.

3.4 INSTRUCTION

A.Furnish the services of a factory-trained technician for one 4-hour training period for instructing personnel in the maintenance and operation of the lighting control system on the dates requested by the COR.
B.Contractor shall submit written instructions on training and maintenance as reviewed in training session.

E N D 26 09 23 - 1