This is a set of 100% construction documents for a federal construction project at Marion VA Medical Center in Marion, Illinois. The project, identified as VAMC Project #657A5-21-105, involves upgrading the campus electrical grid. The documents were prepared by Valhalla Engineering Corporation, LLC, an architect/engineer firm located in Englewood, Colorado, with an issue date of July 7, 2021, and a revision date of September 28, 2021.

The construction documents include electrical symbols, abbreviations, general notes, electrical partial site plans (both demolition and new work phases), electrical duct bank details, and 12.47kV electrical one-line diagrams for both demolition and new configurations. Key work includes removal of existing Feeder #1 medium voltage cable, installation of new XLPE cross-linked polyethylene 3-conductor, #2/0 15kV Feeder #1 cable with ground wire, and coordination with existing underground ductbanks and manholes throughout the facility. Construction activities are restricted to between 7:00 PM and 4:00 AM, and all work coordination must be performed with the VA Contracting Officer Representative. The project incorporates extensive use of existing conduits and ductbanks, with all necessary splices, terminations, and phasing considerations detailed in the specifications. Additional coordination is required with concurrent Project VA 657-502 for Building 42 laboratory expansion regarding medium voltage connections.

View the file

Other files

File Type Posted
Bld 7 1.pdf PDF
EHRM One line 2114 - RECORD DWGS 1.pdf PDF
one line 2019 1.pdf PDF
36C25526R0186 0001.pdf PDF
Previous Results 1.pdf PDF
10-Electrical 42 lab 1.pdf PDF
Sign in Sheet.pdf PDF
Equipment Inventory Schedule WITH EE NUMBERS 1.xlsx XLSX spreadsheet
OR Bld 2 1.pdf PDF
36C25526R0186.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RENDERED IMAGEAREA OF WORK SHEET INDEX

MARION VA MEDICAL CENTER

MARION, IL

VAMC PROJECT #: 657A5-21-105

UPGRADE CAMPUS ELECTRICAL GRID DESIGN

VEG 21.08

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

657A5-21-105

MARION, ILLINOIS

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL

GRID

100% CONSTRUCTION DOCUMENT

100% CONSTRUCTION

DOCUMENT

7/7/2021 RA RW

GI001

N/A

COVER SHEET

9/28/2021

VEG 21.08

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

657A5-21-105

MARION, ILLINOIS

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL

GRID

100% CONSTRUCTION DOCUMENT

100% CONSTRUCTION

DOCUMENT

9/28/2021

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NS NO SCALE

NTS NOT TO SCALE

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

REQ REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

SCC SHORT CIRCUIT CAPACITY

SHT SHEET

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

UTIL UTILITY

V VOLT

VA VOLT·AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

XFMR TRANSFORMER

DS DISCONNECT SWITCH

DWG DRAWING

EXST EXISTING

G OR GND ELECTRICAL GROUND

IMC INTERMEDIATE METAL CONDUIT

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

MOCP MAXIMUM OVERCURRENT PROTECTION

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

3/C THREE-CONDUCTOR

3PH THREE PHASE

4/C FOUR-CONDUCTOR

4W FOUR WIRE

A/E ARCHITECT / ENGINEER

AC ALTERNATING CURRENT OR ARMORED

CABLE

CONDUIT

CKT CIRCUIT

CUR CURRENT

DEMO DEMOLITION

DIAG DIAGRAM

C

ELECTRICAL ABBREVIATIONS

A. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS

PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

B. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES.

KEY NOTE.1

NEW LINE TYPE.

EXISTING LINE TYPE.

DEMO LINE TYPE.

ELECTRICAL GENERAL NOTES - DEMOLITION: KEY NOTES:

NEW - EXISTING & DEMO LINE TYPES:

DEMO HATCH.

