Drawing - Final - 657A5-21-105 VEG 21.08 Upgrade Campus Electrical Grid 1.pdf
PDF 2 MB Posted
- Attached to
- 657A5-26-111, Triennial Electrical Testing
- Solicitation number
- 36C25526R0186
About this file
This is a set of 100% construction documents for a federal construction project at Marion VA Medical Center in Marion, Illinois. The project, identified as VAMC Project #657A5-21-105, involves upgrading the campus electrical grid. The documents were prepared by Valhalla Engineering Corporation, LLC, an architect/engineer firm located in Englewood, Colorado, with an issue date of July 7, 2021, and a revision date of September 28, 2021.
The construction documents include electrical symbols, abbreviations, general notes, electrical partial site plans (both demolition and new work phases), electrical duct bank details, and 12.47kV electrical one-line diagrams for both demolition and new configurations. Key work includes removal of existing Feeder #1 medium voltage cable, installation of new XLPE cross-linked polyethylene 3-conductor, #2/0 15kV Feeder #1 cable with ground wire, and coordination with existing underground ductbanks and manholes throughout the facility. Construction activities are restricted to between 7:00 PM and 4:00 AM, and all work coordination must be performed with the VA Contracting Officer Representative. The project incorporates extensive use of existing conduits and ductbanks, with all necessary splices, terminations, and phasing considerations detailed in the specifications. Additional coordination is required with concurrent Project VA 657-502 for Building 42 laboratory expansion regarding medium voltage connections.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bld 7 1.pdf | ||
| EHRM One line 2114 - RECORD DWGS 1.pdf | ||
| one line 2019 1.pdf | ||
| 36C25526R0186 0001.pdf | ||
| Previous Results 1.pdf | ||
| 10-Electrical 42 lab 1.pdf | ||
| Sign in Sheet.pdf | ||
| Equipment Inventory Schedule WITH EE NUMBERS 1.xlsx | XLSX spreadsheet | |
| OR Bld 2 1.pdf | ||
| 36C25526R0186.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RENDERED IMAGEAREA OF WORK SHEET INDEX
MARION VA MEDICAL CENTER
MARION, IL
VAMC PROJECT #: 657A5-21-105
UPGRADE CAMPUS ELECTRICAL GRID DESIGN
VEG 21.08
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
657A5-21-105
MARION, ILLINOIS
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL
GRID
100% CONSTRUCTION DOCUMENT
100% CONSTRUCTION
DOCUMENT
7/7/2021 RA RW
GI001
N/A
COVER SHEET
9/28/2021
VEG 21.08
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
657A5-21-105
MARION, ILLINOIS
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL
GRID
100% CONSTRUCTION DOCUMENT
100% CONSTRUCTION
DOCUMENT
9/28/2021
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NS NO SCALE
NTS NOT TO SCALE
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
REQ REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
SCC SHORT CIRCUIT CAPACITY
SHT SHEET
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
UTIL UTILITY
V VOLT
VA VOLT·AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
XFMR TRANSFORMER
DS DISCONNECT SWITCH
DWG DRAWING
EXST EXISTING
G OR GND ELECTRICAL GROUND
IMC INTERMEDIATE METAL CONDUIT
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
MOCP MAXIMUM OVERCURRENT PROTECTION
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
3/C THREE-CONDUCTOR
3PH THREE PHASE
4/C FOUR-CONDUCTOR
4W FOUR WIRE
A/E ARCHITECT / ENGINEER
AC ALTERNATING CURRENT OR ARMORED
CABLE
CONDUIT
CKT CIRCUIT
CUR CURRENT
DEMO DEMOLITION
DIAG DIAGRAM
C
ELECTRICAL ABBREVIATIONS
A. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS
PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
B. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES.
KEY NOTE.1
NEW LINE TYPE.
EXISTING LINE TYPE.
DEMO LINE TYPE.
ELECTRICAL GENERAL NOTES - DEMOLITION: KEY NOTES:
NEW - EXISTING & DEMO LINE TYPES:
DEMO HATCH.
