36C25622R0062 Part 8 DRWGS .pdf
PDF 5 MB Posted
- Solicitation number
- 36C25622R0062
About this file
This package includes drawings and specifications for a federal construction project to tuckpoint Building 1, the main hospital, at the Overton Brooks VA Medical Center in Shreveport, Louisiana. The solicitation is for Z1DA-667-19-101 and seeks masonry, concrete, and structural work. Drawings show the existing building layout and details, along with notes specifying materials and construction methods in accordance with industry standards. Relevant agencies are the Department of Veterans Affairs and Veterans Health Administration. Completion is required by the dates outlined in the solicitation package.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GR110
EXTERIOR PHOTO SHEETS
TDM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
OVERTON BROOKS VAMC
TUCKPOINT
SHREVEPORT, LOUISIANA
COR
ZAY/CMYRevisions: Date:
ARCHIE LANHAM
A/E:
O'Brien Engineering Inc.
2340 E. Trinity Mills Rd. Ste 220 Carrollton, TX 75006 972-233-2288 obrieneng.com
DATE: 03 SEPTEMBER 2021
FULLY SPRINKLERED
667-19-101 Architecture Yeates Mancil Architects, LLC 929 South Peters Street New Orleans, LA 70130 504-522-7218 www.yeatesarchitects.com
9/3/2021
(TYP.)
(TYP.)
PHOTO 1 PHOTO 2 PHOTO 3 PHOTO 4 PHOTO 5
A
Roof - Level 11
North Wing
B
Roof - Level 11 (Continued)
North Wing
C
Roof - Level 2
Northeast Addition
D
Roof - Level 4
West Wing Bump/O.R. Addition
(TYP.
ALL
EXISTING
BRICK &
LIMESTONE)
PHOTO 6
E
Roof - Level 11
Center Core
PHOTO 7 PHOTO 8
54 55
44 44
IMPORTANT NOTES:
1. LEGEND - REFER TO SHEET GR001 FOR THE KEYED PHOTO
SHEET KEYED NOTES THAT APPLY TO THE PHOTOGRAPHS
ON THIS SHEET.
2. THE INTENT OF THIS PHOTO SHEET IS TO PROVIDE A
GENERAL DOCUMENTATION OF BOTH TYPICAL AND SPECIFIC
EXISTING EXTERIOR CONDITIONS AND SCOPE OF WORK AT
THE EXISTING BUILDING. THE PHOTOS AND ITEMS NOTED DO
NOT CAPTURE OR DOCUMENT ALL EXISTING INSTANCES OR
LOCATIONS OF THE EXISTING CONDITIONS TO BE
CORRECTED AS PART OF THE PROJECT SCOPE OF WORK.
THE PHOTO SHEETS ALSO DETAIL SPECIFIC SCOPE OF WORK
AREAS AND CONDITIONS THAT ARE NOT EASILY INDICATED IN
THE EXTERIOR ELEVATION SHEETS.
3. REFER TO THE EXTERIOR ELEVATION SHEETS FOR EXACT
LOCATIONS AT THE BUILDING FACADE WHERE THESE
PHOTOGRAPHED AREAS ARE LOCATED.
4. IMPORTANT REQUIREMENT: ALL PHOTOS ON ALL PHOTO
SHEETS MUST BE PRINTED IN COLOR (NOT BLACK AND
WHITE OR GRAY TONES) FOR THE MAXIMUM CLARITY. THIS
COLOR PHOTO REQUIREMENT APPLIES TO ALL PHOTO
SHEETS ON BOTH FULL SIZE DRAWING SHEETS AND HALF
SIZE DRAWING SHEETS.