ELECTRICAL GENERAL NOTES:

A. SPECIFICATIONS TAKE PRECEDENT OVER DRAWINGS.

B. CORE DRILL AND SAW CUT, AS REQUIRED, FOR FLOOR AND WALL PENETRATIONS.

C. PROVIDE ALL ELECTRICAL WORK IN ACCORDANCE WITH DRAWINGS + SPECIFICATIONS.

D. COORDINATE ALL OUTAGES WITH VHA COR PER SPECS PRIOR TO WORK BEING DONE.

E. THE PROJECT WILL UTILIZE EXISTING CONDUIT AND PROVIDE ALL NECESSARY MEDIUM

VOLTAGE SPLICES AND TERMINATIONS. NEW CONDUIT ACROSS ROADWAY SHOWN ON

DRAWINGS.

F. PHASING SHALL ALSO BE CONSIDERED. SEE SPECIFICATION 01 00 00 1.6.G.

G. CONTRACTOR UNDER THIS CONTRACT SHALL PLAN TO REMOVE AND INSTALL NEW

MEDIUM VOLTAGE WIRE FOR FEEDER 1 INCLUDING ANY NEW WORK PERFORMED

UNDER ANOTHER CONTRACT. THE INTENT IS TO HAVE ALL NEW MEDIUM VOLTAGE

FEEDER WITH THE SAME WIRE UNDER THIS CONTRACT.

RA RW

E-001

NA

ELECTRICAL SYMBOLS,

ABBREVIATIONS & GENERAL NOTES

CO CONTRACTING OFFICER

COR CONTRACTING OFFICER REPRESENTATIVE

RMC RIGID METTALIC CONDUIT

MH # MANHOLE NUMBER

Z IMPEDANCE

BUILDINGBLDG

EMH EXISTING MANHOLE

NC NORMALLY CLOSE

NO NORMALLY OPEN

AUTOMATIC TRANSFER SWITCHATS

VFD

G

T

J

PB

P

HVS

LVS

ELECTRICAL SYMBOLS - DIAGRAM

DELTA CONNECTION.

TRANSFORMER.

WYE CONNECTION.

PULL BOX.

MANHOLE.

PRESSURE SWITCH-CLOSE ON

INCREASE.

PRESSURE SWITCH-OPEN ON

INCREASE.

SWITCH, MULTIPOSITION.

SWITCH, NORMALLY CLOSED FLOAT.

SWITCH, NORMALLY CLOSED FOOT OPERATED.

SWITCH, NORMALLY CLOSED LIMIT.

SWITCH, NORMALLY CLOSED TEMPERATURE

ACTIVATED.

SWITCH, NORMALLY CLOSED TIME DELAY.

SWITCH, NORMALLY OPEN FLOAT.

SWITCH, NORMALLY OPEN LIMIT.

SWITCH, NORMALLY OPEN TEMPERATURE

ACTIVATED.

SWITCH, NORMALLY OPEN TIME DELAY.

SWITCH, SINGLE BREAK.

NORMALLY CLOSED RELAY CONTACT.

NORMALLY OPEN RELAY CONTACT.

FUSE WITH RATING.

MOLDED CASE CIRCUIT BREAKER.

LOW-VOLTAGE DRAWOUT AIR CIRCUIT

BREAKER.

MEDIUM-VOLTAGE OIL CIRCUIT BREAKER.

MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT

BREAKER.

SWITCH AND FUSE UNIT.

FUSED DRAWOUT POTENTIAL TRANSFORMER.

RELAY; LETTER INDICATES RELAY TYPE.

50 = INSTANTANEOUS OVERCURRENT OR RATE-

OF-RISE.

51 = AC-TIME OVERCURRENT.

67 = AC-DIRECTIONAL OVERCURRENT.

86 = LOCK OUT.

DISCONNECT SWITCH, FUSED.

DISCONNECT SWITCH, UNFUSED, VAV.

FUSIBLE LINK.

STARTER, COMBINATION W/ DISCONNECT

SWITCH.

STARTER OR MOTOR CONTROLLER.

VARIABLE FREQUENCY DRIVE.

GENERATOR, POWER.

TRANSFORMER, PLAN.

EARTH GROUND.

JUNCTION BOX.

ELECTRICAL SYMBOLS - POWER PLAN

SIGNAL DUCT BANK.

