36C25622R0094 079200 Joint Sealants .docx

DOCX document 29 KB Posted

Attached to
Z2DA--Project #502-19-107 - Replace AHU-104 - Construction - 36C25622R0094
Solicitation number
502-19-107
Issued by

About this file

This document contains technical specifications for a joint sealant project and details of a related federal contract opportunity. The technical specifications outline requirements for interior and exterior joint sealants and backing materials to replace an air handling unit and ductwork at a Department of Veterans Affairs health care facility in Alexandria, Louisiana. Sealant application locations, material standards, submittal requirements, and installation procedures are specified. The related solicitation is for construction services for Project #502-19-107 to replace the air handling unit, with an opportunity type of solicitation. The contracting agency is the Department of Veterans Affairs Veterans Health Administration VISN 16.

View the file

Other files

File Type Posted
36C25622R0094 ECS Geotechnical Report.pdf PDF
36C25622R0094 0004.docx DOCX document
36C25622R0094 RFI Register 08292022.docx DOCX document
36C25622R0094 0003.docx DOCX document
36C25622R0094 0002.docx DOCX document
Site Visit Sign in Sheet 50219107.pdf PDF
36C25622R0094 0001.docx DOCX document
36C25622R0094 282300 Video Surveillance .docx DOCX document
36C25622R0094 233700 AIR OUTLETS AND INLETS.docx DOCX document
36C25622R0094 054000 Cold Formed Metal Framing .docx DOCX document
36C25622R0094 013216.15 Project Schedules (Small Projects-Design-Bid-Build).docx DOCX document
36C25622R0094 018113 Sustainable Construction Requirements.docx DOCX document
36C25622R0094 230923 DIRECT DIGITAL CONTROL SYSTEM FOR HVAC .doc DOC document
36C25622R0094 COVID-19 Safety Protocols for Federal Contractors Rev 2.docx DOCX document
36C25622R0094 260923 Lighting Controls.docx DOCX document
36C25622R0094 Brand Name JA 502-19-107 Redacted.pdf PDF
36C25622R0094 260511 Requirements for ELEC installation.docx DOCX document
36C25622R0094 IFC Drawings Part 3 .pdf PDF
36C25622R0094 260800 Commissioning of Electrical Systems.docx DOCX document
36C25622R0094 283100 Fire Detection and Alarm .doc DOC document
36C25622R0094 280800 Commissioning of Electronic Safety and Security Systems .docx DOCX document
36C25622R0094 232500 HVAC WATER TREATMENT .docx DOCX document
36C25622R0094 096513 Resilient Base and Accessories.docx DOCX document
36C25622R0094 092216 Non-Structural Metal Framing .docx DOCX document
36C25622R0094 IFC Drawings Part 4 .pdf PDF
36C25622R0094 EXHIBIT B.docx DOCX document
36C25622R0094 013323 Shop Drawings Product Data and Samples.docx DOCX document
36C25622R0094 260533 Raceways and Boxes for Electrical Systems .docx DOCX document
36C25622R0094 232123 HYDRONIC PUMPS.docx DOCX document
36C25622R0094 010000 General Requirements .docx DOCX document
36C25622R0094 233400 HVAC FANS.docx DOCX document
36C25622R0094 024100 Demolition .docx DOCX document
36C25622R0094 262911 Motor Controllers .docx DOCX document
36C25622R0094 090600 Schedule for Finishes .docx DOCX document
36C25622R0094 230512 GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.docx DOCX document
36C25622R0094 230593 TESTING ADJUSTING AND BALANCING FOR HVAC.docx DOCX document
36C25622R0094 014500 Quality Control.docx DOCX document
36C25622R0094 092900 Gypsum Board .docx DOCX document
36C25622R0094 232113 HYDRONIC PIPING .docx DOCX document
36C25622R0094 Project Risk Assessment .pdf PDF
36C25622R0094 015719 Temporary Environmental Controls .doc DOC document
36C25622R0094 Revised SOW 05202022 .docx DOCX document
36C25622R0094 237300 INDOOR CENTRAL STATION AIR HANDLING UNITS.docx DOCX document
36C25622R0094 IFC Drawings Part 1 .pdf PDF
36C25622R0094 265100 Interior Lighting .docx DOCX document
36C25622R0094 078400 Firestopping.docx DOCX document
36C25622R0094 RFP.docx DOCX document
36C25622R0094 262921 Enclosed Switches and Circuit Breakers.docx DOCX document
36C25622R0094 IFC Drawings Part 2.pdf PDF
36C25622R0094 323113 Chain Link Fences and Gates .docx DOCX document
Show 40 more

Latest 50 of 95 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REPLACE AHU #104 AND DUCTWORK BLDG. 7

DEPARTMENT OF VETERANS AFFAIRS HEALTH CARE SYSTEM-ALEXANDRIA, LA

PROJECT NO.: 502-19-107

SECTION 07 92 00

JOINT SEALANTS

PART 1 - GENERAL

1.1 DESCRIPTION:

A. This section covers interior and exterior sealant and their application, wherever required for complete installation of building materials or systems.

