36C25622R0094 092216 Non-Structural Metal Framing .docx

DOCX document 27 KB Posted

Attached to
Z2DA--Project #502-19-107 - Replace AHU-104 - Construction - 36C25622R0094
Solicitation number
502-19-107
Issued by

About this file

This document provides specifications for non-structural metal framing required for a construction project to replace an air handling unit and ductwork at a Department of Veterans Affairs health care facility in Alexandria, Louisiana. The specifications cover steel stud wall systems, fasteners, accessories, furring channels, and installation requirements. Products are to be galvanized and include steel studs and runners between 0.75 and 0.48 millimeters thick. Fasteners must meet ASTM standards and be the appropriate size and type for the materials being joined. Wall framing is to be installed according to industry standards at spacings of 24 inches or less on center with bracing and reinforcement at openings and corners as specified.

View the file

Other files

File Type Posted
36C25622R0094 ECS Geotechnical Report.pdf PDF
36C25622R0094 0004.docx DOCX document
36C25622R0094 RFI Register 08292022.docx DOCX document
36C25622R0094 0003.docx DOCX document
36C25622R0094 0002.docx DOCX document
Site Visit Sign in Sheet 50219107.pdf PDF
36C25622R0094 0001.docx DOCX document
36C25622R0094 282300 Video Surveillance .docx DOCX document
36C25622R0094 233700 AIR OUTLETS AND INLETS.docx DOCX document
36C25622R0094 054000 Cold Formed Metal Framing .docx DOCX document
36C25622R0094 013216.15 Project Schedules (Small Projects-Design-Bid-Build).docx DOCX document
36C25622R0094 018113 Sustainable Construction Requirements.docx DOCX document
36C25622R0094 230923 DIRECT DIGITAL CONTROL SYSTEM FOR HVAC .doc DOC document
36C25622R0094 COVID-19 Safety Protocols for Federal Contractors Rev 2.docx DOCX document
36C25622R0094 260923 Lighting Controls.docx DOCX document
36C25622R0094 Brand Name JA 502-19-107 Redacted.pdf PDF
36C25622R0094 260511 Requirements for ELEC installation.docx DOCX document
36C25622R0094 IFC Drawings Part 3 .pdf PDF
36C25622R0094 260800 Commissioning of Electrical Systems.docx DOCX document
36C25622R0094 283100 Fire Detection and Alarm .doc DOC document
36C25622R0094 280800 Commissioning of Electronic Safety and Security Systems .docx DOCX document
36C25622R0094 232500 HVAC WATER TREATMENT .docx DOCX document
36C25622R0094 096513 Resilient Base and Accessories.docx DOCX document
36C25622R0094 IFC Drawings Part 4 .pdf PDF
36C25622R0094 EXHIBIT B.docx DOCX document
36C25622R0094 013323 Shop Drawings Product Data and Samples.docx DOCX document
36C25622R0094 260533 Raceways and Boxes for Electrical Systems .docx DOCX document
36C25622R0094 232123 HYDRONIC PUMPS.docx DOCX document
36C25622R0094 010000 General Requirements .docx DOCX document
36C25622R0094 233400 HVAC FANS.docx DOCX document
36C25622R0094 024100 Demolition .docx DOCX document
36C25622R0094 262911 Motor Controllers .docx DOCX document
36C25622R0094 090600 Schedule for Finishes .docx DOCX document
36C25622R0094 230512 GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.docx DOCX document
36C25622R0094 230593 TESTING ADJUSTING AND BALANCING FOR HVAC.docx DOCX document
36C25622R0094 014500 Quality Control.docx DOCX document
36C25622R0094 092900 Gypsum Board .docx DOCX document
36C25622R0094 232113 HYDRONIC PIPING .docx DOCX document
36C25622R0094 Project Risk Assessment .pdf PDF
36C25622R0094 079200 Joint Sealants .docx DOCX document
36C25622R0094 015719 Temporary Environmental Controls .doc DOC document
36C25622R0094 Revised SOW 05202022 .docx DOCX document
36C25622R0094 237300 INDOOR CENTRAL STATION AIR HANDLING UNITS.docx DOCX document
36C25622R0094 IFC Drawings Part 1 .pdf PDF
36C25622R0094 265100 Interior Lighting .docx DOCX document
36C25622R0094 078400 Firestopping.docx DOCX document
36C25622R0094 RFP.docx DOCX document
36C25622R0094 262921 Enclosed Switches and Circuit Breakers.docx DOCX document
36C25622R0094 IFC Drawings Part 2.pdf PDF
36C25622R0094 323113 Chain Link Fences and Gates .docx DOCX document
Show 40 more