POWER DUCT = P.

POWER MANHOLE.

HI VOLTAGE SWITCH ON CONCRETE PAD.

LOW VOLTAGE SWITCH ON CONCRETE PAD.

S

P

MH

VHA VETERAN HEALTH ADMINISTRATION

S SIGNAL MANHOLE.

REPRESENTS SPLICES IN MANHOLES.

PPP

P

P P

P

SP

P

PPPP

P

P

P

S P

PPP

P

PPP

PP

P

P P

P

P

P

P

P

P

S

S

S S

S

S S

S

S

S

S

S

S

P

P

P

P

P

P

P

P

P

PP

P

SS

S

SSS

S

S

S

P P

P S

S

S S

P

P

EMH#6MH#6AAMH#6BBMH#10

EMH#6B

SHOPS

WAREHOUSE

ENGINEERING/SAFETY

& SUPPLY

BOILER

PLANT

NURSING HOME

CARE UNIT

CLINICAL/OUTPATIENT

ADDITION

MAIN ADMIN. HOSP.

EDUCATIONAL

BUILDING

PA

VI

LL

IO

N

DENTAL/MEDICAL

VENDING/BUILDING

MANAGEMENT & SPD

BLDG #38

BLDG #8

BLDG #43

BLDG #13

BLDG #42

BLDG #1

BLDG #37

BLDG #2

BLDG #49

CHILLER

PLANT

BLDG #15

MH#2AA

EMH#2

EMH#4AA

EMH#4

VEG 21.08

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

657A5-21-105

MARION, ILLINOIS

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL

GRID

00KEYNOTES

GENERAL NOTES

100% CONSTRUCTION DOCUMENT

100% CONSTRUCTION

DOCUMENT

7/7/2021 RA RW

ED101

NA

ELECTRICAL PARTIAL SITE PLAN

DEMOLITION

SCALE: NO SCALE

ELECTRICAL PARTIAL SITE PLAN DEMOLITION

OUTDOOR WALK-IN 12.4KV SERVICE

ENTRANCE SWITCHGEAR

MH#1AA

EMH#1

EMH#2

MH#2AAEMH#3

MH#3AA

EMH#4

MH#4AA

EMH#5

MH#5AA

MH #X1

MH# X2MH# X3MH# X4

TO MH #4A

MH#4A

MH#4B

MH#4BB

MH#8

ELECTRICAL

TRANSFORMER ROOM

METAL

BUILDING

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS AND GENERAL NOTES.

B. CONTRACTOR SHALL TAKE ALL THE NECESSARY PRECAUTIONS TO ENSURE

OTHER FEEDERS ARE NOT DAMAGED DURING THIS PROJECT.

C. ALL EXISTING MANHOLES AND DUCTBANKS SHALL BE REUSED.

D. ALL FEEDER#1 DUCTS SHALL BE CLEANED PER THE SPECIFICATIONS AFTER

REMOVAL OF DEMOED FEEDER.

E. REFER TO THE SPECIFICATIONS FOR PHASING REQUIREMENTS AND WHEN

WORK CAN BE PERFORMED IN THE MANHOLES.

F. CONTRACTOR SHALL BE ADVISED THAT MANHOLES ARE FILLED WITH

WATER UNDER NORMAL CONDITIONS. PROVIDE ALL NECESSARY PORTABLE

PUMPS, FUEL AND ACCESSORIES TO DRAIN MANHOLES AND EXECUTE

WORK.

G. REFER TO ONE LINE ON SHEET E-601 FOR MORE DETAILS ON THE ROUTING

AND REMOVAL OF FEEDER #1.

H. ALL WORK WILL HAVE TO BE DONE BETWEEN 7PM AND 4AM.

I. LABEL MANHOLES WITH FEEDER NUMBERS.

1. EXISTING, EMPTY MANHOLE.

2. EXISTING UNDERGROUND DUCT BANK WITH 4 (4") EMPTY CONDUITS.

3. CUT CONCRETE ROAD AND INSERT 4 (4") FROM MH #X4 TO MH#3AA. REFER

TO ELECTRICAL DETAILS ON E-501.