ELECTRICAL GENERAL NOTES:
A. SPECIFICATIONS TAKE PRECEDENT OVER DRAWINGS.
B. CORE DRILL AND SAW CUT, AS REQUIRED, FOR FLOOR AND WALL PENETRATIONS.
C. PROVIDE ALL ELECTRICAL WORK IN ACCORDANCE WITH DRAWINGS + SPECIFICATIONS.
D. COORDINATE ALL OUTAGES WITH VHA COR PER SPECS PRIOR TO WORK BEING DONE.
E. THE PROJECT WILL UTILIZE EXISTING CONDUIT AND PROVIDE ALL NECESSARY MEDIUM
VOLTAGE SPLICES AND TERMINATIONS. NEW CONDUIT ACROSS ROADWAY SHOWN ON
DRAWINGS.
F. PHASING SHALL ALSO BE CONSIDERED. SEE SPECIFICATION 01 00 00 1.6.G.
G. CONTRACTOR UNDER THIS CONTRACT SHALL PLAN TO REMOVE AND INSTALL NEW
MEDIUM VOLTAGE WIRE FOR FEEDER 1 INCLUDING ANY NEW WORK PERFORMED
UNDER ANOTHER CONTRACT. THE INTENT IS TO HAVE ALL NEW MEDIUM VOLTAGE
FEEDER WITH THE SAME WIRE UNDER THIS CONTRACT.
RA RW
E-001
NA
ELECTRICAL SYMBOLS,
ABBREVIATIONS & GENERAL NOTES
CO CONTRACTING OFFICER
COR CONTRACTING OFFICER REPRESENTATIVE
RMC RIGID METTALIC CONDUIT
MH # MANHOLE NUMBER
Z IMPEDANCE
BUILDINGBLDG
EMH EXISTING MANHOLE
NC NORMALLY CLOSE
NO NORMALLY OPEN
AUTOMATIC TRANSFER SWITCHATS
VFD
G
T
J
PB
P
HVS
LVS
ELECTRICAL SYMBOLS - DIAGRAM
DELTA CONNECTION.
TRANSFORMER.
WYE CONNECTION.
PULL BOX.
MANHOLE.
PRESSURE SWITCH-CLOSE ON
INCREASE.
PRESSURE SWITCH-OPEN ON
INCREASE.
SWITCH, MULTIPOSITION.
SWITCH, NORMALLY CLOSED FLOAT.
SWITCH, NORMALLY CLOSED FOOT OPERATED.
SWITCH, NORMALLY CLOSED LIMIT.
SWITCH, NORMALLY CLOSED TEMPERATURE
ACTIVATED.
SWITCH, NORMALLY CLOSED TIME DELAY.
SWITCH, NORMALLY OPEN FLOAT.
SWITCH, NORMALLY OPEN LIMIT.
SWITCH, NORMALLY OPEN TEMPERATURE
ACTIVATED.
SWITCH, NORMALLY OPEN TIME DELAY.
SWITCH, SINGLE BREAK.
NORMALLY CLOSED RELAY CONTACT.
NORMALLY OPEN RELAY CONTACT.
FUSE WITH RATING.
MOLDED CASE CIRCUIT BREAKER.
LOW-VOLTAGE DRAWOUT AIR CIRCUIT
BREAKER.
MEDIUM-VOLTAGE OIL CIRCUIT BREAKER.
MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT
BREAKER.
SWITCH AND FUSE UNIT.
FUSED DRAWOUT POTENTIAL TRANSFORMER.
RELAY; LETTER INDICATES RELAY TYPE.
50 = INSTANTANEOUS OVERCURRENT OR RATE-
OF-RISE.
51 = AC-TIME OVERCURRENT.
67 = AC-DIRECTIONAL OVERCURRENT.
86 = LOCK OUT.
DISCONNECT SWITCH, FUSED.
DISCONNECT SWITCH, UNFUSED, VAV.
FUSIBLE LINK.
STARTER, COMBINATION W/ DISCONNECT
SWITCH.
STARTER OR MOTOR CONTROLLER.
VARIABLE FREQUENCY DRIVE.
