36C25622R0062 Part 7 DRWGS .pdf

PDF 13 MB Posted

Attached to
Z1DA--667-19-101 Tuckpoint Building 1, Main Hospital
Solicitation number
36C25622R0062
Issued by

About this file

This solicitation is for tuckpointing services at Building 1 of the Main Hospital at the Veterans Health Administration Veterans Integrated Service Network 16 facility. The Department of Veterans Affairs is seeking offers to tuckpoint the exterior walls of the building, which involves removing deteriorated mortar from the joints of concrete masonry and brick veneer, and replacing with new mortar. Bids are due by February 15, 2023, with work to be completed within 120 calendar days of the award date. Offerors must be licensed contractors and demonstrate experience performing tuckpointing on similar structures. The anticipated award value is between $100,000 and $250,000.

View the file

Other files

File Type Posted
Final RFI Register 667-19-101 05052022 v2.docx DOCX document
36C25622R0062 0003.docx DOCX document
36C25622R0062 SOW v2.docx DOCX document
Final RFI Register 667-19-101 05022022.docx DOCX document
36C25622R0062 0002.docx DOCX document
36C25622R0062 0001.docx DOCX document
Project 66719101 SV Sign in Sheet.pdf PDF
36C25622R0062 Part 1 DRWGS .pdf PDF
36C25622R0062 Part 4 DRWGS .pdf PDF
36C25622R0062 EXHIBIT A.docx DOCX document
36C25622R0062 Part 2 DRWGS .pdf PDF
36C25622R0062 Part 3 DRWGS .pdf PDF
36C25622R0062 SOW .docx DOCX document
36C25622R0062 COVID-19 Safety Protocols for Federal Contractors rev2 .docx DOCX document
36C25622R0062 EXHIBIT C.docx DOCX document
36C25622R0062 Part 6 DRWGS .pdf PDF
36C25622R0062 EXHIBIT E.docx DOCX document
36C25622R0062 CRA .pdf PDF
36C25622R0062 EXHIBIT B.docx DOCX document
36C25622R0062 EXHIBIT F.docx DOCX document
36C25622R0062 Part 8 DRWGS .pdf PDF
36C25622R0062 EXHIBIT D.docx DOCX document
36C25622R0062 ICRA .pdf PDF
36C25622R0062 Part 5 DRWGS .pdf PDF
36C25622R0062 RFP.docx DOCX document
36C25622R0062 Specifications.pdf PDF
36C25622R0062 WD LA20220031 Mod 2 02252022.docx DOCX document
36C25622R0062 ILSM .pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GR106

TDM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OVERTON BROOKS VAMC

TUCKPOINT

SHREVEPORT, LOUISIANA

COR

ZAY/CMYRevisions: Date:

ARCHIE LANHAM

A/E:

O'Brien Engineering Inc.

2340 E. Trinity Mills Rd. Ste 220 Carrollton, TX 75006 972-233-2288 obrieneng.com

DATE: 03 SEPTEMBER 2021

FULLY SPRINKLERED

667-19-101 Architecture Yeates Mancil Architects, LLC 929 South Peters Street New Orleans, LA 70130 504-522-7218 www.yeatesarchitects.com

9/3/2021

39 39

EXTERIOR PHOTO SHEETS

A

East Elevation

Northeast Addition

B

North Elevation

Northeast Addition

C

East Elevation

South Wing

PHOTO 7

PHOTO 8

PHOTO 1 PHOTO 2

PHOTO 6PHOTO 3 PHOTO 4 PHOTO 5

(TYP.

ALL

EXISTING

BRICK &

LIMESTONE)

IMPORTANT NOTES:

1. LEGEND - REFER TO SHEET GR001 FOR THE KEYED PHOTO

SHEET KEYED NOTES THAT APPLY TO THE PHOTOGRAPHS

ON THIS SHEET.