4. THIS SECTION OF MEDIUM VOLTAGE CABLE REPLACED BY OTHERS.

COORDINATE WITH PROJECT VA 657-502 "EXPAND & UPGRADE BUILDING 42

FOR LABORATORY" TO MAKE MEDIUM VOLTAGE CONNECTIONS.

PPP

P

P P

P

SP

P

PPPP

P

P

P

S P

PPP

P

PPP

PP

P

P P

P

P

P

P

P

P

S

S

S S

S

S S

S

S

S

S

S

S

P

P

P

P

P

P

P

P

P

PP

P

SS

S

SSS

S

S

S

P P

P S

S

S S

P

EMH#6MH#6AAMH#6BBMH#10

EMH#6B

SHOPS

WAREHOUSE

ENGINEERING/SAFETY

& SUPPLY

BOILER

PLANT

NURSING HOME

CARE UNIT

CLINICAL/OUTPATIENT

ADDITION

MAIN ADMIN. HOSP.

EDUCATIONAL

BUILDING

PA

VI

LL

IO

N

DENTAL/MEDICAL

VENDING/BUILDING

MANAGEMENT & SPD

BLDG #38

BLDG #8

BLDG #43

BLDG #13

BLDG #42

BLDG #1

BLDG #37

BLDG #2

BLDG #49

CHILLER

PLANT

BLDG #15

MH#2AA

EMH#2

EMH#4AA

EMH#4

VEG 21.08

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

657A5-21-105

MARION, ILLINOIS

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL

GRID

00KEYNOTES

GENERAL NOTES

100% CONSTRUCTION DOCUMENT

100% CONSTRUCTION

DOCUMENT

7/7/2021 RA RW

ES101

NA

ELECTRICAL PARTIAL SITE PLAN

NEW

SCALE: NO SCALE

ELECTRICAL PARTIAL SITE PLAN NEW

OUTDOOR WALK-IN 12.4KV SERVICE

ENTRANCE SWITCHGEAR

MH#1AA

EMH#1

EMH#2

MH#2AAEMH#3

MH#3AA

EMH#4

MH#4AA

EMH#5

MH#5AA

MH #X1

MH #X2MH #X3MH #X4

TO MH #4A

MH#4A

MH#4B

MH#4BB

MH#8

ELECTRICAL

TRANSFORMER ROOM

METAL

BUILDING

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS AND GENERAL NOTES.

B. CONTRACTOR SHALL TAKE ALL THE NECESSARY PRECAUTIONS TO ENSURE

OTHER FEEDERS ARE NOT DAMAGED DURING THIS PROJECT.

C. ALL EXISTING MANHOLES AND DUCTBANKS SHALL BE REUSED.

D. ALL FEEDER#1 DUCTS SHALL BE CLEANED PER THE SPECIFICATIONS AFTER

REMOVAL OF DEMOED FEEDER.

E. REFER TO THE SPECIFICATIONS FOR PHASING REQUIREMENTS AND WHEN

WORK CAN BE PERFORMED IN THE MANHOLES.

F. CONTRACTOR SHALL BE ADVISED THAT MOST IF NOT ALL OF THE

MANHOLES ARE FILLED WITH WATER UNDER NORMAL CONDITIONS.

PROVIDE ALL NECESSARY PORTABLE PUMPS, FUEL AND ACCESSORIES TO

DRAIN MANHOLES AND EXECUTE WORK.

G. REFER TO ONE LINE ON SHEET E-602 FOR MORE DETAILS ON THE ROUTING

OF FEEDER #1.

H. ALL WORK WILL HAVE TO BE DONE BETWEEN 7PM AND 4AM.

I. LABEL MANHOLES WITH FEEDER NUMBERS

1. EXISTING, EMPTY MANHOLE.

2. EXISTING UNDERGROUND DUCT BANK WITH 4 (4") EMPTY CONDUITS.

3. CUT CONCRETE ROAD AND INSERT 4 (4") FROM MH #X4 TO MH#3AA. REFER

TO ELECTRICAL DETAILS ON E-501.