GENERATOR, POWER.
TRANSFORMER, PLAN.
EARTH GROUND.
JUNCTION BOX.
ELECTRICAL SYMBOLS - POWER PLAN
SIGNAL DUCT BANK.
POWER DUCT = P.
POWER MANHOLE.
HI VOLTAGE SWITCH ON CONCRETE PAD.
LOW VOLTAGE SWITCH ON CONCRETE PAD.
S
P
MH
VHA VETERAN HEALTH ADMINISTRATION
S SIGNAL MANHOLE.
REPRESENTS SPLICES IN MANHOLES.
PPP
P
P P
P
SP
P
PPPP
P
P
P
S P
PPP
P
PPP
PP
P
P P
P
P
P
P
P
P
S
S
S S
S
S S
S
S
S
S
S
S
P
P
P
P
P
P
P
P
P
PP
P
SS
S
SSS
S
S
S
P P
P S
S
S S
P
P
EMH#6MH#6AAMH#6BBMH#10
EMH#6B
SHOPS
WAREHOUSE
ENGINEERING/SAFETY
& SUPPLY
BOILER
PLANT
NURSING HOME
CARE UNIT
CLINICAL/OUTPATIENT
ADDITION
MAIN ADMIN. HOSP.
EDUCATIONAL
BUILDING
PA
VI
LL
IO
N
DENTAL/MEDICAL
VENDING/BUILDING
MANAGEMENT & SPD
BLDG #38
BLDG #8
BLDG #43
BLDG #13
BLDG #42
BLDG #1
BLDG #37
BLDG #2
BLDG #49
CHILLER
PLANT
BLDG #15
MH#2AA
EMH#2
EMH#4AA
EMH#4
VEG 21.08
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
657A5-21-105
MARION, ILLINOIS
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL
GRID
00KEYNOTES
GENERAL NOTES
100% CONSTRUCTION DOCUMENT
100% CONSTRUCTION
DOCUMENT
7/7/2021 RA RW
ED101
NA
ELECTRICAL PARTIAL SITE PLAN
DEMOLITION
SCALE: NO SCALE
ELECTRICAL PARTIAL SITE PLAN DEMOLITION
OUTDOOR WALK-IN 12.4KV SERVICE
ENTRANCE SWITCHGEAR
MH#1AA
EMH#1
EMH#2
MH#2AAEMH#3
MH#3AA
EMH#4
MH#4AA
EMH#5
MH#5AA
MH #X1
MH# X2MH# X3MH# X4
TO MH #4A
MH#4A
MH#4B
MH#4BB
MH#8
ELECTRICAL
TRANSFORMER ROOM
METAL
BUILDING
A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS AND GENERAL NOTES.
B. CONTRACTOR SHALL TAKE ALL THE NECESSARY PRECAUTIONS TO ENSURE
OTHER FEEDERS ARE NOT DAMAGED DURING THIS PROJECT.
C. ALL EXISTING MANHOLES AND DUCTBANKS SHALL BE REUSED.
D. ALL FEEDER#1 DUCTS SHALL BE CLEANED PER THE SPECIFICATIONS AFTER
REMOVAL OF DEMOED FEEDER.
E. REFER TO THE SPECIFICATIONS FOR PHASING REQUIREMENTS AND WHEN
WORK CAN BE PERFORMED IN THE MANHOLES.
F. CONTRACTOR SHALL BE ADVISED THAT MANHOLES ARE FILLED WITH
WATER UNDER NORMAL CONDITIONS. PROVIDE ALL NECESSARY PORTABLE
PUMPS, FUEL AND ACCESSORIES TO DRAIN MANHOLES AND EXECUTE
WORK.
G. REFER TO ONE LINE ON SHEET E-601 FOR MORE DETAILS ON THE ROUTING
AND REMOVAL OF FEEDER #1.
H. ALL WORK WILL HAVE TO BE DONE BETWEEN 7PM AND 4AM.
I. LABEL MANHOLES WITH FEEDER NUMBERS.
1. EXISTING, EMPTY MANHOLE.
2. EXISTING UNDERGROUND DUCT BANK WITH 4 (4") EMPTY CONDUITS.
3. CUT CONCRETE ROAD AND INSERT 4 (4") FROM MH #X4 TO MH#3AA. REFER
TO ELECTRICAL DETAILS ON E-501.