2. THE INTENT OF THIS PHOTO SHEET IS TO PROVIDE A

GENERAL DOCUMENTATION OF BOTH TYPICAL AND SPECIFIC

EXISTING EXTERIOR CONDITIONS AND SCOPE OF WORK AT

THE EXISTING BUILDING. THE PHOTOS AND ITEMS NOTED DO

NOT CAPTURE OR DOCUMENT ALL EXISTING INSTANCES OR

LOCATIONS OF THE EXISTING CONDITIONS TO BE

CORRECTED AS PART OF THE PROJECT SCOPE OF WORK.

THE PHOTO SHEETS ALSO DETAIL SPECIFIC SCOPE OF WORK

AREAS AND CONDITIONS THAT ARE NOT EASILY INDICATED IN

THE EXTERIOR ELEVATION SHEETS.

3. REFER TO THE EXTERIOR ELEVATION SHEETS FOR EXACT

LOCATIONS AT THE BUILDING FACADE WHERE THESE

PHOTOGRAPHED AREAS ARE LOCATED.

4. IMPORTANT REQUIREMENT: ALL PHOTOS ON ALL PHOTO

SHEETS MUST BE PRINTED IN COLOR (NOT BLACK AND

WHITE OR GRAY TONES) FOR THE MAXIMUM CLARITY. THIS

COLOR PHOTO REQUIREMENT APPLIES TO ALL PHOTO

SHEETS ON BOTH FULL SIZE DRAWING SHEETS AND HALF

SIZE DRAWING SHEETS.

D

South Elevation

Elevator Tower

PHOTO 9 PHOTO 11 PHOTO 12

E

East Elevation

Elevator Tower

PHOTO 10

GR107

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OVERTON BROOKS VAMC

TUCKPOINT

SHREVEPORT, LOUISIANA

COR

ZAY/CMYRevisions: Date:

ARCHIE LANHAM

A/E:

O'Brien Engineering Inc.

2340 E. Trinity Mills Rd. Ste 220 Carrollton, TX 75006 972-233-2288 obrieneng.com

DATE: 03 SEPTEMBER 2021

FULLY SPRINKLERED

667-19-101 Architecture Yeates Mancil Architects, LLC 929 South Peters Street New Orleans, LA 70130 504-522-7218 www.yeatesarchitects.com

9/3/2021

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

1 1

EXTERIOR PHOTO SHEETS

PHOTO 11 PHOTO 12

PHOTO 7 PHOTO 8 PHOTO 9

PHOTO 10

PHOTO 1 PHOTO 2

PHOTO 6

PHOTO 3 PHOTO 4

PHOTO 5

A

East Elevation

West Wing Bump

B

North Elevation

West Wing Bump

C

North Elevation (Continued)

West Wing Bump

D

West Elevation

West Wing Bump

(TYP.

ALL

EXISTING

BRICK &

LIMESTONE)

(TYP.

ALL

EXISTING

BRICK &

LIMESTONE)

IMPORTANT NOTES:

1. LEGEND - REFER TO SHEET GR001 FOR THE KEYED PHOTO

SHEET KEYED NOTES THAT APPLY TO THE PHOTOGRAPHS

ON THIS SHEET.

2. THE INTENT OF THIS PHOTO SHEET IS TO PROVIDE A

GENERAL DOCUMENTATION OF BOTH TYPICAL AND SPECIFIC

EXISTING EXTERIOR CONDITIONS AND SCOPE OF WORK AT

THE EXISTING BUILDING. THE PHOTOS AND ITEMS NOTED DO

NOT CAPTURE OR DOCUMENT ALL EXISTING INSTANCES OR

LOCATIONS OF THE EXISTING CONDITIONS TO BE

CORRECTED AS PART OF THE PROJECT SCOPE OF WORK.

THE PHOTO SHEETS ALSO DETAIL SPECIFIC SCOPE OF WORK

AREAS AND CONDITIONS THAT ARE NOT EASILY INDICATED IN

THE EXTERIOR ELEVATION SHEETS.

3. REFER TO THE EXTERIOR ELEVATION SHEETS FOR EXACT

LOCATIONS AT THE BUILDING FACADE WHERE THESE

PHOTOGRAPHED AREAS ARE LOCATED.