F
Nook Roof - Level 3
Center Core
PHOTO 9
EXIST. ROOF TO
BE PROTECTED
(NIC)
EXIST. ROOF TO
BE PROTECTED
(NIC)
EXIST. ROOF TO
BE PROTECTED
(NIC)
EXIST. ROOF TO
BE PROTECTED
(NIC)
EXIST. ROOF TO
BE PROTECTED
(NIC)
EXIST. ROOF TO
BE PROTECTED
(NIC)
EXIST. ROOF TO
BE PROTECTED
(NIC)
EXIST. ROOF TO
BE PROTECTED
(NIC)
G
Loading Dock Area - Level 2
North Wing
PHOTO 10
(TYP.
ALL
EXISTING
BRICK &
LIMESTONE)
(TYP.
ALL
EXISTING
BRICK &
LIMESTONE)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(SIM.)
STRUCTURAL NOTES
GENERAL CONCRETE EARTHWORK AND FOUNDATIONS
10.“MUSHROOMING”AT THE TOP OF THE PIERS IS PROHIBITED.
PIERESEARCH OR APPROVED EQUAL.
9. PROVIDE PIER BOLSTERS AND CENTERING DEVICES FOR PIER REINFORCEMENT BY
- THE QUALITY OF THE BELL
PENETRATION;
- THE COMPETENCE OF THE FAT CLAY FOR THE FULL SECTION OF THE DESIGN
- THAT GROUNDWATER SEEPAGE IS CORRECTLY HANDLED;
- THE REMOVAL OF ALL SMEAR ZONES AND CUTTINGS;
- THE MINIMUM PENETRATION;
- THE BEARING STRATUM;
ASSUMPTIONS AND TO VERIFY:
GEOTECHNICAL ENGINEER PRIOR TO CONCRETING TO ASSURE COMPLIANCE WITH DESIGN
COMMENCEMENT OF DRILLING. EACH PIER EXCAVATION SHALL BE INSPECTED BY THE
8. THE CONTRACTOR SHALL NOTIFY THE GEOTECHNICAL ENGINEER 24 HOURS PRIOR TO
DURING EXTRACTION.
THAT A SUFFICIENT HEAD OF PLASTIC CONCRETE IS MAINTAINED WITHIN THE CASING
REMOVED PRIOR TO BEGINNING THE DESIGN PENETRATION. CARE MUST THEN BE TAKEN
SEATED IN THE TOP OF THE BEARING STRATUM WITH ALL WATER AND LOOSE MATERIAL
CASING WILL BE ENCOUNTERED DURING EXCAVATION OF THE SHAFT. THE CASING SHALL BE
WATER. IT SHOULD BE ANTICIPATED THAT SEEPAGE REQUIRING THE USE OF TEMPORARY
7. EXCAVATIONS FOR THE SHAFTS SHALL CONTAIN NO MORE THAN 2 INCHES OF STANDING
FOR MORE THAN EIGHT HOURS.
AND TO REDUCE THE POSSIBILITY OF SEEPAGE PROBLEMS. NO SHAFT SHALL BE LEFT OPEN
THE DRILLING AND INSPECTION IN ORDER TO PREVENT DETERIORATION OF BEARING SURFACES
OPERATION AND CONCRETE PLACED AS SOON AS PRACTICAL AFTER COMPLETION OF
6. THE DESIGN PENETRATION OF INDIVIDUAL SHAFTS SHALL BE EXCAVATED IN A CONTINUOUS
TO SHAFTS PENETRATING INTO THE FAT CLAY.
AND A SKIN FRICTION VALUE OF 1,000 PSF PER FOOT. THESE VALUES ARE APPLICABLE
5. DRILLED PIERS ARE DESIGNED FOR AN ALLOWABLE END BEARING PRESSURE OF 6,750 PSF
- CONCRETE CUT-OFF ELEVATION: PLUS 1" TO MINUS 2"
- SHAFTS OUT OF PLUMB: NOT MORE THAN 1”FOR EVERY 10 FEET.
- MAXIMUM PERMISSIBLE VARIATION OF LOCATION: NOT MORE THAN 1".