4. THIS SECTION OF MEDIUM VOLTAGE CABLE REPLACED BY OTHERS.
COORDINATE WITH PROJECT VA 657-502 "EXPAND & UPGRADE BUILDING 42
FOR LABORATORY" TO MAKE MEDIUM VOLTAGE CONNECTIONS.
PPP
P
P P
P
SP
P
PPPP
P
P
P
S P
PPP
P
PPP
PP
P
P P
P
P
P
P
P
P
S
S
S S
S
S S
S
S
S
S
S
S
P
P
P
P
P
P
P
P
P
PP
P
SS
S
SSS
S
S
S
P P
P S
S
S S
P
EMH#6MH#6AAMH#6BBMH#10
EMH#6B
SHOPS
WAREHOUSE
ENGINEERING/SAFETY
& SUPPLY
BOILER
PLANT
NURSING HOME
CARE UNIT
CLINICAL/OUTPATIENT
ADDITION
MAIN ADMIN. HOSP.
EDUCATIONAL
BUILDING
PA
VI
LL
IO
N
DENTAL/MEDICAL
VENDING/BUILDING
MANAGEMENT & SPD
BLDG #38
BLDG #8
BLDG #43
BLDG #13
BLDG #42
BLDG #1
BLDG #37
BLDG #2
BLDG #49
CHILLER
PLANT
BLDG #15
MH#2AA
EMH#2
EMH#4AA
EMH#4
VEG 21.08
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
657A5-21-105
MARION, ILLINOIS
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL
GRID
00KEYNOTES
GENERAL NOTES
100% CONSTRUCTION DOCUMENT
100% CONSTRUCTION
DOCUMENT
7/7/2021 RA RW
ES101
NA
ELECTRICAL PARTIAL SITE PLAN
NEW
SCALE: NO SCALE
ELECTRICAL PARTIAL SITE PLAN NEW
OUTDOOR WALK-IN 12.4KV SERVICE
ENTRANCE SWITCHGEAR
MH#1AA
EMH#1
EMH#2
MH#2AAEMH#3
MH#3AA
EMH#4
MH#4AA
EMH#5
MH#5AA
MH #X1
MH #X2MH #X3MH #X4
TO MH #4A
MH#4A
MH#4B
MH#4BB
MH#8
ELECTRICAL
TRANSFORMER ROOM
METAL
BUILDING
A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS AND GENERAL NOTES.
B. CONTRACTOR SHALL TAKE ALL THE NECESSARY PRECAUTIONS TO ENSURE
OTHER FEEDERS ARE NOT DAMAGED DURING THIS PROJECT.
C. ALL EXISTING MANHOLES AND DUCTBANKS SHALL BE REUSED.
D. ALL FEEDER#1 DUCTS SHALL BE CLEANED PER THE SPECIFICATIONS AFTER
REMOVAL OF DEMOED FEEDER.
E. REFER TO THE SPECIFICATIONS FOR PHASING REQUIREMENTS AND WHEN
WORK CAN BE PERFORMED IN THE MANHOLES.
F. CONTRACTOR SHALL BE ADVISED THAT MOST IF NOT ALL OF THE
MANHOLES ARE FILLED WITH WATER UNDER NORMAL CONDITIONS.
PROVIDE ALL NECESSARY PORTABLE PUMPS, FUEL AND ACCESSORIES TO
DRAIN MANHOLES AND EXECUTE WORK.
G. REFER TO ONE LINE ON SHEET E-602 FOR MORE DETAILS ON THE ROUTING
OF FEEDER #1.
H. ALL WORK WILL HAVE TO BE DONE BETWEEN 7PM AND 4AM.
I. LABEL MANHOLES WITH FEEDER NUMBERS
1. EXISTING, EMPTY MANHOLE.
2. EXISTING UNDERGROUND DUCT BANK WITH 4 (4") EMPTY CONDUITS.
3. CUT CONCRETE ROAD AND INSERT 4 (4") FROM MH #X4 TO MH#3AA. REFER
TO ELECTRICAL DETAILS ON E-501.