Latest 50 of 95 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REPLACE AHU #104 AND DUCTWORK BLDG. 7

DEPARTMENT OF VETERANS AFFAIRS HEALTH CARE SYSTEM-ALEXANDRIA, LA

PROJECT NO.: 502-19-107

SECTION 09 22 16

NON-STRUCTURAL METAL FRAMING

PART 1 GENERAL

1.1 DESCRIPTION

This section specifies steel studs wall systems, fasteners, and accessories for the screw attachment of gypsum board, plaster bases or other building boards.

1.2 RELATED WORK

A.Exterior framing for stucco: Section 05 40 00, COLD-FORMED METAL FRAMING.
B.Ceiling suspension systems for acoustical tile or panels and lay in gypsum board panels: Section 09 29 00, GYPSUM BOARD.

1.3 TERMINOLOGY

A.Description of terms shall be in accordance with ASTM C754, ASTM C11, ASTM C841 and as specified.
B.Underside of Structure Overhead: In spaces where steel trusses or bar joists are shown, the underside of structure overhead shall be the underside of the floor or roof construction supported by beams, trusses, or bar joists. In interstitial spaces with walkon floors the underside of the walkon floor is the underside of structure overhead.
C.Thickness of steel specified is the minimum bare (uncoated) steel thickness.

1.4 SUBMITTALS

A.Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B.Manufacturer's Literature and Data:
1.Studs, runners, and accessories.
2.Hanger inserts.
3.Channels (Rolled steel).
4.Furring channels.
5.Screws, clips, and other fasteners.
C.Shop Drawings:
1.Typical ceiling suspension system.
2.Typical metal stud and furring construction system including details around openings and corner details.
3.Typical shaft wall assembly
4.Typical fire rated assembly and column fireproofing showing details of construction same as that used in fire rating test.
D.Test Results: Fire rating test designation, each fire rating required for each assembly.

1.5 DELIVERY, IDENTIFICATION, HANDLING AND STORAGE

In accordance with the requirements of ASTM C754.

1.6 APPLICABLE PUBLICATIONS

A.The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B.American Society for Testing and Materials (ASTM)
A641-09Zinc-Coated (Galvanized) Carbon Steel Wire
A653/653M-11Specification for Steel Sheet, Zinc Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by Hot-Dip Process.
C11-10Terminology Relating to Gypsum and Related Building Materials and Systems
C635-07Manufacture, Performance, and Testing of Metal Suspension System for Acoustical Tile and Layin Panel Ceilings
C636-08Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Layin Panels
C645-09Non-Structural Steel Framing Members
C754-11Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products
C841-03(R2008)Installation of Interior Lathing and Furring
C954-10Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness
E580-11Application of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Requiring Moderate Seismic Restraint.

PART 2 PRODUCTS

2.1 PROTECTIVE COATING

Galvanize steel studs, runners (track), rigid (hat section) furring channels, "Z" shaped furring channels, and resilient furring channels, with coating designation of G40 or equivalent.

2.2 STEEL STUDS AND RUNNERS (TRACK)

A.ASTM C645, modified for thickness specified and sizes as shown.
1.Use C 645 steel, 0.75 mm (0.0296-inch) minimum base-metal (30 mil).
2.Runners same thickness as studs.

3. Exception: Members that can show certified third-party testing with gypsum board in accordance with ICC ES AC86 (Approved May 2012) need not meet the minimum thickness limitation or minimum section properties set forth in ASTM C 645. The submission of an evaluation report is acceptable to show conformance to this requirement. Use C 645 steel, 0.48mm (0.019 inch) minimum base-metal (19 mil).

B.Provide not less than two cutouts in web of each stud, approximately 300 mm (12 inches) from each end, and intermediate cutouts on approximately 600 mm (24inch) centers.
C.Doubled studs for openings and studs for supporting concrete backerboard.
D.Studs 3600 mm (12 feet) or less in length shall be in one piece.