1.2 RELATED WORK (Including but not limited to the following):

A. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.

B. Firestopping Penetrations: Section 07 84 00, FIRESTOPPING.

C. Mechanical Work: Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION.

1.3 QUALITY ASSURANCE:

A.Installer Qualifications: An experienced installer with a minimum of three (3) years’ experience and who has specialized in installing joint sealants similar in material, design, and extent to those indicated for this Project and whose work has resulted in joint-sealant installations with a record of successful in-service performance. Submit qualification.
B.Source Limitations: Obtain each type of joint sealant through one (1) source from a single manufacturer.

1.4 certification:

A. Contractor is to submit to the COR written certification that joints are of the proper size and design, that the materials supplied are compatible with adjacent materials and backing, that the materials will properly perform to provide permanent watertight, airtight or vapor tight seals (as applicable), and that materials supplied meet specified performance requirements.

1.5 SUBMITTALS:

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Installer qualifications.

C. Contractor certification.

D.Manufacturer's installation instructions for each product used.
E.Cured samples of exposed sealants for each color.
F.Manufacturer's Literature and Data:
1.Primers
2.Sealing compound, each type, including compatibility when different sealants are in contact with each other.

G. Manufacturer warranty.

1.6 PROJECT CONDITIONS:

A.Environmental Limitations:
1.Do not proceed with installation of joint sealants under following conditions:
a.When ambient and substrate temperature conditions are outside limits permitted by joint sealant manufacturer or are below 4.4 degrees C (40 degrees F).
b.When joint substrates are wet.
B.Joint-Width Conditions:
1.Do not proceed with installation of joint sealants where joint widths are less than those allowed by joint sealant manufacturer for applications indicated.
C.Joint-Substrate Conditions:
1.Do not proceed with installation of joint sealants until contaminants capable of interfering with adhesion are removed from joint substrates.

1.7 DELIVERY, HANDLING, AND STORAGE:

A.Deliver materials in manufacturers' original unopened containers, with brand names, date of manufacture, shelf life, and material designation clearly marked thereon.
B.Carefully handle and store to prevent inclusion of foreign materials.
C.Do not subject to sustained temperatures exceeding 32 degrees C (90 degrees F) or less than 5 degrees C (40 degrees F).

1.8 DEFINITIONS:

A.Definitions of terms in accordance with ASTM C717 and as specified.
B.Backing Rod: A type of sealant backing.
C.Bond Breakers: A type of sealant backing.
D.Filler: A sealant backing used behind a back-up rod.

1.9 warranty:

A. Construction Warranty: Comply with FAR clause 52.246-21 "Warranty of Construction".

B. Manufacturer Warranty: Manufacturer shall warranty their sealant for a minimum of five (5) years from the date of installation and final acceptance by the Government. Submit manufacturer warranty.

1.10 APPLICABLE PUBLICATIONS:

A.Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.
B.ASTM International (ASTM):
C509-06Elastomeric Cellular Preformed Gasket and Sealing Material
C612-14Mineral Fiber Block and Board Thermal Insulation
C717-14aStandard Terminology of Building Seals and Sealants
C734-06(R2012)Test Method for Low-Temperature Flexibility of Latex Sealants after Artificial Weathering
C794-10Test Method for Adhesion-in-Peel of Elastomeric Joint Sealants
C919-12.Use of Sealants in Acoustical Applications.
C920-14aElastomeric Joint Sealants.
C1193-13Standard Guide for Use of Joint Sealants.
C1330-02(R2013)Cylindrical Sealant Backing for Use with Cold Liquid Applied Sealants
D217-10Test Methods for Cone Penetration of Lubricating Grease
D1056-14Specification for Flexible Cellular Materials—Sponge or Expanded Rubber
E84-09Surface Burning Characteristics of Building Materials
C.Sealant, Waterproofing and Restoration Institute (SWRI).
The Professionals’ Guide