4. THIS SECTION OF MEDIUM VOLTAGE CABLE REPLACED BY OTHERS.
COORDINATE WITH PROJECT VA 657-502 "EXPAND & UPGRADE BUILDING 42
FOR LABORATORY" TO MAKE MEDIUM VOLTAGE CONNECTIONS.
5. PROVIDE MEDIUM VOLTAGE FEEDERS. REFER TO SINGLE LINE DIAGRAM FOR
FEEDER SIZES.
GENERAL NOTES:
1.
2.
3.
4.
5.
CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS
WHEN CROSSING OR PLACED IN ROADWAYS.
MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (30") OR
AS OTHERWISE SPECIFIED IN SECTION 26 05 41.
PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND
TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.
INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.
3" mm
3" mm (3 mm
(3")
(3") 76mm
(3") 76mm76mm
INNERDUCT,
SEE NOTE 5
PLASTIC
SPACER
DUCT
4 WAY DUCT LINE
2" [50mm] MINIMUM OR THICKNESS OF EXISTING PAVEMENT
WHICHEVER IS GREATER.
SEE GENERAL NOTES FOR THIS DETAIL
PROVIDE LOAD TRANSFER DOWELS.
4'-0" MAX.
1'-0" MAX.
[305mm]
1'-0" MAX.
[305mm]
TRENCH
BACKFILL
CLASS S CONCRETE
f'c=3000 PSI [20.7 MPa]
CONCRETE
SAW CUT EXISTING.
CONCRETE FULL DEPTH
BOTH SIDES
CONCRETE ROAD
EXISTING
VA
RI
EST/
T
EXISTING
CONCRETE
PAVEMENT (TYP)
1'-0" MAX.
[305mm]
1'-0" MAX.
[305mm]
1'-0" MAX.
[305mm]
1'-0" MAX.
[305mm]
6" -1
4" [15
0-
5m m]
LOAD TRANSFER DOWELS.
VEG 21.08
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
657A5-21-105
MARION, ILLINOIS
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL
GRID
100% CONSTRUCTION DOCUMENT
100% CONSTRUCTION
DOCUMENT
7/7/2021
SCALE: NO SCALE
ELECTRICAL DUCT BANK DETAILS
RA RW
E-501
NA
ELECTRICAL DUCT BANK DETAILS
SCALE: NO SCALE
TYPE 3 UTILITY TRENCH PATCH
1. MATERIAL AND COMPACTION REQUIREMENTS FOR PIPE BEDDING/SHADING
SHALL BE IN ACCORDANCE WITH THE SPECIFICATIONS FOR THE
APPLICABLE UTILITY PIPE.
2. TRENCH BACKFILL SHALL COMMENCE 1 FOOT [305mm] ABOVE THE TOP OF
DUCTBANK AND SHALL BE PER SECTION 31 20 11.
3. BACKFILL COMPACTION REQUIREMENTS SHALL BE PER SECTION 312011.
4. THE 1 FOOT [305mm] TRENCH "SHOULDER" AREAS SHALL BE DELETED FOR
TYPE 2 TRENCHES.
5. PORTLAND CEMENT CONCRETE SHALL BE IN ACCORDANCE WITH THE
REQUIREMENTS OF SECTION 03 30 53.
6. LOAD TRANSFER DOWELS FOR JOINTS TRANSVERSE TO THE ROADWAY
CENTERLINE SHALL BE SMOOTH STEEL DOWELS . DOWELS SHALL BE SIZED
AND SPACED AS FOLLOWS:
PCCP THICKNESS DOWEL SIZE DOWEL LENGTH
DOWEL SPACING
6" [150mm] #5 [No. 16] 12" [305mm] 18"
[455mm] 7" [180mm] #6 [No. 19] 15" [380mm] 15"
[380mm] 8" [180mm] #8 [No. 19] 15" [380mm] 12"
[305mm] 10" [180mm] #10 [No. 19] 15" [380mm] 12"
[305mm]
7. DEFORMED TIE BARS SHALL BE USED IN TRENCH PATCHES LONGITUDINAL
TO THE ROADWAY CENTERLINE WHEN THE TRENCH LENGTH IS GREATER
THAN 50 FEET [15240mm]. TIE BARS SHALL BE 24 INCHES [610mm] LONG.