2.3 FASTENERS, CLIPS, AND OTHER METAL ACCESSORIES

A.ASTM C754, except as otherwise specified.
B.Fasteners for steel studs thicker than 0.84 mm (0.033inch) thick. Use ASTM C954 steel drill screws of size and type recommended by the manufacturer of the material being fastened.
C.Clips: ASTM C841 (paragraph 6.11), manufacturer’s standard items. Clips used in lieu of tie wire shall have holding power equivalent to that provided by the tie wire for the specific application.
D.Concrete ceiling hanger inserts (anchorage for hanger wire and hanger straps): Steel, zinccoated (galvanized), manufacturers standard items, designed to support twice the hanger loads imposed and the type of hanger used.
E.Tie Wire and Hanger Wire:
1.ASTM A641, soft temper, Class 1 coating.
2.Gage (diameter) as specified in ASTM C754 or ASTM C841.
F.Power Actuated Fasteners: Type and size as recommended by the manufacturer of the material being fastened.

PART 3 EXECUTION

3.1 INSTALLING STUDS

A.Install studs in accordance with ASTM C754, except as otherwise shown or specified.
B.Space studs not more than 610 mm (24 inches) on center.
C.Cut studs 6 mm to 9 mm (1/4 to 3/8inch) less than floor to underside of structure overhead when extended to underside of structure overhead.
D.Where studs are shown to terminate above suspended ceilings, provide bracing as shown or extend studs to underside of structure overhead.
E.Openings:
1.Frame jambs of openings in stud partitions and furring with two studs placed back-to-back or as shown.
2.Fasten back-to-back studs together with 9 mm (3/8inch) long Type S pan head screws at not less than 600 mm (two feet) on center, staggered along webs.
3.Studs fastened flange to flange shall have splice plates on both sides approximately 50 X 75 mm (2 by 3 inches) screwed to each stud with two screws in each stud. Locate splice plates at 600 mm (24 inches) on center between runner tracks.
F.Fastening Studs:
1.Fasten studs located adjacent to partition intersections, corners and studs at jambs of openings to flange of runner tracks with two screws through each end of each stud and flange of runner.
2.Do not fasten studs to top runner track when studs extend to underside of structure overhead.

3.2 INSTALLING WALL FURRING FOR FINISH APPLIED TO ONE SIDE ONLY

A.In accordance with ASTM C754, or ASTM C841 except as otherwise specified or shown.
B.Wall furringStud System:
1.Framed with 63 mm (21/2 inch) or narrower studs, 600 mm (24 inches) on center.
2.Brace as specified in ASTM C754 for Wall FurringStud System or brace with sections or runners or studs placed horizontally at not less than three foot vertical intervals on side without finish.
3.Securely fasten braces to each stud with two Type S pan head screws at each bearing.
C.Direct attachment to masonry or concrete; rigid channels or "Z" channels:
1.Install rigid (hat section) furring channels at 600 mm (24 inches) on center, horizontally or vertically.
2.Install "Z" furring channels vertically spaced not more than 600 mm (24 inches) on center.
3.At corners where rigid furring channels are positioned horizontally, provide mitered joints in furring channels.
4.Ends of spliced furring channels shall be nested not less than 200 mm (8 inches).
5.Fasten furring channels to walls with poweractuated drive pins or hardened steel concrete nails. Where channels are spliced, provide two fasteners in each flange.
6.Locate furring channels at interior and exterior corners in accordance with wall finish material manufacturers printed erection instructions. Locate "Z" channels within 100 mm (4 inches) of corner.

3.3 INSTALLING SUPPORTS REQUIRED BY OTHER TRADES

A.Provide for attachment and support of electrical outlets and other items supported by stud construction.
B.Provide additional studs where required. Install metal backing plates, or special metal shapes as required, securely fastened to metal studs.

3.4 TOLERANCES

A.Fastening surface for application of subsequent materials shall not vary more than 3 mm (1/8inch) from the layout line.
B.Plumb and align vertical members within 3 mm (1/8inch.)
C.Level or align ceilings within 3 mm (1/8inch.)

E N D