CENTERLINE TOLERANCES:
PIER'S ACTUAL FINAL LOCATION. PIERS SHALL BE CONSTRUCTED WITHIN THE FOLLOWING
PIER TO LINES AND LEVELS REQUIRED BEFORE EXCAVATION, AND MEASUREMENTS OF EACH
LAYOUTS, AND MEASUREMENTS FOR PIER WORK. THIS INCLUDES LAYOUT WORK FOR EACH
4. THE CONTRACTOR SHALL ENGAGE A REGISTERED SURVEYOR TO PERFORM SURVEYS,
EXCAVATION OF ANY KIND.
3. LOCATE ALL UTILITIES AND UNDERGROUND SERVICES PRIOR TO PERFORMING
-CONSULTATION AS REQUIRED DURING CONSTRUCTION
-OBSERVATION AND TESTING DURING PIER DRILLING OPERATIONS
OBSERVATIONS SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING:
RECOMMENDATIONS OF THE AFOREMENTIONED GEOTECHNICAL REPORT. THESE TESTS AND
ALL EARTHWORKING OPERATIONS AND THE REQUIRED TESTING FOR IMPLEMENTING THE
2. A QUALIFIED GEOTECHNICAL ENGINEER SHALL BE RETAINED BY THE CONTRACTOR TO OBSERVE
GEOTECHNICAL REPORT. SHALL BE IN ACCORDANCE WITH THE
AFOREMENTIONED REPORT ARE PROVIDED BELOW FOR INFORMATION ONLY. ALL EARTHWORK
SERVICE INDUSTRIES (PSI PROJECT NO. 02751695) DATED JUNE 8, 2020. EXCERPTS FROM THE
1. FOUNDATION DESIGN IS IN ACCORDANCE WITH A GEOTECHNICAL REPORT BY PROFESSIONAL
TIME.
REQUIREMENT WITHOUT ANY INCREASE TO THE CONTRACT SUM OR CONTRACT
AND INTENDS TO EXECUTE THE MORE STRINGENT OR HIGHER QUALITY
OFFICER REPRESENTATIVE. ITSHALL BE DEEMED THAT THE CONTRACTOR BID
SHALL BE PROVIDED, UNLESS INSTRUCTED OTHERWISE BY THE CONTRACTING
SHOWN AND / OR THE HIGHEST QUALITY PRODUCT OR INSTALLATION METHOD
THE DRAWINGS AND SPECIFICATIONS, THE GREATER QUANTITY OF ITEMS
10. IF ANY INCONSISTENCIES OR DISCREPANCIES OCCUR WITHIN OR BETWEEN
THE STRUCTURES OR CAUSE DISTRESS IN THE STRUCTURES.
ANY CONDITION WHICH, IN HIS OPINION, MIGHT ENDANGER THE STABILITY OF
SHALL IMMEDIATELY NOTIFY THE CONTRACTING OFFICER REPRESENTATIVE OF
STRUCTURES DURING ALL PHASES OF CONSTRUCTION. THE CONTRACTOR
SHORING OF ALL STRUCTURAL WORK AS REQUIRED FOR STABILITY OF THE
9. THE CONTRACTOR SHALL PROVIDE TEMPORARY ERECTION BRACING AND
PERSONS DURING CONSTRUCTION.
PROVIDE ALL MEASURES NECESSARY TO PROTECT THE WORKERS AND OTHER
CONSTRUCTION UNLESS SO STATED OR NOTED. THE CONTRACTOR SHALL
FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHODS OF
8. THE STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE
OF QUANTITIES, LENGTHS, OR FIT OF MATERIALS.
7. THE STRUCTURAL DRAWINGS ARE NOT TO BE SCALED FOR DETERMINATION
BEFORE PROCEEDING WITH THE WORK.
THE ACTUAL CONDITIONS AND INFORMATION SHOWN ON THE DRAWINGS
CONTRACTING OFFICER REPRESENTATIVE OF ANY DISCREPANCIES BETWEEN
DIMENSIONS AND CONDITIONS AT THE SITE AND SHALL NOTIFY THE
6. THE CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL
OFFICER REPRESENTATIVE PRIOR TO COMPLETION OF THE SHOP DRAWINGS.
