This document contains specifications for structural steel framing for a construction project to replace an air handling unit and ductwork at a Department of Veterans Affairs health care facility in Alexandria, Louisiana. The project number is 502-19-107, with a solicitation number of 502-19-107. Structural steel materials required include W shapes, channels, angles, plates, bars, and hollow structural sections according to ASTM standards. Bolts, nuts, and washers must meet specifications for galvanizing and strength. Welding materials must be suitable for the intended application. Structural steel must meet minimum recycled content requirements and VOC limits for paints and coatings. The successful bidder will be required to fabricate, deliver, and erect the structural steel according to industry standards and codes for connections, welding, and finishes including galvanizing and painting.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Project #502-19-107 - Replace AHU-104 - Construction - 36C25622R0094, newest first.
File Type Posted
36C25622R0094 ECS Geotechnical Report.pdf PDF
36C25622R0094 0004.docx DOCX document
36C25622R0094 0001.docx DOCX document
36C25622R0094 Project Risk Assessment .pdf PDF
36C25622R0094 260526 Grounding and Bonding.docx DOCX document
36C25622R0094 260519 Low voltage conductors .docx DOCX document
36C25622R0094 312011 Earthwork .docx DOCX document
36C25622R0094 262416 Panelboards.docx DOCX document
36C25622R0094 281300 Physical Access Control System .doc DOC document
36C25622R0094 EXHIBIT A.docx DOCX document
36C25622R0094 262911 Motor Controllers .docx DOCX document
36C25622R0094 316500 Helical Piles.doc DOC document
36C25622R0094 282300 Video Surveillance .docx DOCX document
36C25622R0094 236400 PACKAGED WATER CHILLERS.docx DOCX document
36C25622R0094 233700 AIR OUTLETS AND INLETS.docx DOCX document
36C25622R0094 260541 UNDERGROUND ELEC CONSTRUCTION .docx DOCX document
36C25622R0094 230541 NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT .docx DOCX document
36C25622R0094 230512 GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.docx DOCX document
36C25622R0094 233100 HVAC DUCTS AND CASINGS.docx DOCX document
36C25622R0094 233600 AIR TERMINAL UNITS .docx DOCX document
36C25622R0094 238216 AIR COILS .doc DOC document
36C25622R0094 230800 COMMISSIONING OF HVAC SYSTEMS.docx DOCX document
36C25622R0094 033000 Cast in Place Concrete.docx DOCX document
36C25622R0094 019100 General Commissioning Requirements .docx DOCX document
36C25622R0094 090600 Schedule for Finishes .docx DOCX document
36C25622R0094 Brand Name JA 502-19-107 Redacted.pdf PDF
36C25622R0094 COVID-19 Safety Protocols for Federal Contractors Rev 2.docx DOCX document
36C25622R0094 280800 Commissioning of Electronic Safety and Security Systems .docx DOCX document
36C25622R0094 000110 VHA Master Specifications Rev 2.docx DOCX document
36C25622R0094 262726 Wiring Devices .docx DOCX document
36C25622R0094 283100 Fire Detection and Alarm .doc DOC document
36C25622R0094 260923 Lighting Controls.docx DOCX document
36C25622R0094 232500 HVAC WATER TREATMENT .docx DOCX document
36C25622R0094 260511 Requirements for ELEC installation.docx DOCX document
36C25622R0094 234000 HVAC AIR CLEANING DEVICES .docx DOCX document
36C25622R0094 238100 DECENTRALIZED UNITARY HVAC EQUIPMENT.docx DOCX document
36C25622R0094 260800 Commissioning of Electrical Systems.docx DOCX document
36C25622R0094 232113 HYDRONIC PIPING .docx DOCX document
36C25622R0094 230923 DIRECT DIGITAL CONTROL SYSTEM FOR HVAC .doc DOC document
36C25622R0094 014500 Quality Control.docx DOCX document
36C25622R0094 013526 Safety Requirements .docx DOCX document
36C25622R0094 099100 Painting .docx DOCX document
36C25622R0094 095100 Acoustical Ceilings .docx DOCX document
36C25622R0094 087100 Door Hardware .docx DOCX document
36C25622R0094 092216 Non-Structural Metal Framing .docx DOCX document
36C25622R0094 096513 Resilient Base and Accessories.docx DOCX document
36C25622R0094 079200 Joint Sealants .docx DOCX document
36C25622R0094 092900 Gypsum Board .docx DOCX document
36C25622R0094 076000 Flashing and Sheet Metal .docx DOCX document
36C25622R0094 015719 Temporary Environmental Controls .doc DOC document
Show all 50