4. THIS SECTION OF MEDIUM VOLTAGE CABLE REPLACED BY OTHERS.

COORDINATE WITH PROJECT VA 657-502 "EXPAND & UPGRADE BUILDING 42

FOR LABORATORY" TO MAKE MEDIUM VOLTAGE CONNECTIONS.

5. PROVIDE MEDIUM VOLTAGE FEEDERS. REFER TO SINGLE LINE DIAGRAM FOR

FEEDER SIZES.

GENERAL NOTES:

1.

2.

3.

4.

5.

CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.

PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS

WHEN CROSSING OR PLACED IN ROADWAYS.

MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (30") OR

AS OTHERWISE SPECIFIED IN SECTION 26 05 41.

PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND

TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.

INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.

3" mm

3" mm (3 mm

(3")

(3") 76mm

(3") 76mm76mm

INNERDUCT,

SEE NOTE 5

PLASTIC

SPACER

DUCT

4 WAY DUCT LINE

2" [50mm] MINIMUM OR THICKNESS OF EXISTING PAVEMENT

WHICHEVER IS GREATER.

SEE GENERAL NOTES FOR THIS DETAIL

PROVIDE LOAD TRANSFER DOWELS.

4'-0" MAX.

1'-0" MAX.

[305mm]

1'-0" MAX.

[305mm]

TRENCH

BACKFILL

CLASS S CONCRETE

f'c=3000 PSI [20.7 MPa]

CONCRETE

SAW CUT EXISTING.

CONCRETE FULL DEPTH

BOTH SIDES

CONCRETE ROAD

EXISTING

VA

RI

EST/

T

EXISTING

CONCRETE

PAVEMENT (TYP)

1'-0" MAX.

[305mm]

1'-0" MAX.

[305mm]

1'-0" MAX.

[305mm]

1'-0" MAX.

[305mm]

6" -1

4" [15

0-

5m m]

LOAD TRANSFER DOWELS.

VEG 21.08

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

657A5-21-105

MARION, ILLINOIS

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL

GRID

100% CONSTRUCTION DOCUMENT

100% CONSTRUCTION

DOCUMENT

7/7/2021

SCALE: NO SCALE

ELECTRICAL DUCT BANK DETAILS

RA RW

E-501

NA

ELECTRICAL DUCT BANK DETAILS

SCALE: NO SCALE

TYPE 3 UTILITY TRENCH PATCH

1. MATERIAL AND COMPACTION REQUIREMENTS FOR PIPE BEDDING/SHADING

SHALL BE IN ACCORDANCE WITH THE SPECIFICATIONS FOR THE

APPLICABLE UTILITY PIPE.

2. TRENCH BACKFILL SHALL COMMENCE 1 FOOT [305mm] ABOVE THE TOP OF

DUCTBANK AND SHALL BE PER SECTION 31 20 11.

3. BACKFILL COMPACTION REQUIREMENTS SHALL BE PER SECTION 312011.

4. THE 1 FOOT [305mm] TRENCH "SHOULDER" AREAS SHALL BE DELETED FOR

TYPE 2 TRENCHES.

5. PORTLAND CEMENT CONCRETE SHALL BE IN ACCORDANCE WITH THE

REQUIREMENTS OF SECTION 03 30 53.

6. LOAD TRANSFER DOWELS FOR JOINTS TRANSVERSE TO THE ROADWAY

CENTERLINE SHALL BE SMOOTH STEEL DOWELS . DOWELS SHALL BE SIZED

AND SPACED AS FOLLOWS:

PCCP THICKNESS DOWEL SIZE DOWEL LENGTH

DOWEL SPACING

6" [150mm] #5 [No. 16] 12" [305mm] 18"

[455mm] 7" [180mm] #6 [No. 19] 15" [380mm] 15"

[380mm] 8" [180mm] #8 [No. 19] 15" [380mm] 12"

[305mm] 10" [180mm] #10 [No. 19] 15" [380mm] 12"

[305mm]

7. DEFORMED TIE BARS SHALL BE USED IN TRENCH PATCHES LONGITUDINAL

TO THE ROADWAY CENTERLINE WHEN THE TRENCH LENGTH IS GREATER

THAN 50 FEET [15240mm]. TIE BARS SHALL BE 24 INCHES [610mm] LONG.