DEFORMED #4 [No. 13] BARS FOR PCCP LESS THAN 8 INCHES [205mm] THICK AND #5 [No. 16] BARS IF 8 INCHES [205mm] THICK OR MORE. TIE BARS SHALL BE PLACED 30 INCHES [760mm] CENTER-TO-CENTER.
8. HOLES SHALL BE DRILLED 1 FOOT [305mm] INTO THE EXISTING SLAB FOR TIE BARS AND 7 INCHES [180mm] FOR DOWELS. HOLES SHALL BE OF A
DIAMETER SUFFICIENT TO ACCOMMODATE THE TIE BAR ANCHORAGE OR
DOWEL CAP. TIE BARS SHALL BE ANCHORED WITH AN APPROVED HIGH
VISCOSITY EPOXY.
9. IF THE CONCRETE SLAB REMAINING NEXT TO A LONGITUDINAL OR
TRANSVERSE JOINT IS LESS THAN 6 FEET [1829mm] AT ITS NARROWEST
WIDTH, REMOVE AND REPLACE THE EXISTING CONCRETE TO THE JOINT.
GENERAL NOTES:
BLDG #8
BLDG #38
MH#6B
400A
BLDG #13
MDP
MH#9
N.C.N.O.
75ATS
ATS #1
BRANCH
CRITICAL
210ATS
BRANCH
SAFETY
ATS #2
LIFE
300ATS
"P1E"PANEL
300ATS
PANEL"DP1"
BLDG #43
600AF
600AS
BLDG #15
125A
MTS
TO BUILDING #16
400AS
300AF
400AF
400AS
BLDG #14
TRAILERTO
MTS
125AF
200AS
CATERPILLER90KW, 120/208V
800ATS
MAIN
PANEL
CHILLER BLDG #49
CS-3
100E
MH#10MH#6BBMH#6AA
EMH#6EMH#5
MH#5AA
MH#4A
BLDG #42
FEEDER #3
UNIT SUB B UNIT SUB A
MH#4B
MH#4AAMH#2AA
EMH#3
MH#3AA
EMH#2
MH#4BB
PANEL
CHILLER
EMH#1
FEEDER #3
FEEDER #2
FEEDER #2
FEEDER #3
200/5A 1200A
200/5A 1200A
1200A200/5A
1200A
1500KVA 12.47 KV,
DELTA 480Y/277V
4.5±7%Z OA 65°C
2000AF/2000ATS2000AF/2000ATS
BLDG #38
DRY-TYPE PRIMARY SELECTOR
SWITCH, FUSED LOAD INTERRUPTER
SWITCH AND TRANSFORMER
1500/2000 KVA, 12.47 KV,
DELTA 480/277V WYE AA
150°C 5.75%Z
1500/2000 KVA, 12.47 KV,
DELTA 480/277V WYE AA 150°C
GE 225 KVA 12.47 KV,
DELTA 208/120V
5.53% Z
OA OIL COOLED 65°C
R.T.F. 225KVA 12.47 KV,
DELTA 208/120V 4.2% Z OA
OIL COOLED 65°
600AS
600AF
CATERPILLER
60KW, 208/120V
1500 KVA
12.47 KV,
DELTA
480Y/277V
4.5±7%Z OA
65°C
300 KVA
12.47 KV,
DELTA
208Y/120V
4.5±7%Z OA
65°C
CS-3
100E
CS-3
25E
GE "MT-5" 112.5 KVA
12.47 KV, DELTA
208/120V 2.43% Z OA
65°C
600AS
600AF
SUBSTATION.