4. IMPORTANT REQUIREMENT: ALL PHOTOS ON ALL PHOTO

SHEETS MUST BE PRINTED IN COLOR (NOT BLACK AND

WHITE OR GRAY TONES) FOR THE MAXIMUM CLARITY. THIS

COLOR PHOTO REQUIREMENT APPLIES TO ALL PHOTO

SHEETS ON BOTH FULL SIZE DRAWING SHEETS AND HALF

SIZE DRAWING SHEETS.

GR108

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OVERTON BROOKS VAMC

TUCKPOINT

SHREVEPORT, LOUISIANA

COR

ZAY/CMYRevisions: Date:

ARCHIE LANHAM

A/E:

O'Brien Engineering Inc.

2340 E. Trinity Mills Rd. Ste 220 Carrollton, TX 75006 972-233-2288 obrieneng.com

DATE: 03 SEPTEMBER 2021

FULLY SPRINKLERED

667-19-101 Architecture Yeates Mancil Architects, LLC 929 South Peters Street New Orleans, LA 70130 504-522-7218 www.yeatesarchitects.com

9/3/2021

10 10

(TYP.)

8 21

(TYP.)

7 21

(TYP.)

EXTERIOR PHOTO SHEETS

34 34

A

North Elevation

West Wing

B

South Elevation

West Wing

C

West Elevation

West Wing

D

South Elevation

West Wing

E

West Elevation

West Wing - O.R. Addition

F

North Elevation

West Wing - O.R. Addition

G

North Elevation (Continued)

West Wing - O.R. Addition

H

South Elevation

West Wing - O.R. Addition (Northwest Stair)

I

East Elevation

West Wing - O.R. Addition (Roof)

PHOTO 15

PHOTO 16 PHOTO 17 PHOTO 18 PHOTO 19

PHOTO 11 PHOTO 12 PHOTO 13 PHOTO 14

PHOTO 7 PHOTO 8 PHOTO 9 PHOTO 10

PHOTO 1 PHOTO 2

PHOTO 6

PHOTO 3 PHOTO 4 PHOTO 5

(TYP.

ALL

EXISTING

BRICK &

LIMESTONE)

IMPORTANT NOTES:

1. LEGEND - REFER TO SHEET GR001 FOR THE KEYED PHOTO

SHEET KEYED NOTES THAT APPLY TO THE PHOTOGRAPHS

ON THIS SHEET.

2. THE INTENT OF THIS PHOTO SHEET IS TO PROVIDE A

GENERAL DOCUMENTATION OF BOTH TYPICAL AND SPECIFIC

EXISTING EXTERIOR CONDITIONS AND SCOPE OF WORK AT

THE EXISTING BUILDING. THE PHOTOS AND ITEMS NOTED DO

NOT CAPTURE OR DOCUMENT ALL EXISTING INSTANCES OR

LOCATIONS OF THE EXISTING CONDITIONS TO BE

CORRECTED AS PART OF THE PROJECT SCOPE OF WORK.

THE PHOTO SHEETS ALSO DETAIL SPECIFIC SCOPE OF WORK

AREAS AND CONDITIONS THAT ARE NOT EASILY INDICATED IN

THE EXTERIOR ELEVATION SHEETS.

3. REFER TO THE EXTERIOR ELEVATION SHEETS FOR EXACT

LOCATIONS AT THE BUILDING FACADE WHERE THESE

PHOTOGRAPHED AREAS ARE LOCATED.

4. IMPORTANT REQUIREMENT: ALL PHOTOS ON ALL PHOTO

SHEETS MUST BE PRINTED IN COLOR (NOT BLACK AND

WHITE OR GRAY TONES) FOR THE MAXIMUM CLARITY. THIS

COLOR PHOTO REQUIREMENT APPLIES TO ALL PHOTO

SHEETS ON BOTH FULL SIZE DRAWING SHEETS AND HALF

SIZE DRAWING SHEETS.

GR109

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

OVERTON BROOKS VAMC

TUCKPOINT

SHREVEPORT, LOUISIANA

COR

ZAY/CMYRevisions: Date:

ARCHIE LANHAM

A/E:

O'Brien Engineering Inc.