DEFORMED #4 [No. 13] BARS FOR PCCP LESS THAN 8 INCHES [205mm] THICK AND #5 [No. 16] BARS IF 8 INCHES [205mm] THICK OR MORE. TIE BARS SHALL BE PLACED 30 INCHES [760mm] CENTER-TO-CENTER.

8. HOLES SHALL BE DRILLED 1 FOOT [305mm] INTO THE EXISTING SLAB FOR TIE BARS AND 7 INCHES [180mm] FOR DOWELS. HOLES SHALL BE OF A

DIAMETER SUFFICIENT TO ACCOMMODATE THE TIE BAR ANCHORAGE OR

DOWEL CAP. TIE BARS SHALL BE ANCHORED WITH AN APPROVED HIGH

VISCOSITY EPOXY.

9. IF THE CONCRETE SLAB REMAINING NEXT TO A LONGITUDINAL OR

TRANSVERSE JOINT IS LESS THAN 6 FEET [1829mm] AT ITS NARROWEST

WIDTH, REMOVE AND REPLACE THE EXISTING CONCRETE TO THE JOINT.

GENERAL NOTES:

BLDG #8

BLDG #38

MH#6B

400A

BLDG #13

MDP

MH#9

N.C.N.O.

75ATS

ATS #1

BRANCH

CRITICAL

210ATS

BRANCH

SAFETY

ATS #2

LIFE

300ATS

"P1E"PANEL

300ATS

PANEL"DP1"

BLDG #43

600AF

600AS

BLDG #15

125A

MTS

TO BUILDING #16

400AS

300AF

400AF

400AS

BLDG #14

TRAILERTO

MTS

125AF

200AS

CATERPILLER90KW, 120/208V

800ATS

MAIN

PANEL

CHILLER BLDG #49

CS-3

100E

MH#10MH#6BBMH#6AA

EMH#6EMH#5

MH#5AA

MH#4A

BLDG #42

FEEDER #3

UNIT SUB B UNIT SUB A

MH#4B

MH#4AAMH#2AA

EMH#3

MH#3AA

EMH#2

MH#4BB

PANEL

CHILLER

EMH#1

FEEDER #3

FEEDER #2

FEEDER #2

FEEDER #3

200/5A 1200A

200/5A 1200A

1200A200/5A

1200A

1500KVA 12.47 KV,

DELTA 480Y/277V

4.5±7%Z OA 65°C

2000AF/2000ATS2000AF/2000ATS

BLDG #38

DRY-TYPE PRIMARY SELECTOR

SWITCH, FUSED LOAD INTERRUPTER

SWITCH AND TRANSFORMER

1500/2000 KVA, 12.47 KV,

DELTA 480/277V WYE AA

150°C 5.75%Z

1500/2000 KVA, 12.47 KV,

DELTA 480/277V WYE AA 150°C

GE 225 KVA 12.47 KV,

DELTA 208/120V

5.53% Z

OA OIL COOLED 65°C

R.T.F. 225KVA 12.47 KV,

DELTA 208/120V 4.2% Z OA

OIL COOLED 65°

600AS

600AF

CATERPILLER

60KW, 208/120V

1500 KVA

12.47 KV,

DELTA

480Y/277V

4.5±7%Z OA

65°C

300 KVA

12.47 KV,

DELTA

208Y/120V

4.5±7%Z OA

65°C

CS-3

100E

CS-3

25E

GE "MT-5" 112.5 KVA

12.47 KV, DELTA

208/120V 2.43% Z OA

65°C

600AS

600AF

SUBSTATION.