AND SECTIONS AND REPORT ANY DISCREPANCIES TO THE CONTRACTING
COMPARE THE STRUCTURAL PLANS AND SECTIONS WITH THE CIVIL PLANS
LOCATIONS AND DIMENSIONS OF ALL CIVIL DETAILS. THE CONTRACTOR SHALL
ELEVATIONS NOT SHOWN ON THE STRUCTURAL DRAWINGS AND FOR EXACT
5. THE CONTRACTOR SHALL REFER TO THE CIVIL DRAWINGS FOR
IT IS CLEARLY NOTED THAT SPECIFIC CHANGES ARE BEING SUGGESTED.
THAT ARE SUBMITTED FOR REVIEW DO NOT CONSTITUTE "IN-WRITING" UNLESS
CONTRACTING OFFICER REPRESENTATIVE FOR REVIEW. SHOP DRAWINGS
SHOWN ON THESE DRAWINGS SHALL BE SUBMITTED IN WRITING TO THE
MODIFICATION TO THE STRUCTURES OR ANY PART OF THE STRUCTURES
4. ANY DEVIATION FROM, ADDITION TO, SUBSTITUTION FOR, OR
REPRESENTATIVE.
UNTIL ALL SHOP DRAWINGS ARE APPROVED BY THE OWNER'S
AND CONSTRUCTION OF THE WORK. NO CONSTRUCTION IS PERMITTED
CONTRACTOR OF FULL RESPONSIBILITY FOR CORRECT FABRICATION
THIS REVIEW. REVIEW OF SHOP DRAWINGS DOES NOT RELIEVE THE
A PERIOD OF AT LEAST 10 WORKING DAYS SHALL BE PROVIDED FOR
SUBMITTED FOR REVIEW PRIOR TO COMMENCEMENT OF CONSTRUCTION.
3. COMPLETE SHOP DRAWINGS FOR THE STRUCTURAL WORK SHALL BE
7-10 "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES."
0.0. WIND LOADS ARE CALCULATED IN ACCORDANCE WITH ASCE
115 MPH (EXPOSURE C) WITH AN INTERNAL PRESSURE COEFFICIENT OF
ACCORDANCE WITH CODE PROVISIONS FOR A BASIC WIND SPEED OF
WIND PRESSURES IN ALL DIRECTIONS HAVE BEEN CALCULATED IN
WALL WIND LOADS
MATERIALS SHOWN ON THE STRUCTURAL DRAWINGS.
DEAD LOADS HAVE BEEN CALCULATED TO INCLUDE THE ACTUAL WEIGHT OF
DEAD LOADS
FOLLOWING:
2. LOADS THAT HAVE BEEN USED IN THE STRUCTURAL DESIGN INCLUDE THE
ACI 530.1/ASCE 6/TMS 602-13 - SPECIFICATION FOR MASONRY STRUCTURES
ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
THE 2018 INTERNATIONAL BUILDING CODE
AND THE FOLLOWING DESIGN CODES AND MATERIAL STANDARDS:
PROVISIONS OF THE UNITED STATES DEPARTMENT OF VETERANS AFFAIRS
1. THE STRUCTURAL DESIGN IS IN ACCORDANCE WITH APPLICABLE
THAN ONCE PER 5000 SF OF WALL OR SLAB SURFACE PLACED.
TAKEN NOT LESS THAN ONCE PER DAY, NOR LESS THAN ONCE PER 100 YD3 PLACED, NOR LESS
20. SAMPLES FOR STRENGTH TESTS OF EACH CLASS OF CONCRETE PLACED EACH DAY SHALL BE
CONCRETE DIMENSIONS SHOWN AND TO MAINTAIN CONCRETE CLEAR COVER REQUIREMENTS.
19. BENT BARS SHALL BE SHOP FABRICATED, UNO. BARS SHALL BE FABRICATED TO FIT WITHIN THE
NOTED OTHERWISE.
