Vol. 2 of 2- 589-21-211 KCVAMC Renovate B26 PPP-Drawings-100 20260417- 37 pages.pdf

PDF 19 MB Posted

Attached to
Z2DA--589-21-211, Renovate Building 26 for Pharmacy, Phlebotomy, and Police Department
Solicitation number
36C25526R0127
Issued by

About this file

This document is a comprehensive set of construction drawings and specifications for the renovation of Building 26 at a Veterans Affairs Medical Center, specifically for the Police Department, Phlebotomy, X-Ray, and CT Scanner areas. The project involves mechanical, plumbing, electrical, and related systems across multiple building areas.

The plumbing scope includes demolition and installation of waste and vent systems, domestic water lines (hot and cold), and medical gas outlets in designated areas. Key plumbing fixtures are detailed in schedules including lavatories, water closets, floor drains, and emergency fixtures. The mechanical systems encompass HVAC demolition and new installations with terminal units serving various rooms, ductwork routing, and hydronic heating connections sized for specific flow rates (ranging from 0.19 to 2.64 GPM). Medical gas outlets (oxygen, vacuum, and medical air) are shown for the CT scan and imaging areas. Electrical work includes demolition of existing systems and new power distribution, lighting, and access control installations across both Police/Phlebotomy and X-Ray/CT areas. The drawings specify seismic bracing requirements for components exceeding 400 pounds or positioned more than four feet above floor level, with flexible connections required between all major systems. Construction coordination drawings must be submitted and approved before work begins, with all work coordinated to minimize disruption to occupied building areas and maintain conditioned space during construction. The renovation is issued for bid as of April 16, 2026.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWING SYMBOLS

26-SF 3

26-TU-I-I

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

TYPICAL UNIT NO.

BUILDING NO. WHERE EQUIPMENT IS LOCATED.

SUPPLY FAN NO. 3 IN BUILDING NO. 26

EQUIPMENT ABBREVIATION (SUPPLY FAN)

ITEM NUMBER (TERMINAL UNIT NO. 1)

ITEM (TERMINAL UNIT SHOWN)

SERVED BY AIR HANDLER UNIT NO. 1

DRAWING NUMBER WHERE DRAWN

BUILDING NO. WHERE EQUIPMENT IS LOCATED

H4

H7

A

GENERAL PLUMBING SYMBOLS

DIRECTION OF PIPE PITCH (DOWN)

FE

CO

DIRECTION OF FLOW

ANCHOR

REDUCER OR INCREASER

ECCENTRIC REDUCER

TOP CONNECTION, 45° OR 90°

BOTTOM CONNECTION, 45° OR 90°

SIDE CONNECTION

CAPPED OUTLET

RISE OR DROP IN PIPE

UNION

PIPE UP

PIPE DOWN

POINT OF CONNECTION BETWEEN NEW

AND EXISTING WORK

LIMIT OF DEMOLITION

INVERTED BUCKET TRAP SET INCLUDING

PIPING ACCESSORIES

FLOAT & THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES

STRAINER

THERMOMETER

PRESSURE GAGE

FLOW ELEMENT

CLEAN OUT

HOSE BIB

PLUMBING ABBREVIATIONS

F FAHRENHEIT

FCO FLOOR CLEANOUT

FCW FILTERED COLD WATER

FD FLOOR DRAIN

FDC FIRE DEPARTMENT

(HOSE) CONNECTION

FM FLOW METER

FOP FUEL OIL PUMP

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FS FLOOR SINK

FS FLOW SWITCH

FU FIXTURE UNITS

EL ELEVATION

EMCS ENERGY MONOSERRAT

AND CENTRAL SYSTEM

EPA ENVIRONMENTAL PROTECTION

AGENCY

EPACT ENERGY POLICY ACT

ESC ESCUTCHEON

ESH EMERGENCY SHOWER

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

EWS EYE WASH STATION

EWS/SH EYE WASH/DRENCH SHOWER

EX EXISTING

DCW DOMESTIC COLD WATER

DFU DRAINAGE FIXTURE UNITS

DHW DOMESTIC HOT WATER

DHWR

DHWS DOMESTIC HOT WATER SUPPLY

DI DEIONIZED WATER

DN DOWN

DOE DEPARTMENT OF ENERGY

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRINKING WATER RETURN

DWS DRINKING WATER SUPPLY

DWV DRAIN WASTE VENT

C CELSIUS

CA COMPRESSED

AIRCGA COMPRESSED GAS ASSOCIATION

CFM CUBIC FEET PER MINUTE

CI CAST IRON

CO CLEANOUT

CS CLINICAL SINK

CV CONTROL VALVE

BHP BREAK HORSEPOWER

BSP BLACK STEEL PIPE

BT BATHTUB

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

A/E ARCHITECT / ENGINEER

AD AREA DRAIN/ACCESS DOOR

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISH GRADE

AG AIR GAP

AP ACCESS PANEL

AS AUTOMATIC SPRINKLER

ASD ADJUSTABLE SPEED DRIVES

ASD AUTOMATIC SPRINKLER DRAIN

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATION, AIR CONDITION

ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

ASPE AMERICAN SOCIETY OF PLUMBING

ENGINEERS

ASR AUTOMATIC SPRINKLER RISER

AV ACID VENT

AW ACID WASTE

BFP REDUCED PRESSURE BACKFLOW

PREVENTER

DOMESTIC HOT WATER RETURN

L/S LITER PER SECOND

LA LABORATORY AIR

LAV

LBS/HR

LCW LABORATORY COLD WATER

LHW LABORATORY HOT WATER

LNG LIQUID NATURAL GAS

LOX LIQUID OXYGEN

LV LABORATORY VACUUM

LW LOW WATER

M METER

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH 1000 BTUH

MED MEDICAL

MER MECHANICAL EQUIPMENT

ROOM

MH MANHOLE

MOU MEMORANDUM OF

UNDERSTANDING

MSB MOP SERVICE BASIN

MV MEDICAL VACUUM

N2 NITROGEN

N20 NITROUS OXIDE

NC NORMALLY CLOSED

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM. NOMINAL

NPW NON POTABLE WATER

NTS NOT TO SCALE

O2 OXYGEN

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OR OPERATING ROOM

OVFL OVERFLOW

KW KILOWATT

KWH

ID INSIDE DIAMETER

IE INVERT ELEVATION

ICW INDUSTRIAL COLD WATER

IHW INDUSTRIAL HOT WATER

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

IRW IRRIGATION WATER

IW INDIRECT WASTE

IWH INSTANTANEOUS WATER HEATER

IWR INDUSTRIAL WATER RETURN

IWS INDUSTRIAL WATER SUPPLY

H&CW

HB HOSE BIBB

HD HUB DRAIN

HEX HEAT EXCHANGER

HP HORSEPOWER

HS

HST

HWB HOT WATER BOILER

HWCP

HWP HOT WATER PUMP

HYD HYDRANT

GAL GALLON

GCO GRADE CLEANOUTS

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GRS GAS REGULATOR STATION

GT GREASE TRAP

GVTR GAS VENT THROUGH ROOF

GWH GAS FIRED WATER HEATER

HOT AND COLD WATER

HAND SINK

HOT WATER STORAGE TANK

(DOMESTIC)

HOT WATER CIRCULATING PUMP

KILOWATT-HOUR

LAVATORY

POUNDS PER HOUR

PA

PD PRESSURE DROP OR DIFFERENCE

PDI PLUMBING AND DRAINAGE INSTITUTE

PG PRESSURE GAGE

PP PLUMBING PUMP

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH

ATMOSPHERE

PSIG POUNDS PER SQUARE INCH

GAGE

PTRV PRESSURE TEMPERATURE RELIEF

VALVE

PW POTABLE WATER

RD

RDL ROOF DRAIN LEADER

RL ROOF LEADER

RP RECIRCULATION PUMP

RO REVERSE OSMOSIS WATER

RWL RAIN WATER LEADER

SAN SANITARY SEWER

SMACNA

SCFM STANDARD CUBIC FOOT/MINUTE

SCW SOFTENED COLD WATER

SDMH

SMH

SP SUMP PUMP

SPR SPRINKLER LINE

SQFT/SF

SS STAINLESS STEEL

ST STORAGE TANK

SW STORM WATER

TCV TEMPERATURE CONTROL VALVE

TD TEMPERATURE DIFFERENCE

TD TRENCH DRAIN

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TSTAT

TWR TEMPERED WATER RETURN

TWS TEMPERED WATER SUPPLY

TYP TYPICAL

V VENT

VAC VACUUM

VB VACUUM BREAKER

VCO VACUUM CLEANER OUTLET

VP VACUUM

PUMPVS VENT

STACKVSD VARIABLE SPEED DRIVE

VTR VENT THROUGH ROOF

W WASTE

WC WATER CLOSET

WCO WALL CLEANOUT

WG WATER GAGE

WH WALL HYDRANT

WH WATER HEATER

WHA WATER HAMMER ARRESTER

WL WATER LINE

WM WATER METER

WPD WATER PRESSURE DROP

WS WASTE STACK

WSFU

YCO YARD CLEANOUT

YH YARD HYDRANT

IPC INTERNATIONAL PLUMBING CODE

PASCAL

ROOF DRAIN

SHEET METAL AND AIR

CONDITIONING CONTRACTORS

NATIONAL ASSOCIATION

STORM DRAIN MANHOLE

SANITARY MANHOLE

SQUARE FEET

THERMOSTAT

WATER SUPPLY FIXTURE UNITS

PLUMBING PIPING SYMBOLS

MA MA MA

MV MV MV

LA LA LA

LV LV LV

OA OA OA

IA IA IA

D D D

W

SD SD SD

SD SD SD

TWR TWR TWR

DWS DWS DWS

DWR DWR DWR

TWS TWS TWS

W W W

SCW SCW SCW

FCW FCW FCW

N2O

0 0 0

NG NG NG

NG NG NG

FOD FOD FOD

FOS FOS FOS

FOR FOR FOR

FOV FOV FOV

N2O N2O

N2 N2 N2

DOMESTIC COLD WATER, COLD WATER

DOMESTIC HOT WATER, HOT WATER

DOMESTIC HOT WATER RETURN, HOT WATER RETURN

MEDICAL AIR

MEDICAL VACUUM

LABORATORY AIR

LABORATORY VACUUM

ORAL EVACUATION

INDUSTRIAL AIR

DRAIN

VENT (SANITARY)