DRY-TYPE PRIMARY SELECTOR

SWITCH, FUSED LOAD INTERRUPTER

SWITCH AND TRANSFORMER

BLDG #38

ATS

600AS

600AS

PULL BOX

3 200/5

SPARE

1200A

20A, 1 POLE, 2#10, 1#10 GRD. IN 3/4"C.

EMERGENCY CIRCUIT FROM PANEL "P" IN BLDG. 15.

NEUTRAL BOND WILL BE IN

SWITCHGEAR

NEUTRAL BOND WILL BE IN

SWITCHGEAR

3200/5A

200/5

200/5

200/5

120/240V PANELBOARD

TO BREAKER OPERATING

POWER

AUXILIARY

CONTROL POWER

SUBSTATION.

12.4KV, 3Ø, 3W OUTDOOR WALK-IN METAL

CLAD SWITCHGEAR

FEEDER #2

FEEDER #2

FEEDER #2

EMH#4

FEEDER #2

FEEDER #3 FEEDER #3

FEEDER #2

FEEDER #2

FEEDER #3

FEEDER #3

FEEDER #3

TYPICAL

FEEDER #3

TYPICAL EXISTING SPLICE TO

REMAIN UNDISTURBED, UNLESS

OTHERWISE NOTED.

CPT

12.47KV/7200

B-13

GE 150 KVA 12.47 KV,

DELTA 208/120V

5.6% Z

AA OIL COOLED 65°C

MH#1AA

VEG 21.08

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

657A5-21-105

MARION, ILLINOIS

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL

GRID

GENERAL NOTES

100% CONSTRUCTION DOCUMENT

100% CONSTRUCTION

DOCUMENT

7/7/2021 RA RW

E-601

NA

12.47kV ELECTRICAL ONE-LINE

DEMOLITION

SCALE: NO SCALE

12.47KV ELECTRICAL ONE LINE DEMOLITION

1. DEMO FEEDER #1 CABLE INCLUDING GROUND WIRE.

2. EXISTING MANHOLES, FOR REFERENCE ONLY.

3. THIS SECTION OF MEDIUM VOLTAGE CABLE REPLACED BY OTHERS.

COORDINATE WITH PROJECT VA 657-502 "EXPAND & UPGRADE BUILDING 42

FOR LABORATORY" TO MAKE MEDIUM VOLTAGE CONNECTIONS.

A. ALL WORK SHOWN IS EXISTING UNLESS NOTED OTHERWISE.

B. ALL WORK SHALL BE DONE BETWEEN 7PM AND 4AM.

2 2

00KEYNOTES

BLDG #8

BLDG #38

MH#6B

400A

BLDG #13

MDP

MH#9

N.C.N.O.

75ATS

ATS #1

BRANCH

CRITICAL

210ATS

ATS #2

300ATS

"P1E"PANEL

300ATS

PANEL"DP1"