18. ALL BAR DETAILS SHOWN ON THESE DRAWINGS ARE DIMENSIONED TO THE C OF BARS UNLESS
AND IN ACCORDANCE WITH THE DESIGN DRAWINGS.
ACI 308 AND THE SPECIFICATIONS. CHAMFERS (3/4" ) SHALL BE PROVIDED AT ALL EXPOSED EDGES
17. EACH AREA OF CONCRETE WORK SHALL BE FINISHED AND MOIST-CURED IN ACCORDANCE WITH
PLACED UNTIL THESE ITEMS ARE CHECKED AND APPROVED BY THE TESTING LABORATORY.
EMBEDS ARE POSITIONED PRIOR TO EACH CONCRETE PLACEMENT. NO CONCRETE SHALL BE
16. THE TESTING LABORATORY SHALL BE NOTIFIED AFTER THE MILD STEEL REINFORCEMENT AND
EARTH AND 1 1/2 " OTHERWISE (UNLESS NOTED OTHERWISE ON THE DRAWINGS).
15. CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE 3" FOR CONCRETE CAST AGAINST
"RECOMMENDED PRACTICE FOR PLACING REINFORCING BARS".
14. MILD STEEL REINFORCEMENT SHALL BE PLACED AND SECURED IN ACCORDANCE WITH CRSI
13. CONCRETE SLUMPS SHALL BE 4" (MAX) FOR STRUCTURAL CONCRETE.
12. THE MAXIMUM NOMINAL SIZE OF COARSE AGGREGATE SHALL BE 1" FOR STRUCTURAL CONCRETE.
4000 PSI.
11. MIXES SHALL BE DESIGNED TO PROVIDE CONCRETE WITH A 28-DAY COMPRESSIVE STRENGTH OF
CHLORIDE ION CONTENT SHALL BE LIMITED TO 0.10% BY WEIGHT OF CEMENT.
10. NONPOTABLE WATER SHALL NOT BE USED IN MIXING CONCRETE. MAXIMUM WATER-SOLUBLE
FURNACE SLAG SHALL CONFORM TO ASTM C989. SILICA FUME SHALL COMPLY WITH ASTM C1240.
9. FLY-ASH AND POZZOLANS SHALL COMPLY WITH ASTM C618. GROUND GRANULATED BLAST-
8. CONCRETE SHALL BE AIR-ENTRAINED TO 6% (+/- 1.5%) IN ACCORDANCE WITH ASTM C260.
CHLORIDE IS PROHIBITED.
ACCORDANCE WITH THE MANUFACTURER'S DIRECTIONS AND ASTM C494. THE USE OF CALCIUM
7. ALL ADDITIVES FOR AIR ENTRAINMENT, WATER REDUCTION, AND SET CONTROL SHALL BE USED IN
SHALL BE PROHIBITED.
NORMAL WEIGHT AGGREGATES, UNLESS NOTED OTHERWISE. ALKALI-REACTIVE AGGREGATES
6. NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C 33. ALL CONCRETE SHALL USE
5. THE MAXIMUM WATER/CEMENT RATIO SHALL BE 0.5 FOR ALL CONCRETE.
4. PORTLAND CEMENT SHALL BE A SINGLE BRAND CONFORMING TO ASTM C 150, TYPE I OR II.
ACCORDANCE WITH ACI SP-66.
3. STEEL REINFORCEMENT AND ACCESSORIES SHALL BE DETAILED AND FABRICATED IN
2. MILD STEEL REINFORCING BARS SHALL CONFORM TO ASTM A 615, GRADE 60.
APPLY IN CASES OF CONFLICT.