SOIL, WASTE, OR SANITARY SEWER

SANITARY SEWER, BELOW GRADE

STORM WATER

STORM WATER, BELOW GRADE

SOFTEN COLD WATER

FILTERED COLD WATER

DRINKING WATER SUPPLY

DRINKING WATER RETURN

TEMPERED WATER SUPPLY

TEMPERED WATER RETURN

NITROUS OXIDE

OXYGEN

NITROGEN

NATURAL GAS

NATURAL GAS, BELOW GRADE

FUEL OIL DISCHARGE

FUEL OIL SUPPLY

FUEL OIL VENT

FUEL OIL RETURN

PLUMBING VALVE SYMBOLS

GATE VALVE

AV

GLOBE VALVE

GATE VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

ANGLE GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

MODULATING CONTROL VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

THREE-WAY TWO POSITION CONTROL VALVE

PRESSURE REGULATING VALVE

AUTOMATIC FLOW CONTROL VALVE

PRESSURE RELIEF VALVE

MANUAL AIR VENT

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

GENERAL NOTES

1. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A

FURRED CHASE OR ABOVE THE HARD SUSPENDED CEILING.

2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR

INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.

3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL

VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS

SHALL BE FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL

SPECIFICATIONS.

4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT

SYSTEM, TERMINAL UNITS, FILTERS, COILS, ETC.

5. FOR TYPICAL WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD

EQUIPMENT DETAILS.

6. DIFFUSER, REGISTER, AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK

SIZES.

7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE

MADE TO PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

LOCATIONS OF CEILING DIFFUSERS, REGISTERS, AND GRILLES.

9. SEISMIC PROVISIONS - SEE SPECS. ALL PRESSURES LISTED ARE GAGE

PRESSURE UNLESS OTHERWISE NOTED.

10. SIZES OF ALL HWS & HWR RUNOUTS TO TERMINAL UNITS CAN BE FOUND ON

THE EQUIPMENT SCHEDULES.

11. THIS CONTRACTOR IS RESPONSIBLE FOR SUBMITTING FULL COORDINATION

AND LAYOUT DRAWINGS PER SPECIFICATIONS SECTION 230511, 1.4(G).

COORDINATION SHOULD BE COMPLETED WITH ALL TRADES INCLUDED.

CONSTRUCTION SHALL NOT BEGIN UNTIL COORDINATION DRAWINGS HAVE

BEEN REVIEWED BT THE ENGINEER AND COR.

12. CONTRACTOR SHALL TAG CEILING AT ALL VALVE AND DAMPER LOCATIONS.

COORDINATE WITH COR.

13. ALL DUCT AND PIPE ELEVATIONS SHOWN IN PARENTHESES ARE BOTTOM OF

DUCT OR PIPE, UNLESS INDICATED OTHERWISE ON PLANS.

DEMOLITION NOTES

1. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. BRING ANY

DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE COR

IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE

DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST.

2. REMOVAL OF EXISTING FIXTURES AND EQUIPMENT WILL REQUIRE ISOLATING

THE PIPING RISERS OR MAINS VIA SHUT-OFF VALVES. INSTALL NEW

ISOLATION VALVES WHERE REQUIRED FOR COMPLETION OF WORK.

3. REMOVAL OF EXISTING PLUMBING FIXTURES AND EQUIPMENT, ETC. WILL

REQUIRE CAPPING AND SEALING EXISTING MAINS OR BRANCHES AS

NECESSARY AND REQUIRED TO ALLOW THE REMAINING SYSTEMS TO FULLY

OPERATE WITHOUT DEGRADATION. REMOVE PIPING BACK TO MAINS.

4. CONTRACTOR SHALL PROVIDE PROTECTIVE PLASTIC DROP CLOTHS TO

PROTECT THE EXISTING OCCUPIED AREAS AND EQUIPMENT FROM DUST AND

DEBRIS DURING THE CONSTRUCTION WORK, AND SHALL CLEAN THE AREAS

OF ALL CONSTRUCTION DIRT DAILY, AND UPON COMPLETION OF THE WORK.

5. ALL DRAINED PIPING RISERS AND MAINS SHALL BE REFILLED WITH PROPER

FLUID AND PROPERLY VENTED BY THIS CONTRACTOR, ONCE NEW WORK HAS

BEEN INSTALLED.

6. COORDINATE WITH GENERAL CONTRACTOR THE REMOVAL AND

REPLACEMENT OF ALL EXISTING CEILINGS, WALLS, ETC. AS REQUIRED FOR

MECHANICAL DEMOLITION WORK.

7. EXISTING PIPING AND EQUIPMENT, ETC., NOT TO BE UTILIZED IN THE

COMPLETED BUILDING SHALL BE DISCONTINUED OR REMOVED BACK TO

MAINS. ALL ENDS OF DISCONTINUED PIPING SHALL BE CAPPED IN THE

NEAREST WALL, CEILING OR FLOOR SO THAT THEY ARE COMPLETELY

CONCEALED. OPENINGS LEFT IN WALLS, CEILINGS, ETC., WHERE EQUIPMENT

AND PIPE, ETC., ARE REMOVED AND NOT REPLACED, SHALL BE PATCHED

NEATLY WITH SIMILAR MATERIAL TO ADJACENT CONSTRUCTION. REFER TO

DRAWINGS DELINEATING NEW WORK FOR ADDITIONAL INFORMATION

REGARDING SYSTEMS OR PORTIONS OF SYSTEMS WHERE USE IS TO BE

DISCONTINUED.

8. EXISTING PIPING, FIXTURES AND EQUIPMENT THAT ARE NOT TO BE REUSED

SHALL BE REMOVED AND SHALL REMAIN THE PROPERTY OF THE OWNER IF

THEY WISH TO RETAIN OWNERSHIP OF SAME. IF NOT, EQUIPMENT SHALL

BECOME THE PROPERTY OF THIS CONTRACTOR AND SHALL BE REMOVED

FROM THE SITE AS SOON AS PRACTICAL AND DISPOSED OF IN ACCORDANCE

WITH APPLICABLE LAWS AND REGULATIONS.

9. ALL CUTTING AND CHANNELING OF EXISTING BUILDING SHALL BE

ACCOMPLISHED IN A NEAT AND WORKMANLIKE MANNER WITHOUT REMOVAL

OF EXCESS MATERIALS. THIS CONTRACTOR SHALL PATCH AND REPLACE

WITH MATERIAL SIMILAR TO ADJACENT CONSTRUCTION.

10. WHERE EXISTING PIPING AND EQUIPMENT, ETC., THAT ARE TO BE UTILIZED IN

THE COMPLETED PROGRAM CONFLICT WITH NEW CONSTRUCTION AND THE

REQUIRED DEMOLITION, THEY SHALL BE RELOCATED AND RECONNECTED TO

MAINTAIN THE DESIRED SERVICE.

11. PORTIONS OF EXISTING SYSTEMS MAY BE SHOWN FOR CLARITY EVEN

THOUGH IT MAY NOT BE NECESSARY TO MODIFY OR REVISE THEM. ALL

EXISTING SYSTEMS ARE SHOWN BASED ON ORIGINAL OR REMODEL BUILDING

DRAWINGS. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS.

12. ALL WORK MUST BE COORDINATED AND SCHEDULED WITH THE OWNER AND

OCCUPANTS OF THIS BUILDING SO AS TO PROVIDE THE LEAST AMOUNT OF

DISRUPTION OF BUILDING ACTIVITIES AS POSSIBLE. MAINTAIN CONDITIONED

SPACE FOR ALL OWNER OCCUPIED AREAS DURING CONSTRUCTION.

13. ALL ACCESSIBLE ABANDONED PIPING AND DUCTWORK SHALL BE REMOVED

AND PROPERLY DISPOSED OF.

