This document contains an AutoCAD drawing file and related federal contract solicitation notice. The AutoCAD file depicts condensate drain piping specifications, including drain lines, drain pans, plugs, pipe diameters, slope requirements, and notes on trap and pipe sizing.
The related solicitation is number 36C25622R0065 from the Department of Veterans Affairs for Project 667-18-121 to upgrade the surgery HVAC system and roof at the Overton Brooks VA Medical Center in Shreveport, Louisiana. The solicitation notice seeks bids to replace the surgery HVAC and complete roofing work. Offerors should review the full solicitation for detailed proposal submission instructions and requirements. The award date is not specified.
View the file
Other files for this federal contract opportunity
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AutoCAD SHX Text
DRAIN LINE
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
DRAIN PAN
AutoCAD SHX Text
SQUARE HEAD PLUG
AutoCAD SHX Text
PER FT.
AutoCAD SHX Text
2 PIPE DIAMETERS
AutoCAD SHX Text
DRAIN LINE TO BE
AutoCAD SHX Text
SLOPED 1/4" MIN.
AutoCAD SHX Text NOTES: 1. FILL TRAP MANUALLY ON INITIAL START-UP. FILL TRAP MANUALLY ON INITIAL START-UP. 2. TRAP EACH COMPONENT DRAIN CONNECTION. TRAP EACH COMPONENT DRAIN CONNECTION. 3. PIPE SIZE SHALL NOT BE LESS THAN DRAIN PAN PIPE SIZE SHALL NOT BE LESS THAN DRAIN PAN CONNECTION SIZE. 4. A=NEG. OR POS. S.P. ON THE DRAIN PAN + 2" A=NEG. OR POS. S.P. ON THE DRAIN PAN + 2" B=(2 X NEG. S.P.) + 4" FOR DRAW THRU UNITS. B=A +2" FOR BLOW THRU UNITS. 5. DETERMINE "A" AND "B" DIMENSIONS FOR THE DETERMINE "A" AND "B" DIMENSIONS FOR THE SUBMITTED UNIT BASED ON MANUFACTURER'S PRESSURE PROFILE.