AND SPECIFIC REFERENCED PORTIONS OF CODE. THE MOST RESTRICTIVE REQUIREMENT SHALL
SPECIFICATIONS FOR STRUCTURAL CONCRETE, THESE DRAWINGS, PROVIDED SPECIFICATIONS,
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE MOST RECENT EDITION OF ACI 301, ABBREVIATIONS
CLR.........................................................................CLEAR
OC..................................................................ON CENTER
MIN......................................................................MINIMUM
ACI............................AMERICAN CONCRETE INSTITUTE
STD..................................................................STANDARD
UNO..................................UNLESS NOTED OTHERWISE
C...................................................................CENTERLINEL
L
10. ALL REINFORCED MASONRY SHALL BE PLACED IN ACCORDANCE WITH CHAPTER 4 OF NCMA TR 75B.
REINFORCEMENT CONTINUOUSLY AT A MAXIMUM VERTICAL SPACING OF 16”O.C.
HEAVIER WIRE CONFORMING TO ASTM A 82. EXCEPT WHERE NOTED OTHERWISE, PLACE
9. HORIZONTAL JOINT REINFORCEMENT SHALL BE FACTORY-FABRICATED, TRUSS TYPE 9 GA. OR
CONTINUOUS THROUGH VERTICAL CONTROL JOINTS.
8. SPACING OF VERTICAL JOINTS SHALL NOT EXCEED 30’-0”. JOINT REINFORCING SHALL NOT BE
OR NOT.
SOLID. ANY CELLS AT OR BELOW FINISHED GRADE SHALL BE GROUTED SOLID, WHETHER REINFORCED
7. ALL CELLS CONTAINING REINFORCING BARS, BOLTS OR OTHER METAL ANCHORS SHALL BE GROUTED
DRAWINGS.
WALL OPENINGS, AT ALL CMU WALL CORNERS, AND WHERE INDICATED ON THE ARCHITECTURAL
6. PROVIDE ADDITIONAL VERTICAL REINFORCING BARS AT FIRST TWO CELLS ADJACENT TO ALL CMU
5. REINFORCING STEEL SHALL CONFORM TO ASTM A 615, GRADE 60.
AT 28 DAYS.
CONFORM TO ASTM C 404. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 2500 PSI
4. GROUT SHALL BE FINE GROUT CONFORMING TO ASTM C 476. AGGREGATES FOR GROUT SHALL
28 DAYS.
TO ASTM C 144. TYPE S MORTAR SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 1800 PSI AT
3. MORTAR SHALL CONFORM TO ASTM C 270, TYPE S. AGGREGATES FOR MORTAR SHALL CONFORM
MINIMUM NET AREA COMPRESSIVE STRENGTH OF 2000 PSI.
2. CONCRETE BLOCK SHALL BE NORMAL WEIGHT UNITS CONFORMING TO ASTM C 90, WITH A
MASONRY”.
WITH NCMA TR 75B, “SPECIFICATIONS FOR THE DESIGN AND CONSTRUCTION OF LOAD BEARING COMPRESSIVE STRENGTH (f’m) OF 1500 PSI THESE VALUES SHALL BE VERIFIED IN ACCORDANCE
1. REINFORCED CONCRETE MASONRY WALL CONSTRUCTION SHALL HAVE A MINIMUM 28 DAY
CONCRETE MASONRY
S-001
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUE FOR BIDOffice of Construction and Facilities Management of Veterans Affairs U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TUCKPOINT
OVERTON BROOKS VAMC
SHREVEPORT, LOUISIANA
COR
Revisions: Date:
ARCHIE LANHAM
A/E:
O'Brien Engineering Inc.
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
972-233-2288 obrieneng.com
FULLY SPRINKLERED
667-19-101
Structural
Pierce Engineering
132 N Main St.
Childress, TX 79201
940-937-8600 www.pierceengineering.net
SHEET TITLE
09/03/2021 BGP KBP
09/03/21
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUE FOR BIDOffice of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TUCKPOINT
OVERTON BROOKS VAMC
SHREVEPORT, LOUISIANA
COR
Revisions: Date:
ARCHIE LANHAM
A/E:
O'Brien Engineering Inc.