Z2DA--Project #502-19-107 - Replace AHU-104 - Construction - 36C25622R0094 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REPLACE AHU #104 AND DUCTWORK BLDG. 7

DEPARTMENT OF VETERANS AFFAIRS HEALTH CARE SYSTEM-ALEXANDRIA, LA

PROJECT NO.: 502-19-107

SECTION 05 12 00

STRUCTURAL STEEL FRAMING

GENERAL

SUMMARY

Section Includes:

Structural steel shapes, plates, and bars.

Structural pipe.

Bolts, nuts, and washers.

RELATED REQUIREMENTS

Materials Testing and Inspection During Construction: Section 01 45 29, TESTING LABORATORY SERVICES.

Steel Decking: Section 05 31 00, STEEL DECKING.

Steel Finishes: Section 09 06 00, SCHEDULE FOR FINISHES.

Painting: Section 09 91 00, PAINTING.

APPLICABLE PUBLICATIONS

Comply with references to extent specified in this section.

American Institute of Steel Construction (AISC):

AISC Manual - Steel Construction Manual, 14th Ed.

30310 - Code of Structural Steel Buildings and Bridges.

36010: Specification for Structural Steel Buildings.

The American Society of Mechanical Engineers (ASME):

B18.22.109 - Washers: Helical SpringLock, Tooth Lock, and Plain Washers.

American Welding Society (AWS):

D1.1/D1.1M15 - Structural Welding Code - Steel.

ASTM International (ASTM):

A6/A6M14 - General Requirements for Rolled Structural Steel Bars, Plates, Shapes, and Sheet Piling.

A36/A36M14 - Carbon Structural Steel.

A123/A123M15 - Zinc (HotDip Galvanized) Coatings on Iron and Steel Products.

A32514 - Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength.

A500/A500M13 - ColdFormed Welded and Seamless Carbon Steel Structural Tubing and Rounds and Shapes.

A992/A992M15 - Structural Shapes.

Master Painters Institute (MPI):

No. 18 - Primer, Zinc Rich, Organic.

Military Specifications (Mil. Spec.):

MILP21035 - Paint, High Zinc Dust Content, Galvanizing, Repair.

Occupational Safety and Health Administration (OSHA):

29 CFR 1926.752(e) - Guidelines For Establishing The Components Of A SiteSpecific Erection Plan.

29 CFR 19262001 - Safety Standards for Steel Erection.

Research Council on Structural Connections (RCSC) of The Engineering Foundation:

Specification for Structural Joints Using ASTM A325 or A490 Bolts.

SUBMITTALS

Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Submittal Drawings:

Show size, configuration, and fabrication and installation details.

Erection Drawings:

Provide erection drawings showing verified field dimensions.

Submit for record purposes. Indicate the sequence of erection, temporary shoring and bracing. The erection drawings must conform to AISC 303. The erection drawings shall include all field dimensions. Clearly note any field conditions that differ from the contract documents.

Fabrication Drawing Requirements:

Submit fabrication drawings for approval prior to fabrication. Prepare in accordance with AISC 326 and AISC 325. Fabrication drawings must not be reproductions of contract drawings. Include complete information for the fabrication and erection of the structure’s components, including the location, type, and size of bolts, welds, member sizes and lengths, connection details, blocks, copes, and cuts. Use AWS A2.4 standard welding symbols.

Sustainable Construction Submittals:

Recycled Content: Identify postconsumer and preconsumer recycled content percentage by weight.

Test Reports: Certify products comply with specifications.

Welders' qualifying tests.

Certificates: Certify each product complies with specifications.

Structural steel.

Steel connections.

Welding materials.

Shop coat primer paint.

Qualifications: Substantiate qualifications comply with specifications.

Fabricator.

Installer.

Welders and welding procedures.

Record Surveys: Signed and sealed by responsible surveyor or engineer.