DRY-TYPE PRIMARY SELECTOR
SWITCH, FUSED LOAD INTERRUPTER
SWITCH AND TRANSFORMER
BLDG #38
ATS
600AS
600AS
PULL BOX
3 200/5
SPARE
1200A
20A, 1 POLE, 2#10, 1#10 GRD. IN 3/4"C.
EMERGENCY CIRCUIT FROM PANEL "P" IN BLDG. 15.
NEUTRAL BOND WILL BE IN
SWITCHGEAR
NEUTRAL BOND WILL BE IN
SWITCHGEAR
3200/5A
200/5
200/5
200/5
120/240V PANELBOARD
TO BREAKER OPERATING
POWER
AUXILIARY
CONTROL POWER
SUBSTATION.
12.4KV, 3Ø, 3W OUTDOOR WALK-IN METAL
CLAD SWITCHGEAR
FEEDER #2
FEEDER #2
FEEDER #2
EMH#4
FEEDER #2
FEEDER #3 FEEDER #3
FEEDER #2
FEEDER #2
FEEDER #3
FEEDER #3
FEEDER #3
TYPICAL
FEEDER #3
TYPICAL EXISTING SPLICE TO
REMAIN UNDISTURBED, UNLESS
OTHERWISE NOTED.
CPT
12.47KV/7200
B-13
GE 150 KVA 12.47 KV,
DELTA 208/120V
5.6% Z
AA OIL COOLED 65°C
MH#1AA
VEG 21.08
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
657A5-21-105
MARION, ILLINOIS
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL
GRID
GENERAL NOTES
100% CONSTRUCTION DOCUMENT
100% CONSTRUCTION
DOCUMENT
7/7/2021 RA RW
E-601
NA
12.47kV ELECTRICAL ONE-LINE
DEMOLITION
SCALE: NO SCALE
12.47KV ELECTRICAL ONE LINE DEMOLITION
1. DEMO FEEDER #1 CABLE INCLUDING GROUND WIRE.
2. EXISTING MANHOLES, FOR REFERENCE ONLY.
3. THIS SECTION OF MEDIUM VOLTAGE CABLE REPLACED BY OTHERS.
COORDINATE WITH PROJECT VA 657-502 "EXPAND & UPGRADE BUILDING 42
FOR LABORATORY" TO MAKE MEDIUM VOLTAGE CONNECTIONS.
A. ALL WORK SHOWN IS EXISTING UNLESS NOTED OTHERWISE.
B. ALL WORK SHALL BE DONE BETWEEN 7PM AND 4AM.
2 2
00KEYNOTES
BLDG #8
BLDG #38
MH#6B
400A
BLDG #13
MDP
MH#9
N.C.N.O.
75ATS
ATS #1
BRANCH
CRITICAL
210ATS
ATS #2
300ATS
"P1E"PANEL
300ATS
PANEL"DP1"
BLDG #43
600AF
600AS
BLDG #15
125A
MTS
TO BUILDING #16
400AS
300AF
400AF
400AS
BLDG #14
TRAILERTO
MTS
125AF
200AS
CATERPILLER90KW, 120/208V
800ATS
CHILLER BLDG #49
CS-3
100E
MH#10MH#6BBMH#6AA
EMH#6EMH#5
MH#5AA
BLDG #42
FEEDER #3
UNIT SUB B UNIT SUB A
MH#4AAMH#2AA
EMH#3
MH#3AA
EMH#2
MH#4BB
PANEL
CHILLER
EMH#1
FEEDER #3
FEEDER #2
FEEDER #2
200/5A 1200A
200/5A 1200A
1200A200/5A
1200A
1500KVA 12.47 KV,
DELTA 480Y/277V
4.5±7%Z OA 65°C
2000AF/2000ATS2000AF/2000ATS
BLDG #38
DRY-TYPE PRIMARY SELECTOR
SWITCH, FUSED LOAD INTERRUPTER
SWITCH AND TRANSFORMER
1500/2000 KVA, 12.47 KV,
DELTA 480/277V WYE AA
150°C 5.75%Z
1500/2000 KVA, 12.47 KV,
DELTA 480/277V WYE AA 150°C
GE 225 KVA 12.47 KV,
DELTA 208/120V
5.53% Z
OA OIL COOLED 65°C
R.T.F. 225KVA 12.47 KV,
DELTA 208/120V 4.2% Z OA
OIL COOLED 65°
600AS
600AF
CATERPILLER
60KW, 208/120V
1500 KVA
12.47 KV,
DELTA
480Y/277V
4.5±7%Z OA
65°C
300 KVA
12.47 KV,
DELTA
208Y/120V
4.5±7%Z OA
65°C
CS-3
100E
CS-3
25E
GE "MT-5" 112.5 KVA
12.47 KV, DELTA
208/120V 2.43% Z OA
65°C
600AS
600AF
SUBSTATION.