SEISMIC BRACING NOTES

SOME MECHANICAL AND PLUMBING COMPONENTS OF THIS BUILDING REQUIRE

SEISMIC BRACING. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR AND THE

GC TO ENGAGE A SEISMIC DESIGN ENGINEER TO DETERMINE AND DESIGN THE

REQUIRED BRACING FOR EACH SYSTEM.

SYSTEM REQUIRING BRACING INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

1. ALL LIFE-SAFETY COMPONENTS INCLUDING FIRE PROTECTION SYSTEMS.

2. COMPONENTS WEIGHING MORE THAN 400 POUNDS.

3. COMPONENTS WITH A CENTER OF MASS GREATER THAN 4 FEET ABOVE

FLOOR LEVEL AND WEIGHING MORE THAN 20 POUNDS. (E.G. TERMINAL

UNITS)

4. DISTRIBUTION SYSTEMS WEIGHING MORE THAN 5 POUNDS PER FOOT. (E.G.

12X12, 22 GAUGE, SHEET STEEL DUCTWORK AND CHILLED, HEATING,

DOMESTIC HOT, AND DOMESTIC COLD WATER PIPING LARGER THAN 1-1/2".

FLEXIBLE CONNECTIONS ARE REQUIRED BETWEEN ALL COMPONENTS AND

ASSOCIATED DUCTWORK, PIPING, AND CONDUITS.

THE FOLLOWING COMPONENTS ARE NOT REQUIRED TO BE BRACED:

1. PLUMBING FIXTURES

THE CONTRACTOR SHALL PROVIDE ALL COMPONENTS WEIGHTS TO SEISMIC

DESIGN ENGINEER FOR USE IN BRACING DESIGN.

BRACING SHALL BE DESIGNED TO MEET ASCE7 AND NFPA 13 BRACING

REQUIREMENTS. REFER TO ASCE7 CHAPTER 13 FOR MORE INFORMATION ON

SYSTEMS REQUIRED TO BE BRACED

ISSUED FOR BID

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 www.pec1.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

FSC, Inc.

Fire Protection and Life Safety Engineers 8675 W. 96th Street, Overland Park, KS 66212

Phone: 913-722-3473 www.fsc-inc.com

/1

/2

:2

:2

P

M B

IM

/1

R

A tr ia x K a n s a s C it y V

A R e n o v a te B ld g

/2

-0

-M E

C H

-R

.r v t

PP000

PLUMBING NOTES AND SYMBOLS Renovate Bldg 26 for Pharmacy, Phlebotomy, and Police

Kansas City VA Medical Center Kansas City, MO

589-21-211

April 17, 2026 EKE AMA 47 83

SHEET LIST

PP000 PLUMBING NOTES AND SYMBOLS

PD101 PLUMBING DEMOLITION PLAN - POLICE & PHLEBOTOMY

PD102 PLUMBING DEMOLITION PLAN - X-RAY & CT SCAN

PL100 PLUMBING BASEMENT PLAN

PL101 PLUMBING FLOOR PLAN - POLICE & PHLEBOTOMY - WASTE

& VENT

PL102 PLUMBING FLOOR PLAN - POLICE & PHLEBOTOMY -

DOMESTIC WATER

PL103 PLUMBING FLOOR PLAN - X-RAY & CT SCAN

PL201 MEDICAL GAS FLOOR PLAN - X-RAY & CT SCAN

PP501 PLUMBING DETAILS & SCHEDULES

Revisions: Date:

04/16/2026

Atriax, pllc 703 Main Ave SW, Hickory, NC 28602 PO Box 1629, Hickory, NC 28603 Phone: 828-315-9962 www.atriaxgroup.com

( EX )3"( EX )3"

( EX )1-1/2''

( EX )1-1/2''

( EX )3"( EX )3"

( EX)2"V

( EX)3/4"( EX)3/4"( EX)3/4"

( EX)2"V

( EX)3/4"( EX)3/4"( EX)3/4"

( EX)1-1/4''

( EX)1/2"( EX)1/2"

( EX)2"V

(E)FD

(E)FD

( EX)4" ( EX)2"

( EX)2"

( EX)2"

( EX)2"

( EX)2"

( EX)2"

( EX)2"

( EX )1"( EX )1"( EX )1"

( EX)1/2"( EX)1/2"

( EX )1-1/2''

( EX )3"

( EX )3"

DEMOLITION THAT REQUIRES ENTRY INTO PHYSICAL MEDICINE

AND REHABILITATION AREA WILL NEED TO BE DONE DURING

OFF HOURS. SCHEDULE ALL WORK IN THIS AREA WITH VA

PERSONNEL TO AVOID DISTURBANCE TO PATIENT CARE.

PLUMBING DEMO NOTES

1. PLANS ARE SCHEMATIC IN NATURE, LAYOUT IS BASED

ON BEST AVAILABLE INFORMATION. CONTRACTOR

SHALL FIELD VERIFY EXISTING CONDITIONS AND

DIMENSIONS. BRING ANY DISCREPANCIES FROM THE

DRAWINGS AND NOTES TO THE OWNER'S

REPRESENTATIVE IMMEDIATELY. MINOR CHANGES IN

THE SCOPE OF THE DEMOLITION WORK SHALL NOT

JUSTIFY AN ADDITIONAL COST.

2. CONTRACTOR SHALL CLEAN ALL EXISTING PLUMBING

FIXTURES TO REMAIN IN AREA OF WORK TO LIKE-NEW

CONDITION AND PROVIDE A LIST OF ANY DEFICIENCIES

TO OWNER'S REPRESENTATIVE.

3. DEMOLISH ALL PLUMBING FIXTURES, DOMESTIC WATER

PIPING, WASTE AND VENT PIPING AND EQUIPMENT

SHOWN SHADED AND DASHED IN A DARK LINE WEIGHT.

CAP PIPING AT MAINS.

4. ANY PIPING OR DUCTWORK DEMOLISHED OUTSIDE OF

CONSTRUCTION BARRIER SHALL BE DONE AFTER

HOURS AND COORDINATED WITH OWNER FOR ACCESS.

ISSUED FOR BID

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 www.pec1.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

POLICE/PHLEBOTOMY

KEYPLAN

PLAN NORTH

FSC, Inc.

Fire Protection and Life Safety Engineers 8675 W. 96th Street, Overland Park, KS 66212

Phone: 913-722-3473 www.fsc-inc.com

/1

/2

:2

:2

P

M B

IM

/1

R

A tr ia x K a n s a s C it y V

A R e n o v a te B ld g

/2

-0

-M E

C H

-R

.r v t

PD101

PLUMBING DEMOLITION PLAN -

POLICE & PHLEBOTOMY

Renovate Bldg 26 for Pharmacy, Phlebotomy, and Police

Kansas City VA Medical Center Kansas City, MO

589-21-211

April 17, 2026 EKE AMA 48 83

PLAN NOTES

1 REMOVE EXISTING SANITARY PIPING BACK TO RISER.

PRIOR TO DEMOLITION, CONFIRM ANY OUT OF SCOPE

PIPING CONNECTIONS THAT WOULD BE AFFECTED BY

WASTE LINE REMOVAL.

2 REMOVE EXISTING PLUMBING FIXTURE AND ALL

ASSOCIATED WATER, WASTE, AND VENT PIPING BACK

TO LOCATION SHOWN AND CAP.

Revisions: Date:

04/16/2026

Atriax, pllc 703 Main Ave SW, Hickory, NC 28602 PO Box 1629, Hickory, NC 28603

( ) E 2-1/2'' ( ) E 1-1/2''( ) E 1-1/2''

( ) E 1/2"( ) E 1/2"( ) E 1/2"

( ) E 1-1/4'' ( ) E 3/4"

( ) E 3/4"

( ) E 1/2"( ) E 1/2"( ) E 1/2"

( ) E 1/2"( ) E 1/2"( ) E 1/2"

EXISTING WASTE

STACK TO REMAIN

REMOVE EXISTING FIXTURE

AND ALL ASSOCIATED PIPING

BACK TO MAINS AND CAP

( ) E 2"V

PREPARE EXISTING SINK FOR

RECONNECTION UNDER NEW WORK.

PLUMBING DEMO NOTES

1. PLANS ARE SCHEMATIC IN NATURE, LAYOUT IS BASED

ON BEST AVAILABLE INFORMATION. CONTRACTOR

SHALL FIELD VERIFY EXISTING CONDITIONS AND

DIMENSIONS. BRING ANY DISCREPANCIES FROM THE

DRAWINGS AND NOTES TO THE OWNER'S

REPRESENTATIVE IMMEDIATELY. MINOR CHANGES IN

THE SCOPE OF THE DEMOLITION WORK SHALL NOT

JUSTIFY AN ADDITIONAL COST.

2. CONTRACTOR SHALL CLEAN ALL EXISTING PLUMBING

FIXTURES TO REMAIN IN AREA OF WORK TO LIKE-NEW

CONDITION AND PROVIDE A LIST OF ANY DEFICIENCIES

TO OWNER'S REPRESENTATIVE.

