36C25622R0094 233600 AIR TERMINAL UNITS .docx
DOCX document 29 KB Posted
- Attached to
- Z2DA--Project #502-19-107 - Replace AHU-104 - Construction - 36C25622R0094 Federal contract opportunity
- Solicitation number
- 502-19-107
About this file
This technical specification outlines requirements for replacing an air handling unit and associated ductwork at a Department of Veterans Affairs health care facility. The project involves replacing Air Handling Unit 104 and ductwork in Building 7 of the VA Health Care System in Alexandria, Louisiana. The specification provides requirements for new air terminal units, including box construction, acoustic performance, controls integration, and installation. It also defines requirements for heating coils and controls components to be furnished with the air terminal units. The related federal contract opportunity is a solicitation issued by the VA Veterans Integrated Service Network 16 to complete the replacement project outlined in the technical specification documentation.
View the file
Other files for this federal contract opportunity
Show all 50
Z2DA--Project #502-19-107 - Replace AHU-104 - Construction - 36C25622R0094 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REPLACE AHU #104 AND DUCTWORK BLDG. 7
DEPARTMENT OF VETERANS AFFAIRS HEALTH CARE SYSTEM-ALEXANDRIA, LA
PROJECT NO.: 502-19-107
SECTION 23 36 00
AIR TERMINAL UNITS
PART 1 GENERAL
1.1 DESCRIPTION
Air terminal units, air flow control valves.
1.2 RELATED WORK
| A. | Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. |
| B. | Section 23 05 11, COMMON WORK RESULTS FOR HVAC. |
| C. | Section 23 05 41, NOISE and VIBRATION CONTROL FOR HVAC PIPING and EQUIPMENT. |
| D. | Section 23 05 93, TESTING, ADJUSTING, and BALANCING FOR HVAC. |
| E. | Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC. |
| F. | Section 23 31 00, HVAC DUCTS and CASINGS. |
1.3 QUALITY ASSURANCE
Refer to Article, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK RESULTS FOR.
1.4 SUBMITTALS
| A. | Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. |
| B. | Manufacturer's Literature and Data: |
| 1. | Air Terminal Units: Submit test data. |
| 2. | Air flow control valves. |
| C. | Samples: Provide one typical air terminal unit for approval by the Resident Engineer. This unit will be returned to the Contractor after all similar units have been shipped and deemed acceptable at the job site. |
| D. | Certificates: |
| 1. | Compliance with Article, QUALITY ASSURANCE. |
| 2. | Compliance with specified standards. |
| E. | Operation and Maintenance Manuals: Submit in accordance with paragraph, INSTRUCTIONS, in Section 01 00 00, GENERAL REQUIREMENTS. |
1.5 APPLICABLE PUBLICATIONS
| A. | The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. |
| B. | Air Conditioning and Refrigeration Institute (AHRI)/(ARI): |
| 8802017 | Performance Rating of Air Terminals |
| C. | National Fire Protection Association (NFPA): |
| 90A-2018 | Standard for the Installation of Air Conditioning and Ventilating Systems |