QUALITY ASSURANCE

Fabricator Qualifications: AISC Quality Certification participant designated as AISC Certified Plant, Category STD.

Regularly fabricates specified products.

Fabricated specified products with satisfactory service on five similar installations for minimum five years.

Installer Qualifications: AISC Quality Certification Program participant designated as AISCCertified Erector, Category ACSE.

Regularly installs specified products.

Installed specified products with satisfactory service on five similar installations for minimum five years.

Before commencement of Work, ensure steel erector provides written notification required by OSHA 29 CFR 1926.752(e). Submit a copy of the notification to Contracting Officer's Representative.

Welders and Welding Procedures Qualifications: AWS D1.1/D1.1M.

WARRANTY

Construction Warranty: FAR clause 52.24621, "Warranty of Construction."

PRODUCTS

MATERIALS

WShapes:

ASTM A992/A992M.

Channel and Angles:

ASTM A36/A36M.

Plates and Bars:

ASTM A36/A36M.

Hollow Structural Sections:

ASTM A500/A500M.

Bolts, Nuts and Washers: Galvanized for galvanized framing and plain finish for other framing.

Highstrength bolts, including nuts and washers: ASTM A325.

Plain washers, other than those in contact with highstrength bolt heads and nuts: ASME B18.22.1.

Welding Materials: AWS D1.1, type to suit application.

PRODUCTS - GENERAL

Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

Sustainable Construction Requirements:

Steel Recycled Content: 30 percent total recycled content, minimum.

Low PollutantEmitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:

Paints and coatings.

FABRICATION

Fabricate structural steel according to Chapter M, AISC 360.

Shop and Field Connections:

Weld connections according to AWS D1.1/D1.1M. Welds shall be made only by welders and welding operators who have been previously qualified by tests as prescribed in AWS D1.1 to perform type of work required.

HighStrength Bolts: Highstrength bolts tightened to a bolt tension minimum 70 percent of their minimum tensile strength. Tightening done with properly calibrated wrenches, by turnofnut method or by use of direct tension indicators (bolts or washers). Tighten bolts in connections identified as slipcritical using Direct Tension Indicators. Twistoff torque bolts are not an acceptable alternate fastener for slip critical connections.

FINISHES

Shop Priming:

Prime paint structural steel according to AISC 303, Section 6.

Interstitial Space Structural Steel: Prime paint, unless indicated to receive sprayed on fireproofing.

Shop Finish Painting: Apply primer and finish paint as specified in Section 09 91 00, PAINTING.

Do not paint:

Surfaces within (2 inches) of field welded joints.

Surfaces indicated to be encased in concrete.

Surfaces receiving sprayed on fireproofing.

Beam top flanges receiving shear connector studs applied.

Structural Steel Galvanizing: ASTM A123/A123M, hot dipped, after fabrication. Touchup after erection: Clean and wire brush any abraded and other spots worn through zinc coating, including threaded portions of bolts and welds and touchup with galvanizing repair paint.

Galvanize structural steel framing installed at exterior locations.

Bolts, Nuts, and Washers Galvanizing: ASTM F2329, hotdipped.

ACCESSORIES

General: Shop paint steel according to AISC 303, Section 6.

Finish Paint System: Primer and finish as specified in Section 09 91 00, PAINTING.

Galvanizing Repair Paint: MPI No. 18.

EXECUTION

ERECTION

Erect structural steel according to AISC 303 and AISC 360.

Set structural steel accurately at locations and elevations indicated on drawings.

Maintain erection tolerances of structural steel within AISC 303 requirements.

Pour Stop Elevation Tolerance: 1/4 inch, maximum, before concrete placement.

Weld and bolt connections as specified for shop connections.

FIELD PAINTING

After welding, clean, and prime weld areas to match adjacent finish.

Touchup primer damaged by construction operations.

Apply galvanizing repair paint to galvanized coatings damaged by construction operations.

Finish Painting: As specified in Section 09 91 00, PAINTING.

FIELD QUALITY CONTROL

Record Survey:

Measure and record structural steel framing plumbness, level, and alignment after completing bolting and welding and before installation of work supported by structural steel.

Identify deviations from allowable tolerances specified in AISC Manual.

- E N D - 05 12 00 - 8