3. DEMOLISH ALL PLUMBING FIXTURES, DOMESTIC WATER

PIPING, WASTE AND VENT PIPING AND EQUIPMENT

SHOWN SHADED AND DASHED IN A DARK LINE WEIGHT.

CAP PIPING AT MAINS.

4. ANY PIPING OR DUCTWORK DEMOLISHED OUTSIDE OF

CONSTRUCTION BARRIER SHALL BE DONE AFTER

HOURS AND COORDINATED WITH OWNER FOR ACCESS.

ISSUED FOR BID

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 www.pec1.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

XRAY/CT

KEYPLAN

PLAN NORTH

FSC, Inc.

Fire Protection and Life Safety Engineers 8675 W. 96th Street, Overland Park, KS 66212

Phone: 913-722-3473 www.fsc-inc.com

/1

/2

:2

:2

P

M B

IM

/1

R

A tr ia x K a n s a s C it y V

A R e n o v a te B ld g

/2

-0

-M E

C H

-R

.r v t

PD102

PLUMBING DEMOLITION PLAN -

X-RAY & CT SCAN

Renovate Bldg 26 for Pharmacy, Phlebotomy, and Police

Kansas City VA Medical Center Kansas City, MO

589-21-211

April 17, 2026 EKE AMA 49 83

0 4' 8'2'1/4" = 1'-0"A

PLUMBING DEMOLITION PLAN - X-RAY & CT SCANNER

PLAN NOTES

1 REMOVE EXISTING PLUMBING FIXTURE AND ALL

ASSOCIATED WATER, WASTE, AND VENT PIPING BACK

TO LOCATION SHOWN AND CAP.

Revisions: Date:

04/16/2026

Atriax, pllc 703 Main Ave SW, Hickory, NC 28602 PO Box 1629, Hickory, NC 28603

(EX)26-AHU-B-10

4"W UP TO WCO/VENT

4"W DOWN FROM WC

2"W DOWN FROM LAV

2"W DOWN FROM SHOWER

2"V UP IN WALL

2"W DOWN

FROM 2"FD

4"W

4"W

2"W DOWN

FROM LAV

4"W DOWN

FROM WC

2"V UP IN WALL

2"W DOWN FROM FD

2"W DOWN

FROM SHOWER

3"W DOWN

FROM MB

2"W DOWN

FROM FD

2"V UP IN WALL

2"W DOWN

FROM SINK

2"W DOWN FROM FD 2"V UP IN WALL

4"W DOWN

FROM WC

2"W DOWN FROM SINK

2"W DOWN FROM LAV

2"W DOWN FROM FD

2"V UP

IN WALL

4"W DOWN

FROM WC

2"W DOWN

FROM SINK

CO

2"W DOWN

FROM LAV

4"W

4"W

CONNECT TO EXISTING 2"W

SERVING EXISTING SINK ABOVE.

2"W DOWN

FROM SINK

2"W DOWN

FROM SINK

4"W DOWN FROM WC

2"W DOWN

FROM SINK

2"W DOWN

FROM FD

EXISTING 4" WASTE STACK (EX)26-AHU-B-11

2"V UP IN WALL

( ) E 4"W

2"W

4"W

2"W 4"W

ROUTE 1-1/4" CONDENSATE LINE AND 1"

DRAIN LINE TO CLOSEST FLOOR DRAIN.

4"W DOWN FROM WCO

4"W DOWN FROM WCO

3"W DOWN

FROM FS

2"V UP IN WALL

4"W DOWN FROM WCO

2"W DOWN FROM SINK

2"CO

THERE IS SIGNIFICANT EXISTING DUCTWORK AND PIPING

IN THIS SPACE. IT IS CONTRACTORS RESPONSIBILITY TO

FIELD VERIFY ALL CONDITIONS PRIOR TO BID.

4"W DOWN FROM WCO

2"W DOWN FROM WCO

PLUMBING GENERAL NOTES

1. REFER TO THE PLUMBING FIXTURE SCHEDULE FOR

PIPE SIZES TO INDIVIDUAL FIXTURES.

2. PROVIDE CLEANOUTS ON WASTE, VENT AND STORM

PIPING AS REQUIRED BY CODE AND FOR REASONABLE

MAINTENANCE BASED ON ACTUAL FIELD INSTALLATION.

3. PIPING ON EXTERIOR WALLS OR PRE-CAST WALLS TO

BE ROUTED IN FRAMED WALL ON INTERIOR SIDE OF

INSULATION.

4. TERMINATE PLUMBING VENTS NOT LESS THAN 12”

ABOVE ROOF AND A MINIMUM OF 25’-0” FROM

MECHANICAL OUTDOOR AIR INTAKES.

5. AVOID ROUTING OVER ELECTRICAL ROOMS AND

ELECTRICAL PANELS; MAINTAIN N.E.C. CLEARANCES.

COORDINATE ROUTING WITH ELECTRICAL

CONTRACTOR.

6. ROUTE DOMESTIC HOT WATER RECIRCULATION PIPES

DOWN THE WALL TO WITHIN 2’ OF ALL PUBLIC

LAVATORIES WITH A ½” RUNOUT. IF TWO OR MORE

LAVATORIES SHARE A ¾” OR LARGER BRANCH PIPE,

THE HOT WATER RECIRCULATION PIPE SHALL CONNECT

TO WITHIN 6” OF EACH LAVATORY.

7. ALL VALVES SHALL BE INSTALLED ABOVE DROP-IN

CEILINGS IN ACCESSIBLE LOCATIONS, OR WITH ACCESS

PANELS IN HARD LID CEILINGS.

8. ACCESS PANELS SHALL BE 24x24, UNLESS NOTED

OTHERWISE. LOCATIONS SHOWN ARE APPROXIMATE,

EXACT LOCATIONS SHALL BE COORDINATED WITH THE

ARCHITECTURAL DRAWINGS AND EQUIPMENT

LOCATIONS. PROVIDE RATED ACCESS PANELS

WHEREVER REQUIRED BY APPLICABLE CODES.

9. ALL PIPING SHALL BE ROUTED AS HIGH AS POSSIBLE IN

THE CEILING SPACE. UTILIZE JOIST SPACE WHEN

POSSIBLE, ESPECIALLY WHERE CROSSING OTHER

PIPES, DUCTS AND ELECTRICAL.

10. PROVIDE ACCESSIBLE SHUT-OFF VALVES TO ALL

APPLIANCES AND EQUIPMENT.

11. TRAP GUARDS SHALL BE INSTALLED AT ALL FLOOR

RECEPTORS. INSTALL IN ACCORDANCE WITH IPC.

12. COORDINATE ROUTING OF CONDENSATE DRAIN LINES

WITH OTHER TRADES PRIOR TO INSTALLATION TO

ENSURE SLOPE CAN BE MET.

13. VERIFY AND REFER TO ARCHITECTURAL DIMENSIONAL

FLOOR PLAN FOR EXACT LOCATIONS OF ALL FIXTURES

AND EQUIPMENT.

14. ANY PIPING REQUIRED TO BE INSTALLED OUTSIDE OF

CONSTRUCTION BARRIER SHALL BE DONE AFTER

HOURS AND COORDINATED WITH OWNER FOR ACCESS.

ISSUED FOR BID

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 www.pec1.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

KEYPLAN

PLAN NORTH

BASEMENT

FSC, Inc.

Fire Protection and Life Safety Engineers 8675 W. 96th Street, Overland Park, KS 66212

Phone: 913-722-3473 www.fsc-inc.com

/1

/2

:2

:3

P

M B

IM

/1

R

A tr ia x K a n s a s C it y V

A R e n o v a te B ld g

/2

-0

-M E

C H

-R

.r v t

PL100

PLUMBING BASEMENT PLAN Renovate Bldg 26 for Pharmacy, Phlebotomy, and Police

Kansas City VA Medical Center Kansas City, MO

589-21-211

April 17, 2026 EKE AMA 50 83

0 8' 16'4'1/8" = 1'-0"A

PLUMBING FLOOR PLAN - BASEMENT

Revisions: Date:

04/16/2026

Atriax, pllc 703 Main Ave SW, Hickory, NC 28602 PO Box 1629, Hickory, NC 28603

MEN'S LOCKER

V1-613

INTERVIEW

V1-611

LOUNGE, STAFF

V1-608

GUN CLEANING

V1-610

ARMORY

V1-610a

WOMEN'S LOCKER

V1-612

WOMEN'S RR

V1-612a

EVID

V1-616

SUPERVISOR

V1-618

OFFICE, CHIEF

V1-620

OFFICE, ASST CHIEF

V1-622

SQUAD

V1-624

CONF/INCIDENT COMMAND CENTER

V1-619

OFFICE, ADMIN ASST

V1-623

MEN'S RR

V1-613a

CORRIDOR

C1-60

RECEPTION

V1-630a

TLT

V1-633

BLOOD SPECIMEN COLLECTION ROOM

V1-635

BLOOD SPECIMEN COLLECTION ROOM

V1-631

CORRIDOR

C1-64

WAITING

V1-630

BLOOD SPECIMEN COLLECTION ROOM

V1-637

BLOOD SPECIMEN COLLECTION ROOM

V1-639

TLT

V1-641

JAN

V1-632

LOUNGE, STAFF

V1-638

ID/COMMAND CTR

M1-341

STORAGE

M1-346

MECHANICAL

M1-344

HOLDING

M1-342SECURITY

M1-343

ENTRY

M1-340

CORRIDOR

C1-35

WAITING ROOM

V1-615

BIOMED NETWORK CLOSET

V1-602

ELEC. CLOSET

V1-604

ELEVATOR NO. 22

E22

ELEVATOR NO. 12

E12

ELEVATOR NO. 11

E11

STAIRWELL NO. 16

S16

Room

V1-600

CORRIDOR

C1-62B

P-418

P-418 P-418

P-418

P-528

P-418

P-502

P-115

P-529

P-418

P-115

P-418P-418

P-702

P-115

P-702

2"V

( ) E 2"

( EX)2"V

CO

P-812

P-812

2"FD

2"FD

WCO

FD-2

1-1/2''V

2"V

2"V

2"V

2"V

2"FD

2"FD

P-115

2"V

WCO

WCO

2"FD

WCO

WCO

PLUMBING GENERAL NOTES

1. REFER TO THE PLUMBING FIXTURE SCHEDULE FOR

PIPE SIZES TO INDIVIDUAL FIXTURES.