| D. | Underwriters Laboratories, Inc. (UL): |
| 1812013 | Standard for Factory-Made Air Ducts and Air Connectors |
| E. | American Society for Testing and Materials (ASTM): |
| C 665-2006 | Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing |
1.6 GUARANTY
In accordance with the GENERAL CONDITIONS
PART 2 PRODUCTS
2.1 General
A. Coils:
1. Provide aluminum fins and copper coils for all hot water reheat coils.
| 2. | Water Heating Coils: |
| a. | ARI certified, continuous plate or spiral fin type, leak tested at 2070 kPa (300 PSI). |
| b. | Capacity: As indicated, based on scheduled entering water temperature. |
| c. | Headers: Copper or Brass. |
| d. | Fins: Aluminum, maximum 315 fins per meter (8 fins per inch). |
| e. | Tubes: Copper, arrange for counter-flow of heating water. |
| f. | Water Flow Rate: Minimum 0.032 Liters/second (0.5 GPM). |
| g. | Provide vent and drain connection at high and low point, respectively of each coil. |
| h. | Coils shall be guaranteed to drain. |
| B. | Labeling: Control box shall be clearly marked with an identification label that lists such information as nominal CFM, maximum and minimum factory-set airflow limits, coil type and coil connection orientation, where applicable. |
| C. | Factory calibrate air terminal units to air flow rate indicated. All settings including maximum and minimum air flow shall be field adjustable. |
| D. | Dampers with internal air volume control: See section 23 31 00 HVAC DUCTS and CASINGS. |
2.2 AIR TERMINAL UNITS (BOXES)
| A. | General: Factory built, pressure independent units, factory setfield adjustable air flow rate, suitable for single duct applications. Use of dual-duct air terminal units is not permitted. Clearly show on each unit the unit number and factory set air volumes corresponding to the contract drawings. Section 23 05 93, TESTING, ADJUSTING, and BALANCING FOR HVAC work assumes factory set air volumes. Coordinate flow controller sequence and damper operation details with the drawings and Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC. All air terminal units shall be brand new products of the same manufacturer. |
| B. | Capacity and Performance: The Maximum Capacity of a single terminal unit shall not exceed 566 Liters/second (1,200 CFM) with the exception of operating rooms and Cystoscopy rooms, which shall be served by a single air terminal unit at a maximum of 1,250 Liters/second (3,000 CFM). |
| C. | Sound Power Levels: |
| Acoustic performance of the air terminal units shall be based on the design noise levels for the spaces stipulated in Section 23 05 41 (Noise and Vibration Control for HVAC Piping and Equipment). Equipment schedule shall show the sound power levels in all octave bands. Terminal sound attenuators shall be provided, as required, to meet the intent of the design. | |
| D. | Casing: Unit casing shall be constructed of galvanized steel no lighter than 0.85 mm (22 Gauge). Air terminal units serving the operating rooms and Cystoscopy rooms shall be fabricated without lining. Provide hanger brackets for attachment of supports. |
| 1. | Lining material: Suitable to provide required acoustic performance, thermal insulation and prevent sweating. Meet the requirements of NFPA 90A and comply with UL 181 for erosion as well as ASTMC 665 antimicrobial requirements. Insulation shall consist of 13 mm (1/2 IN) thick non-porous foil faced rigid fiberglass insulation of 4-lb/cu.ft, secured by full length galvanized steel z-strips which enclose and seal all edges. Tape and adhesives shall not be used. Materials shall be non-friable and with surfaces, including all edges, fully encapsulated and faced with perforated metal or coated so that the air stream will not detach material. No lining material is permitted in the boxes serving operating rooms and Cystoscopy rooms. |
| 2. | Access panels (or doors): Provide panels large enough for inspection, adjustment, and maintenance without disconnecting ducts, and for cleaning heating coils attached to unit, even if there are no moving parts. Panels shall be insulated to same standards as the rest of the casing and shall be secured and gasketed airtight. It shall require no tool other than a screwdriver to remove. |
| 3. | Total leakage from casing: Not to exceed 2 percent of the nominal capacity of the unit when subjected to a static pressure of 750 Pa (3-inch WG), with all outlets sealed shut and inlets fully open. |
| 4. | Octopus connector: Factory installed, lined air distribution terminal. Provide where flexible duct connections are shown on the drawings connected directly to terminals. Provide butterfly-balancing damper, with locking means in connectors with more than one outlet. Octopus connectors and flexible connectors are not permitted in the Surgical Suite. |
| E. | Construct dampers and other internal devices of corrosion resisting materials which do not require lubrication or other periodic maintenance. |
| 1. | Damper Leakage: Not greater than 2 percent of maximum rated capacity, when closed against inlet static pressure of 1 kPa (4-inch WG). |
| F. | Provide multi-point velocity pressure sensors with external pressure taps. |
| 1. | Provide direct reading air flow rate table pasted to box. |
| G. | Provide static pressure tubes. |
| H. | Externally powered DDC variable air volume controller and damper actuator to be furnished under Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC for factory mounting on air terminal units. The DDC controller shall be electrically actuated. |
PART 3 EXECUTION
3.1 INSTALLATION
| A. | Work shall be installed as shown and according to the manufacturer’s diagrams and recommendations. |
| B. | Handle and install units in accordance with manufacturer's written instructions. |
| C. | Support units rigidly so they remain stationary at all times. Crossbracing or other means of stiffening shall be provided as necessary. Method of support shall be such that distortion and malfunction of units cannot occur. |
| D. | Locate air terminal units to provide a straight section of inlet duct for proper functioning of volume controls. See VA Standard Detail. |
3.2 OPERATIONAL TEST
Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
E N D
23 36 00 - 1