D. Environmental Protection Agency (EPA):

40 CFR 59(2014) National Volatile Organic Compound Emission Standards for Consumer and Commercial Products

PART 2 - PRODUCTS

2.1 SEALANTS:

A. Exterior Sealants:

1. Vertical surfaces, provide non-staining ASTM C920, Type S or M, Grade NS, Class 25, Use NT.

2. Horizontal surfaces, provide ASTM C920, Type S or M, Grade P, Class 25, Use T.

3. Provide location(s) of exterior sealant as follows:

a. Joints formed where frames and subsills of windows, doors, louvers, and vents adjoin masonry, concrete, or metal frames. Provide sealant at exterior surfaces of exterior wall penetrations.

b. Metal to metal.

c. Masonry to masonry or stone.

d. Stone to stone.

e. Cast stone to cast stone.

f. Masonry expansion and control joints.

g. Wood to masonry.

h. Masonry joints where shelf angles occur.

i. Voids where items penetrate exterior walls.

j. Metal reglets, where flashing is inserted into masonry joints, and where flashing is penetrated by coping dowels.

B. Interior Sealants:

1. VOC Content of Interior Sealants: Sealants and sealant primers used inside the weatherproofing system are to comply with the following limits for VOC content when calculated according to 40 CFR 59, (EPA Method 24):

a. Architectural Sealants: 250 g/L.

b. Sealant Primers for Nonporous Substrates: 250 g/L.

c. Sealant Primers for Porous Substrates: 775 g/L.

2. Vertical and Horizontal Surfaces: ASTM C920, Type S or M, Grade NS, Class 25, Use NT.

3. Provide location(s) of interior sealant as follows:

a. Typical narrow joint 6 mm, (1/4 inch) or less at walls and adjacent components.

2.2 COLOR:

A. Color of sealants for other locations to be light gray or aluminum, unless otherwise indicated in construction documents.

2.3 JOINT SEALANT BACKING:

A.General: Provide sealant backings of material and type that are nonstaining; are compatible with joint substrates, sealants, primers, and other joint fillers; and are approved for applications indicated by sealant manufacturer based on field experience and laboratory testing.
B.Cylindrical Sealant Backings: ASTM C1330, of type indicated below and of size and density to control sealant depth and otherwise contribute to producing optimum sealant performance:
1.Type C: Closed-cell material with a surface skin.
C.Elastomeric Tubing Sealant Backings: Neoprene, butyl, EPDM, or silicone tubing complying with ASTM D1056 or synthetic rubber (ASTM C509), nonabsorbent to water and gas, and capable of remaining resilient at temperatures down to minus 32 degrees C (minus 26 degrees F). Provide products with low compression set and of size and shape to provide a secondary seal, to control sealant depth, and otherwise contribute to optimum sealant performance.
D.Bond-Breaker Tape: Polyethylene tape or other plastic tape recommended by sealant manufacturer for preventing sealant from adhering to rigid, inflexible joint-filler materials or joint surfaces at back of joint where such adhesion would result in sealant failure. Provide self-adhesive tape where applicable.

2.4 FILLER:

A.Mineral fiberboard: ASTM C612, Class 1.
B.Thickness same as joint width.
C.Depth to fill void completely behind back-up rod.

2.5 PRIMER:

A.As recommended by manufacturer of caulking or sealant material.
B.Stain free type.

2.6 CLEANERS-NON POROUS SURFACES:

A. Chemical cleaners compatible with sealant and acceptable to manufacturer of sealants and sealant backing material. Cleaners to be free of oily residues and other substances capable of staining or harming joint substrates and adjacent non-porous surfaces and formulated to promote adhesion of sealant and substrates.

PART 3 - EXECUTION

3.1 INSPECTION:

A.Inspect substrate surface for bond breaker contamination and unsound materials at adherent faces of sealant.
B.Coordinate for repair and resolution of unsound substrate materials.
C.Inspect for uniform joint widths and that dimensions are within tolerance established by sealant manufacturer.

