CONDENSATE DRAIN PIPING.pdf

PDF 29 KB Posted

Attached to
Z1DA--667-18-121 Upgrade & Replace Surgery HVAC System & Roofing Federal contract opportunity
Solicitation number
36C25622R0065
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document contains an AutoCAD drawing file and related federal contract solicitation notice. The AutoCAD file depicts condensate drain piping specifications, including drain lines, drain pans, plugs, pipe diameters, slope requirements, and notes on trap and pipe sizing.

The related solicitation is number 36C25622R0065 from the Department of Veterans Affairs for Project 667-18-121 to upgrade the surgery HVAC system and roof at the Overton Brooks VA Medical Center in Shreveport, Louisiana. The solicitation notice seeks bids to replace the surgery HVAC and complete roofing work. Offerors should review the full solicitation for detailed proposal submission instructions and requirements. The award date is not specified.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--667-18-121 Upgrade & Replace Surgery HVAC System & Roofing, newest first.
File Type Posted
15 VA Shreveport Surgery Roof Asbestos Report.pdf PDF
Above 3rd Floor Surgery Ceiling 3.jpg JPG image
Above 3rd Floor Surgery Ceiling 1.jpg JPG image
Pre-Bid RFIs 667-18-121 Surgery HVAC Roofing.pdf PDF
Above 3rd Floor Surgery Ceiling 2.jpg JPG image
36C25622R0065 0002.pdf PDF
Site Visit Sign In Sheet 667-18-121 Upgrade Surgery HVAC Roofing.pdf PDF
S06 36C25622R0065 0001.pdf PDF
S02 OR HVAC and Roof - Drawings.pdf PDF
36C25622R0065 EXHIBIT C R1.docx DOCX document
36C25622R0065 EXHIBIT B R1.docx DOCX document
36C25622R0065 EXHIBIT F R1.docx DOCX document
36C25622R0065 EXHIBIT E R1.docx DOCX document
P09 OR Air Handlers Preliminary ICRA (002).pdf PDF
P09 OR HVAC and Roof - REVISED SOW.docx DOCX document
36C25622R0065 EXHIBIT A R1.docx DOCX document
36C25622R0065 VHA Supplemental Contract Requirements for Combatting COVID-19.docx DOCX document
S02 OR HVAC and Roof - Specifications.pdf PDF
P09 OR Air Handlers Preliminary Class III-IV Precautions (002).pdf PDF
P07 WD - LA20220031 Mod 2 dated 2-25-2022.txt TXT text file
36C25622R0065 Solicitation FINAL.pdf PDF
36C25622R0065 EXHIBIT D R1.docx DOCX document
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AutoCAD SHX Text

DRAIN LINE

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

DRAIN PAN

AutoCAD SHX Text

SQUARE HEAD PLUG

AutoCAD SHX Text

PER FT.

AutoCAD SHX Text

2 PIPE DIAMETERS

AutoCAD SHX Text

DRAIN LINE TO BE

AutoCAD SHX Text

SLOPED 1/4" MIN.

AutoCAD SHX Text NOTES: 1. FILL TRAP MANUALLY ON INITIAL START-UP. FILL TRAP MANUALLY ON INITIAL START-UP. 2. TRAP EACH COMPONENT DRAIN CONNECTION. TRAP EACH COMPONENT DRAIN CONNECTION. 3. PIPE SIZE SHALL NOT BE LESS THAN DRAIN PAN PIPE SIZE SHALL NOT BE LESS THAN DRAIN PAN CONNECTION SIZE. 4. A=NEG. OR POS. S.P. ON THE DRAIN PAN + 2" A=NEG. OR POS. S.P. ON THE DRAIN PAN + 2" B=(2 X NEG. S.P.) + 4" FOR DRAW THRU UNITS. B=A +2" FOR BLOW THRU UNITS. 5. DETERMINE "A" AND "B" DIMENSIONS FOR THE DETERMINE "A" AND "B" DIMENSIONS FOR THE SUBMITTED UNIT BASED ON MANUFACTURER'S PRESSURE PROFILE.

AutoCAD SHX Text 1"

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

CONDENSATE DRAIN PIPING

Sheets and Views
M501

File details come from the government source that posted it. Updated .