2. PROVIDE CLEANOUTS ON WASTE, VENT AND STORM

PIPING AS REQUIRED BY CODE AND FOR REASONABLE

MAINTENANCE BASED ON ACTUAL FIELD INSTALLATION.

3. PIPING ON EXTERIOR WALLS OR PRE-CAST WALLS TO

BE ROUTED IN FRAMED WALL ON INTERIOR SIDE OF

INSULATION.

4. TERMINATE PLUMBING VENTS NOT LESS THAN 12”

ABOVE ROOF AND A MINIMUM OF 25’-0” FROM

MECHANICAL OUTDOOR AIR INTAKES.

5. AVOID ROUTING OVER ELECTRICAL ROOMS AND

ELECTRICAL PANELS; MAINTAIN N.E.C. CLEARANCES.

COORDINATE ROUTING WITH ELECTRICAL

CONTRACTOR.

6. ROUTE DOMESTIC HOT WATER RECIRCULATION PIPES

DOWN THE WALL TO WITHIN 2’ OF ALL PUBLIC

LAVATORIES WITH A ½” RUNOUT. IF TWO OR MORE

LAVATORIES SHARE A ¾” OR LARGER BRANCH PIPE,

THE HOT WATER RECIRCULATION PIPE SHALL CONNECT

TO WITHIN 6” OF EACH LAVATORY.

7. ALL VALVES SHALL BE INSTALLED ABOVE DROP-IN

CEILINGS IN ACCESSIBLE LOCATIONS, OR WITH ACCESS

PANELS IN HARD LID CEILINGS.

8. ACCESS PANELS SHALL BE 24x24, UNLESS NOTED

OTHERWISE. LOCATIONS SHOWN ARE APPROXIMATE,

EXACT LOCATIONS SHALL BE COORDINATED WITH THE

ARCHITECTURAL DRAWINGS AND EQUIPMENT

LOCATIONS. PROVIDE RATED ACCESS PANELS

WHEREVER REQUIRED BY APPLICABLE CODES.

9. ALL PIPING SHALL BE ROUTED AS HIGH AS POSSIBLE IN

THE CEILING SPACE. UTILIZE JOIST SPACE WHEN

POSSIBLE, ESPECIALLY WHERE CROSSING OTHER

PIPES, DUCTS AND ELECTRICAL.

10. PROVIDE ACCESSIBLE SHUT-OFF VALVES TO ALL

APPLIANCES AND EQUIPMENT.

11. TRAP GUARDS SHALL BE INSTALLED AT ALL FLOOR

RECEPTORS. INSTALL IN ACCORDANCE WITH IPC.

12. COORDINATE ROUTING OF CONDENSATE DRAIN LINES

WITH OTHER TRADES PRIOR TO INSTALLATION TO

ENSURE SLOPE CAN BE MET.

13. VERIFY AND REFER TO ARCHITECTURAL DIMENSIONAL

FLOOR PLAN FOR EXACT LOCATIONS OF ALL FIXTURES

AND EQUIPMENT.

14. ANY PIPING REQUIRED TO BE INSTALLED OUTSIDE OF

CONSTRUCTION BARRIER SHALL BE DONE AFTER

HOURS AND COORDINATED WITH OWNER FOR ACCESS.

ISSUED FOR BID

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 www.pec1.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

POLICE/PHLEBOTOMY

KEYPLAN

PLAN NORTH

FSC, Inc.

Fire Protection and Life Safety Engineers 8675 W. 96th Street, Overland Park, KS 66212

Phone: 913-722-3473 www.fsc-inc.com

/1

/2

:2

:3

P

M B

IM

/1

R

A tr ia x K a n s a s C it y V

A R e n o v a te B ld g

/2

-0

-M E

C H

-R

.r v t

PL101

PLUMBING FLOOR PLAN - POLICE &

PHLEBOTOMY - WASTE & VENT

Renovate Bldg 26 for Pharmacy, Phlebotomy, and Police

Kansas City VA Medical Center Kansas City, MO

589-21-211

April 17, 2026 EKE AMA 51 83

0 4' 8'2'1/4" = 1'-0"A

PLUMBING FLOOR PLAN - POLICE & PHLEBOTOMY - WASTE AND VENT

PLAN NOTES

1 ROUTE CONDENSATE FROM ICE MAKER TO FLOOR

DRAIN AND TERMINATE WITH AIR GAP.

2 EXISTING SANITARY RISER TO REMAIN.

Revisions: Date:

04/16/2026

Atriax, pllc 703 Main Ave SW, Hickory, NC 28602 PO Box 1629, Hickory, NC 28603

MEN'S LOCKER

V1-613

INTERVIEW

V1-611

LOUNGE, STAFF

V1-608

GUN CLEANING

V1-610

ARMORY

V1-610a

WOMEN'S LOCKER

V1-612

WOMEN'S RR

V1-612a

EVID

V1-616

SUPERVISOR

V1-618

OFFICE, CHIEF

V1-620

OFFICE, ASST CHIEF

V1-622

SQUAD

V1-624

CONF/INCIDENT COMMAND CENTER

V1-619

OFFICE, ADMIN ASST

V1-623

MEN'S RR

V1-613a

CORRIDOR

C1-60

RECEPTION

V1-630a

TLT

V1-633

BLOOD SPECIMEN COLLECTION ROOM

V1-635

BLOOD SPECIMEN COLLECTION ROOM

V1-631

CORRIDOR

C1-64

WAITING

V1-630

BLOOD SPECIMEN COLLECTION ROOM

V1-637

BLOOD SPECIMEN COLLECTION ROOM

V1-639

TLT

V1-641

JAN

V1-632

LOUNGE, STAFF

V1-638

ID/COMMAND CTR

M1-341

STORAGE

M1-346

MECHANICAL

M1-344

HOLDING

M1-342SECURITY

M1-343

ENTRY

M1-340

CORRIDOR

C1-35

WAITING ROOM

V1-615

BIOMED NETWORK CLOSET

V1-602

ELEC. CLOSET

V1-604

ELEVATOR NO. 22

E22

ELEVATOR NO. 12

E12

ELEVATOR NO. 11

E11

STAIRWELL NO. 16

S16

Room

V1-600

CORRIDOR

C1-62B

P-418

P-418 P-418

P-418

P-528

P-418

P-502

P-115

P-529

P-418

P-115

P-418P-418

P-702

P-115

P-702

3/4" CW AND HW DOWN IN WALL

TO SERVE LAV AND JANITOR SINK

3/4" CW AND 3/4" HW DOWN IN CHASE.

ROUTE WATER PIPING BENEATH

COUNTER TO SERVE SINK.

3/4"

( EX )1"( EX )1"( EX )1"

( EX )1-1/2''

1"

3/4"1/2"

3"

3/4"

WHA-A

WHA-A

WATER BOX MOUNT

BOTTOM AT 42" AFF

SET AT .5 GPM

1/2"

P-812

P-812

1/2"

1/2"1/2"

3"

1-1/2''

1-1/2''

3" 3"

( EX )3"

1/2"

1-1/2''

WHA-A

3"

3"

3"

3/4"

3"

1-1/4''

3"

PLUMBING GENERAL NOTES

1. REFER TO THE PLUMBING FIXTURE SCHEDULE FOR

PIPE SIZES TO INDIVIDUAL FIXTURES.

2. PROVIDE CLEANOUTS ON WASTE, VENT AND STORM

PIPING AS REQUIRED BY CODE AND FOR REASONABLE

MAINTENANCE BASED ON ACTUAL FIELD INSTALLATION.

3. PIPING ON EXTERIOR WALLS OR PRE-CAST WALLS TO

BE ROUTED IN FRAMED WALL ON INTERIOR SIDE OF

INSULATION.