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
972-233-2288 obrieneng.com
FULLY SPRINKLERED
667-19-101
Structural
Pierce Engineering
132 N Main St.
Childress, TX 79201
940-937-8600 www.pierceengineering.net
09/03/2021 BGP KBP
09/03/21
10100 228.0 slab cor
10101 228.1 slab cor
10102 228.2 slab cor
10103 228.1 slab cor
10104 227.8 slab cor
10105 227.8 slab cor
10106 227.7 slab cor
10107 227.8 slab cor
10108 227.8 slab cor
10109 227.8 slab cor
10110 228.0 slab cor
10111 228.0 slab cor
10112 228.0 slab cor
10113 228.1 slab cor
10114 228.0 slab cor
10115 228.1 slab cor
10116 228.0 slab cor
10117 228.1 slab cor
10118 227.7 slab cor
10119 227.8 slab cor
10120 227.7 slab cor
10121 227.7 slab cor
10122 227.7 slab cor
10123 227.7 slab cor
10124 227.7 slab cor
10125 227.7 slab cor
10126 227.7 slab cor
10127 227.7 slab cor
10128 227.8 slab cor
10129 227.9 slab cor
10130 227.9 slab cor
10132 227.9 slab cor
10133 227.6 slab cor
10134 slab cor
10135 227.4 conc dra in
10136 227.5 conc dra in
10137 227.4 conc dra in
10138 227.3 conc dra in
10139 227.1 conc dra in
10140 227.1 conc dra in
10141 227.1 conc dra in
10142 227.4 conc dra in
10143 227.4 conc dra in
10144 227.4 conc dra in
10145 227.4 conc dra in
10146 227.4 conc dra in
10147 227.3 conc dra in
10148 227.4 conc dra in
10149 227.4 conc dra in
10150 227.7 equip rac k
10151 227.6 equip rac k
10152 227.6 conc
10153 227.5 conc
10154 227.5 conc
10155 227.7 conc
10156 227.5 conc
10157 227.5 conc
10158 227.5 conc
10159 227.5 conc
10160 227.5 conc
10161 227.5 conc
10162 227.5 conc
10164 227.5 conc
10166 227.3 conc 10167 227.4 conc
10168 227.4 conc
10169 227.4 conc
10170 227.5 conc
10171 227.5 conc
10172 227.4 conc
10173 227.6 conc
10174 227.4 conc
10228 227.0 conc
10229 227.1 conc
10230 227.5 conc
10231 227.5 conc
10232 227.5 conc
10233 227.5 conc
10234 227.5 conc
10235 227.5 conc 10236
227.5 conc
10237 227.6 conc
10238 227.5 conc
10239 227.4 conc
10240 227.7 conc
10241 227.6 conc
10242 227.6 conc
10243 227.4 conc
10244 227.6 conc
10245 227.5 conc
10246 227.5 conc
10247 227.6 conc
10248 227.6 conc 10249
227.5 conc
10250 227.6 conc
10251 227.6 conc
10252 227.5 conc
10253 227.6 conc
10254 227.5 conc
10255 227.6 conc
10260 227.2 conc
10429 228.4 bldg cor
10430 228.3 bldg cor
10431 228.9 bldg cor
10495 230.8 fenc e
10496 230.6 fenc e
10497 225.8 brick wall cor
10498 225.7 brick wall cor 10499
226.2 brick wall cor
10500 227.1 conc
10501 227.2 conc
10502 227.2 conc
10533 conc
10534 227.0 sidewalk
10546 227.2 sign
10556 227.0 grnd
10562 227.4 grnd
10563 227.0 grnd
10570 227.4 conc
10572 227.3 conc
10573 227.6 conc 10574
226.9 bldg corn er
PAD
HVAC
PAD
HVAC
PAD
HVAC
SIDEWALK
EDGE OF BUILDING
BUILDING
BUILDING
BACK OF CURB
BRICK WALL
B R
IC
K
W A
L L
C/L DRAINS
C/L DRAINS
C/L DRAINS
RACK
EQUIP
P A
D
PAD
227 227 227
PAD
HVAC
PAD
HVAC
S-100
SCREEN WALL PLAN
OF CONFLICT.