BLDG #43

600AF

600AS

BLDG #15

125A

MTS

TO BUILDING #16

400AS

300AF

400AF

400AS

BLDG #14

TRAILERTO

MTS

125AF

200AS

CATERPILLER90KW, 120/208V

800ATS

CHILLER BLDG #49

CS-3

100E

MH#10MH#6BBMH#6AA

EMH#6EMH#5

MH#5AA

BLDG #42

FEEDER #3

UNIT SUB B UNIT SUB A

MH#4AAMH#2AA

EMH#3

MH#3AA

EMH#2

MH#4BB

PANEL

CHILLER

EMH#1

FEEDER #3

FEEDER #2

FEEDER #2

200/5A 1200A

200/5A 1200A

1200A200/5A

1200A

1500KVA 12.47 KV,

DELTA 480Y/277V

4.5±7%Z OA 65°C

2000AF/2000ATS2000AF/2000ATS

BLDG #38

DRY-TYPE PRIMARY SELECTOR

SWITCH, FUSED LOAD INTERRUPTER

SWITCH AND TRANSFORMER

1500/2000 KVA, 12.47 KV,

DELTA 480/277V WYE AA

150°C 5.75%Z

1500/2000 KVA, 12.47 KV,

DELTA 480/277V WYE AA 150°C

GE 225 KVA 12.47 KV,

DELTA 208/120V

5.53% Z

OA OIL COOLED 65°C

R.T.F. 225KVA 12.47 KV,

DELTA 208/120V 4.2% Z OA

OIL COOLED 65°

600AS

600AF

CATERPILLER

60KW, 208/120V

1500 KVA

12.47 KV,

DELTA

480Y/277V

4.5±7%Z OA

65°C

300 KVA

12.47 KV,

DELTA

208Y/120V

4.5±7%Z OA

65°C

CS-3

100E

CS-3

25E

GE "MT-5" 112.5 KVA

12.47 KV, DELTA

208/120V 2.43% Z OA

65°C

600AS

600AF

SUBSTATION.

DRY-TYPE PRIMARY SELECTOR

SWITCH, FUSED LOAD INTERRUPTER

SWITCH AND TRANSFORMER

BLDG #38

ATS

600AS

600AS

PULL BOX

3 200/5

SPARE

1200A

20A, 1 POLE, 2#10, 1#10 GRD. IN 3/4"C.

EMERGENCY CIRCUIT FROM PANEL "P" IN BLDG. 15.

NEUTRAL BOND WILL BE IN

SWITCHGEAR

NEUTRAL BOND WILL BE IN

SWITCHGEAR

3200/5A

200/5

200/5

200/5

120/240V PANELBOARD

TO BREAKER OPERATING

POWER

AUXILIARY

CONTROL POWER

SUBSTATION.

12.4KV, 3Ø, 3W OUTDOOR WALK-IN METAL

CLAD SWITCHGEAR

FEEDER #2

FEEDER #2

FEEDER #2

EMH#4

FEEDER #2

FEEDER #3 FEEDER #3

FEEDER #2

FEEDER #2

FEEDER #3

FEEDER #3

FEEDER #3

TYPICAL

FEEDER #3

TYPICAL EXISTING SPLICE TO

REMAIN UNDISTURBED, UNLESS

OTHERWISE NOTED.

CPT

12.47KV/7200

FEEDER #1

FEEDER #1

FEEDER #1

B-13

FEEDER #1

FEEDER #1

FEEDER #1

FEEDER #1

FEEDER #1

GE 150 KVA 12.47 KV,

DELTA 208/120V

5.6% Z

AA OIL COOLED 65°C

MH #X1

MH#1AA

FEEDER #1

FEEDER #1

FEEDER #1

FEEDER #1

MH#4B

MH#4A

MH #X2 MH #X3 MH #X4

MAIN

PANEL

FEEDER #1

FEEDER #1

VEG 21.08

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

657A5-21-105

MARION, ILLINOIS

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: UPGRADE CAMPUS ELECTRICAL

GRID

GENERAL NOTES

100% CONSTRUCTION DOCUMENT

100% CONSTRUCTION

DOCUMENT

7/7/2021 RA RW

E-602

NA

12.47KV ELECTRICAL ONE-LINE

DIAGRAM NEW

SCALE: NO SCALE

12.47KV ELECTRICAL ONE LINE NEW

1. PROVIDE NEW XLPE (CROSS-LINKED POLYETHYLENE) 3-1/C, 2#0 15KV FEEDER

#1 CABLE AND GROUND WIRE.

2. NEW EXISTING MANHOLE

3. THIS SECTION OF MEDIUM VOLTAGE CABLE REPLACED BY OTHERS.

COORDINATE WITH PROJECT VA 657-502 "EXPAND & UPGRADE BUILDING 42

FOR LABORATORY" TO MAKE MEDIUM VOLTAGE CONNECTIONS.1

A. ALL WORK SHOWN IS EXISTING UNLESS NOTED OTHERWISE.

B. ALL WORK WILL HAVE TO BE DONE BETWEEN 7PM AND 4AM.

2 2 2 2

B00KEYNOTES

1 1 1

Sheets and Views
GI001
E-001
ED101
ES101
E-501
E-601
E-602