4. TERMINATE PLUMBING VENTS NOT LESS THAN 12”

ABOVE ROOF AND A MINIMUM OF 25’-0” FROM

MECHANICAL OUTDOOR AIR INTAKES.

5. AVOID ROUTING OVER ELECTRICAL ROOMS AND

ELECTRICAL PANELS; MAINTAIN N.E.C. CLEARANCES.

COORDINATE ROUTING WITH ELECTRICAL

CONTRACTOR.

6. ROUTE DOMESTIC HOT WATER RECIRCULATION PIPES

DOWN THE WALL TO WITHIN 2’ OF ALL PUBLIC

LAVATORIES WITH A ½” RUNOUT. IF TWO OR MORE

LAVATORIES SHARE A ¾” OR LARGER BRANCH PIPE,

THE HOT WATER RECIRCULATION PIPE SHALL CONNECT

TO WITHIN 6” OF EACH LAVATORY.

7. ALL VALVES SHALL BE INSTALLED ABOVE DROP-IN

CEILINGS IN ACCESSIBLE LOCATIONS, OR WITH ACCESS

PANELS IN HARD LID CEILINGS.

8. ACCESS PANELS SHALL BE 24x24, UNLESS NOTED

OTHERWISE. LOCATIONS SHOWN ARE APPROXIMATE,

EXACT LOCATIONS SHALL BE COORDINATED WITH THE

ARCHITECTURAL DRAWINGS AND EQUIPMENT

LOCATIONS. PROVIDE RATED ACCESS PANELS

WHEREVER REQUIRED BY APPLICABLE CODES.

9. ALL PIPING SHALL BE ROUTED AS HIGH AS POSSIBLE IN

THE CEILING SPACE. UTILIZE JOIST SPACE WHEN

POSSIBLE, ESPECIALLY WHERE CROSSING OTHER

PIPES, DUCTS AND ELECTRICAL.

10. PROVIDE ACCESSIBLE SHUT-OFF VALVES TO ALL

APPLIANCES AND EQUIPMENT.

11. TRAP GUARDS SHALL BE INSTALLED AT ALL FLOOR

RECEPTORS. INSTALL IN ACCORDANCE WITH IPC.

12. COORDINATE ROUTING OF CONDENSATE DRAIN LINES

WITH OTHER TRADES PRIOR TO INSTALLATION TO

ENSURE SLOPE CAN BE MET.

13. VERIFY AND REFER TO ARCHITECTURAL DIMENSIONAL

FLOOR PLAN FOR EXACT LOCATIONS OF ALL FIXTURES

AND EQUIPMENT.

14. ANY PIPING REQUIRED TO BE INSTALLED OUTSIDE OF

CONSTRUCTION BARRIER SHALL BE DONE AFTER

HOURS AND COORDINATED WITH OWNER FOR ACCESS.

ISSUED FOR BID

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 www.pec1.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

POLICE/PHLEBOTOMY

KEYPLAN

PLAN NORTH

FSC, Inc.

Fire Protection and Life Safety Engineers 8675 W. 96th Street, Overland Park, KS 66212

Phone: 913-722-3473 www.fsc-inc.com

/1

/2

:2

:3

P

M B

IM

/1

R

A tr ia x K a n s a s C it y V

A R e n o v a te B ld g

/2

-0

-M E

C H

-R

.r v t

PL102

PLUMBING FLOOR PLAN - POLICE &

PHLEBOTOMY - DOMESTIC WATER

Renovate Bldg 26 for Pharmacy, Phlebotomy, and Police

Kansas City VA Medical Center Kansas City, MO

589-21-211

April 17, 2026 EKE AMA 52 83

NOT TO SCALE

PLUMBING FLOOR PLAN - POLICE & PHLEBOTOMY - WATER

PLAN NOTES

1 PROVIDE SHUT-OFF VALVES AT EACH BRANCH

TAKE-OFF FOR HW & CW FOR EACH FIXTURE ABOVE

THE CEILING.

Revisions: Date:

04/16/2026

Atriax, pllc 703 Main Ave SW, Hickory, NC 28602 PO Box 1629, Hickory, NC 28603

CT COMPONENT RM

V1-799

CT SCAN RM

V1-682

CONTROL RM

V1-682a

R/F IMAGING ROOM

V1-680

R/F CONTROL ROOM

V1-680a

R/F PT TOILET / DRESSING

V1-680b

C45 EXAM ROOM

V1-795

C34 EXAM ROOM

V1-781

SUPPLY ROOM

V1-684

C46 EXAM ROOM

V1-797

SUPPLY CLOSET

V1-684A

BIOMED NETWORK CLOSET

V1-685

CORRIDOR

C1-74

CORRIDOR

C1-63

VESTIBULE

C1-63A

CORRIDOR

C1-72A

C34 EXAM ROOM

V1-783

P-115

P-418

P-418

P-528

2"

(E)4" WASTE DOWN

(E)2" VENT UP

1"1"

CD

( ) E 2"V

26-MS-IU-01

26-MS-IU-02

2"FD

1"

1" DRAIN FOR HUMIDIFIER

1-1/4" CONDENSATE LINE AND

1" DRAIN LINE DOWN IN CHASE

TO FLOOR BELOW.

CD

D

WCO

PLUMBING GENERAL NOTES

1. REFER TO THE PLUMBING FIXTURE SCHEDULE FOR

PIPE SIZES TO INDIVIDUAL FIXTURES.

2. PROVIDE CLEANOUTS ON WASTE, VENT AND STORM

PIPING AS REQUIRED BY CODE AND FOR REASONABLE

MAINTENANCE BASED ON ACTUAL FIELD INSTALLATION.

3. PIPING ON EXTERIOR WALLS OR PRE-CAST WALLS TO

BE ROUTED IN FRAMED WALL ON INTERIOR SIDE OF

INSULATION.

4. TERMINATE PLUMBING VENTS NOT LESS THAN 12”

ABOVE ROOF AND A MINIMUM OF 25’-0” FROM

MECHANICAL OUTDOOR AIR INTAKES.

5. AVOID ROUTING OVER ELECTRICAL ROOMS AND

ELECTRICAL PANELS; MAINTAIN N.E.C. CLEARANCES.

COORDINATE ROUTING WITH ELECTRICAL

CONTRACTOR.

6. ROUTE DOMESTIC HOT WATER RECIRCULATION PIPES

DOWN THE WALL TO WITHIN 2’ OF ALL PUBLIC

LAVATORIES WITH A ½” RUNOUT. IF TWO OR MORE

LAVATORIES SHARE A ¾” OR LARGER BRANCH PIPE,

THE HOT WATER RECIRCULATION PIPE SHALL CONNECT

TO WITHIN 6” OF EACH LAVATORY.

7. ALL VALVES SHALL BE INSTALLED ABOVE DROP-IN

CEILINGS IN ACCESSIBLE LOCATIONS, OR WITH ACCESS

PANELS IN HARD LID CEILINGS.

8. ACCESS PANELS SHALL BE 24x24, UNLESS NOTED

OTHERWISE. LOCATIONS SHOWN ARE APPROXIMATE,

EXACT LOCATIONS SHALL BE COORDINATED WITH THE

ARCHITECTURAL DRAWINGS AND EQUIPMENT

LOCATIONS. PROVIDE RATED ACCESS PANELS

WHEREVER REQUIRED BY APPLICABLE CODES.

9. ALL PIPING SHALL BE ROUTED AS HIGH AS POSSIBLE IN

THE CEILING SPACE. UTILIZE JOIST SPACE WHEN

POSSIBLE, ESPECIALLY WHERE CROSSING OTHER

PIPES, DUCTS AND ELECTRICAL.

10. PROVIDE ACCESSIBLE SHUT-OFF VALVES TO ALL

APPLIANCES AND EQUIPMENT.

11. TRAP GUARDS SHALL BE INSTALLED AT ALL FLOOR

RECEPTORS. INSTALL IN ACCORDANCE WITH IPC.

12. COORDINATE ROUTING OF CONDENSATE DRAIN LINES

WITH OTHER TRADES PRIOR TO INSTALLATION TO

ENSURE SLOPE CAN BE MET.

13. VERIFY AND REFER TO ARCHITECTURAL DIMENSIONAL

FLOOR PLAN FOR EXACT LOCATIONS OF ALL FIXTURES

AND EQUIPMENT.

14. ANY PIPING REQUIRED TO BE INSTALLED OUTSIDE OF

CONSTRUCTION BARRIER SHALL BE DONE AFTER

HOURS AND COORDINATED WITH OWNER FOR ACCESS.

CT COMPONENT RM

V1-799

CT SCAN RM

V1-682

CONTROL RM

V1-682a

R/F IMAGING ROOM

V1-680

R/F CONTROL ROOM

V1-680a

R/F PT TOILET / DRESSING

V1-680b

C45 EXAM ROOM

V1-795

C34 EXAM ROOM

V1-781

SUPPLY ROOM

V1-684

C46 EXAM ROOM

V1-797

SUPPLY CLOSET

V1-684A

BIOMED NETWORK CLOSET

V1-685

CORRIDOR

C1-74

CORRIDOR

C1-63

VESTIBULE

C1-63A

CORRIDOR

C1-72A

C34 EXAM ROOM

V1-783

P-115

P-418

P-418

P-528

1/2"

( EX )1-1/2''( EX )1-1/2''

2-1/2''

1/2"

FD

26-MS-IU-01

26-MS-IU-02

CONNECT NEW 1/2"CW, 1/2"HW

TO EXISTING SINK.