NOTIFY CONTRACTING OFFICER REPRESENTATIVE IN CASE
SUBSURFACE OBSTRUCTIONS PRIOR TO EXCAVATION.
4. LOCATE ALL UTILITIES, BURIED FOUNDATIONS, AND OTHER
CONSTRUCTION.
3. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
2. REFER GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.
GEOMETRICAL INFORMATION NOT SHOWN.
1. REFER CIVIL FOR LOCATIONS, ORIENTATION, AND OTHER
NOTES:
49'-2"
AT 16" OC, HORIZ
LADDER REINFORCING
CONTINUOUS 9 GAGE
WITH #5 AT 16" OC VERT,
6" CMU WALL REINFORCED
TYP
REFER 2/S-500,
BELLED PIER,
1 SCREEN WALL PLAN
S-100 1/2"=1'-0"
DETAIL, 3/S-500
REFER GRADE BEAM CORNER
S-500
S-500
3'-11"1'-4"8'-8"1'-4"8'-8"1'-4"8'-8"1'-4"8'-8"1'-4"3'-11"
T Y
P
DETAIL
TYPICAL PILASTER
REFER 2/S-100 FOR
OPENING, TYP
2-#5 VERT EACH SIDE OF EACH
CMU WALL OPENING, REFER A-120,
REFER A-120
FACE BRICK,
9"12'-3"11'-7"11'-7"12'-3"9"
/2
/4
/4
2 PILASTER SECTION
S-100 1"=1'-0"
1'-2"
6" CMU
8" CMU
EACH CELL WITH #5
GROUT AND REINFORCE
FACE BRICK
T Y
P
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUE FOR BIDOffice of
Construction and Facilities
Management of Veterans Affairs
U.S. Department
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TUCKPOINT
OVERTON BROOKS VAMC
SHREVEPORT, LOUISIANA
COR
Revisions: Date:
ARCHIE LANHAM
A/E:
O'Brien Engineering Inc.
2340 E. Trinity Mills Rd. Ste 220
Carrollton, TX 75006
972-233-2288 obrieneng.com
FULLY SPRINKLERED
667-19-101
Structural
Pierce Engineering
132 N Main St.
Childress, TX 79201
940-937-8600 www.pierceengineering.net
09/03/2021 BGP KBP
09/03/21
STRUCTURAL DETAILS
S-500
WITH #5 AT 16" OC
6-INCH CMU REINFORCED
L
A P
EW
WITH BRICK TIES AT 24" OC,
FACE BRICK, ATTACH
BRICK CAP
#5 AT 16" OC
2-#6, TOP AND BOTTOM
HILTI-RE 500 V3, EACH SIDE
#5 AT 24" OC, DRILL AND EPOXY WITH
TYP
6"
HOOK, TYP
STD ACI 90°
1 WALL SECTION
S-500 1"=1'-0"
2 PIER DETAIL
S-500 1"=1'-0"
3 GRADE BEAM CORNER
S-500 1"=1'-0"
TYP
3" CLR
30°
3'-0"
AT TOP AS SHOWN
#3 AT 10" OC, 2 EXTRA
4-#5
CLR
3"
EXTEND 1'-9" INTO GRADE BEAM
3'-2"
1'-6"
HOOK
STD ACI 90°
FACE OF GRADE BEAM
2-#6 TOP AND BOTTOM
#3 AT 12" OC
WITH 2-#4 CONTINUOUS
BOND BEAM REINFORCED
1'-6"
#3 AT 12" OC
HOOK, TYP
STD ACI 90°
| S-001 - STRUCTURAL NOTES |
| S-100 - SCREEN WALL PLAN |
| S-500 - STRUCTURAL DETAILS |
| GR-110 - EXTERIOR PHOTO SHEET (ROOF AREAS CONT) |