3.2 PREPARATIONS:

A.Prepare joints in accordance with manufacturer's instructions and SWRI (The Professionals’ Guide).
B.Clean surfaces of joint to receive caulking or sealants leaving joint dry to the touch, free from frost, moisture, grease, oil, wax, lacquer paint, or other foreign matter that would tend to destroy or impair adhesion.
1.Clean porous joint substrate surfaces by brushing, grinding, blast cleaning, mechanical abrading, or a combination of these methods to produce a clean, sound substrate capable of developing optimum bond with joint sealants.
2.Remove loose particles remaining from above cleaning operations by vacuuming or blowing out joints with oil-free compressed air. Porous joint surfaces include but are not limited to the following:
a.Concrete.
b.Masonry.
c.Unglazed surfaces of ceramic tile.
3.Remove laitance and form-release agents from concrete.
4.Clean nonporous surfaces with chemical cleaners or other means that do not stain, harm substrates, or leave residues capable of interfering with adhesion of joint sealants. Nonporous surfaces include but are not limited to the following:
a.Metal.
b.Glass.
c.Porcelain enamel.
d.Glazed surfaces of ceramic tile.
C.Do not cut or damage joint edges.
D.Apply non-staining masking tape to face of surfaces adjacent to joints before applying primers, caulking, or sealing compounds.
1.Do not leave gaps between ends of sealant backings.
2.Do not stretch, twist, puncture, or tear sealant backings.
3.Remove absorbent sealant backings that have become wet before sealant application and replace them with dry materials.
E.Apply primer to sides of joints wherever required by compound manufacturer's printed instructions or as indicated by pre-construction joint sealant substrate test.
1.Apply primer prior to installation of back-up rod or bond breaker tape.
2.Use brush or other approved means that will reach all parts of joints. Avoid application to or spillage onto adjacent substrate surfaces.

3.3 BACKING INSTALLATION:

A.Install backing material, to form joints enclosed on three sides as required for specified depth of sealant.
B.Where deep joints occur, install filler to fill space behind the backing rod and position the rod at proper depth.
C.Cut fillers installed by others to proper depth for installation of backing rod and sealants.
D.Install backing rod, without puncturing the material, to a uniform depth, within plus or minus 3 mm (1/8 inch) for sealant depths specified.
E.Where space for backing rod does not exist, install bond breaker tape strip at bottom (or back) of joint so sealant bonds only to two opposing surfaces.

3.4 SEALANT DEPTHS AND GEOMETRY:

A.At widths up to 6 mm (1/4 inch), sealant depth equal to width.
B.At widths over 6 mm (1/4 inch), sealant depth 1/2 of width up to 13 mm (1/2 inch) maximum depth at center of joint with sealant thickness at center of joint approximately 1/2 of depth at adhesion surface.

3.5 INSTALLATION:

A.General:
1.Apply sealants and caulking only when ambient temperature is between

5 degrees C and 38 degrees C (40 degrees and 100 degrees F).

2.Do not install polysulfide base sealants where sealant may be exposed to fumes from bituminous materials, or where water vapor in continuous contact with cementitious materials may be present.
3.Do not install sealant type listed by manufacture as not suitable for use in locations specified.
4.Apply caulking and sealing compound in accordance with manufacturer's printed instructions.
5.Avoid dropping or smearing compound on adjacent surfaces.
6.Fill joints solidly with compound and finish compound smooth.
7.Tool exposed joints to form smooth and uniform beds, with slightly concave surface conforming to joint configuration per Figure 5A in ASTM C1193 unless shown or specified otherwise in construction documents. Remove masking tape immediately after tooling of sealant and before sealant face starts to “skin” over. Remove any excess sealant from adjacent surfaces of joint, leaving the working in a clean finished condition.
8.Apply compounds with nozzle size to fit joint width.
9.Test sealants for compatibility with each other and substrate. Use only compatible sealant. Submit test reports.

10. Replace sealant which is damaged during construction process.

B. For application of sealants, follow requirements of ASTM C1193 unless specified otherwise. Take all necessary steps to prevent three-sided adhesion of sealants.

C.Interior Sealants: Where gypsum board partitions are of sound rated, fire rated, or smoke barrier construction, follow requirements of ASTM C919 only to seal all cut-outs and intersections with the adjoining construction unless specified otherwise.
1.Apply a 6 mm (1/4 inch) minimum bead of sealant each side of runners (tracks), including those used at partition intersections with dissimilar wall construction.
2.Coordinate with application of gypsum board to install sealant immediately prior to application of gypsum board.
3.Partition intersections: Seal edges of face layer of gypsum board abutting intersecting partitions, before taping and finishing or application of veneer plaster-joint reinforcing.
4.Openings: Apply a 6 mm (1/4 inch) bead of sealant around all cutouts to seal openings of electrical boxes, ducts, pipes and similar penetrations. To seal electrical boxes, seal sides and backs.

3.6 CLEANING:

A.Fresh compound accidentally smeared on adjoining surfaces: Scrape off immediately and rub clean with a solvent as recommended by manufacturer of the adjacent material or if not otherwise indicated by the caulking or sealant manufacturer.
B.Leave adjacent surfaces in a clean and unstained condition.

E N D 07 92 00 - 1