1/2" CW TO HUMIDIFIER

2-1/2''

( EX )2-1/2'' ( EX )2-1/2''

2-1/2''

2-1/2''

WHA

1/2"

ISSUED FOR BID

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 www.pec1.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

XRAY/CT

KEYPLAN

PLAN NORTH

FSC, Inc.

Fire Protection and Life Safety Engineers 8675 W. 96th Street, Overland Park, KS 66212

Phone: 913-722-3473 www.fsc-inc.com

/1

/2

:2

:4

P

M B

IM

/1

R

A tr ia x K a n s a s C it y V

A R e n o v a te B ld g

/2

-0

-M E

C H

-R

.r v t

PL103

PLUMBING FLOOR PLAN - X-RAY & CT

SCAN

Renovate Bldg 26 for Pharmacy, Phlebotomy, and Police

Kansas City VA Medical Center Kansas City, MO

589-21-211

April 17, 2026 EKE AMA 53 83

0 4' 8'2'1/4" = 1'-0"A

PLUMBING FLOOR PLAN - X-RAY & CT SCANNER - WASTE & VENT

0 4' 8'2'1/4" = 1'-0"B

PLUMBING FLOOR PLAN - X-RAY & CT SCANNER - WATER

PLAN NOTES

1 PROVIDE SHUT-OFF VALVES AT EACH BRANCH

TAKE-OFF FOR HW & CW FOR EACH FIXTURE ABOVE

THE CEILING.

2 VALVE AND CONNECT 1/2" CW AND 1" DRAIN LINE TO

HUMIDIFIER. INSTALL 5 MICRON FILTER ON COLD

WATERLINE. FROM HUMIDIFIER, VERIFY WATER AND

DRAIN REQUIREMENTS WITH MANUFACTURER.

Revisions: Date:

04/16/2026

Atriax, pllc 703 Main Ave SW, Hickory, NC 28602 PO Box 1629, Hickory, NC 28603

DN

( EX)3/4"VAC

( EX)1/2"O2

( EX)1/2"MA

1/2"MA

1/2"O2

3/4"VAC

CT COMPONENT RM

V1-799

CT SCAN RM

V1-682

CONTROL RM

V1-682a

R/F IMAGING ROOM

V1-680

R/F CONTROL ROOM

V1-680a

R/F PT TOILET / DRESSING

V1-680b

TOILET, FEMALE

V1-793

C45 EXAM ROOM

V1-795

C34 EXAM ROOM

V1-781

SUPPLY ROOM

V1-684

C46 EXAM ROOM

V1-797

SUPPLY CLOSET

V1-684A

BIOMED NETWORK CLOSET

V1-685

CHECK-IN

V1-706A

ARMORY & EVIDENCE ROOM

V1-675B

VA POLICE

V1-675A

OFFICE, SUPERVISOR

V1-673

OFFICE

V1-675

BIOMED NETWORK CLOSET

V1-671A

STAFF LOCKER / LOUNGE

V1-671

TRIAGE/ STATION 2

V1-654

ADMISSIONS

V1-683

ADMISSIONS

V1-687

EXAM

V1-642D

ED 11

V1-650

ED 12

V1-652

STAIRWELL NO. 18

S18

CORRIDOR

C1-74

CORRIDOR

C1-72

CORRIDOR

C1-63

CORRIDOR

C1-62

VESTIBULE

C1-63A

CORRIDOR

C1-72A

VESTIBULE

C1-62A

CORRIDOR

CORRIDOR

C1-77

AMBULANCE ENTRY

C1-62C

C34 EXAM ROOM

V1-783

MGO-1

( EX)3/4"VAC

( EX)1/2"O2

( EX)1/2"MA

( EX)1-1/4''VAC

( EX)3/4"O2

( EX)3/4"MA

1/2"MA

1/2"O2

3/4"VAC

LOCATION OF ZONE VALVE BOX

MED GAS GENERAL NOTES

1. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED

ON BEST AVAILABLE INFORMATION. CONTRACTOR

SHALL FIELD VERIFY EXISTING CONDITIONS AND

DIMENSIONS.

2. ALL CUTTING, PATCHING, AND DEMOLITION WORK

SHALL BE CLOSELY COORDINATED WITH THE EXISTING

CONDITIONS AND THE REQUIRED NEW WORK. G.C.

SHALL PATCH AND FINISH PENETRATIONS OF EXISTING

SURFACES TO MATCH ADJACENT SURFACES.

3. FIELD VERIFY BEST ROUTING FOR NEW PIPING AND

DUCTWORK. COORDINATE WITH EXISTING EQUIPMENT,

PIPING, AND DUCTWORK. PIPING SHALL RISE AND

DROP, JOG OR OFFSET AS REQUIRED TO AVOID

CONFLICTS. DUCTWORK SHALL TAKE PRECEDENCE

OVER ALL PIPING, EXCEPT WHERE GRADE MUST BE

MAINTAINED FOR DRAINAGE. ANY EXPENSES RISING

FROM LACK OF COORDINATION SHALL BE MADE AT THE

CONTRACTOR'S EXPENSE.

4. REFER TO ARCHITECTURAL SPECIFICATIONS AND

PLANS FOR PHASING OF DEMOLITION AND NEW WORK.

ADJACENT AREAS ARE OCCUPIED AND CONTRACTOR

SHALL WORK CLOSELY WITH OWNER TO SCHEDULE

DEMOLITION AND CONSTRUCTION TO BE AS LEAST

DISRUPTIVE AS POSSIBLE.

5. ANY PIPING REQUIRED TO BE INSTALLED OUTSIDE OF

CONSTRUCTION BARRIER SHALL BE DONE AFTER

HOURS AND COORDINATED WITH OWNER FOR ACCESS.

ISSUED FOR BID

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 www.pec1.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

XRAY/CT

KEYPLAN

PLAN NORTH

FSC, Inc.

Fire Protection and Life Safety Engineers 8675 W. 96th Street, Overland Park, KS 66212

Phone: 913-722-3473 www.fsc-inc.com

/1

/2

:2

:4

P

M B

IM

/1

R

A tr ia x K a n s a s C it y V

A R e n o v a te B ld g

/2

-0

-M E

C H

-R

.r v t

PL201

MEDICAL GAS FLOOR PLAN - X-RAY &

CT SCAN

Renovate Bldg 26 for Pharmacy, Phlebotomy, and Police

Kansas City VA Medical Center Kansas City, MO

589-21-211

April 17, 2026 EKE AMA 54 83 Revisions: Date:

04/16/2026

Atriax, pllc 703 Main Ave SW, Hickory, NC 28602 PO Box 1629, Hickory, NC 28603

5 FT

THRU [20]

6 8 10

[32][25] [40]

[65]

[50]

[75]

-1312 14 -16 -

[125][100]

[150]

[250]

[200]

[300]

[400]

[350]

[450]

[600]

[500]

20 241814 16128 1064 532 2 1/21 1/21 1 1/4

[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]

--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]

THRU 3/4

[2100] [2100]

[2100]

[2700]

[2400]

SIDE VIEW TRAPEZE HANGER FOR UP

TO 1000 LB. [453KG] UNIFORM LOAD

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

IN.

[mm]

FT.

[mm]

FT.

[mm]

[2 5m m

1" M

AX

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING

(8" [200mm] MIN.)

BAND

1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE

1/2" [15mm] DIA.

HANGER RODS WITH

36" [900mm] MAX.

SPACING ON EACH

CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH

COMPRESSIVE STRENGTH

INSULATION (9 PSF MIN.

DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

ADJUSTABLE CLEVIS HANGER

TYPE 1 - SEE SPECIFICATIONS ADJUSTABLE CLEVIS HANGER

TYPE 1 - SEE SPECIFICATIONS

FLOOR/HUB DRAIN

FLOOR

CLOSED

DIAPHRAGM

WASTE PIPE

OPEN DIAPHRAGM

WASTE PIPE

NOTES:

TRAP GUARD DIAPHRAGM AS MANUFACTURED BY PROVENT SYSTEMS, INC.

REFER TO SPECIFICATION. WHERE ALLOWED BY LOCAL CODE, TRAP GUARD MAY

BE USED IN LIEU OF TRAP PRIMER. TYPICAL ALL FLOOR DRAINS.

ISSUED FOR BID

Drawing Title

Approved: Associate Director

Project Title

Date

Location

Checked

Building Number

Project Number:

Drawing Number

Drawn

CONSULTANTS: ARCHITECT/ENGINEERS:

Dwg. of o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Veterans Health

Administration Approved: Chief of Staff

Approved: Infection Control

Approved: Chief Engineer

Approved: Safety Officer

Approved: Chief, Police & Security

GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211

Phone: 316-265-9367 www.glmv.com

Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044

Phone: 785-842-6464 www.pec1.com

Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603

Phone: 828-315-9962 www.atriaxgroup.com

FSC, Inc.