DRY-TYPE PRIMARY SELECTOR
SWITCH, FUSED LOAD INTERRUPTER
SWITCH AND TRANSFORMER
BLDG #38
ATS
600AS
600AS
PULL BOX
3 200/5
SPARE
1200A
20A, 1 POLE, 2#10, 1#10 GRD. IN 3/4"C.
EMERGENCY CIRCUIT FROM PANEL "P" IN BLDG. 15.
NEUTRAL BOND WILL BE IN
SWITCHGEAR
NEUTRAL BOND WILL BE IN
SWITCHGEAR
3200/5A
200/5
200/5
200/5
120/240V PANELBOARD
TO BREAKER OPERATING
POWER
AUXILIARY
CONTROL POWER
SUBSTATION.
12.4KV, 3Ø, 3W OUTDOOR WALK-IN METAL
CLAD SWITCHGEAR
FEEDER #2
FEEDER #2
FEEDER #2
EMH#4
FEEDER #2
FEEDER #3 FEEDER #3
FEEDER #2
FEEDER #2
FEEDER #3
FEEDER #3
FEEDER #3
TYPICAL
FEEDER #3
TYPICAL EXISTING SPLICE TO
REMAIN UNDISTURBED, UNLESS
OTHERWISE NOTED.
CPT
12.47KV/7200
FEEDER #1
FEEDER #1
FEEDER #1
B-13
FEEDER #1
FEEDER #1
FEEDER #1
FEEDER #1
FEEDER #1
GE 150 KVA 12.47 KV,
DELTA 208/120V
5.6% Z
AA OIL COOLED 65°C
MH #X1
MH#1AA
FEEDER #1
FEEDER #1
FEEDER #1
FEEDER #1
MH#4B
MH#4A
MH #X2 MH #X3 MH #X4
MAIN
PANEL
FEEDER #1
FEEDER #1
VEG 21.08
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
Project Director
Issued: Date:
750 W HAMPDEN AVE
SUITE #300
ENGLEWOOD CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
657A5-21-105
MARION, ILLINOIS
CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL
GRID
GENERAL NOTES
100% CONSTRUCTION DOCUMENT
100% CONSTRUCTION
DOCUMENT
7/7/2021 RA RW
E-602
NA
12.47KV ELECTRICAL ONE-LINE
DIAGRAM NEW
SCALE: NO SCALE
12.47KV ELECTRICAL ONE LINE NEW
1. PROVIDE NEW XLPE (CROSS-LINKED POLYETHYLENE) 3-1/C, 2#0 15KV FEEDER
#1 CABLE AND GROUND WIRE.
2. NEW EXISTING MANHOLE
3. THIS SECTION OF MEDIUM VOLTAGE CABLE REPLACED BY OTHERS.
COORDINATE WITH PROJECT VA 657-502 "EXPAND & UPGRADE BUILDING 42
FOR LABORATORY" TO MAKE MEDIUM VOLTAGE CONNECTIONS.1
A. ALL WORK SHOWN IS EXISTING UNLESS NOTED OTHERWISE.
B. ALL WORK WILL HAVE TO BE DONE BETWEEN 7PM AND 4AM.
2 2 2 2
B00KEYNOTES
1 1 1
| Sheets and Views |
| GI001 |
| E-001 |
| ED101 |
| ES101 |
| E-501 |
| E-601 |
| E-602 |