2340 E. Trinity Mills Rd. Ste 220 Carrollton, TX 75006 972-233-2288 obrieneng.com

DATE: 03 SEPTEMBER 2021

FULLY SPRINKLERED

667-19-101 Architecture Yeates Mancil Architects, LLC 929 South Peters Street New Orleans, LA 70130 504-522-7218 www.yeatesarchitects.com

9/3/2021

44 23

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

51 51

41 40

(TYP.)

(TYP.)

(TYP.)

(TYP.)

EXTERIOR PHOTO SHEETS

PHOTO 15

PHOTO 16 PHOTO 17 PHOTO 18 PHOTO 19

PHOTO 11 PHOTO 12 PHOTO 13 PHOTO 14

PHOTO 7 PHOTO 8 PHOTO 9 PHOTO 10

PHOTO 1 PHOTO 2

PHOTO 6

PHOTO 3 PHOTO 4 PHOTO 5

A

Roof - Level 11

Center Core

PHOTO 20

B

Roof - Level 11 (Continued)

Center Core

C

Roof - Level 11

North Wing (Former Cooling Tower)

D

Roof - Level 11 (Continued)

North Wing (Former Cooling Tower)

E

Roof - Level 11

East Wing

(TYP.

ALL

EXISTING

BRICK &

LIMESTONE)

(TYP.)

IMPORTANT NOTES:

1. LEGEND - REFER TO SHEET GR001 FOR THE KEYED PHOTO

SHEET KEYED NOTES THAT APPLY TO THE PHOTOGRAPHS

ON THIS SHEET.

2. THE INTENT OF THIS PHOTO SHEET IS TO PROVIDE A

GENERAL DOCUMENTATION OF BOTH TYPICAL AND SPECIFIC

EXISTING EXTERIOR CONDITIONS AND SCOPE OF WORK AT

THE EXISTING BUILDING. THE PHOTOS AND ITEMS NOTED DO

NOT CAPTURE OR DOCUMENT ALL EXISTING INSTANCES OR

LOCATIONS OF THE EXISTING CONDITIONS TO BE

CORRECTED AS PART OF THE PROJECT SCOPE OF WORK.

THE PHOTO SHEETS ALSO DETAIL SPECIFIC SCOPE OF WORK

AREAS AND CONDITIONS THAT ARE NOT EASILY INDICATED IN

THE EXTERIOR ELEVATION SHEETS.

3. REFER TO THE EXTERIOR ELEVATION SHEETS FOR EXACT

LOCATIONS AT THE BUILDING FACADE WHERE THESE

PHOTOGRAPHED AREAS ARE LOCATED.

4. IMPORTANT REQUIREMENT: ALL PHOTOS ON ALL PHOTO

SHEETS MUST BE PRINTED IN COLOR (NOT BLACK AND

WHITE OR GRAY TONES) FOR THE MAXIMUM CLARITY. THIS

COLOR PHOTO REQUIREMENT APPLIES TO ALL PHOTO

SHEETS ON BOTH FULL SIZE DRAWING SHEETS AND HALF

SIZE DRAWING SHEETS.

EXIST. ROOF TO

BE PROTECTED

(NIC)

EXIST. ROOF TO

BE PROTECTED

(NIC)

EXIST. ROOF TO

BE PROTECTED

(NIC)

EXIST. ROOF TO

BE PROTECTED

(NIC)

EXIST. ROOF TO

BE PROTECTED

(NIC)

EXIST. ROOF TO

BE PROTECTED

(NIC)

EXIST. ROOF TO

BE PROTECTED

(NIC)

EXIST. ROOF TO

BE PROTECTED

(NIC)

EXIST. ROOF TO

BE PROTECTED

(NIC)

S-001 - STRUCTURAL NOTES
S-100 - SCREEN WALL PLAN
GR-106 - EXTERIOR PHOTO SHEET (NORTHEAST ADDITION)
GR-107 - EXTERIOR PHOTO SHEET (WEST BUMP)
GR-108 - EXTERIOR PHOTO SHEET (WEST WING)
GR-109 - EXTERIOR PHOTO SHEET (ROOF AREAS)
GR-110 - EXTERIOR PHOTO SHEET (ROOF AREAS CONT)

File details come from the government source that posted it. Updated .