Fire Protection and Life Safety Engineers 8675 W. 96th Street, Overland Park, KS 66212

Phone: 913-722-3473 www.fsc-inc.com

/1

/2

:2

:4

P

M B

IM

/1

R

A tr ia x K a n s a s C it y V

A R e n o v a te B ld g

/2

-0

-M E

C H

-R

.r v t

PP501

PLUMBING DETAILS & SCHEDULES Renovate Bldg 26 for Pharmacy, Phlebotomy, and Police

Kansas City VA Medical Center Kansas City, MO

589-21-211

April 17, 2026 EKE AMA 55 83

PLUMBING FIXTURE SCHEDULE

MARK FIXTURE

WATER WASTE

VENT REMARKSCOLD HOT

RUNOUT CONN.

RUNOUT CONN. RUNOUT CONN.

FD-1 FLOOR DRAIN -- -- -- -- 2" 2" 1-1/2"

FD-2 FLOOR DRAIN -- -- -- -- 3" 3" 1-1/2"

P-114 BARIATRIC WATER CLOSET 1-1/4" 1" -- -- 4" 3" 2"

P-115 WATER CLOSET 1-1/4" 1" -- -- 4" 3" 2" ADA COMPLIANT

P-418 LAVATORY 1/2" 3/8" 1/2" 3/8" 2" 1-1/4" 1-1/2" ADA COMPLIANT

P-421 BARIATRIC LAVATORY 1/2" 3/8" 1/2" 3/8" 2" 1-1/4" 1-1/2"

P-502 MOP BASIN 3/4" 1/2" 3/4" 1/2" 3" 3" 2"

P-528 KITCHEN SINK 1/2" 3/8" 1/2" 3/8" 2" 1-1/4" 1-1/2"

P-529 HAND SINK 1/2" 3/8" 1/2" 3/8" 2" 1-1/4" 1-1/2"

P-702 SHOWER 3/4" 1/2" 3/4" 1/2" 2" 2" 1-1/2"

P-812 WATER SUPPLY BOX 1/2" 3/8" -- -- -- -- --

PLUMBING FIXTURE LIST

FD-1: FLOOR DRAIN:

SERIES FD-100-A EPOXY COATED CAST IRON FLOOR DRAIN WITH ANCHOR FLANGE, REVERSIBLE CLAMPING COLLAR WITH PRIMARY AND SECONDARY WEEPHOLES, ADJUSTABLE ROUND HEEL PROOF NICKEL BRONZE STRAINER, AND NO HUB (STANDARD) OUTLET.

FD-2: FLOOR DRAIN:

SERIES FD-100-A EPOXY COATED CAST IRON FLOOR DRAIN WITH ANCHOR FLANGE, REVERSIBLE CLAMPING COLLAR WITH PRIMARY AND SECONDARY WEEPHOLES, ADJUSTABLE ROUND HEEL PROOF NICKEL BRONZE STRAINER, AND NO HUB (STANDARD) OUTLET.

P-115: WATER CLOSET: (ADA COMPLIANT)

AMERICAN STANDARD "MADERA" FLOOR MOUNTED, VITREOUS CHINA, BOTTOM OUTLET, 16-1/2” HIGH ELONGATED BOWL 1.6 GPF SIPHON JET TOILET WITH 1-1/2” TOP SPUD – AMERICAN STANDARD 6047 SERIES FLUSH VALVE WITH VACUUM BREAKER, DUAL FILTERED BYPASS – WHITE SOLID PLASTIC ELONGATED OPEN FRONT SEAT, LESS COVER. THE TOILET SHALL BE INSTALLED SO THAT THE CENTERLINE OF BOWL SHALL BE 16”-18” FROM THE NEAREST FINISHED WALL, FLUSH HANDLE SHALL BE ON THE WIDE SIDE OF THE TOILET ROOM.

P-418: LAVATORY:

AMERICAN STANDARD 0355.012 LUCERNE WALL HUNG VITREOUS CHINA LAVATORY WITH SINGLE HOLE, FRONT OVERFLOW, DRILLED FOR CONCEALED ARM CARRIER. FAUCET BASED ON ZURN Z81200-XL DECK MOUNTED, DOUBLE BLADE HANDLE FAUCET WITH 1.5 GPM VANDAL PROOF NON-AERATING LAMINAR OUTLET, LEONARD MODEL 270 THERMOSTATIC MIXING VALVE UNDER LAVATORY –DRAIN WITH GRID STRAINER –CHROME PLATED WALL SUPPLIES WITH LOOSE KEY STOPS –1-1/4”CHROME PLATED CAST BRASS “P”TRAP –FLOOR MOUNTED CONCEALED ARM CARRIER – P-TRAP AND WATER PIPING TO BE INSTALLED

WITHIN LAVATORY SHROUD.

P-502: SERVICE SINK, FLOOR MOUNTED:

STERN WILLIAMS SB-900 24”X24”X12”DEEP TERRAZZO MOP BASIN WITH STAINLESS STEEL CAP –CAST BRASS DRAIN WITH STAINLESS STEEL STRAINER – T&S BRASS B 0665 BSTP SERVICE SINK FAUCET WITH INTEGRAL CHECKSTOPS, SPOUT WITH BUCKET HOOK, 3/4" HOSE THREAD END, VACUUM BREAKER, ADJUSTABLE TOP BRACE, LEVER HANDLES – STAINLESS STEEL BACKSPLASH PANELS ON ADJACENT WALLS. INSTALL CHECK VALVES ON WATER SUPPLIES.

P-528 SINK:

ELKAY LR2219 STAINLESS STEEL 22" X 19-1/2" X 7-5/8" DEEP SINGLE BOWL DROP IN SINK WITH THREE HOLE DRILLING-FAUCET BASED ON ZURN Z81200-XL DECK MOUNTED, DOUBLE BLADE HANDLE FAUCET WITH 1.5 GPM VANDAL PROOF NON-AERATING LAMINAR OUTLET, LEONARD MODEL 270 THERMOSTATIC MIXING VALVE UNDER LAVATORY –DRAIN WITH GRID STRAINER –WALL SUPPLIES WITH LOOSE KEY STOPS –1-1/2”CHROME PLATED CAST BRASS “P”TRAP. SUPPORT COUNTERTOP USING FLOOR MOUNTED CARRIER EQUAL TO WADE 510-02. INSTALL PIPING TO FIT WITHIN ARCHITECTURAL ENCLOSURE.

P-529: HAND SINK:

ELKAY LRAD191860L STAINLESS STEEL 19" X 18" X 7-1/2" DEEP SINGLE BOWL DROP IN SINK WITH THREE HOLE DRILLING AND CENTERED DRAIN-FAUCET BASED ON ZURN Z81200-XL DECK MOUNTED, DOUBLE BLADE HANDLE FAUCET WITH 1.5 GPM VANDAL PROOF NON-AERATING LAMINAR OUTLET, LEONARD MODEL 270 THERMOSTATIC MIXING VALVE UNDER SINK –DRAIN WITH GRID STRAINER - PROVIDE 1/2" HW SUPPLY (UNTEMPERED) WITH SHUTOFF VALVE TO ADJACENT DISHWASHER. PROVIDE TAILPIECE WITH AIR GAP FITTING FOR CONNECTION OF DISHWASHER DRAIN HOSE. –WALL SUPPLIES WITH LOOSE KEY STOPS –1-1/2” CHROME PLATED CAST BRASS “P”TRAP. SUPPORT COUNTERTOP USING FLOOR MOUNTED CARRIER EQUAL TO WADE 510-02. INSTALL PIPING TO FIT WITHIN

ARCHITECTURAL ENCLOSURE.

P-702 SHOWER:

BASED ON SYMMONS C-96-300-B30-V CONCEALED THERMOSTATIC/PRESSURE BALANCING SHOWER VALVE WITH BRASS LEVER HANDLE, INTEGRAL SERVICE STOPS - CHICAGO FAUCETS 151-ACP WALL MOUNTED HAND SPRAY WITH WALL ELBOW AND INLINE VACUUM BREAKER, 2.5 GPM HAND SPRAY, 26" WALL MOUNTED SLIDE BAR, 59" STAINLESS STEEL HOSE - 2" STAINLESS STEEL, NICKEL BRONZE OR CHROME PLATED SHOWER DRAIN.

P-812 WATER SUPPLY BOX:

BASED ON SIOUX CHIEF 696-1010 ICE MAKER OUTLET BOX WITH ABS BOX AND FRAME, QUARTER TURN BALL VALVE, WATER HAMMER ARRESTOR, SUPPORT

BRACKET AS NEEDED.

NOT TO SCALE

PIPE HANGERS

NOT TO SCALE

FLOOR DRAIN TRAP GUARD DETAIL

1.

2.

MINIMUM RUNOUT SIZE TO BRANCH MAIN TO BE 1/2" FOR OXYGEN AND MED AIR; 3/4" FOR VAC.

PROVIDE MEDICAL GAS OUTLETS TO MEET…